Chiller (water-cooled) · Modbus register map

Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus register map

Updated 17 November 2026

Short answer

Daikin Applied Europe's EWWD(H)(S)-VZ water-cooled inverter screw chillers expose a Modbus RTU slave on RS-485 through a POL902 module or, on Microtech 4, a licensed on-board option. All points are 16-bit holding registers covering unit and circuit status, evaporator and condenser water temperatures, refrigerant pressures, compressor current/power/VFD data, setpoints, pump states and individual alarm flags.

This page lists 198 Modbus registers for the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin Applied
Model
EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
Equipment type
Chiller (water-cooled)
Registers
198 (12 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
Firmware
Adam control software (no version printed)
Also known as
EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam
Source document
BAS integration guide - Modbus protocol, EWWD(H)(S)_VZ (Adam) · D-EIGOC00201-22_03EN
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)

Integration in brief

Read holding registers from wire address 0: Unit Status (col 15), evaporator leaving water (col 17) and capacity (col 13). Enable with col 9 and write the cooling setpoint to col 35 in tenths of °C.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 14Unit - StatusUINT16Unit statusRead
HR 16Evaporator Leaving Water TemperatureINT16Evaporator leaving water temperatureRead
HR 19Condenser Leaving Water TemperatureINT16Condenser leaving water temperatureRead
HR 12Unit - Actual CapacityINT16Actual capacityRead
HR 8Unit - Enable SetpointUINT16Unit enable commandRead/write
HR 34Unit - Cool Temperature SetpointINT16Cooling temperature setpointRead/write
HR 32Unit Alarm - Fault CodeINT16Active fault codeRead

Enable Modbus control & writes

Fit a POL902 module and set the Modbus parameters under Main menu > Commissioning > Modbus (service password); or on Microtech 4 turn on software option #1 'Modbus Slave MSTP' (unlock password needed) and set it under Commissioning > Commission Unit > SW Modbus MSTP.

Byte order & addressing

Network setup

Watch out for

Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

198 of 198 shown
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Unit - Control SourceUINT16Read0 = Network; 1 = Local
HR1doc 2Unit - Enabled StateUINT16Read0 = Disabled; 1 = Enabled
HR2doc 3Unit - Run AllowedUINT16Read0 = Off; 1 = RunAllowed
HR3doc 4Unit - Capacity LimitedUINT16Read0 = NotLimited; 1 = Limited
HR4doc 5Unit - Alarm OutputUINT16Read0 = NoAlarm; 1 = Alarm
HR5doc 6Evaporator - Water Flow StateUINT16Read0 = NoFlow; 1 = Flow
HR6doc 7Condenser - Water Flow StateUINT16Read0 = NoFlow; 1 = Flow
HR7doc 8Unit - Operating StateUINT16Read0 = Off; 1 = On
HR8doc 9Unit - Enable SetpointUINT16Read/write0 = Disable; 1 = Enable
HR9doc 10Unit - Alarm Reset SetpointUINT16Read/write0 = None; 1 = ClearAlarm
HR10doc 11Unit - Active Operation ModeUINT16Read1 = Ice; 2 = Cool; 3 = Heat; 4 = Pursuit
HR11doc 12Unit - Active Temperature SetpointINT16× 0.1°CRead
HR12doc 13Unit - Actual CapacityINT16× 0.1%Read
HR13doc 14Unit - Active Capacity LimitINT16× 0.1%Read
HR14doc 15Unit - StatusUINT16Read1 = Off; 2 = Start; 3 = Run; 4 = PreShutdown; 5 = Service
HR15doc 16Evaporator Entering Water TemperatureINT16× 0.1°CRead
HR16doc 17Evaporator Leaving Water TemperatureINT16× 0.1°CRead
HR18doc 19Condenser Entering Water TemperatureINT16× 0.1°CRead
HR19doc 20Condenser Leaving Water TemperatureINT16× 0.1°CRead
HR24doc 25Unit - Average CurrentINT16ARead
HR25doc 26Unit - Average VoltageINT16× 0.1VRead
HR26doc 27Unit - Active PowerINT16× 0.1kWRead
HR27doc 28Unit Alarm - Warning IndexNumeric code; see the alarm code and index table in section 5.1.INT16Read
HR28doc 29Unit Alarm - Problem IndexNumeric code; see the alarm code and index table in section 5.1.INT16Read
HR29doc 30Unit Alarm - Fault IndexNumeric code; see the alarm code and index table in section 5.1.INT16Read
HR30doc 31Unit Alarm - Warning CodeNumeric code; see the alarm code and index table in section 5.1.INT16Read
HR31doc 32Unit Alarm - Problem CodeNumeric code; see the alarm code and index table in section 5.1.INT16Read
HR32doc 33Unit Alarm - Fault CodeNumeric code; see the alarm code and index table in section 5.1.INT16Read
HR33doc 34Unit - Operation Mode SetpointUINT16Read/write1 = Ice; 2 = Cool; 3 = Heat; 4 = Pursuit
HR34doc 35Unit - Cool Temperature SetpointINT16× 0.1°CRead/write
HR35doc 36Unit - Ice Temperature SetpointINT16× 0.1°CRead/write
HR36doc 37Unit - Heat Temperature SetpointINT16× 0.1°CRead/write
HR37doc 38Unit - Capacity Limit SetpointINT16× 0.1%Read/write
HR38doc 39Circuit 1 - Condenser Refrigerant PressureINT16× 0.1kPaRead
HR39doc 40Circuit 1 - Condeser Saturated TemperatureINT16× 0.1°CRead
HR40doc 41Circuit 1 - Evaporator Refrigerant PressureINT16× 0.1kPaRead
HR41doc 42Circuit 1 - Evaporator Saturated TemperatureINT16× 0.1°CRead
HR42doc 43Circuit 2 - Condenser Refrigerant PressureINT16× 0.1kPaRead
HR43doc 44Circuit 2 - Condeser Saturated TemperatureINT16× 0.1°CRead
HR44doc 45Circuit 2 - Evaporator Refrigerant PressureINT16× 0.1kPaRead
HR45doc 46Circuit 2 - Evaporator Saturated TemperatureINT16× 0.1°CRead
HR50doc 51Circuit 1 - Shutdown AlarmUINT16Read0 = NoAlarm; 1 = Alarm
HR51doc 52Circuit 2 - Shutdown AlarmUINT16Read0 = NoAlarm; 1 = Alarm
HR64doc 65Circ 1 Compressor 1 - Suction TemperatureINT16× 0.1°CRead
HR67doc 68Circ 1 Compressor 1 - Discharge TemperatureINT16× 0.1°CRead
HR68doc 69Circ 1 Compressor 1 - RLA PercentageINT16%Read
HR69doc 70Circ 1 Compressor 1 - CurrentINT16ARead
HR70doc 71Circ 1 Compressor 1 - VoltageINT16VRead
HR71doc 72Circ 1 Compressor 1 - PowerINT16kWRead
HR72doc 73Circ 1 Compressor 1 - Number of StartsUINT16Read/write
HR103doc 104Circ 2 Compressor 1 - Suction TemperatureINT16× 0.1°CRead
HR106doc 107Circ 2 Compressor 1 - Discharge TemperatureINT16× 0.1°CRead
HR107doc 108Circ 2 Compressor 1 - RLA PercentageINT16%Read
HR108doc 109Circ 2 Compressor 1 - CurrentINT16ARead
HR109doc 110Circ 2 Compressor 1 - VoltageINT16VRead
HR110doc 111Circ 2 Compressor 1 - PowerINT16kWRead
HR111doc 112Circ 2 Compressor 1 - Number of StartsUINT16Read/write
HR263doc 264Performance - Unit EfficiencyUINT16× 0.01Read
HR264doc 265Performance - Unit Integrated EfficiencyUINT16× 0.01Read
HR298doc 299Condenser Pump 1 - Operating StateUINT16Read0 = OffRequest; 1 = OnRequest
HR301doc 302Condenser Pump 2 - Operating StateUINT16Read0 = OffRequest; 1 = OnRequest
HR304doc 305Evaporator Pump 1 - Operating StateUINT16Read0 = OffRequest; 1 = OnRequest
HR307doc 308Evaporator Pump 2 - Operating StateUINT16Read0 = OffRequest; 1 = OnRequest
HR315doc 316Unit - Measurement unit setpointUINT16Read/write0 = English; 1 = Metric
HR316doc 317Unit - ModelUINT16Read0 = Centrifugal; 1 = Water Cooled; 2 = Air Cooled; 3 = HeatPump; 4 = Reserved; 5 = Reserved; 6 = Reserved; 7 = Reserved; 8 = Other
HR364doc 365Unit Alarm - Condenser Entering Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR365doc 366Unit Alarm - Evaporator Entering Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR367doc 368Unit Alarm - Condenser Leaving Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR376doc 377Unit Warning - Setpoint Reset Input Out of RangeUINT16Read0 = NoAlarm; 1 = Alarm
HR377doc 378Unit Warning - Demand Limit Input Out of RangeUINT16Read0 = NoAlarm; 1 = Alarm
HR383doc 384Circuit 1 Warning - Power Loss while Compressor RunningUINT16Read0 = NoAlarm; 1 = Alarm
HR384doc 385Circuit 2 Warning - Power Loss while Compressor RunningUINT16Read0 = NoAlarm; 1 = Alarm
HR389doc 390Circuit 1 Warning - Inhibition for Condenser High PressureINT16kPaRead
HR390doc 391Circuit 2 Warning - Inhibition for Condenser High PressureINT16kPaRead
HR394doc 395Circuit 1 Warning - Unload for Condenser High PressureINT16kPaRead
HR395doc 396Circuit 2 Warning - Unload for Condenser High PressureINT16kPaRead
HR410doc 411Circuit 1 Warning - Inhibition for Evaporator Low PressureINT16kPaRead
HR411doc 412Circuit 2 Warning - Inhibition for Evaporator Low PressureINT16kPaRead
HR415doc 416Circuit 1 Warning - Unload for Evaporator Low PressureINT16kPaRead
HR416doc 417Circuit 2 Warning - Unload for Evaporator Low PressureINT16kPaRead
HR419doc 420Circ 1 Comp 1 Warning - Unload for High CurrentINT16ARead
HR421doc 422Circ 2 Comp 1 Warning - Unload for High CurrentINT16ARead
HR427doc 428Condenser Pump 1 - FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR428doc 429Condenser Pump 2 - FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR429doc 430Evaporator Pump 1 - FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR430doc 431Evaporator Pump 2 - FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR439doc 440Circ 1 Comp 1 Alarm - Low Pressure RatioUINT16Read0 = NoAlarm; 1 = Alarm
HR441doc 442Circ 2 Comp 1 Alarm - Low Pressure RatioUINT16Read0 = NoAlarm; 1 = Alarm
HR446doc 447Circ 1 Comp 1 Alarm - High Motor CurrentUINT16Read0 = NoAlarm; 1 = Alarm
HR448doc 449Circ 2 Comp 1 Alarm - High Motor CurrentUINT16Read0 = NoAlarm; 1 = Alarm
HR477doc 478Circ 1 Comp 1 Alarm - High Motor TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR479doc 480Circ 2 Comp 1 Alarm - High Motor TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR508doc 509Circuit 1 Alarm - Condenser Pressure Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR510doc 511Circuit 2 Alarm - Condenser Pressure Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR513doc 514Unit Alarm - Condenser Water FreezeUINT16Read0 = NoAlarm; 1 = Alarm
HR514doc 515Unit Alarm - Condenser Water Flow LossUINT16Read0 = NoAlarm; 1 = Alarm
HR516doc 517Circuit 1 Alarm - Condenser High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR518doc 519Circuit 2 Alarm - Condenser High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR528doc 529Circuit 1 Alarm - Discharge Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR530doc 531Circuit 2 Alarm - Discharge Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR534doc 535Circ 1 Comp 1 Alarm - High Discharge TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR536doc 537Circ 2 Comp 1 Alarm - High Discharge TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR541doc 542Unit Alarm - Evaporator Water Flow LossUINT16Read0 = NoAlarm; 1 = Alarm
HR542doc 543Unit Alarm - Evaporator Water FreezeUINT16Read0 = NoAlarm; 1 = Alarm
HR544doc 545Circuit 1 Alarm - Evaporator Pressure LowUINT16Read0 = NoAlarm; 1 = Alarm
HR546doc 547Circuit 2 Alarm - Evaporator Pressure LowUINT16Read0 = NoAlarm; 1 = Alarm
HR551doc 552Circuit 1 Alarm - Evaporator Pressure Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR553doc 554Circuit 2 Alarm - Evaporator Pressure Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR582doc 583Circuit 1 Alarm - Too many restartUINT16Read0 = NoAlarm; 1 = Alarm
HR584doc 585Circuit 2 Alarm - Too many restartUINT16Read0 = NoAlarm; 1 = Alarm
HR588doc 589Unit Alarm - Evaporator Leaving Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR600doc 601Circuit 1 Alarm - Mechanical High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR602doc 603Circuit 2 Alarm - Mechanical High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR630doc 631Circuit 1 Alarm - Oil Level LowUINT16Read0 = NoAlarm; 1 = Alarm
HR632doc 633Circuit 2 Alarm - Oil Level LowUINT16Read0 = NoAlarm; 1 = Alarm
HR636doc 637Circuit 1 Alarm - Oil Filter High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR638doc 639Circuit 2 Alarm - Oil Filter High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR642doc 643Circuit 1 Alarm - Oil Pressure Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR644doc 645Circuit 2 Alarm - Oil Pressure Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR651doc 652Circuit 1 Alarm - Liquid Temperature Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR654doc 655Circuit 2 Alarm - Liquid Temperature Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR660doc 661Unit Alarm - Phase VoltageUINT16Read0 = NoAlarm; 1 = Alarm
HR661doc 662Circ 1 Comp 1 Alarm - Starter FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR663doc 664Circ 2 Comp 1 Alarm - Starter FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR666doc 667Circuit 1 Alarm - OverVoltageUINT16Read0 = NoAlarm; 1 = Alarm
HR667doc 668Circuit 2 Alarm - OverVoltageUINT16Read0 = NoAlarm; 1 = Alarm
HR669doc 670Circuit 1 Alarm - UnderVoltageUINT16Read0 = NoAlarm; 1 = Alarm
HR670doc 671Circuit 2 Alarm - UnderVoltageUINT16Read0 = NoAlarm; 1 = Alarm
HR697doc 698Circ 1 Comp 1 Alarm - Suction Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR699doc 700Circ 2 Comp 1 Alarm - Suction Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR710doc 711Circuit 1 Alarm - No Pressure at StartUINT16Read0 = NoAlarm; 1 = Alarm
HR711doc 712Circuit 2 Alarm - No Pressure at StartUINT16Read0 = NoAlarm; 1 = Alarm
HR716doc 717Circuit 1 Alarm - Mechanical Low PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR718doc 719Circuit 2 Alarm - Mechanical Low PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR722doc 723Controller Alarm - Circuit 1 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR723doc 724Controller Alarm - Circuit 2 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR725doc 726Controller Alarm - Expansion Valve 1 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR726doc 727Controller Alarm - Expansion Valve 2 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR728doc 729Controller Alarm - Compressor 1 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR729doc 730Controller Alarm - Compressor 2 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR733doc 734Circ 1 Comp1 Alarm - Motor Temperature Sesnor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR735doc 736Circ 2 Comp1 Alarm - Motor Temperature Sesnor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR739doc 740Unit - Power RestoreUINT16Read0 = NoAlarm; 1 = Alarm
HR740doc 741Circuit 1 Alarm - Pumpdown FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR741doc 742Circuit 2 Alarm - Pumpdown FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR744doc 745Unit Alarm - External EventUINT16Read0 = NoAlarm; 1 = Alarm
HR746doc 747Circuit 1 Alarm - No Pressure change at StartUINT16Read0 = NoAlarm; 1 = Alarm
HR747doc 748Circuit 2 Alarm - No Pressure change at StartUINT16Read0 = NoAlarm; 1 = Alarm
HR750doc 751Circuit 1 Alarm - Pahse VoltageUINT16Read0 = NoAlarm; 1 = Alarm
HR751doc 752Circuit 2 Alarm - Pahse VoltageUINT16Read0 = NoAlarm; 1 = Alarm
HR761doc 762Circ 1 Compr 1 Alarm - VFD FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR763doc 764Circ 2 Compr 1 Alarm - VFD FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR767doc 768Circ 1 Compr 1 Alarm - VFD High TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR769doc 770Circ 2 Compr 1 Alarm - VFD High TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR773doc 774Circ 1 Compr 1 Alarm - VFD Communication FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR775doc 776Circ 2 Compr 1 Alarm - VFD Communication FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR779doc 780Circ 1 Comp 1 Warning - Inhibition for High Current AbsorptionINT16Read0 = NoAlarm; 1 = Alarm
HR781doc 782Circ 2 Comp 1 Warning - Inhibition for High Current AbsorptionINT16Read0 = NoAlarm; 1 = Alarm
HR797doc 798Unit Alarm - Emergency Stop SwitchUINT16Read0 = NoAlarm; 1 = Alarm
HR798doc 799Unit Alarm - Evaporator Temperature Sensors InvertedUINT16Read0 = NoAlarm; 1 = Alarm
HR799doc 800Unit Alarm - External AlarmUINT16Read0 = NoAlarm; 1 = Alarm
HR807doc 808Circ 1 Compr 1 Problem - Low Discharge SuperheatUINT16Read0 = NoAlarm; 1 = Alarm
HR809doc 810Circ 2 Compr 1 Problem - Low Discharge SuperheatUINT16Read0 = NoAlarm; 1 = Alarm
HR813doc 814Unit Warning - Curennt Limit Input Out Of RangeUINT16Read0 = NoAlarm; 1 = Alarm
HR829doc 830Circuit 1 Alarm - VFD Card High TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR830doc 831Circuit 2 Alarm - VFD Card High TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR874doc 875Unit Warning - Gas LeakageUINT16Read0 = NoAlarm; 1 = Alarm
HR897doc 898Controller Alarm - Energy Meter Communication FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR903doc 904Controller Alarm - Rapid Restart Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR904doc 905Controller Alarm - Marine Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR1799doc 1800Circ 2 Compressor 1 - Actual CapacityINT16× 0.1%Read
HR1800doc 1801Circ 2 Compressor 1 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1801doc 1802Circ 2 Compressor 1 - Full Load StateUINT16Read0 = Normal; 1 = Full Load
HR1804doc 1805Circ 2 Compressor 1 - VFD OutputINT16%Read
HR1808doc 1809Circ 2 Compressor 1 - Oil Feed PressureINT16× 0.1kPaRead
HR1810doc 1811Circ 2 Compressor 1 - Oil Level StateUINT16Read0 = Off; 1 = On
HR1811doc 1812Circ 2 Compressor 1 - Operating StateUINT16Read0 = Off; 1 = On
HR1839doc 1840Circ 1 Compressor 1 - Actual CapacityINT16× 0.1%Read
HR1840doc 1841Circ 1 Compressor 1 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1841doc 1842Circ 1 Compressor 1 - Full Load StateUINT16Read0 = Normal; 1 = Full Load
HR1844doc 1845Circ 1 Compressor 1 - VFD OutputINT16HzRead
HR1848doc 1849Circ 1 Compressor 1 - Oil Feed PressureINT16× 0.1kPaRead
HR1850doc 1851Circ 1 Compressor 1 - Oil Level StateUINT16Read0 = Off; 1 = On
HR1851doc 1852Circ 1 Compressor 1 - Operating StateUINT16Read0 = Off; 1 = On
HR1853doc 1854Unit - Refrigerant typeUINT16Read1 = R22; 2 = R134a; 3 = R407c; 4 = R410a; 5 = R1234ze; 6 = resv3; 7 = R513a
HR1854doc 1855Unit - Number of CircuitsRange 1-2.INT16Read
HR1856doc 1857Unit - Number of TonsINT16kWRead
HR1895doc 1896Circuit 2 - Evaporator Superheat Active SetpointINT16× 0.1dKRead
HR1896doc 1897Circuit 1 - Evaporator Superheat Active SetpointINT16× 0.1dKRead
HR1897doc 1898Circuit 2 - Evaporator Superheat TemperatureINT16× 0.1dKRead
HR1898doc 1899Circuit 1 - Evaporator Superheat TemperatureINT16× 0.1dKRead
HR1901doc 1902Unit - Power FactorINT16× 0.01Read
HR1965doc 1966Circuit 2 - Expansion Valve PositionINT16%Read
HR1970doc 1971Circuit 2 - Condenser Approach TemperatureINT16× 0.1dKRead
HR1971doc 1972Circuit 2 - Evaporator Approach TemperatureINT16× 0.1dKRead
HR1981doc 1982Circuit 1 - Expansion Valve PositionINT16%Read
HR1986doc 1987Circuit 1 - Condenser Approach TemperatureINT16× 0.1dKRead
HR1987doc 1988Circuit 1 - Evaporator Approach TemperatureINT16× 0.1dKRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)

What Modbus registers does the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) have?

This map lists 198 registers: 198 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide's address column is headed (4xxxx): the column value 1 is holding register 40001 = wire address 0. Subtract 1 from the column value for the PDU address.

What are the minimum Modbus registers to integrate the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)?

Start with HR 14 Unit - Status (Unit status); HR 16 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); HR 19 Condenser Leaving Water Temperature (Condenser leaving water temperature); HR 12 Unit - Actual Capacity (Actual capacity); HR 8 Unit - Enable Setpoint (Unit enable command); HR 34 Unit - Cool Temperature Setpoint (Cooling temperature setpoint); HR 32 Unit Alarm - Fault Code (Active fault code).

How do I enable Modbus control of the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)?

Fit a POL902 module and set the Modbus parameters under Main menu > Commissioning > Modbus (service password); or on Microtech 4 turn on software option #1 'Modbus Slave MSTP' (unlock password needed) and set it under Commissioning > Commission Unit > SW Modbus MSTP.

Where is the official Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus documentation?

The source is BAS integration guide - Modbus protocol, EWWD(H)(S)_VZ (Adam) (D-EIGOC00201-22_03EN), published free by Daikin Applied at https://www.daikinapplied.eu/hubfs/portale-documentale/D_EIGOC00201_22_03EN_VZ.pdf.

More Daikin Applied Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: BAS integration guide - Modbus protocol, EWWD(H)(S)_VZ (Adam) · D-EIGOC00201-22_03EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.