Chiller · Modbus register map
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus register map
Updated 19 November 2026
Trane's Ascend ACS is an air-cooled scroll chiller and the ACX its reversible air-to-water heat-pump version. Both use a Symbio 800 controller that serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (water and refrigerant temperatures, pressures, capacity, starts and run time, energy meter values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.
This page lists 397 Modbus registers for the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
- Equipment type
- Chiller
- Registers
- 397 (16 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump
Integration notes: Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Cool/Heat Setpoint Temperature | FLOAT32 ABCD | Active cool/heat setpoint | Read |
| IR 12 | Evaporator Leaving Water Temperature | FLOAT32 ABCD | Evaporator leaving water temperature | Read |
| IR 14 | Evaporator Entering Water Temperature | FLOAT32 ABCD | Evaporator entering water temperature | Read |
| IR 42 | Actual Running Capacity | FLOAT32 ABCD | Actual running capacity | Read |
| IR 20 | Outdoor Air Temperature | FLOAT32 ABCD | Outdoor air temperature | Read |
| IR 2010 | Chiller Running Status | UINT16 | Chiller running status | Read |
| IR 3036 | Diagnostic Present | UINT16 | Diagnostic present | Read |
| HR 10 | Chilled Water Setpoint | FLOAT32 ABCD | Chilled water setpoint (BAS) | Read/write |
| HR 2010 | BAS Chiller Mode Command | UINT16 | BAS chiller mode command | Read/write |
| HR 3010 | Reset Diagnostic | UINT16 | Reset diagnostic | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Byte order & addressing
- Analog values are 32-bit floats occupying two registers; read both registers in one request.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid or not present.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (1-247); address 000 disables Modbus RTU.
- Modbus TCP uses Ethernet port 2; the rotary address is ignored for TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Cool/Heat Setpoint Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Evaporator Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 14doc 30015 | Evaporator Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 16doc 30017 | Active Demand Limit Setpoint | Needs: Ice Building = Not Installed | FLOAT32 | ABCD | % | Read | ||
| IR | 18doc 30019 | Unit Power Consumption | Electrical power. Needs: Energy Meter - Pulse Input Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 20doc 30021 | Outdoor Air Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 22doc 30023 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 24doc 30025 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 26doc 30027 | Differential Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 28doc 30029 | Evaporator Saturated Rfgt Temp Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | Condenser Saturated Rfgt Temp Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Evaporator Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Condenser Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Differential Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 38doc 30039 | Evaporator Saturated Rfgt Temp Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Condenser Saturated Rfgt Temp Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 42doc 30043 | Actual Running Capacity | FLOAT32 | ABCD | % | Read | |||
| IR | 44doc 30045 | Active Heat Recovery Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Total Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 46doc 30047 | Active Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control (Heat Pump) | FLOAT32 | ABCD | Read | |||
| IR | 48doc 30049 | Air Flow Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 50doc 30051 | Air Flow Circuit 2 | FLOAT32 | ABCD | % | Read | |||
| IR | 52doc 30053 | Starts Cprsr1A | FLOAT32 | ABCD | Read | ||||
| IR | 54doc 30055 | Running Time Cprsr1A | FLOAT32 | ABCD | Read | ||||
| IR | 56doc 30057 | Starts Cprsr2A | FLOAT32 | ABCD | Read | ||||
| IR | 58doc 30059 | Running Time Cprsr2A | FLOAT32 | ABCD | Read | ||||
| IR | 60doc 30061 | Heat Recovery Entering Water Temp | Temperature in the factory unit system (I-P or SI). Needs: Total Heat Recovery Partial Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | Heat Recovery Leaving Water Temp | Temperature in the factory unit system (I-P or SI). Needs: Total Heat Recovery Partial Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 64doc 30065 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 66doc 30067 | Starts Cprsr1B | FLOAT32 | ABCD | Read | ||||
| IR | 68doc 30069 | Running Time Cprsr1B | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 | Starts Cprsr2B | FLOAT32 | ABCD | Read | ||||
| IR | 72doc 30073 | Running Time Cprsr2B | FLOAT32 | ABCD | Read | ||||
| IR | 74doc 30075 | Number Of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 76doc 30077 | Number of Compressors for Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 78doc 30079 | Number of Compressors for Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 80doc 30081 | Free Cooling Capacity | Needs: Free Cooling | FLOAT32 | ABCD | % | Read | ||
| IR | 82doc 30083 | Free Cooling Entering Water Temperature | Temperature in the factory unit system (I-P or SI). Needs: Free Cooling | FLOAT32 | ABCD | Read | |||
| IR | 84doc 30085 | Free Cooling Entering Glycol Temperature | Temperature in the factory unit system (I-P or SI). Needs: Free Cooling | FLOAT32 | ABCD | Read | |||
| IR | 86doc 30087 | Free Cooling Leaving Glycol Temperature | Temperature in the factory unit system (I-P or SI). Needs: Free Cooling | FLOAT32 | ABCD | Read | |||
| IR | 88doc 30089 | Energy Consumption NonReset | Electrical power. Needs: Energy Meter - Pulse Input Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 90doc 30091 | Energy Consumption Resettable | Electrical power. Needs: Energy Meter - Pulse Input Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 92doc 30093 | Starts Cprsr1C | Needs: Circuit 1 = 3 compressors | FLOAT32 | ABCD | Read | |||
| IR | 94doc 30095 | Running Time Cprsr1C | Needs: Circuit 1 = 3 compressors | FLOAT32 | ABCD | Read | |||
| IR | 96doc 30097 | Starts Cprsr2C | Needs: Circuit 2 = 3 compressors | FLOAT32 | ABCD | Read | |||
| IR | 98doc 30099 | Running Time Cprsr2C | Needs: Circuit 2 = 3 compressors | FLOAT32 | ABCD | Read | |||
| IR | 100doc 30101 | Estimated Discharge Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp Sensor = Not Installed | FLOAT32 | ABCD | Read | |||
| IR | 102doc 30103 | Estimated Discharge Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp Sensor = Not Installed | FLOAT32 | ABCD | Read | |||
| IR | 104doc 30105 | Compressor Discharge Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp Sensor = Installed | FLOAT32 | ABCD | Read | |||
| IR | 106doc 30107 | Compressor Discharge Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Discharge Temp Sensor = Installed | FLOAT32 | ABCD | Read | |||
| IR | 108doc 30109 | Free Cooling Glycol Pressure | Pressure in the factory unit system (I-P or SI). Needs: Free Cooling | FLOAT32 | ABCD | Read | |||
| IR | 110doc 30111 | Unit Source ID | FLOAT32 | ABCD | Read | ||||
| IR | 112doc 30113 | Unit Load Command | FLOAT32 | ABCD | % | Read | |||
| IR | 114doc 30115 | Average Line Current Meter 1 | Current. Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 | Average Line Voltage Meter 1 | Voltage. Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 118doc 30119 | Meter Line Current L1 | Current. Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 | Meter Line Current L2 | Current. Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 122doc 30123 | Meter Line Current L3 | Current. Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 | Meter Line Voltage L1-L2 | Voltage. Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 126doc 30127 | Meter Line Voltage L2-L3 | Voltage. Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 128doc 30129 | Meter Line Voltage L1-L3 | Voltage. Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 130doc 30131 | Chiller Power Demand | Electrical power. Needs: Energy Meter - Pulse Input Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 | Unit Line Frequency | Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 134doc 30135 | Unit Power Factor | Needs: Energy Meter - Schneider Modbus | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 | Heat Recovery Valve Position | Needs: Total Heat Recovery | FLOAT32 | ABCD | % | Read | ||
| IR | 138doc 30139 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 | Condenser Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 | Condenser Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | Free Cooling Glycol Absolute Pressure | Pressure in the factory unit system (I-P or SI). Needs: Free Cooling | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 | Supplemental Heater Status | Needs: Supplemental Heater | FLOAT32 | ABCD | % | Read | ||
| IR | 150doc 30151 | Evaporator Approach Temperature Circuit 1 (Cooling Mode Only) | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 | Evaporator Approach Temperature Circuit 2 (Cooling Mode Only) | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 154doc 30155 | Condenser Approach Temperature Circuit 1 (Heating Mode Only) | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 156doc 30157 | Condenser Approach Temperature Circuit 2 (Heating Mode Only) | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 158doc 30159 | Active Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 | Chilled Water Setpoint Status | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 162doc 30163 | Hot Water Setpoint Status | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control (Heat Pump) | FLOAT32 | ABCD | Read | |||
| IR | 164doc 30165 | Demand Limit Setpoint Status | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 166doc 30167 | Active Demand Limit Setpoint | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 2010doc 32011 | Chiller Running Status | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2011doc 32012 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making | ||||
| IR | 2012doc 32013 | Chiller Setpoint Source | UINT16 | Read | 1 = BAS; 2 = External; 3 = Front Panel | ||||
| IR | 2013doc 32014 | Refrigerant Type | UINT16 | Read | 1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 6 = R-407C; 7 = R-410A; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 12 = R-404A; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A; 16 = R-1234z(E); 17 = R-454B; 18 = R-515B | ||||
| IR | 2014doc 32015 | Cooling Type | UINT16 | Read | 1 = Water Cooled; 2 = Air Cooled | ||||
| IR | 2015doc 32016 | Manufacture Location | UINT16 | Read | 1 = Field Applied; 2 = La Crosse; 3 = Pueblo; 4 = Charmes; 5 = Rushville; 6 = Macon; 7 = Waco; 8 = Lexington; 9 = Forsyth; 10 = Clarksville; 11 = Ft. Smith; 12 = Penang; 13 = Colchester; 14 = Curitiba; 15 = Taicang; 16 = Taiwan; 17 = Epinal; 18 = Golbey | ||||
| IR | 2016doc 32017 | Front Panel Chiller Mode Command | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making | ||||
| IR | 2017doc 32018 | Model Information [GEN2] | UINT16 | Read | 1 = CVHF; 2 = CVGF; 3 = CVHS; 4 = RTAE; 5 = RTAF; 6 = RTHA; 7 = RTHB; 8 = RTHC; 9 = RTHD; 10 = RTWE; 11 = CTVD; 12 = CVR; 13 = CVHH; 14 = CDHH; 15 = VMAX; 16 = GVAF; 17 = RTWF; 18 = RTHF; 19 = RTAC; 20 = CVHM; 21 = RTAG; 22 = CGAF; 23 = RTXG; 24 = GVWF; 25 = HDWA; 26 = CMAC; 27 = IPAK; 28 = CXAF; 29 = ACSA; 30 = RTSF; 31 = HSWA; 32 = ACRA; 33 = RTEG; 34 = ACXA; 35 = CMAF; 36 = ACRB Large; 37 = ACRB Small | ||||
| IR | 2018doc 32019 | Circuit 1 Status | UINT16 | Read | 1 = Available; 2 = Heat Recovery; 3 = Cooling; 4 = Heating; 5 = Defrost; 6 = Not Available | ||||
| IR | 2019doc 32020 | Circuit 2 Status | UINT16 | Read | 1 = Available; 2 = Heat Recovery; 3 = Cooling; 4 = Heating; 5 = Defrost; 6 = Not Available | ||||
| IR | 3010doc 33011 | Limit Mode Relay Status | UINT16 | Read | 0 = Auto; 1 = On | ||||
| IR | 3011doc 33012 | Emergency Stop | UINT16 | Read | 0 = Auto; 1 = Emergency Stop - Manual Reset Required | ||||
| IR | 3012doc 33013 | Manual Override Exists | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3013doc 33014 | Run Enable | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3014doc 33015 | Local Setpoint Control | UINT16 | Read | 0 = Remote control; 1 = Local control | ||||
| IR | 3015doc 33016 | Maximum Capacity Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3016doc 33017 | Running Status Cprsr1A | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3017doc 33018 | Running Status Cprsr2A | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3018doc 33019 | Running Status Cprsr1B | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3019doc 33020 | Running Status Cprsr2B | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3020doc 33021 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3021doc 33022 | Running Status Cprsr1C | Needs: Circuit 1 = 3 compressors | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3022doc 33023 | Running Status Cprsr2C | Needs: Circuit 2 = 3 compressors | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3023doc 33024 | Free Cooling Active | Needs: Free Cooling | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3024doc 33025 | Heat Recovery Active | Needs: Total Heat Recovery | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3025doc 33026 | Front Panel Auto/Stop | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3026doc 33027 | Circuit Manual Reset Indicator (CMR) Circuit 1 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3027doc 33028 | Circuit Manual Reset Indicator (CMR) Circuit 2 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3028doc 33029 | Circuit Auto Reset Indicator (CAR) Circuit 1 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3029doc 33030 | Circuit Auto Reset Indicator (CAR) Circuit 2 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3030doc 33031 | Evaporator Water Pump Command | UINT16 | Read | |||||
| IR | 3031doc 33032 | Evaporator Water Flow Status | UINT16 | Read | |||||
| IR | 3032doc 33033 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3033doc 33034 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3034doc 33035 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3035doc 33036 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3036doc 33037 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3037doc 33038 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3038doc 33039 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3039doc 33040 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3040doc 33041 | External Auto Stop | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3041doc 33042 | Noise Reduction Request Active | Needs: Noise Reduction | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3042doc 33043 | Heat Recovery Request Active | Needs: Total Heat Recovery | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3043doc 33044 | Evaporator Water Pump Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3044doc 33045 | Circuit 1 Defrost Delay Status | Needs: Hot Water Control (Heat Pump) | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3045doc 33046 | Circuit 2 Defrost Delay Status | Needs: Hot Water Control (Heat Pump) | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3046doc 33047 | In Defrost | Needs: Hot Water Control (Heat Pump) | UINT16 | Read | 0 = Not in Defrost; 1 = Defrost | |||
| IR | 3047doc 33048 | Circuit 1 Defrost Status | Needs: Hot Water Control (Heat Pump) | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3048doc 33049 | Circuit 2 Defrost Status | Needs: Hot Water Control (Heat Pump) | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3049doc 33050 | Circuit 1 Running Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3050doc 33051 | Circuit 2 Running Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3051doc 33052 | Low Ambient Lockout Status | UINT16 | Read | 0 = No Lockout; 1 = Lockout Present | ||||
| IR | 3052doc 33053 | Circuit 1 Lockout Front Panel | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3053doc 33054 | Circuit 2 Lockout Front Panel | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3054doc 33055 | Circuit 1 Lockout External | Needs: External Circuit Lockout | UINT16 | Read | 0 = Normal; 1 = Locked Out | |||
| IR | 3055doc 33056 | Circuit 2 Lockout External | Needs: External Circuit Lockout | UINT16 | Read | 0 = Normal; 1 = Locked Out | |||
| IR | 3056doc 33057 | Circuit 1 Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3057doc 33058 | Circuit 2 Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 4000doc 34001 | Diagnostic: Comm Loss: Percent Capacity Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Diagnostic: Comm Loss: Supplemental Heater Relay 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Diagnostic: Comm Loss: Supplemental Heater Relay 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Diagnostic: Comm Loss: Supplemental Heater Relay 3 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Diagnostic: Comm Loss: Supplemental Heater Relay 4 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Diagnostic: Comm Loss: Energy Meter | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Diagnostic: Comm Loss: Outdoor Air Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Diagnostic: Comm Loss: Phase Protection Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Diagnostic: Energy Meter Write Command Failure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Diagnostic: Outdoor Air Temperature Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Diagnostic: Phase Protection Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Diagnostic: Software Error 1003: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Diagnostic: Pumpdown Terminated By Time - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Diagnostic: Pumpdown Terminated By Time - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Diagnostic: Comm Loss: Discharge Pressure Transducer - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Diagnostic: Comm Loss: Discharge Pressure Transducer - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Diagnostic: Comm Loss: Discharge Temperature Sensor - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Diagnostic: Comm Loss: Discharge Temperature Sensor - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Diagnostic: Comm Loss: External Circuit 2 Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Diagnostic: Comm Loss: External Circuit 1 Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Diagnostic: Comm Loss: Reversing Valve - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Diagnostic: Comm Loss: Reversing Valve - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Diagnostic: Comm Loss: Suction Pressure Transducer - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Diagnostic: Comm Loss: Suction Pressure Transducer - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Diagnostic: Comm Loss: Suction Temperature - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Diagnostic: Comm Loss: Suction Temperature - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Diagnostic: Discharge Pressure Transducer - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Diagnostic: Discharge Pressure Transducer - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Diagnostic: Discharge Temperature Sensor - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Diagnostic: Discharge Temperature Sensor - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Diagnostic: Suction Pressure Transducer - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Diagnostic: Suction Pressure Transducer - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Diagnostic: Suction Temperature Sensor - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Diagnostic: Suction Temperature Sensor - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Diagnostic: Comm Loss: Sump Heater - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Diagnostic: Comm Loss: Sump Heater - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4036doc 34037 | Diagnostic: High Compressor Pressure Differential - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4037doc 34038 | Diagnostic: High Compressor Pressure Differential - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Diagnostic: High Discharge Refrigerant Pressure - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Diagnostic: High Discharge Refrigerant Pressure - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Diagnostic: High Discharge Temperature - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Diagnostic: High Discharge Temperature - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Diagnostic: High Discharge Temperature Lockout - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Diagnostic: High Discharge Temperature Lockout - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Diagnostic: Loss of Charge - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Diagnostic: Loss of Charge - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Diagnostic: Low Discharge Saturated Temperature - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Diagnostic: Low Discharge Saturated Temperature - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Diagnostic: Low Refrigerant Pressure Ratio - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Diagnostic: Low Refrigerant Pressure Ratio - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Diagnostic: Low Refrigerant Temperature - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Diagnostic: Low Refrigerant Temperature - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Diagnostic: Low Suction Refrigerant Pressure - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Diagnostic: Low Suction Refrigerant Pressure - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Diagnostic: Low Suction Superheat - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Diagnostic: Low Suction Superheat - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Diagnostic: Suction Temperature Too High - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Diagnostic: Suction Temperature Too High - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Diagnostic: Very Low Suction Pressure - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Diagnostic: Very Low Suction Pressure - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Diagnostic: Comm Loss: Compressor 1C Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Diagnostic: Comm Loss: Compressor 1B Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Diagnostic: Comm Loss: Compressor 1A Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Diagnostic: Compressor 1A Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Diagnostic: Compressor 1B Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Diagnostic: Compressor 1C Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Diagnostic: Compressor 1C Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Diagnostic: Compressor 1B Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Diagnostic: Compressor 1A Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Diagnostic: Starts/Hours Modified 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Diagnostic: Starts/Hours Modified 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Diagnostic: Starts/Hours Modified 1C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4072doc 34073 | Diagnostic: Comm Loss: Compressor 2C Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Diagnostic: Comm Loss: Compressor 2B Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4074doc 34075 | Diagnostic: Comm Loss: Compressor 2A Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4075doc 34076 | Diagnostic: Compressor 2A Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Diagnostic: Compressor 2B Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Diagnostic: Compressor 2C Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Diagnostic: Compressor 2C Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Diagnostic: Compressor 2B Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Diagnostic: Compressor 2A Fault Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Diagnostic: Starts/Hours Modified 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Diagnostic: Starts/Hours Modified 2C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Diagnostic: Starts/Hours Modified 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Diagnostic: Comm Loss: High Pressure Cutout Switch - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Diagnostic: Comm Loss: High Pressure Cutout Switch - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Diagnostic: High Pressure Cutout - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Diagnostic: High Pressure Cutout - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Diagnostic: Comm Loss: Shared V Coil Isolating Valve - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Diagnostic: Comm Loss: Shared V Coil Isolating Valve - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Diagnostic: Comm Loss: Dynamic Receiver Fill Valve - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Diagnostic: Comm Loss: Dynamic Receiver Fill Valve - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Diagnostic: Comm Loss: Hot Gas Bypass Valve - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Diagnostic: Comm Loss: Hot Gas Bypass Valve - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Diagnostic: Comm Loss: Liquid Line Pressure - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4095doc 34096 | Diagnostic: Comm Loss: Liquid Line Pressure - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4096doc 34097 | Diagnostic: Comm Loss: Liquid Line Temperature - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Diagnostic: Comm Loss: Liquid Line Temperature - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Diagnostic: Liquid Line Pressure Transducer - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Diagnostic: Liquid Line Pressure Transducer - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4100doc 34101 | Diagnostic: Liquid Line Temperature Sensor - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4101doc 34102 | Diagnostic: Liquid Line Temperature Sensor - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Diagnostic: Comm Loss:Evaporator Antifreeze Heater | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Diagnostic: Comm Loss:Heat Recovery Antifreeze Heater | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Diagnostic: Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Diagnostic: Evaporator Water Flow Lost Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Diagnostic: Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Diagnostic: High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Diagnostic: High Suction Rfgt Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4109doc 34110 | Diagnostic: Inverted Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4110doc 34111 | Diagnostic: Inverted Water Temp (Heating) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4111doc 34112 | Diagnostic: Low Evaporator Water Temp (Unit On) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Diagnostic: Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Diagnostic: Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Diagnostic: Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Diagnostic: Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Diagnostic: Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Diagnostic: Comm Loss: Cooling EXV - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Diagnostic: Comm Loss: Cooling EXV - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Diagnostic: Comm Loss: Electronic Expansion Valve - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4121doc 34122 | Diagnostic: Comm Loss: Electronic Expansion Valve - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Diagnostic: Comm Loss: Heating EXV - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Diagnostic: Comm Loss: Heating EXV - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Diagnostic: Comm Loss: Auxiliary Setpoint Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Diagnostic: Comm Loss: Emergency Stop Feedback Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Diagnostic: Comm Loss: Ext Chilled/Hot Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Diagnostic: Comm Loss: Ext Noise Reduction Request | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Diagnostic: Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Diagnostic: Comm Loss: Ext Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Diagnostic: Comm Loss: External Hot Water Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Diagnostic: Comm Loss: Programmable Relay Board 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Diagnostic: Comm Loss: Programmable Relay Board 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Diagnostic: Emergency Stop Feedback Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Diagnostic: External Chilled/Hot Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Diagnostic: External Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Diagnostic: Comm Loss: Condenser Fan Enable - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Diagnostic: Comm Loss: Condenser Fan Enable - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4138doc 34139 | Diagnostic: Comm Loss: Cond Fan Enbl Shared Ckt 1&2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4139doc 34140 | Diagnostic: Comm Loss: Condenser Fan Fault - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Diagnostic: Comm Loss: Condenser Fan Fault - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Diagnostic: Comm Loss: Fan Board 1 Relay 1 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4142doc 34143 | Diagnostic: Comm Loss: Fan Board 1 Relay 1 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4143doc 34144 | Diagnostic: Comm Loss: Fan Board 1 Relay 2 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Diagnostic: Comm Loss: Fan Board 1 Relay 2 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Diagnostic: Comm Loss: Fan Board 1 Relay 3 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4146doc 34147 | Diagnostic: Comm Loss: Fan Board 1 Relay 3 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Diagnostic: Comm Loss: Fan Board 1 Relay 4 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Diagnostic: Comm Loss: Fan Board 1 Relay 4 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Diagnostic: Comm Loss: Fan Board 2 Relay 1 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4150doc 34151 | Diagnostic: Comm Loss: Fan Board 2 Relay 1 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4151doc 34152 | Diagnostic: Comm Loss: Fan Board 2 Relay 2 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4152doc 34153 | Diagnostic: Comm Loss: Fan Board 2 Relay 2 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4153doc 34154 | Diagnostic: Comm Loss: Fan Board 2 Relay 3 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4154doc 34155 | Diagnostic: Comm Loss: Fan Board 2 Relay 3 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4155doc 34156 | Diagnostic: Comm Loss: Fan Board 2 Relay 4 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Diagnostic: Comm Loss: Fan Board 2 Relay 4 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Diagnostic: Comm Loss: Fan Inverter Speed Command - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Diagnostic: Comm Loss: Fan Inverter Speed Command - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Diagnostic: Comm Loss: Fan Inv Spd Cmd, Shrd Circuit 1&2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Diagnostic: Comm Loss: Fan Speed Select Board Relay 1 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Diagnostic: Comm Loss: Fan Speed Select Board Relay 2 - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Diagnostic: Comm Loss: Fan Speed Select Board Relay 3 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4163doc 34164 | Diagnostic: Comm Loss: Fan Speed Select Board Relay 4 - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4164doc 34165 | Diagnostic: Condenser Fan Fault - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4165doc 34166 | Diagnostic: Condenser Fan Fault - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4166doc 34167 | Diagnostic: Comm Loss: FC Entering Glycol Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4167doc 34168 | Diagnostic: Comm Loss: FC Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4168doc 34169 | Diagnostic: Comm Loss: FC Leaving Glycol Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4169doc 34170 | Diagnostic: Comm Loss: Free Cooling Glycol Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4170doc 34171 | Diagnostic: Comm Loss: Free Cooling Glycol Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4171doc 34172 | Diagnostic: Comm Loss: Free Cooling Glycol Pump Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4172doc 34173 | Diagnostic: Comm Loss: Free Cooling Pump | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4173doc 34174 | Diagnostic: Comm Loss: Free Cooling Valve | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4174doc 34175 | Diagnostic: Free Cooling Entering Glycol Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4175doc 34176 | Diagnostic: Free Cooling Entering Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4176doc 34177 | Diagnostic: Free Cooling Glycol Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4177doc 34178 | Diagnostic: Free Cooling Glycol Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4178doc 34179 | Diagnostic: Free Cooling Glycol Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4179doc 34180 | Diagnostic: Free Cooling Glycol Temperature Equalization Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4180doc 34181 | Diagnostic: Free Cooling Leaving Glycol Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4181doc 34182 | Diagnostic: Free Cooling Glycol Pump Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4182doc 34183 | Diagnostic: Low Glycol Pressure Free Cooling | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4183doc 34184 | Diagnostic: Low Glycol Temp Free Cooling | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4184doc 34185 | Diagnostic: Comm Loss: External Heat Recovery Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4185doc 34186 | Diagnostic: Comm Loss: External Heat Recovery Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4186doc 34187 | Diagnostic: Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4187doc 34188 | Diagnostic: Comm Loss: Heat Rec Rfgt Bypass Valve Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4188doc 34189 | Diagnostic: Comm Loss: HR Entering Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4189doc 34190 | Diagnostic: Comm Loss: HR Leaving Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4190doc 34191 | Diagnostic: Comm Loss: Heat Recovery Three Way Valve | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4191doc 34192 | Diagnostic: External Heat Recovery Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4192doc 34193 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4193doc 34194 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4194doc 34195 | Diagnostic: No Heat Recovery | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4195doc 34196 | Diagnostic: Comm Loss: External Ice Building Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4196doc 34197 | Diagnostic: Restart Inhibit Invoked - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4197doc 34198 | Diagnostic: Restart Inhibit Invoked - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4198doc 34199 | Diagnostic: Restart Inhibit Invoked - 1C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4199doc 34200 | Diagnostic: Restart Inhibit Invoked - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4200doc 34201 | Diagnostic: Restart Inhibit Invoked - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4201doc 34202 | Diagnostic: Restart Inhibit Invoked - 2C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4202doc 34203 | Diagnostic: Comm Loss: Energy Meter Pulse Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4203doc 34204 | Diagnostic: Comm Loss: Run Command Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4204doc 34205 | Diagnostic: Comm Loss: Run Command Compressor 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4205doc 34206 | Diagnostic: Comm Loss: Run Command Compressor 1C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4206doc 34207 | Diagnostic: Comm Loss: Run Command Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4207doc 34208 | Diagnostic: Comm Loss: Run Command Compressor 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4208doc 34209 | Diagnostic: Comm Loss: Run Command Compressor 2C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4209doc 34210 | Diagnostic: MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4210doc 34211 | Diagnostic: MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4211doc 34212 | Diagnostic: Comm Loss: Evap Pump Inv1 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4212doc 34213 | Diagnostic: Comm Loss: Evap Pump Inv1 Freq Feedback | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4213doc 34214 | Diagnostic: Comm Loss: Evap Pump Inv1 Run Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4214doc 34215 | Diagnostic: Comm Loss: Evaporator Pump 2 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4215doc 34216 | Diagnostic: Comm Loss: Evaporator Water Pump 1 Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4216doc 34217 | Diagnostic: Comm Loss: Evaporator Water Pump 2 Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4217doc 34218 | Diagnostic: Comm Loss: Evaporator Pump 1 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4218doc 34219 | Diagnostic: Evap Pump 1 Starts Run time Written | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4219doc 34220 | Diagnostic: Evap Pump 2 Starts Run time Written | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4220doc 34221 | Diagnostic: Evaporator Pump 1 Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4221doc 34222 | Diagnostic: Evaporator Pump 2 Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4222doc 34223 | Diagnostic: Evaporator Water Flow Lost - Pump1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4223doc 34224 | Diagnostic: Evaporator Water Flow Lost - Pump2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4224doc 34225 | Diagnostic: Evaporator Water Flow Overdue - Pump1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4225doc 34226 | Diagnostic: Evaporator Water Flow Overdue - Pump2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4226doc 34227 | Diagnostic: Comm Loss: SLHX Entering Refrigerant Temp - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4227doc 34228 | Diagnostic: Comm Loss: SLHX Entering Refrigerant Temp - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4228doc 34229 | Diagnostic: Comm Loss: SLHX Valve - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4229doc 34230 | Diagnostic: Comm Loss: SLHX Valve - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4230doc 34231 | Diagnostic: SLHX Entering Temp Sensor - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4231doc 34232 | Diagnostic: SLHX Entering Temp Sensor - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4232doc 34233 | Diagnostic: Chiller Service Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4233doc 34234 | Diagnostic: Evap Water Pump 1 Svc Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4234doc 34235 | Diagnostic: Evap Water Pump 2 Svc Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4235doc 34236 | Diagnostic: Mfr Maintenance Recommended - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4236doc 34237 | Diagnostic: Mfr Maintenance Recommended - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4237doc 34238 | Diagnostic: Mfr Maintenance Recommended - 1C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4238doc 34239 | Diagnostic: Mfr Maintenance Recommended - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4239doc 34240 | Diagnostic: Mfr Maintenance Recommended - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4240doc 34241 | Diagnostic: Mfr Maintenance Recommended - 2C | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4241doc 34242 | Diagnostic: Evaporator Water Flow Too Low | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4242doc 34243 | Diagnostic: Comm Loss: Evap Water Pump Inverter Speed | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4243doc 34244 | Diagnostic: Energy Meter Write Value Failure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 14doc 40015 | BAS Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control (Heat Pump) | FLOAT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | BAS Heat Recovery Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Total Heat Recovery Partial Heat Recovery | FLOAT32 | ABCD | Read/write | |||
| HR | 18doc 40019 | Evaporator Water Pump Speed Setpoint | Needs: Variable Speed Evap Pump | FLOAT32 | ABCD | % | Read/write | ||
| HR | 2010doc 42011 | BAS Chiller Mode Command | UINT16 | Read/write | 1 = Cool; 2 = Heat; 3 = Ice Making | ||||
| HR | 3010doc 43011 | Reset Diagnostic | UINT16 | Read/write | 0 = Normal; 1 = Reset | ||||
| HR | 3011doc 43012 | BAS Noise Reduction Request | Needs: Noise Reduction | UINT16 | Read/write | 0 = Normal; 1 = Reduce Noise | |||
| HR | 3012doc 43013 | BAS Heat Recovery Command | Needs: Total Heat Recovery Partial Heat Recovery | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 3013doc 43014 | Energy Consumption Reset | Needs: Energy Meter - Pulse Input Energy Meter - Schneider Modbus | UINT16 | Read/write | 0 = Accumulating; 1 = Reset | |||
| HR | 3014doc 43015 | BAS Circuit 1 Lockout | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3015doc 43016 | BAS Circuit 2 Lockout | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3016doc 43017 | BAS Free Cooling Auto Stop Command | Needs: Free Cooling | UINT16 | Read/write | 0 = Stop; 1 = Auto | |||
| HR | 3017doc 43018 | BAS Chiller Auto Stop Command | UINT16 | Read/write | 0 = Stop; 1 = Auto | ||||
| HR | 3018doc 43019 | Evaporator Water Pump Request BAS | UINT16 | Read/write | 0 = Auto; 1 = On | ||||
| HR | 3019doc 43020 | Defrost Delay Request BAS | Needs: Hot Water Control (Heat Pump) | UINT16 | Read/write | 0 = Off; 1 = On |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Controller setup and the I-P/SI units statement come from Trane's Symbio 800 integration guide BAS-SVP047B-EN (Sept 2023, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP047B-EN_09092023.pdf), which describes the same Symbio 800 controller.
- Evaporator Water Pump Command (33031) and Evaporator Water Flow Status (33032) are printed with the states '0 = Normal, 1 = In Alarm' in the Modbus table, which does not fit a pump command or flow status; their value lists are left blank.
- Hot-water setpoints, defrost and heat-mode points apply to the ACX heat pump (configuration 'Hot Water Control (Heat Pump)').
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
What Modbus registers does the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) have?
This map lists 397 registers: 381 input registers, 16 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)?
Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 12 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 14 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 42 Actual Running Capacity (Actual running capacity); IR 20 Outdoor Air Temperature (Outdoor air temperature); IR 2010 Chiller Running Status (Chiller running status); IR 3036 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 BAS Chiller Mode Command (BAS chiller mode command); HR 3010 Reset Diagnostic (Reset diagnostic).
How do I enable Modbus control of the Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)?
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Where is the official Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, Ascend Models ACS and ACX (BAS-PTS011A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS011A-EN_11152024.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121 - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, Ascend Models ACS and ACX · BAS-PTS011A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.