Chiller · Modbus register map

Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus register map

Updated 19 November 2026

Short answer

Water-cooled magnetic-bearing centrifugal chiller (Magnitude WME, B vintage), on the MicroTech chiller controller. A plug-on RS-485 module exposes Modbus RTU and every point is a 16-bit holding register: water temperatures, refrigerant and lift pressures, motor stator/gap/case temperatures, amps/volts/kW, pump status, enable/mode/setpoint commands, status enums and alarm indexes. Values follow an English/Metric setting.

This page lists 82 Modbus registers for the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin Applied
Model
Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Equipment type
Chiller
Registers
82 (15 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
WME-B, WME B-Vintage, Magnitude WME B, ED 15121
Source document
MicroTech Chiller Unit Controller Protocol Information - Modbus Networks (ED 15121-13) · ED 15121-13 · rev. 2026-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)

Integration in brief

Fit the Modbus module, set address and baud at the keypad (Modbus Setup), apply so the controller reboots, then poll holding registers with function 03. Read 1 (Local/Remote) and 316 (Units) first; use 9 to enable, 35 for the chilled-water setpoint, 38 for capacity limit, and 5 plus 28-33 for alarms.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Chiller Local/RemoteUINT16Local/Remote - network commands only work in RemoteRead
HR 14Chiller StatusUINT16Chiller statusRead
HR 16Evaporator Leaving Fluid TemperatureINT16Leaving chilled water temperatureRead
HR 12Actual CapacityUINT16Actual capacityRead
HR 8Chiller Enable SetpointUINT16Network enable commandRead/write
HR 34Cool Setpoint - NetworkINT16Cooling setpoint commandRead/write
HR 37Capacity Limit Setpoint - NetworkUINT16Capacity limit commandRead/write
HR 4Alarm Digital OutputUINT16Any alarm activeRead
HR 29Fault Alarm IndexUINT16Active fault indexRead
HR 315Units (English/Metric)UINT16English/Metric flagRead/write

Enable Modbus control & writes

A Modbus communication module must be attached to the unit controller. Set Network Address and Baud Rate at the keypad (password 5321, View/Set Unit > Modbus Setup), then Apply Changes = Yes to reboot the controller. Chiller Local/Remote (register 1) must read Remote (0) - it can only be changed at the keypad - or enable, mode, setpoint, capacity-limit and clear-alarm writes are ignored.

Communication loss & watchdog

The module's Com LED Timeout (0-3600 s, default 3 s) only turns the BUS LED red when the master stops polling; no control fallback on communication loss is documented. Enable, mode and clear-alarm commands have a Null value that falls back to Disable / Cool / Normal when nothing writes them.

Byte order & addressing

Network setup

Watch out for

Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

82 of 82 shown
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Chiller Local/RemoteSet at the keypad only; Local makes the controller ignore network commands.UINT16Read0 = Remote; 1 = Local
HR1doc 2Chiller Enable OutputUINT16Read0 = Disable; 1 = Enable
HR2doc 3Run EnabledChiller may start if operating conditions allow.UINT16Read0 = Off; 1 = Run allowed
HR3doc 4Chiller Capacity LimitedUINT16Read0 = Not limited; 1 = Limited
HR4doc 5Alarm Digital OutputPoll this for any active alarm.UINT16Read0 = No alarm; 1 = Alarm
HR5doc 6Evaporator Flow Switch StatusUINT16Read0 = No flow; 1 = Flow
HR6doc 7Condenser Flow Switch StatusUINT16Read0 = Off; 1 = On
HR7doc 8Chiller On/OffUINT16Read0 = Off; 1 = On
HR8doc 9Chiller Enable SetpointNetwork enable; Null behaves as Disable.UINT16Read/write0 = Disable; 1 = Enable; 2 = Null
HR9doc 10Clear Alarms - NetworkSome lockout alarms cannot be cleared from the network.UINT16Read/write0 = Normal; 1 = Clear alarms; 2 = Null
HR10doc 11Chiller Mode OutputUINT16Read1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery; 5 = Defrost
HR11doc 12Active SetpointLeaving water setpoint in use (Cool or Ice), °F x10.INT16× 0.1°FRead
HR12doc 13Actual CapacityPercent of maximum capacity, x10.UINT16× 0.1%Read
HR13doc 14Active Capacity Limit OutputLowest of all active capacity limits, x10.UINT16× 0.1%Read
HR14doc 15Chiller StatusUINT16Read1 = Off; 2 = Start; 3 = Run; 4 = Pre Shutdown; 5 = Service
HR15doc 16Evaporator Entering Fluid Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR16doc 17Evaporator Leaving Fluid Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR18doc 19Condenser Entering Fluid Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR19doc 20Condenser Leaving Fluid Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR26doc 27Total KilowattsTotal chiller power, 0-3500 kW.UINT16kWRead
HR27doc 28Warning Alarm IndexIndex of the active warning (highest index); 0 = none.UINT16Read
HR28doc 29Problem Alarm IndexIndex of the active problem alarm (highest index); 0 = none.UINT16Read
HR29doc 30Fault Alarm IndexIndex of the active fault (highest index); 0 = none.UINT16Read
HR30doc 31Warning Alarm CodeEncoded code of the active warning; 0 = none.UINT16Read
HR31doc 32Problem Alarm CodeEncoded code of the active problem alarm; 0 = none.UINT16Read
HR32doc 33Fault Alarm CodeEncoded code of the active fault; 0 = none.UINT16Read
HR33doc 34Chiller Mode Setpoint - NetworkNull runs Cool. Needs Available Modes other than Cool Only.UINT16Read/write0 = Null; 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery
HR34doc 35Cool Setpoint - NetworkChilled fluid setpoint 24.98-60.08 °F x10; default 43.88 °F.INT16× 0.1°FRead/write
HR37doc 38Capacity Limit Setpoint - NetworkNetwork capacity limit 0-100 % x10; default 100 %.UINT16× 0.1%Read/write
HR38doc 39Circuit 1 Condenser Refrigerant Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR39doc 40Circuit 1 Condenser Saturated Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR62doc 63Compressor 1 Suction Refrigerant Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR64doc 65Compressor 1 Suction Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR65doc 66Compressor 1 Discharge Refrigerant Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR67doc 68Compressor 1 Discharge Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR68doc 69Compressor 1 Percent RLAPercent of rated load amps, 0-100 %.UINT16%Read
HR69doc 70Compressor 1 CurrentAverage motor current, 0-10000 A.UINT16ARead
HR70doc 71Compressor 1 VoltageAverage motor voltage, 0-15000 VAC.UINT16VRead
HR71doc 72Compressor 1 PowerMotor power, 0-3500 kW.UINT16kWRead
HR72doc 73Compressor 1 StartsStart counter, 0-65535.UINT16Read
HR73doc 74-75Compressor 1 Run Hours0-999,999 h; low word in 74.UINT32CDABhRead/write
HR75doc 76Compressor 2 Suction Refrigerant Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR78doc 79Compressor 2 Discharge Refrigerant Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR81doc 82Compressor 2 Percent RLAPercent of rated load amps, 0-100 %.UINT16%Read
HR85doc 86Compressor 2 StartsStart counter, 0-65535.UINT16Read
HR86doc 87-88Compressor 2 Run Hours0-999,999 h; low word in 87.UINT32CDABhRead/write
HR296doc 297-298Condenser Pump 1 Run Hours0-999,999 h; low word in 297.UINT32CDABhRead
HR298doc 299Condenser Pump 1 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR299doc 300-301Condenser Pump 2 Run Hours0-999,999 h; low word in 300.UINT32CDABhRead
HR301doc 302Condenser Pump 2 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR302doc 303-304Evaporator Pump 1 Run Hours0-999,999 h; low word in 303.UINT32CDABhRead
HR304doc 305Evaporator Pump 1 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR305doc 306-307Evaporator Pump 2 Run Hours0-999,999 h; low word in 306.UINT32CDABhRead
HR307doc 308Evaporator Pump 2 StatusUINT16Read0 = Pump off request; 1 = Pump on request
HR308doc 309Clock YearController clock; write to sync with the BAS.UINT16Read/write
HR309doc 310Clock Month1-12.UINT16Read/write
HR310doc 311Clock DateDay of month, 1-31.UINT16Read/write
HR311doc 312Clock Day of WeekCalculated by the controller.UINT16Read0 = Monday; 1 = Tuesday; 2 = Wednesday; 3 = Thursday; 4 = Friday; 5 = Saturday; 6 = Sunday
HR312doc 313Clock Hour0-23.UINT16Read/write
HR313doc 314Clock Minute0-59.UINT16Read/write
HR314doc 315Clock Second0-59.UINT16Read/write
HR315doc 316Units (English/Metric)Unit system for all network values; default English.UINT16Read/write0 = English; 1 = Metric
HR316doc 317Chiller ModelUINT16Read0 = Centrifugal; 1 = Water cooled; 2 = Air cooled; 3 = Heat pump; 9 = Other
HR317doc 318-327Chiller LocationUp to 20 ASCII characters, two per register, first character in the high byte.STRING[20]Read/write
HR333doc 334-338Application Software VersionUp to 10 ASCII characters, two per register, first character in the high byte.STRING[10]Read
HR903doc 904Compressor 1 Stator Temperature 1°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR904doc 905Compressor 2 Stator Temperature 1°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR909doc 910Compressor 1 Stator Temperature 2°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR910doc 911Compressor 2 Stator Temperature 2°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR915doc 916Compressor 1 Stator Temperature 3°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR916doc 917Compressor 2 Stator Temperature 3°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR921doc 922Compressor 1 Motor Gap Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR922doc 923Compressor 2 Motor Gap Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR927doc 928Compressor 1 Motor Case Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR928doc 929Compressor 2 Motor Case Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR933doc 934Compressor 1 Rotor Pump Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR934doc 935Compressor 2 Rotor Pump Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR939doc 940Compressor 1 Lift Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR940doc 941Compressor 2 Lift Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead
HR945doc 946Compressor 1 Lift Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR946doc 947Compressor 2 Lift Pressurepsi x10 (kPa x10 in Metric; to 4826 kPa for R-410A).UINT16× 0.1psiRead
HR1983doc 1984Liquid Line Refrigerant Temperature°F x10 (°C x10 when Units = Metric).INT16× 0.1°FRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)

What Modbus registers does the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) have?

This map lists 82 registers: 82 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. ED 15121 prints holding registers without the 4xxxx prefix (register 8 = 40008) and states the module is zero-based: register 40003 goes out as 0002 in the PDU. Wire address = printed number - 1.

What byte order does the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)?

Start with HR 0 Chiller Local/Remote (Local/Remote - network commands only work in Remote); HR 14 Chiller Status (Chiller status); HR 16 Evaporator Leaving Fluid Temperature (Leaving chilled water temperature); HR 12 Actual Capacity (Actual capacity); HR 8 Chiller Enable Setpoint (Network enable command); HR 34 Cool Setpoint - Network (Cooling setpoint command); HR 37 Capacity Limit Setpoint - Network (Capacity limit command); HR 4 Alarm Digital Output (Any alarm active); HR 29 Fault Alarm Index (Active fault index); HR 315 Units (English/Metric) (English/Metric flag).

How do I enable Modbus control of the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)?

A Modbus communication module must be attached to the unit controller. Set Network Address and Baud Rate at the keypad (password 5321, View/Set Unit > Modbus Setup), then Apply Changes = Yes to reboot the controller. Chiller Local/Remote (register 1) must read Remote (0) - it can only be changed at the keypad - or enable, mode, setpoint, capacity-limit and clear-alarm writes are ignored.

What happens when the Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) loses Modbus communication?

The module's Com LED Timeout (0-3600 s, default 3 s) only turns the BUS LED red when the master stops polling; no control fallback on communication loss is documented. Enable, mode and clear-alarm commands have a Null value that falls back to Disable / Cool / Normal when nothing writes them.

Where is the official Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller) Modbus documentation?

The source is MicroTech Chiller Unit Controller Protocol Information - Modbus Networks (ED 15121-13) (ED 15121-13), revision 2026-09, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15121-13.pdf/.

More Daikin Applied Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: MicroTech Chiller Unit Controller Protocol Information - Modbus Networks (ED 15121-13) · ED 15121-13 · rev. 2026-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.