Chiller · Modbus register map
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus register map
Updated 19 November 2026
Trane's Series R RTHD is a single-compressor water-cooled helical-rotary (screw) chiller. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, evaporator and condenser water temperatures, refrigerant and oil pressures, starter currents and voltages, energy meter values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.
This page lists 275 Modbus registers for the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
- Equipment type
- Chiller
- Registers
- 275 (12 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RTHD, Series R RTHD
Integration notes: Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Cool/Heat Setpoint Temperature | FLOAT32 ABCD | Active cool/heat setpoint | Read |
| IR 18 | Evaporator Leaving Water Temperature | FLOAT32 ABCD | Evaporator leaving water temperature | Read |
| IR 16 | Evaporator Entering Water Temperature | FLOAT32 ABCD | Evaporator entering water temperature | Read |
| IR 26 | Actual Running Capacity | FLOAT32 ABCD | Actual running capacity | Read |
| IR 2010 | Running Mode | UINT16 | Running mode | Read |
| IR 3010 | Run Enabled | UINT16 | Run enabled | Read |
| IR 3016 | Diagnostic Present | UINT16 | Diagnostic present | Read |
| HR 10 | Chilled Water Setpoint | FLOAT32 ABCD | Chilled water setpoint (BAS) | Read/write |
| HR 2010 | Chiller Mode Command BAS | UINT16 | BAS chiller mode command | Read/write |
| HR 3010 | Chiller Auto Stop Command BAS | UINT16 | Chiller auto/stop command | Read/write |
| HR 3011 | Reset Diagnostic | UINT16 | Reset diagnostic | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Byte order & addressing
- Analog values are 32-bit floats occupying two registers; read both registers in one request.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid or not present.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (1-247); address 000 disables Modbus RTU.
- Modbus TCP uses Ethernet port 2; the rotary address is ignored for TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Cool/Heat Setpoint Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Active Demand Limit Setpoint | FLOAT32 | ABCD | % | Read | |||
| IR | 14doc 30015 | Active Base Loading Setpoint | Needs: Base Loading | FLOAT32 | ABCD | % | Read | ||
| IR | 16doc 30017 | Evaporator Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | Evaporator Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 20doc 30021 | Number of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 22doc 30023 | Number of Compressors Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 24doc 30025 | Number of Compressors Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 26doc 30027 | Actual Running Capacity | FLOAT32 | ABCD | % | Read | |||
| IR | 28doc 30029 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | Condenser Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Refrigerant Discharge Temperature - Compressor 1A | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 38doc 30039 | High Side Oil Absolute Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Starts - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 42doc 30043 | Run Time - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 44doc 30045 | Motor Winding Temperature 1 Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Motor Winding Temp | FLOAT32 | ABCD | Read | |||
| IR | 46doc 30047 | Motor Winding Temperature 2 Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Motor Winding Temp | FLOAT32 | ABCD | Read | |||
| IR | 48doc 30049 | Condenser Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 50doc 30051 | Condenser Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 52doc 30053 | Starter Voltage Phase AB | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 54doc 30055 | Starter Voltage Phase BC | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 56doc 30057 | Starter Voltage Phase CA | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 58doc 30059 | Line 1 Current - Compressor 1A | Current. Needs: Starter Non Comm AFD TR200 Modbus AFD | FLOAT32 | ABCD | Read | |||
| IR | 60doc 30061 | Line 2 Current - Compressor 1A | Current. Needs: Starter Non Comm AFD TR200 Modbus AFD | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | Line 3 Current - Compressor 1A | Current. Needs: Starter Non Comm AFD TR200 Modbus AFD | FLOAT32 | ABCD | Read | |||
| IR | 64doc 30065 | Line 1 Current - Compressor 1A | Current. Needs: Local Comm AFD | FLOAT32 | ABCD | Read | |||
| IR | 66doc 30067 | Line 2 Current - Compressor 1A | Current. Needs: Local Comm AFD | FLOAT32 | ABCD | Read | |||
| IR | 68doc 30069 | Line 3 Current - Compressor 1A | Current. Needs: Local Comm AFD | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | Line 1 Current RLA - Compressor 1A | Needs: Starter Non Comm AFD TR200 Modbus AFD | FLOAT32 | ABCD | % | Read | ||
| IR | 72doc 30073 | Line 2 Current RLA - Compressor 1A | Needs: Starter Non Comm AFD TR200 Modbus AFD | FLOAT32 | ABCD | % | Read | ||
| IR | 74doc 30075 | Line 3 Current RLA - Compressor 1A | Needs: Starter Non Comm AFD TR200 Modbus AFD | FLOAT32 | ABCD | % | Read | ||
| IR | 76doc 30077 | Line 1 Current RLA - Compressor 1A | Needs: Local Comm AFD | FLOAT32 | ABCD | % | Read | ||
| IR | 78doc 30079 | Line 2 Current RLA - Compressor 1A | Needs: Local Comm AFD | FLOAT32 | ABCD | % | Read | ||
| IR | 80doc 30081 | Line 3 Current RLA - Compressor 1A | Needs: Local Comm AFD | FLOAT32 | ABCD | % | Read | ||
| IR | 82doc 30083 | Expansion Valve Position - Compressor 1A | FLOAT32 | ABCD | % | Read | |||
| IR | 84doc 30085 | Drive Output Power Circuit 1 | Electrical power. Needs: Non Comm AFD TR200 Modbus AFD Local Comm AFD | FLOAT32 | ABCD | Read | |||
| IR | 86doc 30087 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 88doc 30089 | Active Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 90doc 30091 | Active Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 92doc 30093 | Evaporator Water Flow Rate | Flow in the factory unit system (I-P or SI). Needs: Evap Differential Water Pressure | FLOAT32 | ABCD | Read | |||
| IR | 94doc 30095 | Condenser Water Flow Rate | Flow in the factory unit system (I-P or SI). Needs: Cond Differential Water Pressure | FLOAT32 | ABCD | Read | |||
| IR | 96doc 30097 | Condenser Differential Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Cond Differential Water Pressure | FLOAT32 | ABCD | Read | |||
| IR | 98doc 30099 | Evaporator Differential Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Evap Differential Water Pressure | FLOAT32 | ABCD | Read | |||
| IR | 100doc 30101 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 102doc 30103 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 104doc 30105 | Condenser Control Output | Needs: Head Pressure Control | FLOAT32 | ABCD | % | Read | ||
| IR | 106doc 30107 | High Side Oil Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 110doc 30111 | Evaporator Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 | Condenser Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 114doc 30115 | Line Frequency Circuit 1 | Needs: Non Comm AFD TR200 Modbus AFD Local Comm AFD | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 | Heat Recovery Entering Water Temperature | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 118doc 30119 | Heat Recovery Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 | Heat Recovery Tank Water Temp | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 122doc 30123 | Heat Recovery Water Tank Temperature Setpoint Active | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 | Chilled Water Setpoint Status | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 126doc 30127 | Demand Limit Setpoint Status | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 128doc 30129 | Unit Source ID (Last Diagnostic Code) | FLOAT32 | ABCD | Read | ||||
| IR | 130doc 30131 | Current L1 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 | Current L2 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 134doc 30135 | Current L3 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 | Average Current | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 138doc 30139 | Voltage L1-L2 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 | Voltage L2-L3 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | Voltage L1-L3 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 | Average Voltage L-L | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | Line Frequency | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 | Power Factor | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 2010doc 32011 | Running Mode | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre- Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2011doc 32012 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| IR | 2012doc 32013 | Refrigerant Type | UINT16 | Read | 1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 6 = R-407C; 7 = R-410A; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 12 = R-404A; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A; 16 = R-1234ze(E) | ||||
| IR | 2013doc 32014 | Manufacture Location | UINT16 | Read | 1 = Field Applied; 2 = La Crosse; 3 = Pueblo; 4 = Charmes; 5 = Rushville; 6 = Macon; 7 = Waco; 8 = Lexington; 9 = Forsyth; 10 = Clarksville; 11 = Ft. Smith; 12 = Penang; 13 = Colchester; 14 = Curitiba; 15 = Taicang; 16 = Taiwan; 17 = Epinal; 18 = Golbey | ||||
| IR | 2014doc 32015 | Cooling Type | UINT16 | Read | 1 = Water Cooled; 2 = Air Cooled | ||||
| IR | 2015doc 32016 | Model Information [GEN2] | UINT16 | Read | 1 = CVHF; 2 = CVGF; 3 = CVHS; 4 = RTAE; 5 = RTAF; 6 = RTHA; 7 = RTHB; 8 = RTHC; 9 = RTHD; 10 = RTWE; 11 = CTVD; 12 = CVR; 13 = CVHH; 14 = CDHH; 15 = VMAX; 16 = GVAF; 17 = RTWF; 18 = RTHF; 19 = RTAC; 20 = CVHM; 21 = RTAG; 22 = CGAF; 23 = RTXG; 24 = GVWF; 25 = HDWA; 26 = CMAC; 27 = IPAK; 28 = CXAF; 29 = ACSA; 30 = RTSF; 31 = HSWA; 32 = ACRA; 33 = RTEG; 34 = ACXA; 35 = CMAF; 36 = ACRB Large; 37 = ACRB Small | ||||
| IR | 3010doc 33011 | Run Enabled | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3011doc 33012 | Local Setpoint Control | UINT16 | Read | 0 = Remote control; 1 = Local control | ||||
| IR | 3012doc 33013 | Limit Mode Relay Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3013doc 33014 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3014doc 33015 | Base Loading Request Active | Needs: Base Loading | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3015doc 33016 | Evaporator Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3016doc 33017 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3017doc 33018 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3018doc 33019 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3019doc 33020 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3020doc 33021 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3021doc 33022 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3022doc 33023 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3023doc 33024 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3024doc 33025 | Compressor 1A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3025doc 33026 | Condenser Water Pump Request | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3026doc 33027 | Evaporator Water Pump Request | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3027doc 33028 | Condenser Water Flow Status | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3028doc 33029 | Heat Recovery Water Flow Status | Needs: Heat Recovery | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3029doc 33030 | Heat Recovery Control Active Status | Needs: Heat Recovery | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3030doc 33031 | Heat Recovery Request Active | Needs: Heat Recovery | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 3031doc 33032 | Front Panel Auto Stop | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3032doc 33033 | External Auto Stop Input Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3033doc 33034 | Head Relief Request | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| IR | 3034doc 33035 | Base Loading Active | Needs: Base Loading | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 4000doc 34001 | Comm Loss: Ext Base Loading Command | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Comm Loss: Ext Base Loading Setpoint | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Diagnostic: External Base Loading Setpoint | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Comm Loss: Outdoor Air Temperature | Diagnostic flag. Needs: Outdoor Air Temperature | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Diagnostic: Outdoor Air Temperature Sensor | Diagnostic flag. Needs: Outdoor Air Temperature | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Diagnostic: Software Error 1001: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Diagnostic: AFD Drive Fault | Diagnostic flag. Needs: Non Comm AFD TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Comm Loss: Cprsr Discharge Rfgt Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Comm Loss: Cond High Pressure Cutout | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD TR200 Modbus Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Comm Loss: Primary Oil Line Solenoid Valve | Diagnostic flag. Needs: Solid State Starter Non Comm AFD TR200 Modbus AFD Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Comm Loss: Oil Loss Level Sensor Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Comm Loss: Oil Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Comm Loss: Oil Return Gas Pump Drain | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Comm Loss: Oil Return Gas Pump Fill | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Comm Loss: SSS/AFD Fault | Diagnostic flag. Needs: Non Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Diagnostic: High Cprsr Rfgt Discharge Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Diagnostic: High Differential Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Diagnostic: High Pressure Cutout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Diagnostic: High Refrigerant Pressure Ratio | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Diagnostic: Loss of Oil at Compressor (Running) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Diagnostic: Loss of Oil at Compressor (Stopped) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Diagnostic: Low Differential Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Diagnostic: Low Discharge Superheat | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Diagnostic: Low Oil Flow | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Diagnostic: No Differential Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Diagnostic: Oil Flow Protection Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Diagnostic: Oil Pressure Transducer | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Diagnostic: AFD Output Power Input | Diagnostic flag. Needs: Non Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Comm Loss: AFD Output Power Input | Diagnostic flag. Needs: Non Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Comm Loss: AFD Speed Signal Output | Diagnostic flag. Needs: Non Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Comm Loss: Adaptive Frequency Drive | Diagnostic flag. Needs: TR200 Modbus AFD Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Comm Loss: Economizer Bypass Valve | Diagnostic flag. Needs: Economizer | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Comm Loss: Economizer Pressure | Diagnostic flag. Needs: Economizer | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4036doc 34037 | Comm Loss: Economizer Temperature | Diagnostic flag. Needs: Economizer | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4037doc 34038 | Comm Loss: Economizer Valve | Diagnostic flag. Needs: Economizer | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Comm Loss: Hot Gas Bypass Valve | Diagnostic flag. Needs: Variable Vi | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Comm Loss: Liquid Line Bypass Valve | Diagnostic flag. Needs: Liquid Line Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Comm Loss: Oil Return Purge Valve | Diagnostic flag. Needs: Variable Vi | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Comm Loss: Slide Valve Load | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Comm Loss: Slide Valve Unload | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Diagnostic: Economizer Pressure Sensor | Diagnostic flag. Needs: Economizer | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Diagnostic: Economizer Temperature Sensor | Diagnostic flag. Needs: Economizer | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Diagnostic: Restart Inhibit | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Comm Loss: Cond Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Diagnostic: Condenser Refrigerant Pressure Xdcr | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Diagnostic: Excessive Condenser Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Comm Loss: Condenser Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Comm Loss: Condenser Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Comm Loss: Cond Diff Water Pressure | Diagnostic flag. Needs: Cond Differential Water Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Diagnostic: Condenser Diff Water Pressure Xdcr | Diagnostic flag. Needs: Cond Differential Water Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Diagnostic: Condenser Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Diagnostic: Condenser Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Comm Loss: Condenser Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Comm Loss: Condenser Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Diagnostic: Condenser Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Diagnostic: Condenser Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Comm Loss: Evaporator Rfgt Liquid Level | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Diagnostic: Evaporator Liquid Level Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Diagnostic: High Evaporator Liquid Level | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Diagnostic: Low Evaporator Liquid Level | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Diagnostic: Low Evaporator Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Diagnostic: Low Evaporator Refrigerant Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Diagnostic: Low Evaporator Temp: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Comm Loss: Evaporator Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Comm Loss: Evap Diff Water Pressure | Diagnostic flag. Needs: Evap Differential Water Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Diagnostic flag. Needs: Evap Differential Water Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Diagnostic: Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Diagnostic: Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4072doc 34073 | Diagnostic: High Evaporator Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Diagnostic: High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4074doc 34075 | Diagnostic: Low Evaporator Water Flow | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4075doc 34076 | Diagnostic: Evap Water Flow (Entering Water Temp) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Diagnostic: Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Diagnostic: Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Diagnostic: Low Evaporator Water Temp (Unit On) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Comm Loss: Electronic Expansion Valve 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Comm Loss: Electronic Expansion Valve 2 | Diagnostic flag. Needs: Dual Expansion Valve | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Comm Loss: Evaporator Rfgt Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Diagnostic: Evaporator Rfgt Pressure Transducer | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Comm Loss: Compressor % RLA Output | Diagnostic flag. Needs: Motor Current Analog Output | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Comm Loss: Cond Head Press Cntrl Output | Diagnostic flag. Needs: Head Pressure Control | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Comm Loss: Cond Rfgt Pressure Output | Diagnostic flag. Needs: Delta P HPC Setting | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Comm Loss: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Comm Loss: Ext Chilled/Hot Water Setpoint | Diagnostic flag. Needs: Ext Chilled Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Comm Loss: External Demand Limit Setpoint | Diagnostic flag. Needs: Ext Demand Limit Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Comm Loss: External Hot Water Command | Diagnostic flag. Needs: Hot Water Control | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Comm Loss: Op Status Programmable Relays | Diagnostic flag. Needs: Programmable Status Relay | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Comm Loss: Refrigerant Monitor Input | Diagnostic flag. Needs: Refrigerant Monitor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Diagnostic: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4095doc 34096 | Diagnostic: External Chilled/Hot Water Setpoint | Diagnostic flag. Needs: Ext Chilled Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4096doc 34097 | Diagnostic: External Demand Limit Setpoint | Diagnostic flag. Needs: Ext Demand Limit Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Diagnostic: Refrigerant Monitor Input | Diagnostic flag. Needs: Refrigerant Monitor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Comm Loss: External Heat Recovery Command | Diagnostic flag. Needs: Ext Heat Recovery Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Comm Loss: External Heat Recovery Setpoint | Diagnostic flag. Needs: Ext Heat Recovery Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4100doc 34101 | Comm Loss: HR Entering Water Temp Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4101doc 34102 | Comm Loss: HR Leaving Water Temp Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Comm Loss: Heat Recovery Tank Water Temp | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Comm Loss: Heat Recovery Water Flow Switch | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Comm Loss: Heat Recovery Water Pump Relay | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Diagnostic: Ext Heat Recovery Temp Setpoint Sensor | Diagnostic flag. Needs: Ext Heat Recovery Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Diagnostic: Heat Recovery Entering Water Temperature Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Diagnostic: Heat Recovery Leaving Water Temperature Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Diagnostic: Heat Recovery Tank Water Temp Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4109doc 34110 | Diagnostic: Heat Recovery Water Flow Lost | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4110doc 34111 | Diagnostic: Heat Recovery Water Flow Overdue | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4111doc 34112 | Diagnostic: Unexpected Heat Recovery Water Flow | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Diagnostic: Unexpected Condenser Water Flow | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Comm Loss: External Ice Building Command | Diagnostic flag. Needs: Ice Building | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Comm Loss: Ice Building Relay | Diagnostic flag. Needs: Ice Building | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Comm Loss: SSS/AFD Fault | Diagnostic flag. Needs: Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Comm Loss: Starter | Diagnostic flag. Needs: Solid State Starter Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Diagnostic: Solid State Starter Fault | Diagnostic flag. Needs: Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Diagnostic: Starter Failed to Arm/Start | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Diagnostic: Unexpected Starter Shutdown | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Diagnostic: AFD Bus Over Voltage | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4121doc 34122 | Diagnostic: AFD Bus Under Voltage | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Diagnostic: AFD Comm Loss: Main Processor | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Diagnostic: AFD Emergency Stop Fault | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Diagnostic: AFD General Failure | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Diagnostic: AFD Ground Fault | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Diagnostic: AFD Instantaneous Current Overload | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Diagnostic: AFD Interrupt Failure | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Diagnostic: AFD Inverter Heatsink Over Temp | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Diagnostic: AFD Motor Current Overload | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Diagnostic: AFD Output Phase Loss | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Diagnostic: AFD Rated Current Out of Range | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Diagnostic: At Speed Input Opened | Diagnostic flag. Needs: Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Diagnostic: At Speed Input Shorted | Diagnostic flag. Needs: Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Comm Loss: Motor Winding Temperature 1 | Diagnostic flag. Needs: Motor Winding Temp | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Comm Loss: Motor Winding Temperature 2 | Diagnostic flag. Needs: Motor Winding Temp | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Diagnostic: Cprsr Did Not Accelerate: Transition | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Diagnostic: Compressor Did Not Accelerate Fully | Diagnostic flag. Needs: Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4138doc 34139 | Diagnostic: Compressor Did Not Accelerate: Shutdown | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4139doc 34140 | Diagnostic: High Motor Winding Temperature | Diagnostic flag. Needs: Motor Winding Temp | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Diagnostic: High Pressure Cutout | Diagnostic flag. Needs: Local Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Diagnostic: Momentary Power Loss | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4142doc 34143 | Diagnostic: Motor Current Overload | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4143doc 34144 | Diagnostic: Motor Winding Temp Sensor - Cprsr1A | Diagnostic flag. Needs: Motor Winding Temp | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Diagnostic: Over Voltage | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Diagnostic: Phase Loss | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4146doc 34147 | Diagnostic: Phase Reversal | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Diagnostic: Power Loss | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Diagnostic: Severe Current Unbalance | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Starter Comm Loss: Main Processor | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4150doc 34151 | Diagnostic: Starter Contactor Interrupt Failure | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4151doc 34152 | Diagnostic: Starter Did Not Transition | Diagnostic flag. Needs: Wye-Delta Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4152doc 34153 | Diagnostic: Starter Dry Run Test | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4153doc 34154 | Diagnostic: Starter Fault Type I | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4154doc 34155 | Diagnostic: Starter Fault Type II | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4155doc 34156 | Diagnostic: Starter Fault Type III | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Diagnostic: Starter Module Memory Error Type 1 | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Diagnostic: Starter Module Memory Error Type 2 | Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Diagnostic: Transition Complete Input Opened | Diagnostic flag. Needs: Wye-Delta Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Diagnostic: Transition Complete Input Shorted | Diagnostic flag. Needs: Wye-Delta Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Diagnostic: Under Voltage | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Diagnostic: MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Diagnostic: MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 14doc 40015 | Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | Base Loading Setpoint | Needs: Base Loading | FLOAT32 | ABCD | % | Read/write | ||
| HR | 18doc 40019 | Heat Recovery Water Tank Temperature Setpoint BAS | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read/write | |||
| HR | 2010doc 42011 | Chiller Mode Command BAS | UINT16 | Read/write | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| HR | 3010doc 43011 | Chiller Auto Stop Command BAS | UINT16 | Read/write | 0 = Stop; 1 = Auto | ||||
| HR | 3011doc 43012 | Reset Diagnostic | UINT16 | Read/write | 0 = Normal; 1 = Reset | ||||
| HR | 3012doc 43013 | Base Loading Request | Needs: Base Loading | UINT16 | Read/write | 0 = Normal; 1 = Reduce Noise | |||
| HR | 3013doc 43014 | Heat Recovery Enable BAS | Needs: Heat Recovery | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 3014doc 43015 | Evaporator Water Pump Request BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3015doc 43016 | Condenser Water Pump Request BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Controller setup and the I-P/SI units statement come from Trane's Symbio 800 integration guide BAS-SVP047B-EN (Sept 2023, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP047B-EN_09092023.pdf), which describes the same Symbio 800 controller.
- Page 37 of the list, headed Modbus Binary Values, repeats the binary inputs 33011-33032; it is ignored here and the binary values are taken from page 38 (43011-43016).
- Some Binary Value states are printed with text copied from other points (Base Loading Request '1 = Reduce Noise', pump requests '1 = Locked Out'); they are copied as printed.
- The list skips 30109.
- Trane publishes a separate points list for the older UC800 controller on the RTHD (BAS-PTS034A-EN); that register set is not this one.
- Condenser/Evaporator Water Pump Request and Condenser Water Flow Status (33026-33028) are printed with the states 0 = Normal / 1 = In Alarm; copied as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
What Modbus registers does the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) have?
This map lists 275 registers: 263 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)?
Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 18 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 16 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 26 Actual Running Capacity (Actual running capacity); IR 2010 Running Mode (Running mode); IR 3010 Run Enabled (Run enabled); IR 3016 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3010 Chiller Auto Stop Command BAS (Chiller auto/stop command); HR 3011 Reset Diagnostic (Reset diagnostic).
How do I enable Modbus control of the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)?
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Where is the official Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTHD (BAS-PTS015A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS015A-EN_11152024.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121 - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTHD · BAS-PTS015A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.