- Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Chiller · Modbus register map
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus register map
Updated 19 November 2026
Water-cooled magnetic-bearing centrifugal chiller (Magnitude WME, B vintage), on the MicroTech chiller controller. A plug-on RS-485 module exposes Modbus RTU and every point is a 16-bit holding register: water temperatures, refrigerant and lift pressures, motor stator/gap/case temperatures, amps/volts/kW, pump status, enable/mode/setpoint commands, status enums and alarm indexes. Values follow an English/Metric setting.
This page lists 82 Modbus registers for the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin Applied
- Model
- Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
- Equipment type
- Chiller
- Registers
- 82 (15 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N2
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- WME-B, WME B-Vintage, Magnitude WME B, ED 15121
Integration notes: Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Fit the Modbus module, set address and baud at the keypad (Modbus Setup), apply so the controller reboots, then poll holding registers with function 03. Read 1 (Local/Remote) and 316 (Units) first; use 9 to enable, 35 for the chilled-water setpoint, 38 for capacity limit, and 5 plus 28-33 for alarms.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Chiller Local/Remote | UINT16 | Local/Remote - network commands only work in Remote | Read |
| HR 14 | Chiller Status | UINT16 | Chiller status | Read |
| HR 16 | Evaporator Leaving Fluid Temperature | INT16 | Leaving chilled water temperature | Read |
| HR 12 | Actual Capacity | UINT16 | Actual capacity | Read |
| HR 8 | Chiller Enable Setpoint | UINT16 | Network enable command | Read/write |
| HR 34 | Cool Setpoint - Network | INT16 | Cooling setpoint command | Read/write |
| HR 37 | Capacity Limit Setpoint - Network | UINT16 | Capacity limit command | Read/write |
| HR 4 | Alarm Digital Output | UINT16 | Any alarm active | Read |
| HR 29 | Fault Alarm Index | UINT16 | Active fault index | Read |
| HR 315 | Units (English/Metric) | UINT16 | English/Metric flag | Read/write |
Enable Modbus control & writes
A Modbus communication module must be attached to the unit controller. Set Network Address and Baud Rate at the keypad (password 5321, View/Set Unit > Modbus Setup), then Apply Changes = Yes to reboot the controller. Chiller Local/Remote (register 1) must read Remote (0) - it can only be changed at the keypad - or enable, mode, setpoint, capacity-limit and clear-alarm writes are ignored.
Communication loss & watchdog
The module's Com LED Timeout (0-3600 s, default 3 s) only turns the BUS LED red when the master stops polling; no control fallback on communication loss is documented. Enable, mode and clear-alarm commands have a Null value that falls back to Disable / Cool / Normal when nothing writes them.
Byte order & addressing
- Printed register numbers are 1-based without the 4xxxx prefix: subtract 1 for the wire address.
- 32-bit run-hour counters are low word first (CDAB).
- Most analog values are x10 and follow the English/Metric Units register (316); the multiplier does not change with units.
- Alarm codes carry the alarm index in the high byte; the low byte holds circuit (bits 5-7), compressor (bits 2-4) and level (bits 0-1: 1 warning, 2 problem, 3 fault).
Network setup
- Address 1-247 (default 1); baud 4800/9600/19200/38400 (default 38400); parity Even/Odd/None (default None); Two Stop Bits Yes/No (default Yes).
- RS-485 is 3-wire (+, -, REF) shielded twisted pair, daisy-chained. The module's Load Resistor setting (default No) switches in termination; set Yes only on the first or last device.
- Response Delay defaults to 5 ms; raise it only for slow masters.
- Network parameters revert to defaults after an application software field upgrade - recheck them.
Watch out for
- Writes are silently ignored while register 1 reads Local (1).
- Chiller Mode Setpoint only matters when Available Modes at the keypad is not Cool Only.
- Some manual-reset lockouts (low evaporator pressure, high condenser pressure, freeze) cannot be cleared from the network.
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Chiller Local/Remote | Set at the keypad only; Local makes the controller ignore network commands. | UINT16 | Read | 0 = Remote; 1 = Local | |||
| HR | 1doc 2 | Chiller Enable Output | UINT16 | Read | 0 = Disable; 1 = Enable | ||||
| HR | 2doc 3 | Run Enabled | Chiller may start if operating conditions allow. | UINT16 | Read | 0 = Off; 1 = Run allowed | |||
| HR | 3doc 4 | Chiller Capacity Limited | UINT16 | Read | 0 = Not limited; 1 = Limited | ||||
| HR | 4doc 5 | Alarm Digital Output | Poll this for any active alarm. | UINT16 | Read | 0 = No alarm; 1 = Alarm | |||
| HR | 5doc 6 | Evaporator Flow Switch Status | UINT16 | Read | 0 = No flow; 1 = Flow | ||||
| HR | 6doc 7 | Condenser Flow Switch Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 7doc 8 | Chiller On/Off | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8doc 9 | Chiller Enable Setpoint | Network enable; Null behaves as Disable. | UINT16 | Read/write | 0 = Disable; 1 = Enable; 2 = Null | |||
| HR | 9doc 10 | Clear Alarms - Network | Some lockout alarms cannot be cleared from the network. | UINT16 | Read/write | 0 = Normal; 1 = Clear alarms; 2 = Null | |||
| HR | 10doc 11 | Chiller Mode Output | UINT16 | Read | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery; 5 = Defrost | ||||
| HR | 11doc 12 | Active Setpoint | Leaving water setpoint in use (Cool or Ice), °F x10. | INT16 | × 0.1 | °F | Read | ||
| HR | 12doc 13 | Actual Capacity | Percent of maximum capacity, x10. | UINT16 | × 0.1 | % | Read | ||
| HR | 13doc 14 | Active Capacity Limit Output | Lowest of all active capacity limits, x10. | UINT16 | × 0.1 | % | Read | ||
| HR | 14doc 15 | Chiller Status | UINT16 | Read | 1 = Off; 2 = Start; 3 = Run; 4 = Pre Shutdown; 5 = Service | ||||
| HR | 15doc 16 | Evaporator Entering Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 16doc 17 | Evaporator Leaving Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 18doc 19 | Condenser Entering Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 19doc 20 | Condenser Leaving Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 26doc 27 | Total Kilowatts | Total chiller power, 0-3500 kW. | UINT16 | kW | Read | |||
| HR | 27doc 28 | Warning Alarm Index | Index of the active warning (highest index); 0 = none. | UINT16 | Read | ||||
| HR | 28doc 29 | Problem Alarm Index | Index of the active problem alarm (highest index); 0 = none. | UINT16 | Read | ||||
| HR | 29doc 30 | Fault Alarm Index | Index of the active fault (highest index); 0 = none. | UINT16 | Read | ||||
| HR | 30doc 31 | Warning Alarm Code | Encoded code of the active warning; 0 = none. | UINT16 | Read | ||||
| HR | 31doc 32 | Problem Alarm Code | Encoded code of the active problem alarm; 0 = none. | UINT16 | Read | ||||
| HR | 32doc 33 | Fault Alarm Code | Encoded code of the active fault; 0 = none. | UINT16 | Read | ||||
| HR | 33doc 34 | Chiller Mode Setpoint - Network | Null runs Cool. Needs Available Modes other than Cool Only. | UINT16 | Read/write | 0 = Null; 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery | |||
| HR | 34doc 35 | Cool Setpoint - Network | Chilled fluid setpoint 24.98-60.08 °F x10; default 43.88 °F. | INT16 | × 0.1 | °F | Read/write | ||
| HR | 37doc 38 | Capacity Limit Setpoint - Network | Network capacity limit 0-100 % x10; default 100 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 38doc 39 | Circuit 1 Condenser Refrigerant Pressure | psi x10 (kPa x10 in Metric; to 4826 kPa for R-410A). | UINT16 | × 0.1 | psi | Read | ||
| HR | 39doc 40 | Circuit 1 Condenser Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 62doc 63 | Compressor 1 Suction Refrigerant Pressure | psi x10 (kPa x10 in Metric; to 4826 kPa for R-410A). | UINT16 | × 0.1 | psi | Read | ||
| HR | 64doc 65 | Compressor 1 Suction Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 65doc 66 | Compressor 1 Discharge Refrigerant Pressure | psi x10 (kPa x10 in Metric; to 4826 kPa for R-410A). | UINT16 | × 0.1 | psi | Read | ||
| HR | 67doc 68 | Compressor 1 Discharge Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 68doc 69 | Compressor 1 Percent RLA | Percent of rated load amps, 0-100 %. | UINT16 | % | Read | |||
| HR | 69doc 70 | Compressor 1 Current | Average motor current, 0-10000 A. | UINT16 | A | Read | |||
| HR | 70doc 71 | Compressor 1 Voltage | Average motor voltage, 0-15000 VAC. | UINT16 | V | Read | |||
| HR | 71doc 72 | Compressor 1 Power | Motor power, 0-3500 kW. | UINT16 | kW | Read | |||
| HR | 72doc 73 | Compressor 1 Starts | Start counter, 0-65535. | UINT16 | Read | ||||
| HR | 73doc 74-75 | Compressor 1 Run Hours | 0-999,999 h; low word in 74. | UINT32 | CDAB | h | Read/write | ||
| HR | 75doc 76 | Compressor 2 Suction Refrigerant Pressure | psi x10 (kPa x10 in Metric; to 4826 kPa for R-410A). | UINT16 | × 0.1 | psi | Read | ||
| HR | 78doc 79 | Compressor 2 Discharge Refrigerant Pressure | psi x10 (kPa x10 in Metric; to 4826 kPa for R-410A). | UINT16 | × 0.1 | psi | Read | ||
| HR | 81doc 82 | Compressor 2 Percent RLA | Percent of rated load amps, 0-100 %. | UINT16 | % | Read | |||
| HR | 85doc 86 | Compressor 2 Starts | Start counter, 0-65535. | UINT16 | Read | ||||
| HR | 86doc 87-88 | Compressor 2 Run Hours | 0-999,999 h; low word in 87. | UINT32 | CDAB | h | Read/write | ||
| HR | 296doc 297-298 | Condenser Pump 1 Run Hours | 0-999,999 h; low word in 297. | UINT32 | CDAB | h | Read | ||
| HR | 298doc 299 | Condenser Pump 1 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 299doc 300-301 | Condenser Pump 2 Run Hours | 0-999,999 h; low word in 300. | UINT32 | CDAB | h | Read | ||
| HR | 301doc 302 | Condenser Pump 2 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 302doc 303-304 | Evaporator Pump 1 Run Hours | 0-999,999 h; low word in 303. | UINT32 | CDAB | h | Read | ||
| HR | 304doc 305 | Evaporator Pump 1 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 305doc 306-307 | Evaporator Pump 2 Run Hours | 0-999,999 h; low word in 306. | UINT32 | CDAB | h | Read | ||
| HR | 307doc 308 | Evaporator Pump 2 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 308doc 309 | Clock Year | Controller clock; write to sync with the BAS. | UINT16 | Read/write | ||||
| HR | 309doc 310 | Clock Month | 1-12. | UINT16 | Read/write | ||||
| HR | 310doc 311 | Clock Date | Day of month, 1-31. | UINT16 | Read/write | ||||
| HR | 311doc 312 | Clock Day of Week | Calculated by the controller. | UINT16 | Read | 0 = Monday; 1 = Tuesday; 2 = Wednesday; 3 = Thursday; 4 = Friday; 5 = Saturday; 6 = Sunday | |||
| HR | 312doc 313 | Clock Hour | 0-23. | UINT16 | Read/write | ||||
| HR | 313doc 314 | Clock Minute | 0-59. | UINT16 | Read/write | ||||
| HR | 314doc 315 | Clock Second | 0-59. | UINT16 | Read/write | ||||
| HR | 315doc 316 | Units (English/Metric) | Unit system for all network values; default English. | UINT16 | Read/write | 0 = English; 1 = Metric | |||
| HR | 316doc 317 | Chiller Model | UINT16 | Read | 0 = Centrifugal; 1 = Water cooled; 2 = Air cooled; 3 = Heat pump; 9 = Other | ||||
| HR | 317doc 318-327 | Chiller Location | Up to 20 ASCII characters, two per register, first character in the high byte. | STRING[20] | Read/write | ||||
| HR | 333doc 334-338 | Application Software Version | Up to 10 ASCII characters, two per register, first character in the high byte. | STRING[10] | Read | ||||
| HR | 903doc 904 | Compressor 1 Stator Temperature 1 | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 904doc 905 | Compressor 2 Stator Temperature 1 | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 909doc 910 | Compressor 1 Stator Temperature 2 | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 910doc 911 | Compressor 2 Stator Temperature 2 | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 915doc 916 | Compressor 1 Stator Temperature 3 | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 916doc 917 | Compressor 2 Stator Temperature 3 | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 921doc 922 | Compressor 1 Motor Gap Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 922doc 923 | Compressor 2 Motor Gap Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 927doc 928 | Compressor 1 Motor Case Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 928doc 929 | Compressor 2 Motor Case Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 933doc 934 | Compressor 1 Rotor Pump Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 934doc 935 | Compressor 2 Rotor Pump Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 939doc 940 | Compressor 1 Lift Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 940doc 941 | Compressor 2 Lift Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 945doc 946 | Compressor 1 Lift Pressure | psi x10 (kPa x10 in Metric; to 4826 kPa for R-410A). | UINT16 | × 0.1 | psi | Read | ||
| HR | 946doc 947 | Compressor 2 Lift Pressure | psi x10 (kPa x10 in Metric; to 4826 kPa for R-410A). | UINT16 | × 0.1 | psi | Read | ||
| HR | 1983doc 1984 | Liquid Line Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read |
Notes on this map
- Network settings (address 1, 38400 bps, parity None, two stop bits, response delay, Com LED timeout) are from the companion manual IM 969-7, MicroTech Chiller Unit Controller Modbus Communication Module (Oct 2023): https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/Daikin_Applied_IM_969-7_MT_Chiller_Modbus_Comm_Manual.pdf/
- ED 15121 is shared by AGZ, AMZ, AWS, AWV, ADS, WME-B and WWV/TWV chillers. Only points that Table 3 marks in the WME-B column are listed.
- Two-register counters: the document's worked example (run hours 99900 = 0x0001863C stored as 74 = 0x863C, 75 = 0x0001) puts the low word in the lower register, so they are CDAB.
- Strings: two ASCII characters per register, leftmost character in the lowest register and in the high byte (Figure 1 example: 0x3235 = '25').
- The document never defines 'x 10'. Its ranges and defaults (for example 'Default: 43.88°F x 10', '0-100% x 10') only make sense as raw = value x 10, so those registers use scale 0.1.
- Signedness is not stated. A register is INT16 when its published English or Metric range goes negative; otherwise UINT16. Condenser pressure is UINT16 because 4826 kPa x10 does not fit a signed register.
- Units follow register 316 (English default). Units shown are the English ones (°F, psi); in Metric the same registers carry °C and kPa with the same multiplier.
- Left out: Circuit 1 Evaporator Saturated Refrigerant Temperature (42), because ED 15121-13 prints its range without the 'x 10' that the other circuits' copies carry, so its scaling is not settled.
- Left out: the individual per-alarm registers (Tables 9-12) and the alarm index/code meanings; the alarm text for each index and code is in the document. Alarm codes carry the index in the high byte and circuit/compressor/level in the low byte (Figure 2).
- Compressor 2 points marked 'only used for WME Vintage B' in Table 6 (percent RLA, discharge pressure, lift, motor and stator temperatures) are listed alongside compressor 1. The document gives no compressor 2 current, power or voltage register.
- Pressures are UINT16 because their ranges (to 4826 kPa x10) do not fit a signed register.
- Left out: evaporator and condenser flow rates (18, 21), printed as 0-65,535 GPM / 0-4135 L/S with no multiplier, so the Metric scaling is not settled.
- Left out: points Table 3 does not mark for WME-B (outdoor air temperature, evaporator refrigerant pressure and saturated temperature, ice setpoint, oil feed pressure, VFD temperature).
- Not the same map as the WME-C/WME-D file (ED 19111): this B-vintage map comes from ED 15121.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
What Modbus registers does the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) have?
This map lists 82 registers: 82 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. ED 15121 prints holding registers without the 4xxxx prefix (register 8 = 40008) and states the module is zero-based: register 40003 goes out as 0002 in the PDU. Wire address = printed number - 1.
What byte order does the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)?
Start with HR 0 Chiller Local/Remote (Local/Remote - network commands only work in Remote); HR 14 Chiller Status (Chiller status); HR 16 Evaporator Leaving Fluid Temperature (Leaving chilled water temperature); HR 12 Actual Capacity (Actual capacity); HR 8 Chiller Enable Setpoint (Network enable command); HR 34 Cool Setpoint - Network (Cooling setpoint command); HR 37 Capacity Limit Setpoint - Network (Capacity limit command); HR 4 Alarm Digital Output (Any alarm active); HR 29 Fault Alarm Index (Active fault index); HR 315 Units (English/Metric) (English/Metric flag).
How do I enable Modbus control of the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)?
A Modbus communication module must be attached to the unit controller. Set Network Address and Baud Rate at the keypad (password 5321, View/Set Unit > Modbus Setup), then Apply Changes = Yes to reboot the controller. Chiller Local/Remote (register 1) must read Remote (0) - it can only be changed at the keypad - or enable, mode, setpoint, capacity-limit and clear-alarm writes are ignored.
What happens when the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) loses Modbus communication?
The module's Com LED Timeout (0-3600 s, default 3 s) only turns the BUS LED red when the master stops polling; no control fallback on communication loss is documented. Enable, mode and clear-alarm commands have a Null value that falls back to Disable / Cool / Normal when nothing writes them.
Where is the official Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus documentation?
The source is MicroTech Chiller Unit Controller Protocol Information - Modbus Networks (ED 15121-13) (ED 15121-13), revision 2026-09, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15121-13.pdf/.
More Daikin Applied Modbus register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121
Other chillers & heat pumps register maps
- Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800
All chillers & heat pumps Modbus register maps →
Source: MicroTech Chiller Unit Controller Protocol Information - Modbus Networks (ED 15121-13) · ED 15121-13 · rev. 2026-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.