  4. Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)

Chiller · Modbus register map

Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus register map

Updated 19 November 2026

Short answer

Trane's Ascend ACS is an air-cooled scroll chiller and the ACX its reversible air-to-water heat-pump version. Both use a Symbio 800 controller that serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (water and refrigerant temperatures, pressures, capacity, starts and run time, energy meter values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.

This page lists 397 Modbus registers for the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Equipment type
Chiller
Registers
397 (16 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump
Source document
Symbio 800 Integration Points List, BACnet/Modbus, Ascend Models ACS and ACX · BAS-PTS011A-EN · rev. 2024-11-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Cool/Heat Setpoint TemperatureFLOAT32 ABCDActive cool/heat setpointRead
IR 12Evaporator Leaving Water TemperatureFLOAT32 ABCDEvaporator leaving water temperatureRead
IR 14Evaporator Entering Water TemperatureFLOAT32 ABCDEvaporator entering water temperatureRead
IR 42Actual Running CapacityFLOAT32 ABCDActual running capacityRead
IR 20Outdoor Air TemperatureFLOAT32 ABCDOutdoor air temperatureRead
IR 2010Chiller Running StatusUINT16Chiller running statusRead
IR 3036Diagnostic PresentUINT16Diagnostic presentRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 2010BAS Chiller Mode CommandUINT16BAS chiller mode commandRead/write
HR 3010Reset DiagnosticUINT16Reset diagnosticRead/write

Enable Modbus control & writes

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Byte order & addressing

Network setup

Watch out for

Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

397 of 397 shown
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Cool/Heat Setpoint TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Evaporator Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR14doc 30015Evaporator Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR16doc 30017Active Demand Limit SetpointNeeds: Ice Building = Not InstalledFLOAT32ABCD%Read
IR18doc 30019Unit Power ConsumptionElectrical power. Needs: Energy Meter - Pulse Input Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR20doc 30021Outdoor Air TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR22doc 30023Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR24doc 30025Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR26doc 30027Differential Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR28doc 30029Evaporator Saturated Rfgt Temp Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR30doc 30031Condenser Saturated Rfgt Temp Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR32doc 30033Evaporator Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR34doc 30035Condenser Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR36doc 30037Differential Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR38doc 30039Evaporator Saturated Rfgt Temp Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR40doc 30041Condenser Saturated Rfgt Temp Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR42doc 30043Actual Running CapacityFLOAT32ABCD%Read
IR44doc 30045Active Heat Recovery SetpointTemperature in the factory unit system (I-P or SI). Needs: Total Heat RecoveryFLOAT32ABCDRead
IR46doc 30047Active Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water Control (Heat Pump)FLOAT32ABCDRead
IR48doc 30049Air Flow Circuit 1FLOAT32ABCD%Read
IR50doc 30051Air Flow Circuit 2FLOAT32ABCD%Read
IR52doc 30053Starts Cprsr1AFLOAT32ABCDRead
IR54doc 30055Running Time Cprsr1AFLOAT32ABCDRead
IR56doc 30057Starts Cprsr2AFLOAT32ABCDRead
IR58doc 30059Running Time Cprsr2AFLOAT32ABCDRead
IR60doc 30061Heat Recovery Entering Water TempTemperature in the factory unit system (I-P or SI). Needs: Total Heat Recovery Partial Heat RecoveryFLOAT32ABCDRead
IR62doc 30063Heat Recovery Leaving Water TempTemperature in the factory unit system (I-P or SI). Needs: Total Heat Recovery Partial Heat RecoveryFLOAT32ABCDRead
IR64doc 30065Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR66doc 30067Starts Cprsr1BFLOAT32ABCDRead
IR68doc 30069Running Time Cprsr1BFLOAT32ABCDRead
IR70doc 30071Starts Cprsr2BFLOAT32ABCDRead
IR72doc 30073Running Time Cprsr2BFLOAT32ABCDRead
IR74doc 30075Number Of CircuitsFLOAT32ABCDRead
IR76doc 30077Number of Compressors for Circuit 1FLOAT32ABCDRead
IR78doc 30079Number of Compressors for Circuit 2FLOAT32ABCDRead
IR80doc 30081Free Cooling CapacityNeeds: Free CoolingFLOAT32ABCD%Read
IR82doc 30083Free Cooling Entering Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR84doc 30085Free Cooling Entering Glycol TemperatureTemperature in the factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR86doc 30087Free Cooling Leaving Glycol TemperatureTemperature in the factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR88doc 30089Energy Consumption NonResetElectrical power. Needs: Energy Meter - Pulse Input Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR90doc 30091Energy Consumption ResettableElectrical power. Needs: Energy Meter - Pulse Input Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR92doc 30093Starts Cprsr1CNeeds: Circuit 1 = 3 compressorsFLOAT32ABCDRead
IR94doc 30095Running Time Cprsr1CNeeds: Circuit 1 = 3 compressorsFLOAT32ABCDRead
IR96doc 30097Starts Cprsr2CNeeds: Circuit 2 = 3 compressorsFLOAT32ABCDRead
IR98doc 30099Running Time Cprsr2CNeeds: Circuit 2 = 3 compressorsFLOAT32ABCDRead
IR100doc 30101Estimated Discharge Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp Sensor = Not InstalledFLOAT32ABCDRead
IR102doc 30103Estimated Discharge Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp Sensor = Not InstalledFLOAT32ABCDRead
IR104doc 30105Compressor Discharge Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp Sensor = InstalledFLOAT32ABCDRead
IR106doc 30107Compressor Discharge Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp Sensor = InstalledFLOAT32ABCDRead
IR108doc 30109Free Cooling Glycol PressurePressure in the factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR110doc 30111Unit Source IDFLOAT32ABCDRead
IR112doc 30113Unit Load CommandFLOAT32ABCD%Read
IR114doc 30115Average Line Current Meter 1Current. Needs: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR116doc 30117Average Line Voltage Meter 1Voltage. Needs: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR118doc 30119Meter Line Current L1Current. Needs: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR120doc 30121Meter Line Current L2Current. Needs: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR122doc 30123Meter Line Current L3Current. Needs: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR124doc 30125Meter Line Voltage L1-L2Voltage. Needs: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR126doc 30127Meter Line Voltage L2-L3Voltage. Needs: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR128doc 30129Meter Line Voltage L1-L3Voltage. Needs: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR130doc 30131Chiller Power DemandElectrical power. Needs: Energy Meter - Pulse Input Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR132doc 30133Unit Line FrequencyNeeds: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR134doc 30135Unit Power FactorNeeds: Energy Meter - Schneider ModbusFLOAT32ABCDRead
IR136doc 30137Heat Recovery Valve PositionNeeds: Total Heat RecoveryFLOAT32ABCD%Read
IR138doc 30139Evaporator Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR140doc 30141Condenser Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR142doc 30143Evaporator Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR144doc 30145Condenser Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR146doc 30147Free Cooling Glycol Absolute PressurePressure in the factory unit system (I-P or SI). Needs: Free CoolingFLOAT32ABCDRead
IR148doc 30149Supplemental Heater StatusNeeds: Supplemental HeaterFLOAT32ABCD%Read
IR150doc 30151Evaporator Approach Temperature Circuit 1 (Cooling Mode Only)Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR152doc 30153Evaporator Approach Temperature Circuit 2 (Cooling Mode Only)Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR154doc 30155Condenser Approach Temperature Circuit 1 (Heating Mode Only)Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR156doc 30157Condenser Approach Temperature Circuit 2 (Heating Mode Only)Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR158doc 30159Active Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR160doc 30161Chilled Water Setpoint StatusTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR162doc 30163Hot Water Setpoint StatusTemperature in the factory unit system (I-P or SI). Needs: Hot Water Control (Heat Pump)FLOAT32ABCDRead
IR164doc 30165Demand Limit Setpoint StatusNeeds: Ice BuildingFLOAT32ABCD%Read
IR166doc 30167Active Demand Limit SetpointNeeds: Ice BuildingFLOAT32ABCD%Read
IR2010doc 32011Chiller Running StatusUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making
IR2012doc 32013Chiller Setpoint SourceUINT16Read1 = BAS; 2 = External; 3 = Front Panel
IR2013doc 32014Refrigerant TypeUINT16Read1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 6 = R-407C; 7 = R-410A; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 12 = R-404A; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A; 16 = R-1234z(E); 17 = R-454B; 18 = R-515B
IR2014doc 32015Cooling TypeUINT16Read1 = Water Cooled; 2 = Air Cooled
IR2015doc 32016Manufacture LocationUINT16Read1 = Field Applied; 2 = La Crosse; 3 = Pueblo; 4 = Charmes; 5 = Rushville; 6 = Macon; 7 = Waco; 8 = Lexington; 9 = Forsyth; 10 = Clarksville; 11 = Ft. Smith; 12 = Penang; 13 = Colchester; 14 = Curitiba; 15 = Taicang; 16 = Taiwan; 17 = Epinal; 18 = Golbey
IR2016doc 32017Front Panel Chiller Mode CommandUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making
IR2017doc 32018Model Information [GEN2]UINT16Read1 = CVHF; 2 = CVGF; 3 = CVHS; 4 = RTAE; 5 = RTAF; 6 = RTHA; 7 = RTHB; 8 = RTHC; 9 = RTHD; 10 = RTWE; 11 = CTVD; 12 = CVR; 13 = CVHH; 14 = CDHH; 15 = VMAX; 16 = GVAF; 17 = RTWF; 18 = RTHF; 19 = RTAC; 20 = CVHM; 21 = RTAG; 22 = CGAF; 23 = RTXG; 24 = GVWF; 25 = HDWA; 26 = CMAC; 27 = IPAK; 28 = CXAF; 29 = ACSA; 30 = RTSF; 31 = HSWA; 32 = ACRA; 33 = RTEG; 34 = ACXA; 35 = CMAF; 36 = ACRB Large; 37 = ACRB Small
IR2018doc 32019Circuit 1 StatusUINT16Read1 = Available; 2 = Heat Recovery; 3 = Cooling; 4 = Heating; 5 = Defrost; 6 = Not Available
IR2019doc 32020Circuit 2 StatusUINT16Read1 = Available; 2 = Heat Recovery; 3 = Cooling; 4 = Heating; 5 = Defrost; 6 = Not Available
IR3010doc 33011Limit Mode Relay StatusUINT16Read0 = Auto; 1 = On
IR3011doc 33012Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop - Manual Reset Required
IR3012doc 33013Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3013doc 33014Run EnableUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3014doc 33015Local Setpoint ControlUINT16Read0 = Remote control; 1 = Local control
IR3015doc 33016Maximum Capacity RelayUINT16Read0 = Off; 1 = On
IR3016doc 33017Running Status Cprsr1AUINT16Read0 = Off; 1 = Running
IR3017doc 33018Running Status Cprsr2AUINT16Read0 = Off; 1 = Running
IR3018doc 33019Running Status Cprsr1BUINT16Read0 = Off; 1 = Running
IR3019doc 33020Running Status Cprsr2BUINT16Read0 = Off; 1 = Running
IR3020doc 33021Chiller Running StateUINT16Read0 = Off; 1 = On
IR3021doc 33022Running Status Cprsr1CNeeds: Circuit 1 = 3 compressorsUINT16Read0 = Off; 1 = Running
IR3022doc 33023Running Status Cprsr2CNeeds: Circuit 2 = 3 compressorsUINT16Read0 = Off; 1 = Running
IR3023doc 33024Free Cooling ActiveNeeds: Free CoolingUINT16Read0 = Inactive; 1 = Active
IR3024doc 33025Heat Recovery ActiveNeeds: Total Heat RecoveryUINT16Read0 = Inactive; 1 = Active
IR3025doc 33026Front Panel Auto/StopUINT16Read0 = Stop; 1 = Auto
IR3026doc 33027Circuit Manual Reset Indicator (CMR) Circuit 1UINT16Read0 = Normal; 1 = In Alarm
IR3027doc 33028Circuit Manual Reset Indicator (CMR) Circuit 2UINT16Read0 = Normal; 1 = In Alarm
IR3028doc 33029Circuit Auto Reset Indicator (CAR) Circuit 1UINT16Read0 = Normal; 1 = In Alarm
IR3029doc 33030Circuit Auto Reset Indicator (CAR) Circuit 2UINT16Read0 = Normal; 1 = In Alarm
IR3030doc 33031Evaporator Water Pump CommandUINT16Read
IR3031doc 33032Evaporator Water Flow StatusUINT16Read
IR3032doc 33033Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3033doc 33034Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3034doc 33035Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3035doc 33036Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3036doc 33037Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3037doc 33038Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3038doc 33039Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3039doc 33040Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3040doc 33041External Auto StopUINT16Read0 = Stop; 1 = Auto
IR3041doc 33042Noise Reduction Request ActiveNeeds: Noise ReductionUINT16Read0 = Off; 1 = On
IR3042doc 33043Heat Recovery Request ActiveNeeds: Total Heat RecoveryUINT16Read0 = Off; 1 = On
IR3043doc 33044Evaporator Water Pump StatusUINT16Read0 = Off; 1 = On
IR3044doc 33045Circuit 1 Defrost Delay StatusNeeds: Hot Water Control (Heat Pump)UINT16Read0 = Off; 1 = On
IR3045doc 33046Circuit 2 Defrost Delay StatusNeeds: Hot Water Control (Heat Pump)UINT16Read0 = Off; 1 = On
IR3046doc 33047In DefrostNeeds: Hot Water Control (Heat Pump)UINT16Read0 = Not in Defrost; 1 = Defrost
IR3047doc 33048Circuit 1 Defrost StatusNeeds: Hot Water Control (Heat Pump)UINT16Read0 = Inactive; 1 = Active
IR3048doc 33049Circuit 2 Defrost StatusNeeds: Hot Water Control (Heat Pump)UINT16Read0 = Inactive; 1 = Active
IR3049doc 33050Circuit 1 Running StatusUINT16Read0 = Off; 1 = On
IR3050doc 33051Circuit 2 Running StatusUINT16Read0 = Off; 1 = On
IR3051doc 33052Low Ambient Lockout StatusUINT16Read0 = No Lockout; 1 = Lockout Present
IR3052doc 33053Circuit 1 Lockout Front PanelUINT16Read0 = Normal; 1 = Locked Out
IR3053doc 33054Circuit 2 Lockout Front PanelUINT16Read0 = Normal; 1 = Locked Out
IR3054doc 33055Circuit 1 Lockout ExternalNeeds: External Circuit LockoutUINT16Read0 = Normal; 1 = Locked Out
IR3055doc 33056Circuit 2 Lockout ExternalNeeds: External Circuit LockoutUINT16Read0 = Normal; 1 = Locked Out
IR3056doc 33057Circuit 1 Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR3057doc 33058Circuit 2 Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR4000doc 34001Diagnostic: Comm Loss: Percent Capacity OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Diagnostic: Comm Loss: Supplemental Heater Relay 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Diagnostic: Comm Loss: Supplemental Heater Relay 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Diagnostic: Comm Loss: Supplemental Heater Relay 3Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Diagnostic: Comm Loss: Supplemental Heater Relay 4Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Diagnostic: Comm Loss: Energy MeterDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Diagnostic: Comm Loss: Outdoor Air TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Diagnostic: Comm Loss: Phase Protection Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Diagnostic: Energy Meter Write Command FailureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Diagnostic: Outdoor Air Temperature SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Diagnostic: Phase Protection FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Diagnostic: Software Error 1003: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Diagnostic: Pumpdown Terminated By Time - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Diagnostic: Pumpdown Terminated By Time - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Diagnostic: Comm Loss: Discharge Pressure Transducer - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Diagnostic: Comm Loss: Discharge Pressure Transducer - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Diagnostic: Comm Loss: Discharge Temperature Sensor - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Diagnostic: Comm Loss: Discharge Temperature Sensor - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Diagnostic: Comm Loss: External Circuit 2 LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Diagnostic: Comm Loss: External Circuit 1 LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Diagnostic: Comm Loss: Reversing Valve - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Diagnostic: Comm Loss: Reversing Valve - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Diagnostic: Comm Loss: Suction Pressure Transducer - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Diagnostic: Comm Loss: Suction Pressure Transducer - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Diagnostic: Comm Loss: Suction Temperature - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Diagnostic: Comm Loss: Suction Temperature - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Diagnostic: Discharge Pressure Transducer - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Diagnostic: Discharge Pressure Transducer - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Diagnostic: Discharge Temperature Sensor - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Diagnostic: Discharge Temperature Sensor - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Diagnostic: Suction Pressure Transducer - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Diagnostic: Suction Pressure Transducer - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Diagnostic: Suction Temperature Sensor - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Diagnostic: Suction Temperature Sensor - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Diagnostic: Comm Loss: Sump Heater - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Diagnostic: Comm Loss: Sump Heater - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Diagnostic: High Compressor Pressure Differential - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Diagnostic: High Compressor Pressure Differential - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Diagnostic: High Discharge Refrigerant Pressure - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Diagnostic: High Discharge Refrigerant Pressure - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Diagnostic: High Discharge Temperature - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Diagnostic: High Discharge Temperature - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Diagnostic: High Discharge Temperature Lockout - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Diagnostic: High Discharge Temperature Lockout - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Diagnostic: Loss of Charge - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Diagnostic: Loss of Charge - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Diagnostic: Low Discharge Saturated Temperature - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Diagnostic: Low Discharge Saturated Temperature - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Diagnostic: Low Refrigerant Pressure Ratio - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Diagnostic: Low Refrigerant Pressure Ratio - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Diagnostic: Low Refrigerant Temperature - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Diagnostic: Low Refrigerant Temperature - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Diagnostic: Low Suction Refrigerant Pressure - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Diagnostic: Low Suction Refrigerant Pressure - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Diagnostic: Low Suction Superheat - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Diagnostic: Low Suction Superheat - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Diagnostic: Suction Temperature Too High - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Diagnostic: Suction Temperature Too High - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Diagnostic: Very Low Suction Pressure - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Diagnostic: Very Low Suction Pressure - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Diagnostic: Comm Loss: Compressor 1C Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Diagnostic: Comm Loss: Compressor 1B Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Diagnostic: Comm Loss: Compressor 1A Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Diagnostic: Compressor 1A FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Diagnostic: Compressor 1B FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Diagnostic: Compressor 1C FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Diagnostic: Compressor 1C Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Diagnostic: Compressor 1B Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Diagnostic: Compressor 1A Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Diagnostic: Starts/Hours Modified 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Diagnostic: Starts/Hours Modified 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Diagnostic: Starts/Hours Modified 1CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Diagnostic: Comm Loss: Compressor 2C Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Diagnostic: Comm Loss: Compressor 2B Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Diagnostic: Comm Loss: Compressor 2A Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Diagnostic: Compressor 2A FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Diagnostic: Compressor 2B FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Diagnostic: Compressor 2C FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Diagnostic: Compressor 2C Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Diagnostic: Compressor 2B Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Diagnostic: Compressor 2A Fault LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Diagnostic: Starts/Hours Modified 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Diagnostic: Starts/Hours Modified 2CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Diagnostic: Starts/Hours Modified 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Diagnostic: Comm Loss: High Pressure Cutout Switch - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Diagnostic: Comm Loss: High Pressure Cutout Switch - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Diagnostic: High Pressure Cutout - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Diagnostic: High Pressure Cutout - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Diagnostic: Comm Loss: Shared V Coil Isolating Valve - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Diagnostic: Comm Loss: Shared V Coil Isolating Valve - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Diagnostic: Comm Loss: Dynamic Receiver Fill Valve - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Diagnostic: Comm Loss: Dynamic Receiver Fill Valve - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Diagnostic: Comm Loss: Hot Gas Bypass Valve - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Diagnostic: Comm Loss: Hot Gas Bypass Valve - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Diagnostic: Comm Loss: Liquid Line Pressure - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Diagnostic: Comm Loss: Liquid Line Pressure - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Diagnostic: Comm Loss: Liquid Line Temperature - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Diagnostic: Comm Loss: Liquid Line Temperature - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Diagnostic: Liquid Line Pressure Transducer - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Diagnostic: Liquid Line Pressure Transducer - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Diagnostic: Liquid Line Temperature Sensor - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Diagnostic: Liquid Line Temperature Sensor - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Diagnostic: Comm Loss:Evaporator Antifreeze HeaterDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Diagnostic: Comm Loss:Heat Recovery Antifreeze HeaterDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Diagnostic: Evaporator Water Flow Lost LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Diagnostic: High Suction Rfgt PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Diagnostic: Inverted Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Diagnostic: Inverted Water Temp (Heating)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Diagnostic: Low Evaporator Water Temp (Unit On)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Diagnostic: Low Evaporator Water Temp (Unit Off)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Diagnostic: Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Diagnostic: Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Diagnostic: Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Diagnostic: Comm Loss: Cooling EXV - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Diagnostic: Comm Loss: Cooling EXV - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Diagnostic: Comm Loss: Electronic Expansion Valve - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Diagnostic: Comm Loss: Electronic Expansion Valve - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Diagnostic: Comm Loss: Heating EXV - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Diagnostic: Comm Loss: Heating EXV - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Diagnostic: Comm Loss: Auxiliary Setpoint CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Diagnostic: Comm Loss: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Diagnostic: Comm Loss: Ext Chilled/Hot Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Diagnostic: Comm Loss: Ext Noise Reduction RequestDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Diagnostic: Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Diagnostic: Comm Loss: Ext Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Diagnostic: Comm Loss: External Hot Water CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Diagnostic: Comm Loss: Programmable Relay Board 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Diagnostic: Comm Loss: Programmable Relay Board 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Diagnostic: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Diagnostic: External Chilled/Hot Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Diagnostic: External Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Diagnostic: Comm Loss: Condenser Fan Enable - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Diagnostic: Comm Loss: Condenser Fan Enable - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Diagnostic: Comm Loss: Cond Fan Enbl Shared Ckt 1&2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Diagnostic: Comm Loss: Condenser Fan Fault - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Diagnostic: Comm Loss: Condenser Fan Fault - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Diagnostic: Comm Loss: Fan Board 1 Relay 1 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Diagnostic: Comm Loss: Fan Board 1 Relay 1 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Diagnostic: Comm Loss: Fan Board 1 Relay 2 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Diagnostic: Comm Loss: Fan Board 1 Relay 2 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Diagnostic: Comm Loss: Fan Board 1 Relay 3 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Diagnostic: Comm Loss: Fan Board 1 Relay 3 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Diagnostic: Comm Loss: Fan Board 1 Relay 4 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Diagnostic: Comm Loss: Fan Board 1 Relay 4 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Diagnostic: Comm Loss: Fan Board 2 Relay 1 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Diagnostic: Comm Loss: Fan Board 2 Relay 1 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Diagnostic: Comm Loss: Fan Board 2 Relay 2 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Diagnostic: Comm Loss: Fan Board 2 Relay 2 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Diagnostic: Comm Loss: Fan Board 2 Relay 3 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Diagnostic: Comm Loss: Fan Board 2 Relay 3 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Diagnostic: Comm Loss: Fan Board 2 Relay 4 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Diagnostic: Comm Loss: Fan Board 2 Relay 4 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Diagnostic: Comm Loss: Fan Inverter Speed Command - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Diagnostic: Comm Loss: Fan Inverter Speed Command - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Diagnostic: Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1&2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Diagnostic: Comm Loss: Fan Speed Select Board Relay 1 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Diagnostic: Comm Loss: Fan Speed Select Board Relay 2 - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Diagnostic: Comm Loss: Fan Speed Select Board Relay 3 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Diagnostic: Comm Loss: Fan Speed Select Board Relay 4 - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Diagnostic: Condenser Fan Fault - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Diagnostic: Condenser Fan Fault - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Diagnostic: Comm Loss: FC Entering Glycol TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Diagnostic: Comm Loss: FC Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Diagnostic: Comm Loss: FC Leaving Glycol TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Diagnostic: Comm Loss: Free Cooling Glycol Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Diagnostic: Comm Loss: Free Cooling Glycol PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Diagnostic: Comm Loss: Free Cooling Glycol Pump FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Diagnostic: Comm Loss: Free Cooling PumpDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Diagnostic: Comm Loss: Free Cooling ValveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Diagnostic: Free Cooling Entering Glycol TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Diagnostic: Free Cooling Entering Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Diagnostic: Free Cooling Glycol Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Diagnostic: Free Cooling Glycol Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Diagnostic: Free Cooling Glycol PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Diagnostic: Free Cooling Glycol Temperature Equalization OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Diagnostic: Free Cooling Leaving Glycol TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Diagnostic: Free Cooling Glycol Pump FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4182doc 34183Diagnostic: Low Glycol Pressure Free CoolingDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4183doc 34184Diagnostic: Low Glycol Temp Free CoolingDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4184doc 34185Diagnostic: Comm Loss: External Heat Recovery CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4185doc 34186Diagnostic: Comm Loss: External Heat Recovery SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4186doc 34187Diagnostic: Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4187doc 34188Diagnostic: Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4188doc 34189Diagnostic: Comm Loss: HR Entering Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4189doc 34190Diagnostic: Comm Loss: HR Leaving Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4190doc 34191Diagnostic: Comm Loss: Heat Recovery Three Way ValveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4191doc 34192Diagnostic: External Heat Recovery SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4192doc 34193Diagnostic: Heat Recovery Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4193doc 34194Diagnostic: Heat Recovery Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4194doc 34195Diagnostic: No Heat RecoveryDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4195doc 34196Diagnostic: Comm Loss: External Ice Building CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4196doc 34197Diagnostic: Restart Inhibit Invoked - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4197doc 34198Diagnostic: Restart Inhibit Invoked - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4198doc 34199Diagnostic: Restart Inhibit Invoked - 1CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4199doc 34200Diagnostic: Restart Inhibit Invoked - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4200doc 34201Diagnostic: Restart Inhibit Invoked - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4201doc 34202Diagnostic: Restart Inhibit Invoked - 2CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4202doc 34203Diagnostic: Comm Loss: Energy Meter Pulse InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4203doc 34204Diagnostic: Comm Loss: Run Command Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4204doc 34205Diagnostic: Comm Loss: Run Command Compressor 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4205doc 34206Diagnostic: Comm Loss: Run Command Compressor 1CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4206doc 34207Diagnostic: Comm Loss: Run Command Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4207doc 34208Diagnostic: Comm Loss: Run Command Compressor 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4208doc 34209Diagnostic: Comm Loss: Run Command Compressor 2CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4209doc 34210Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4210doc 34211Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4211doc 34212Diagnostic: Comm Loss: Evap Pump Inv1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4212doc 34213Diagnostic: Comm Loss: Evap Pump Inv1 Freq FeedbackDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4213doc 34214Diagnostic: Comm Loss: Evap Pump Inv1 Run CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4214doc 34215Diagnostic: Comm Loss: Evaporator Pump 2 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4215doc 34216Diagnostic: Comm Loss: Evaporator Water Pump 1 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4216doc 34217Diagnostic: Comm Loss: Evaporator Water Pump 2 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4217doc 34218Diagnostic: Comm Loss: Evaporator Pump 1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4218doc 34219Diagnostic: Evap Pump 1 Starts Run time WrittenDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4219doc 34220Diagnostic: Evap Pump 2 Starts Run time WrittenDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4220doc 34221Diagnostic: Evaporator Pump 1 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4221doc 34222Diagnostic: Evaporator Pump 2 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4222doc 34223Diagnostic: Evaporator Water Flow Lost - Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4223doc 34224Diagnostic: Evaporator Water Flow Lost - Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4224doc 34225Diagnostic: Evaporator Water Flow Overdue - Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4225doc 34226Diagnostic: Evaporator Water Flow Overdue - Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4226doc 34227Diagnostic: Comm Loss: SLHX Entering Refrigerant Temp - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4227doc 34228Diagnostic: Comm Loss: SLHX Entering Refrigerant Temp - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4228doc 34229Diagnostic: Comm Loss: SLHX Valve - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4229doc 34230Diagnostic: Comm Loss: SLHX Valve - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4230doc 34231Diagnostic: SLHX Entering Temp Sensor - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4231doc 34232Diagnostic: SLHX Entering Temp Sensor - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4232doc 34233Diagnostic: Chiller Service RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4233doc 34234Diagnostic: Evap Water Pump 1 Svc RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4234doc 34235Diagnostic: Evap Water Pump 2 Svc RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4235doc 34236Diagnostic: Mfr Maintenance Recommended - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4236doc 34237Diagnostic: Mfr Maintenance Recommended - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4237doc 34238Diagnostic: Mfr Maintenance Recommended - 1CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4238doc 34239Diagnostic: Mfr Maintenance Recommended - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4239doc 34240Diagnostic: Mfr Maintenance Recommended - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4240doc 34241Diagnostic: Mfr Maintenance Recommended - 2CDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4241doc 34242Diagnostic: Evaporator Water Flow Too LowDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4242doc 34243Diagnostic: Comm Loss: Evap Water Pump Inverter SpeedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4243doc 34244Diagnostic: Energy Meter Write Value FailureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015BAS Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water Control (Heat Pump)FLOAT32ABCDRead/write
HR16doc 40017BAS Heat Recovery SetpointTemperature in the factory unit system (I-P or SI). Needs: Total Heat Recovery Partial Heat RecoveryFLOAT32ABCDRead/write
HR18doc 40019Evaporator Water Pump Speed SetpointNeeds: Variable Speed Evap PumpFLOAT32ABCD%Read/write
HR2010doc 42011BAS Chiller Mode CommandUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making
HR3010doc 43011Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3011doc 43012BAS Noise Reduction RequestNeeds: Noise ReductionUINT16Read/write0 = Normal; 1 = Reduce Noise
HR3012doc 43013BAS Heat Recovery CommandNeeds: Total Heat Recovery Partial Heat RecoveryUINT16Read/write0 = Off; 1 = On
HR3013doc 43014Energy Consumption ResetNeeds: Energy Meter - Pulse Input Energy Meter - Schneider ModbusUINT16Read/write0 = Accumulating; 1 = Reset
HR3014doc 43015BAS Circuit 1 LockoutUINT16Read/write0 = Normal; 1 = Locked Out
HR3015doc 43016BAS Circuit 2 LockoutUINT16Read/write0 = Normal; 1 = Locked Out
HR3016doc 43017BAS Free Cooling Auto Stop CommandNeeds: Free CoolingUINT16Read/write0 = Stop; 1 = Auto
HR3017doc 43018BAS Chiller Auto Stop CommandUINT16Read/write0 = Stop; 1 = Auto
HR3018doc 43019Evaporator Water Pump Request BASUINT16Read/write0 = Auto; 1 = On
HR3019doc 43020Defrost Delay Request BASNeeds: Hot Water Control (Heat Pump)UINT16Read/write0 = Off; 1 = On

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)

What Modbus registers does the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) have?

This map lists 397 registers: 381 input registers, 16 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)?

Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 12 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 14 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 42 Actual Running Capacity (Actual running capacity); IR 20 Outdoor Air Temperature (Outdoor air temperature); IR 2010 Chiller Running Status (Chiller running status); IR 3036 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 BAS Chiller Mode Command (BAS chiller mode command); HR 3010 Reset Diagnostic (Reset diagnostic).

How do I enable Modbus control of the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)?

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Where is the official Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, Ascend Models ACS and ACX (BAS-PTS011A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS011A-EN_11152024.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, Ascend Models ACS and ACX · BAS-PTS011A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.