- EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
Chiller (water-cooled) · Modbus register map
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus register map
Updated 17 November 2026
Daikin Applied Europe's EWWD(H)(S)-VZ water-cooled inverter screw chillers expose a Modbus RTU slave on RS-485 through a POL902 module or, on Microtech 4, a licensed on-board option. All points are 16-bit holding registers covering unit and circuit status, evaporator and condenser water temperatures, refrigerant pressures, compressor current/power/VFD data, setpoints, pump states and individual alarm flags.
This page lists 198 Modbus registers for the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin Applied
- Model
- EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
- Equipment type
- Chiller (water-cooled)
- Registers
- 198 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Firmware
- Adam control software (no version printed)
- Also known as
- EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam
Integration notes: Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
Read holding registers from wire address 0: Unit Status (col 15), evaporator leaving water (col 17) and capacity (col 13). Enable with col 9 and write the cooling setpoint to col 35 in tenths of °C.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 14 | Unit - Status | UINT16 | Unit status | Read |
| HR 16 | Evaporator Leaving Water Temperature | INT16 | Evaporator leaving water temperature | Read |
| HR 19 | Condenser Leaving Water Temperature | INT16 | Condenser leaving water temperature | Read |
| HR 12 | Unit - Actual Capacity | INT16 | Actual capacity | Read |
| HR 8 | Unit - Enable Setpoint | UINT16 | Unit enable command | Read/write |
| HR 34 | Unit - Cool Temperature Setpoint | INT16 | Cooling temperature setpoint | Read/write |
| HR 32 | Unit Alarm - Fault Code | INT16 | Active fault code | Read |
Enable Modbus control & writes
Fit a POL902 module and set the Modbus parameters under Main menu > Commissioning > Modbus (service password); or on Microtech 4 turn on software option #1 'Modbus Slave MSTP' (unlock password needed) and set it under Commissioning > Commission Unit > SW Modbus MSTP.
Byte order & addressing
- Addresses are Modicon-style: subtract 1 from the guide's column value.
- Several 0.1-gain values (capacity, temperatures, pressures) are signed words.
Network setup
- POL902 module defaults: address 1, no parity, 2 stop bits, 19200 baud, 5 ms response delay.
- Software-option defaults: 19200 baud, no parity, 1 stop bit, 100 ms delay and timeout.
Watch out for
- Running hours, energy and thermal capacity are 32-bit points with no stated word order; they are not in this map.
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Unit - Control Source | UINT16 | Read | 0 = Network; 1 = Local | ||||
| HR | 1doc 2 | Unit - Enabled State | UINT16 | Read | 0 = Disabled; 1 = Enabled | ||||
| HR | 2doc 3 | Unit - Run Allowed | UINT16 | Read | 0 = Off; 1 = RunAllowed | ||||
| HR | 3doc 4 | Unit - Capacity Limited | UINT16 | Read | 0 = NotLimited; 1 = Limited | ||||
| HR | 4doc 5 | Unit - Alarm Output | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 5doc 6 | Evaporator - Water Flow State | UINT16 | Read | 0 = NoFlow; 1 = Flow | ||||
| HR | 6doc 7 | Condenser - Water Flow State | UINT16 | Read | 0 = NoFlow; 1 = Flow | ||||
| HR | 7doc 8 | Unit - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8doc 9 | Unit - Enable Setpoint | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 9doc 10 | Unit - Alarm Reset Setpoint | UINT16 | Read/write | 0 = None; 1 = ClearAlarm | ||||
| HR | 10doc 11 | Unit - Active Operation Mode | UINT16 | Read | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Pursuit | ||||
| HR | 11doc 12 | Unit - Active Temperature Setpoint | INT16 | × 0.1 | °C | Read | |||
| HR | 12doc 13 | Unit - Actual Capacity | INT16 | × 0.1 | % | Read | |||
| HR | 13doc 14 | Unit - Active Capacity Limit | INT16 | × 0.1 | % | Read | |||
| HR | 14doc 15 | Unit - Status | UINT16 | Read | 1 = Off; 2 = Start; 3 = Run; 4 = PreShutdown; 5 = Service | ||||
| HR | 15doc 16 | Evaporator Entering Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 16doc 17 | Evaporator Leaving Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 18doc 19 | Condenser Entering Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 19doc 20 | Condenser Leaving Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 24doc 25 | Unit - Average Current | INT16 | A | Read | ||||
| HR | 25doc 26 | Unit - Average Voltage | INT16 | × 0.1 | V | Read | |||
| HR | 26doc 27 | Unit - Active Power | INT16 | × 0.1 | kW | Read | |||
| HR | 27doc 28 | Unit Alarm - Warning Index | Numeric code; see the alarm code and index table in section 5.1. | INT16 | Read | ||||
| HR | 28doc 29 | Unit Alarm - Problem Index | Numeric code; see the alarm code and index table in section 5.1. | INT16 | Read | ||||
| HR | 29doc 30 | Unit Alarm - Fault Index | Numeric code; see the alarm code and index table in section 5.1. | INT16 | Read | ||||
| HR | 30doc 31 | Unit Alarm - Warning Code | Numeric code; see the alarm code and index table in section 5.1. | INT16 | Read | ||||
| HR | 31doc 32 | Unit Alarm - Problem Code | Numeric code; see the alarm code and index table in section 5.1. | INT16 | Read | ||||
| HR | 32doc 33 | Unit Alarm - Fault Code | Numeric code; see the alarm code and index table in section 5.1. | INT16 | Read | ||||
| HR | 33doc 34 | Unit - Operation Mode Setpoint | UINT16 | Read/write | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Pursuit | ||||
| HR | 34doc 35 | Unit - Cool Temperature Setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 35doc 36 | Unit - Ice Temperature Setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 36doc 37 | Unit - Heat Temperature Setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 37doc 38 | Unit - Capacity Limit Setpoint | INT16 | × 0.1 | % | Read/write | |||
| HR | 38doc 39 | Circuit 1 - Condenser Refrigerant Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 39doc 40 | Circuit 1 - Condeser Saturated Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 40doc 41 | Circuit 1 - Evaporator Refrigerant Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 41doc 42 | Circuit 1 - Evaporator Saturated Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 42doc 43 | Circuit 2 - Condenser Refrigerant Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 43doc 44 | Circuit 2 - Condeser Saturated Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 44doc 45 | Circuit 2 - Evaporator Refrigerant Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 45doc 46 | Circuit 2 - Evaporator Saturated Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 50doc 51 | Circuit 1 - Shutdown Alarm | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 51doc 52 | Circuit 2 - Shutdown Alarm | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 64doc 65 | Circ 1 Compressor 1 - Suction Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 67doc 68 | Circ 1 Compressor 1 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 68doc 69 | Circ 1 Compressor 1 - RLA Percentage | INT16 | % | Read | ||||
| HR | 69doc 70 | Circ 1 Compressor 1 - Current | INT16 | A | Read | ||||
| HR | 70doc 71 | Circ 1 Compressor 1 - Voltage | INT16 | V | Read | ||||
| HR | 71doc 72 | Circ 1 Compressor 1 - Power | INT16 | kW | Read | ||||
| HR | 72doc 73 | Circ 1 Compressor 1 - Number of Starts | UINT16 | Read/write | |||||
| HR | 103doc 104 | Circ 2 Compressor 1 - Suction Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 106doc 107 | Circ 2 Compressor 1 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 107doc 108 | Circ 2 Compressor 1 - RLA Percentage | INT16 | % | Read | ||||
| HR | 108doc 109 | Circ 2 Compressor 1 - Current | INT16 | A | Read | ||||
| HR | 109doc 110 | Circ 2 Compressor 1 - Voltage | INT16 | V | Read | ||||
| HR | 110doc 111 | Circ 2 Compressor 1 - Power | INT16 | kW | Read | ||||
| HR | 111doc 112 | Circ 2 Compressor 1 - Number of Starts | UINT16 | Read/write | |||||
| HR | 263doc 264 | Performance - Unit Efficiency | UINT16 | × 0.01 | Read | ||||
| HR | 264doc 265 | Performance - Unit Integrated Efficiency | UINT16 | × 0.01 | Read | ||||
| HR | 298doc 299 | Condenser Pump 1 - Operating State | UINT16 | Read | 0 = OffRequest; 1 = OnRequest | ||||
| HR | 301doc 302 | Condenser Pump 2 - Operating State | UINT16 | Read | 0 = OffRequest; 1 = OnRequest | ||||
| HR | 304doc 305 | Evaporator Pump 1 - Operating State | UINT16 | Read | 0 = OffRequest; 1 = OnRequest | ||||
| HR | 307doc 308 | Evaporator Pump 2 - Operating State | UINT16 | Read | 0 = OffRequest; 1 = OnRequest | ||||
| HR | 315doc 316 | Unit - Measurement unit setpoint | UINT16 | Read/write | 0 = English; 1 = Metric | ||||
| HR | 316doc 317 | Unit - Model | UINT16 | Read | 0 = Centrifugal; 1 = Water Cooled; 2 = Air Cooled; 3 = HeatPump; 4 = Reserved; 5 = Reserved; 6 = Reserved; 7 = Reserved; 8 = Other | ||||
| HR | 364doc 365 | Unit Alarm - Condenser Entering Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 365doc 366 | Unit Alarm - Evaporator Entering Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 367doc 368 | Unit Alarm - Condenser Leaving Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 376doc 377 | Unit Warning - Setpoint Reset Input Out of Range | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 377doc 378 | Unit Warning - Demand Limit Input Out of Range | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 383doc 384 | Circuit 1 Warning - Power Loss while Compressor Running | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 384doc 385 | Circuit 2 Warning - Power Loss while Compressor Running | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 389doc 390 | Circuit 1 Warning - Inhibition for Condenser High Pressure | INT16 | kPa | Read | ||||
| HR | 390doc 391 | Circuit 2 Warning - Inhibition for Condenser High Pressure | INT16 | kPa | Read | ||||
| HR | 394doc 395 | Circuit 1 Warning - Unload for Condenser High Pressure | INT16 | kPa | Read | ||||
| HR | 395doc 396 | Circuit 2 Warning - Unload for Condenser High Pressure | INT16 | kPa | Read | ||||
| HR | 410doc 411 | Circuit 1 Warning - Inhibition for Evaporator Low Pressure | INT16 | kPa | Read | ||||
| HR | 411doc 412 | Circuit 2 Warning - Inhibition for Evaporator Low Pressure | INT16 | kPa | Read | ||||
| HR | 415doc 416 | Circuit 1 Warning - Unload for Evaporator Low Pressure | INT16 | kPa | Read | ||||
| HR | 416doc 417 | Circuit 2 Warning - Unload for Evaporator Low Pressure | INT16 | kPa | Read | ||||
| HR | 419doc 420 | Circ 1 Comp 1 Warning - Unload for High Current | INT16 | A | Read | ||||
| HR | 421doc 422 | Circ 2 Comp 1 Warning - Unload for High Current | INT16 | A | Read | ||||
| HR | 427doc 428 | Condenser Pump 1 - Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 428doc 429 | Condenser Pump 2 - Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 429doc 430 | Evaporator Pump 1 - Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 430doc 431 | Evaporator Pump 2 - Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 439doc 440 | Circ 1 Comp 1 Alarm - Low Pressure Ratio | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 441doc 442 | Circ 2 Comp 1 Alarm - Low Pressure Ratio | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 446doc 447 | Circ 1 Comp 1 Alarm - High Motor Current | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 448doc 449 | Circ 2 Comp 1 Alarm - High Motor Current | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 477doc 478 | Circ 1 Comp 1 Alarm - High Motor Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 479doc 480 | Circ 2 Comp 1 Alarm - High Motor Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 508doc 509 | Circuit 1 Alarm - Condenser Pressure Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 510doc 511 | Circuit 2 Alarm - Condenser Pressure Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 513doc 514 | Unit Alarm - Condenser Water Freeze | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 514doc 515 | Unit Alarm - Condenser Water Flow Loss | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 516doc 517 | Circuit 1 Alarm - Condenser High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 518doc 519 | Circuit 2 Alarm - Condenser High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 528doc 529 | Circuit 1 Alarm - Discharge Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 530doc 531 | Circuit 2 Alarm - Discharge Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 534doc 535 | Circ 1 Comp 1 Alarm - High Discharge Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 536doc 537 | Circ 2 Comp 1 Alarm - High Discharge Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 541doc 542 | Unit Alarm - Evaporator Water Flow Loss | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 542doc 543 | Unit Alarm - Evaporator Water Freeze | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 544doc 545 | Circuit 1 Alarm - Evaporator Pressure Low | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 546doc 547 | Circuit 2 Alarm - Evaporator Pressure Low | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 551doc 552 | Circuit 1 Alarm - Evaporator Pressure Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 553doc 554 | Circuit 2 Alarm - Evaporator Pressure Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 582doc 583 | Circuit 1 Alarm - Too many restart | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 584doc 585 | Circuit 2 Alarm - Too many restart | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 588doc 589 | Unit Alarm - Evaporator Leaving Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 600doc 601 | Circuit 1 Alarm - Mechanical High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 602doc 603 | Circuit 2 Alarm - Mechanical High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 630doc 631 | Circuit 1 Alarm - Oil Level Low | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 632doc 633 | Circuit 2 Alarm - Oil Level Low | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 636doc 637 | Circuit 1 Alarm - Oil Filter High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 638doc 639 | Circuit 2 Alarm - Oil Filter High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 642doc 643 | Circuit 1 Alarm - Oil Pressure Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 644doc 645 | Circuit 2 Alarm - Oil Pressure Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 651doc 652 | Circuit 1 Alarm - Liquid Temperature Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 654doc 655 | Circuit 2 Alarm - Liquid Temperature Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 660doc 661 | Unit Alarm - Phase Voltage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 661doc 662 | Circ 1 Comp 1 Alarm - Starter Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 663doc 664 | Circ 2 Comp 1 Alarm - Starter Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 666doc 667 | Circuit 1 Alarm - OverVoltage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 667doc 668 | Circuit 2 Alarm - OverVoltage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 669doc 670 | Circuit 1 Alarm - UnderVoltage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 670doc 671 | Circuit 2 Alarm - UnderVoltage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 697doc 698 | Circ 1 Comp 1 Alarm - Suction Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 699doc 700 | Circ 2 Comp 1 Alarm - Suction Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 710doc 711 | Circuit 1 Alarm - No Pressure at Start | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 711doc 712 | Circuit 2 Alarm - No Pressure at Start | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 716doc 717 | Circuit 1 Alarm - Mechanical Low Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 718doc 719 | Circuit 2 Alarm - Mechanical Low Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 722doc 723 | Controller Alarm - Circuit 1 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 723doc 724 | Controller Alarm - Circuit 2 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 725doc 726 | Controller Alarm - Expansion Valve 1 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 726doc 727 | Controller Alarm - Expansion Valve 2 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 728doc 729 | Controller Alarm - Compressor 1 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 729doc 730 | Controller Alarm - Compressor 2 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 733doc 734 | Circ 1 Comp1 Alarm - Motor Temperature Sesnor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 735doc 736 | Circ 2 Comp1 Alarm - Motor Temperature Sesnor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 739doc 740 | Unit - Power Restore | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 740doc 741 | Circuit 1 Alarm - Pumpdown Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 741doc 742 | Circuit 2 Alarm - Pumpdown Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 744doc 745 | Unit Alarm - External Event | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 746doc 747 | Circuit 1 Alarm - No Pressure change at Start | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 747doc 748 | Circuit 2 Alarm - No Pressure change at Start | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 750doc 751 | Circuit 1 Alarm - Pahse Voltage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 751doc 752 | Circuit 2 Alarm - Pahse Voltage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 761doc 762 | Circ 1 Compr 1 Alarm - VFD Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 763doc 764 | Circ 2 Compr 1 Alarm - VFD Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 767doc 768 | Circ 1 Compr 1 Alarm - VFD High Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 769doc 770 | Circ 2 Compr 1 Alarm - VFD High Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 773doc 774 | Circ 1 Compr 1 Alarm - VFD Communication Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 775doc 776 | Circ 2 Compr 1 Alarm - VFD Communication Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 779doc 780 | Circ 1 Comp 1 Warning - Inhibition for High Current Absorption | INT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 781doc 782 | Circ 2 Comp 1 Warning - Inhibition for High Current Absorption | INT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 797doc 798 | Unit Alarm - Emergency Stop Switch | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 798doc 799 | Unit Alarm - Evaporator Temperature Sensors Inverted | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 799doc 800 | Unit Alarm - External Alarm | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 807doc 808 | Circ 1 Compr 1 Problem - Low Discharge Superheat | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 809doc 810 | Circ 2 Compr 1 Problem - Low Discharge Superheat | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 813doc 814 | Unit Warning - Curennt Limit Input Out Of Range | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 829doc 830 | Circuit 1 Alarm - VFD Card High Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 830doc 831 | Circuit 2 Alarm - VFD Card High Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 874doc 875 | Unit Warning - Gas Leakage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 897doc 898 | Controller Alarm - Energy Meter Communication Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 903doc 904 | Controller Alarm - Rapid Restart Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 904doc 905 | Controller Alarm - Marine Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 1799doc 1800 | Circ 2 Compressor 1 - Actual Capacity | INT16 | × 0.1 | % | Read | |||
| HR | 1800doc 1801 | Circ 2 Compressor 1 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1801doc 1802 | Circ 2 Compressor 1 - Full Load State | UINT16 | Read | 0 = Normal; 1 = Full Load | ||||
| HR | 1804doc 1805 | Circ 2 Compressor 1 - VFD Output | INT16 | % | Read | ||||
| HR | 1808doc 1809 | Circ 2 Compressor 1 - Oil Feed Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 1810doc 1811 | Circ 2 Compressor 1 - Oil Level State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1811doc 1812 | Circ 2 Compressor 1 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1839doc 1840 | Circ 1 Compressor 1 - Actual Capacity | INT16 | × 0.1 | % | Read | |||
| HR | 1840doc 1841 | Circ 1 Compressor 1 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1841doc 1842 | Circ 1 Compressor 1 - Full Load State | UINT16 | Read | 0 = Normal; 1 = Full Load | ||||
| HR | 1844doc 1845 | Circ 1 Compressor 1 - VFD Output | INT16 | Hz | Read | ||||
| HR | 1848doc 1849 | Circ 1 Compressor 1 - Oil Feed Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 1850doc 1851 | Circ 1 Compressor 1 - Oil Level State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1851doc 1852 | Circ 1 Compressor 1 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1853doc 1854 | Unit - Refrigerant type | UINT16 | Read | 1 = R22; 2 = R134a; 3 = R407c; 4 = R410a; 5 = R1234ze; 6 = resv3; 7 = R513a | ||||
| HR | 1854doc 1855 | Unit - Number of Circuits | Range 1-2. | INT16 | Read | ||||
| HR | 1856doc 1857 | Unit - Number of Tons | INT16 | kW | Read | ||||
| HR | 1895doc 1896 | Circuit 2 - Evaporator Superheat Active Setpoint | INT16 | × 0.1 | dK | Read | |||
| HR | 1896doc 1897 | Circuit 1 - Evaporator Superheat Active Setpoint | INT16 | × 0.1 | dK | Read | |||
| HR | 1897doc 1898 | Circuit 2 - Evaporator Superheat Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1898doc 1899 | Circuit 1 - Evaporator Superheat Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1901doc 1902 | Unit - Power Factor | INT16 | × 0.01 | Read | ||||
| HR | 1965doc 1966 | Circuit 2 - Expansion Valve Position | INT16 | % | Read | ||||
| HR | 1970doc 1971 | Circuit 2 - Condenser Approach Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1971doc 1972 | Circuit 2 - Evaporator Approach Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1981doc 1982 | Circuit 1 - Expansion Valve Position | INT16 | % | Read | ||||
| HR | 1986doc 1987 | Circuit 1 - Condenser Approach Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1987doc 1988 | Circuit 1 - Evaporator Approach Temperature | INT16 | × 0.1 | dK | Read |
Notes on this map
- Addressing: the guide says every point is a holding register addressed as 4xxxx plus the number in its Address column, i.e. Modicon references (1 = 40001). On the wire that is the column value minus 1. Registers are listed here with that wire address; the documented field keeps the guide's column value.
- Values are 16-bit words; 'Gain' is the multiplier (0.1 means tenths of a unit). Temperatures and pressures are shown in metric units; the 'Measurement unit setpoint' register (column 316) switches the unit system between English and Metric.
- The Read/Write column only uses R and W; W points are taken as writable (and readable) and listed as RW.
- Left out: every 'UNSIGNED DOUBLE' (32-bit) point (74-75 Circ 1 Compressor 1 - Number of Running Hours (32-bit); 113-114 Circ 2 Compressor 1 - Number of Running Hours (32-bit); 260-261 Performance - Unit Thermal Capacity (32-bit); 262-263 Performance - Unit Power Input (32-bit); 266-267 Performance - Unit Thermal Energy (32-bit); 268-269 Performance - Unit Electrical Energy (32-bit); 297 Condenser Pump 1 - Number of Running Hours (32-bit); 300-301 Condenser Pump 2 - Number of Running Hours (32-bit); 303-303 Evaporator Pump 1 - Number of Running Hours (32-bit); 306-307 Evaporator Pump 2 - Number of Running Hours (32-bit); 1900-1901 Unit - Active Energy (32-bit)). The guide does not say which word is high, and some address spans are misprinted, so they cannot be decoded safely from this document.
- Left out: the alarm code/index table in section 5.1; the Warning/Problem/Fault Index and Code registers are listed, but their meanings need that table.
- The 'Number of Tons' point (col 1857) is printed with unit kW; it is listed as printed.
- Circuit 1 compressor VFD output (col 1845) is printed in Hz while circuit 2 (col 1805) is printed in %; both are listed as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
What Modbus registers does the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) have?
This map lists 198 registers: 198 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide's address column is headed (4xxxx): the column value 1 is holding register 40001 = wire address 0. Subtract 1 from the column value for the PDU address.
What are the minimum Modbus registers to integrate the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)?
Start with HR 14 Unit - Status (Unit status); HR 16 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); HR 19 Condenser Leaving Water Temperature (Condenser leaving water temperature); HR 12 Unit - Actual Capacity (Actual capacity); HR 8 Unit - Enable Setpoint (Unit enable command); HR 34 Unit - Cool Temperature Setpoint (Cooling temperature setpoint); HR 32 Unit Alarm - Fault Code (Active fault code).
How do I enable Modbus control of the Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)?
Fit a POL902 module and set the Modbus parameters under Main menu > Commissioning > Modbus (service password); or on Microtech 4 turn on software option #1 'Modbus Slave MSTP' (unlock password needed) and set it under Commissioning > Commission Unit > SW Modbus MSTP.
Where is the official Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software) Modbus documentation?
The source is BAS integration guide - Modbus protocol, EWWD(H)(S)_VZ (Adam) (D-EIGOC00201-22_03EN), published free by Daikin Applied at https://www.daikinapplied.eu/hubfs/portale-documentale/D_EIGOC00201_22_03EN_VZ.pdf.
More Daikin Applied Modbus register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121
Other chillers & heat pumps register maps
- Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).
Also known as: WTX, TBX - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001 - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump
All chillers & heat pumps Modbus register maps →
Source: BAS integration guide - Modbus protocol, EWWD(H)(S)_VZ (Adam) · D-EIGOC00201-22_03EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.