Chiller · Modbus register map

Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus register map

Updated 19 November 2026

Short answer

Trane's Series R RTHD is a single-compressor water-cooled helical-rotary (screw) chiller. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, evaporator and condenser water temperatures, refrigerant and oil pressures, starter currents and voltages, energy meter values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.

This page lists 275 Modbus registers for the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Equipment type
Chiller
Registers
275 (12 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RTHD, Series R RTHD
Source document
Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTHD · BAS-PTS015A-EN · rev. 2024-11-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Cool/Heat Setpoint TemperatureFLOAT32 ABCDActive cool/heat setpointRead
IR 18Evaporator Leaving Water TemperatureFLOAT32 ABCDEvaporator leaving water temperatureRead
IR 16Evaporator Entering Water TemperatureFLOAT32 ABCDEvaporator entering water temperatureRead
IR 26Actual Running CapacityFLOAT32 ABCDActual running capacityRead
IR 2010Running ModeUINT16Running modeRead
IR 3010Run EnabledUINT16Run enabledRead
IR 3016Diagnostic PresentUINT16Diagnostic presentRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 2010Chiller Mode Command BASUINT16BAS chiller mode commandRead/write
HR 3010Chiller Auto Stop Command BASUINT16Chiller auto/stop commandRead/write
HR 3011Reset DiagnosticUINT16Reset diagnosticRead/write

Enable Modbus control & writes

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Byte order & addressing

Network setup

Watch out for

Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

275 of 275 shown
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Cool/Heat Setpoint TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Active Demand Limit SetpointFLOAT32ABCD%Read
IR14doc 30015Active Base Loading SetpointNeeds: Base LoadingFLOAT32ABCD%Read
IR16doc 30017Evaporator Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR18doc 30019Evaporator Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR20doc 30021Number of CircuitsFLOAT32ABCDRead
IR22doc 30023Number of Compressors Circuit 1FLOAT32ABCDRead
IR24doc 30025Number of Compressors Circuit 2FLOAT32ABCDRead
IR26doc 30027Actual Running CapacityFLOAT32ABCD%Read
IR28doc 30029Evaporator Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR30doc 30031Condenser Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR32doc 30033Evaporator Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR34doc 30035Condenser Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR36doc 30037Refrigerant Discharge Temperature - Compressor 1ATemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR38doc 30039High Side Oil Absolute Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR40doc 30041Starts - Compressor 1AFLOAT32ABCDRead
IR42doc 30043Run Time - Compressor 1AFLOAT32ABCDRead
IR44doc 30045Motor Winding Temperature 1 Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Motor Winding TempFLOAT32ABCDRead
IR46doc 30047Motor Winding Temperature 2 Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Motor Winding TempFLOAT32ABCDRead
IR48doc 30049Condenser Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR50doc 30051Condenser Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR52doc 30053Starter Voltage Phase ABVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR54doc 30055Starter Voltage Phase BCVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR56doc 30057Starter Voltage Phase CAVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR58doc 30059Line 1 Current - Compressor 1ACurrent. Needs: Starter Non Comm AFD TR200 Modbus AFDFLOAT32ABCDRead
IR60doc 30061Line 2 Current - Compressor 1ACurrent. Needs: Starter Non Comm AFD TR200 Modbus AFDFLOAT32ABCDRead
IR62doc 30063Line 3 Current - Compressor 1ACurrent. Needs: Starter Non Comm AFD TR200 Modbus AFDFLOAT32ABCDRead
IR64doc 30065Line 1 Current - Compressor 1ACurrent. Needs: Local Comm AFDFLOAT32ABCDRead
IR66doc 30067Line 2 Current - Compressor 1ACurrent. Needs: Local Comm AFDFLOAT32ABCDRead
IR68doc 30069Line 3 Current - Compressor 1ACurrent. Needs: Local Comm AFDFLOAT32ABCDRead
IR70doc 30071Line 1 Current RLA - Compressor 1ANeeds: Starter Non Comm AFD TR200 Modbus AFDFLOAT32ABCD%Read
IR72doc 30073Line 2 Current RLA - Compressor 1ANeeds: Starter Non Comm AFD TR200 Modbus AFDFLOAT32ABCD%Read
IR74doc 30075Line 3 Current RLA - Compressor 1ANeeds: Starter Non Comm AFD TR200 Modbus AFDFLOAT32ABCD%Read
IR76doc 30077Line 1 Current RLA - Compressor 1ANeeds: Local Comm AFDFLOAT32ABCD%Read
IR78doc 30079Line 2 Current RLA - Compressor 1ANeeds: Local Comm AFDFLOAT32ABCD%Read
IR80doc 30081Line 3 Current RLA - Compressor 1ANeeds: Local Comm AFDFLOAT32ABCD%Read
IR82doc 30083Expansion Valve Position - Compressor 1AFLOAT32ABCD%Read
IR84doc 30085Drive Output Power Circuit 1Electrical power. Needs: Non Comm AFD TR200 Modbus AFD Local Comm AFDFLOAT32ABCDRead
IR86doc 30087Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR88doc 30089Active Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR90doc 30091Active Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR92doc 30093Evaporator Water Flow RateFlow in the factory unit system (I-P or SI). Needs: Evap Differential Water PressureFLOAT32ABCDRead
IR94doc 30095Condenser Water Flow RateFlow in the factory unit system (I-P or SI). Needs: Cond Differential Water PressureFLOAT32ABCDRead
IR96doc 30097Condenser Differential Water PressurePressure in the factory unit system (I-P or SI). Needs: Cond Differential Water PressureFLOAT32ABCDRead
IR98doc 30099Evaporator Differential Water PressurePressure in the factory unit system (I-P or SI). Needs: Evap Differential Water PressureFLOAT32ABCDRead
IR100doc 30101Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR102doc 30103Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR104doc 30105Condenser Control OutputNeeds: Head Pressure ControlFLOAT32ABCD%Read
IR106doc 30107High Side Oil Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR110doc 30111Evaporator Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR112doc 30113Condenser Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR114doc 30115Line Frequency Circuit 1Needs: Non Comm AFD TR200 Modbus AFD Local Comm AFDFLOAT32ABCDRead
IR116doc 30117Heat Recovery Entering Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR118doc 30119Heat Recovery Leaving Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR120doc 30121Heat Recovery Tank Water TempTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR122doc 30123Heat Recovery Water Tank Temperature Setpoint ActiveTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR124doc 30125Chilled Water Setpoint StatusTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR126doc 30127Demand Limit Setpoint StatusNeeds: Ice BuildingFLOAT32ABCD%Read
IR128doc 30129Unit Source ID (Last Diagnostic Code)FLOAT32ABCDRead
IR130doc 30131Current L1Current. Needs: Energy MeterFLOAT32ABCDRead
IR132doc 30133Current L2Current. Needs: Energy MeterFLOAT32ABCDRead
IR134doc 30135Current L3Current. Needs: Energy MeterFLOAT32ABCDRead
IR136doc 30137Average CurrentCurrent. Needs: Energy MeterFLOAT32ABCDRead
IR138doc 30139Voltage L1-L2Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR140doc 30141Voltage L2-L3Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR142doc 30143Voltage L1-L3Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR144doc 30145Average Voltage L-LVoltage. Needs: Energy MeterFLOAT32ABCDRead
IR146doc 30147Line FrequencyNeeds: Energy MeterFLOAT32ABCDRead
IR148doc 30149Power FactorNeeds: Energy MeterFLOAT32ABCDRead
IR2010doc 32011Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre- Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2012doc 32013Refrigerant TypeUINT16Read1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 6 = R-407C; 7 = R-410A; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 12 = R-404A; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A; 16 = R-1234ze(E)
IR2013doc 32014Manufacture LocationUINT16Read1 = Field Applied; 2 = La Crosse; 3 = Pueblo; 4 = Charmes; 5 = Rushville; 6 = Macon; 7 = Waco; 8 = Lexington; 9 = Forsyth; 10 = Clarksville; 11 = Ft. Smith; 12 = Penang; 13 = Colchester; 14 = Curitiba; 15 = Taicang; 16 = Taiwan; 17 = Epinal; 18 = Golbey
IR2014doc 32015Cooling TypeUINT16Read1 = Water Cooled; 2 = Air Cooled
IR2015doc 32016Model Information [GEN2]UINT16Read1 = CVHF; 2 = CVGF; 3 = CVHS; 4 = RTAE; 5 = RTAF; 6 = RTHA; 7 = RTHB; 8 = RTHC; 9 = RTHD; 10 = RTWE; 11 = CTVD; 12 = CVR; 13 = CVHH; 14 = CDHH; 15 = VMAX; 16 = GVAF; 17 = RTWF; 18 = RTHF; 19 = RTAC; 20 = CVHM; 21 = RTAG; 22 = CGAF; 23 = RTXG; 24 = GVWF; 25 = HDWA; 26 = CMAC; 27 = IPAK; 28 = CXAF; 29 = ACSA; 30 = RTSF; 31 = HSWA; 32 = ACRA; 33 = RTEG; 34 = ACXA; 35 = CMAF; 36 = ACRB Large; 37 = ACRB Small
IR3010doc 33011Run EnabledUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3011doc 33012Local Setpoint ControlUINT16Read0 = Remote control; 1 = Local control
IR3012doc 33013Limit Mode Relay StatusUINT16Read0 = Off; 1 = On
IR3013doc 33014Chiller Running StateUINT16Read0 = Off; 1 = On
IR3014doc 33015Base Loading Request ActiveNeeds: Base LoadingUINT16Read0 = Off; 1 = On
IR3015doc 33016Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3016doc 33017Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3017doc 33018Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3018doc 33019Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3019doc 33020Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3020doc 33021Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3021doc 33022Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3022doc 33023Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3023doc 33024Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3024doc 33025Compressor 1A StatusUINT16Read0 = Off; 1 = Running
IR3025doc 33026Condenser Water Pump RequestUINT16Read0 = Normal; 1 = In Alarm
IR3026doc 33027Evaporator Water Pump RequestUINT16Read0 = Normal; 1 = In Alarm
IR3027doc 33028Condenser Water Flow StatusUINT16Read0 = Normal; 1 = In Alarm
IR3028doc 33029Heat Recovery Water Flow StatusNeeds: Heat RecoveryUINT16Read0 = Off; 1 = Running
IR3029doc 33030Heat Recovery Control Active StatusNeeds: Heat RecoveryUINT16Read0 = Off; 1 = Running
IR3030doc 33031Heat Recovery Request ActiveNeeds: Heat RecoveryUINT16Read0 = Off; 1 = Running
IR3031doc 33032Front Panel Auto StopUINT16Read0 = Stop; 1 = Auto
IR3032doc 33033External Auto Stop Input StatusUINT16Read0 = Stop; 1 = Auto
IR3033doc 33034Head Relief RequestUINT16Read0 = Inactive; 1 = Active
IR3034doc 33035Base Loading ActiveNeeds: Base LoadingUINT16Read0 = Off; 1 = On
IR4000doc 34001Comm Loss: Ext Base Loading CommandDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Comm Loss: Ext Base Loading SetpointDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Diagnostic: External Base Loading SetpointDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Comm Loss: Outdoor Air TemperatureDiagnostic flag. Needs: Outdoor Air TemperatureUINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Diagnostic: Outdoor Air Temperature SensorDiagnostic flag. Needs: Outdoor Air TemperatureUINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Diagnostic: Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Diagnostic: AFD Drive FaultDiagnostic flag. Needs: Non Comm AFD TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Comm Loss: Cprsr Discharge Rfgt TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Comm Loss: Cond High Pressure CutoutDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFD TR200 Modbus Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Comm Loss: Primary Oil Line Solenoid ValveDiagnostic flag. Needs: Solid State Starter Non Comm AFD TR200 Modbus AFD Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Comm Loss: Oil Loss Level Sensor InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Comm Loss: Oil PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Comm Loss: Oil Return Gas Pump DrainDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Comm Loss: Oil Return Gas Pump FillDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Comm Loss: SSS/AFD FaultDiagnostic flag. Needs: Non Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Diagnostic: Cprsr Discharge Refrigerant Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Diagnostic: High Cprsr Rfgt Discharge TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Diagnostic: High Differential Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Diagnostic: High Pressure CutoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Diagnostic: High Refrigerant Pressure RatioDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Diagnostic: Loss of Oil at Compressor (Running)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Diagnostic: Loss of Oil at Compressor (Stopped)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Diagnostic: Low Differential Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Diagnostic: Low Discharge SuperheatDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Diagnostic: Low Oil FlowDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Diagnostic: No Differential Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Diagnostic: Oil Flow Protection FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Diagnostic: Oil Pressure TransducerDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Diagnostic: AFD Output Power InputDiagnostic flag. Needs: Non Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Comm Loss: AFD Output Power InputDiagnostic flag. Needs: Non Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Comm Loss: AFD Speed Signal OutputDiagnostic flag. Needs: Non Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Comm Loss: Adaptive Frequency DriveDiagnostic flag. Needs: TR200 Modbus AFD Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Comm Loss: Economizer Bypass ValveDiagnostic flag. Needs: EconomizerUINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Comm Loss: Economizer PressureDiagnostic flag. Needs: EconomizerUINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Comm Loss: Economizer TemperatureDiagnostic flag. Needs: EconomizerUINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Comm Loss: Economizer ValveDiagnostic flag. Needs: EconomizerUINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Comm Loss: Hot Gas Bypass ValveDiagnostic flag. Needs: Variable ViUINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Comm Loss: Liquid Line Bypass ValveDiagnostic flag. Needs: Liquid Line BypassUINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Comm Loss: Oil Return Purge ValveDiagnostic flag. Needs: Variable ViUINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Comm Loss: Slide Valve LoadDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Comm Loss: Slide Valve UnloadDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Diagnostic: Economizer Pressure SensorDiagnostic flag. Needs: EconomizerUINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Diagnostic: Economizer Temperature SensorDiagnostic flag. Needs: EconomizerUINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Diagnostic: Restart InhibitDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Comm Loss: Cond Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Diagnostic: Condenser Refrigerant Pressure XdcrDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Diagnostic: Excessive Condenser PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Comm Loss: Condenser Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Comm Loss: Condenser Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Comm Loss: Cond Diff Water PressureDiagnostic flag. Needs: Cond Differential Water PressureUINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Diagnostic: Condenser Diff Water Pressure XdcrDiagnostic flag. Needs: Cond Differential Water PressureUINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Diagnostic: Condenser Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Diagnostic: Condenser Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Comm Loss: Condenser Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Comm Loss: Condenser Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Diagnostic: Condenser Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Diagnostic: Condenser Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Comm Loss: Evaporator Rfgt Liquid LevelDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Diagnostic: Evaporator Liquid Level SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Diagnostic: High Evaporator Liquid LevelDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Diagnostic: Low Evaporator Liquid LevelDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Diagnostic: Low Evaporator Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Diagnostic: Low Evaporator Refrigerant TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Diagnostic: Low Evaporator Temp: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Comm Loss: Evaporator Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Comm Loss: Evap Diff Water PressureDiagnostic flag. Needs: Evap Differential Water PressureUINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Diagnostic: Evaporator Diff Water Pressure XdcrDiagnostic flag. Needs: Evap Differential Water PressureUINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Diagnostic: High Evaporator Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Diagnostic: Low Evaporator Water FlowDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Diagnostic: Evap Water Flow (Entering Water Temp)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Diagnostic: Low Evaporator Water Temp (Unit On)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Diagnostic: Low Evaporator Water Temp (Unit Off)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Comm Loss: Electronic Expansion Valve 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Comm Loss: Electronic Expansion Valve 2Diagnostic flag. Needs: Dual Expansion ValveUINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Comm Loss: Evaporator Rfgt PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Diagnostic: Evaporator Rfgt Pressure TransducerDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Comm Loss: Compressor % RLA OutputDiagnostic flag. Needs: Motor Current Analog OutputUINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Comm Loss: Cond Head Press Cntrl OutputDiagnostic flag. Needs: Head Pressure ControlUINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Comm Loss: Cond Rfgt Pressure OutputDiagnostic flag. Needs: Delta P HPC SettingUINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Comm Loss: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Comm Loss: Ext Chilled/Hot Water SetpointDiagnostic flag. Needs: Ext Chilled Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Comm Loss: External Demand Limit SetpointDiagnostic flag. Needs: Ext Demand Limit SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Comm Loss: External Hot Water CommandDiagnostic flag. Needs: Hot Water ControlUINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Comm Loss: Op Status Programmable RelaysDiagnostic flag. Needs: Programmable Status RelayUINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Comm Loss: Refrigerant Monitor InputDiagnostic flag. Needs: Refrigerant MonitorUINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Diagnostic: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Diagnostic: External Chilled/Hot Water SetpointDiagnostic flag. Needs: Ext Chilled Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Diagnostic: External Demand Limit SetpointDiagnostic flag. Needs: Ext Demand Limit SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Diagnostic: Refrigerant Monitor InputDiagnostic flag. Needs: Refrigerant MonitorUINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Comm Loss: External Heat Recovery CommandDiagnostic flag. Needs: Ext Heat Recovery SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Comm Loss: External Heat Recovery SetpointDiagnostic flag. Needs: Ext Heat Recovery SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Comm Loss: HR Entering Water Temp SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Comm Loss: HR Leaving Water Temp SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Comm Loss: Heat Recovery Tank Water TempDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Comm Loss: Heat Recovery Water Flow SwitchDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Comm Loss: Heat Recovery Water Pump RelayDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Diagnostic: Ext Heat Recovery Temp Setpoint SensorDiagnostic flag. Needs: Ext Heat Recovery SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Diagnostic: Heat Recovery Entering Water Temperature SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Diagnostic: Heat Recovery Leaving Water Temperature SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Diagnostic: Heat Recovery Tank Water Temp SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Diagnostic: Heat Recovery Water Flow LostDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Diagnostic: Heat Recovery Water Flow OverdueDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Diagnostic: Unexpected Heat Recovery Water FlowDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Diagnostic: Unexpected Condenser Water FlowDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Comm Loss: External Ice Building CommandDiagnostic flag. Needs: Ice BuildingUINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Comm Loss: Ice Building RelayDiagnostic flag. Needs: Ice BuildingUINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Comm Loss: SSS/AFD FaultDiagnostic flag. Needs: Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Comm Loss: StarterDiagnostic flag. Needs: Solid State Starter Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Diagnostic: Solid State Starter FaultDiagnostic flag. Needs: Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Diagnostic: Starter Failed to Arm/StartDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Diagnostic: Unexpected Starter ShutdownDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Diagnostic: AFD Bus Over VoltageDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Diagnostic: AFD Bus Under VoltageDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Diagnostic: AFD Comm Loss: Main ProcessorDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Diagnostic: AFD Emergency Stop FaultDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Diagnostic: AFD General FailureDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Diagnostic: AFD Ground FaultDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Diagnostic: AFD Instantaneous Current OverloadDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Diagnostic: AFD Interrupt FailureDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Diagnostic: AFD Inverter Heatsink Over TempDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Diagnostic: AFD Motor Current OverloadDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Diagnostic: AFD Output Phase LossDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Diagnostic: AFD Rated Current Out of RangeDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Diagnostic: At Speed Input OpenedDiagnostic flag. Needs: Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Diagnostic: At Speed Input ShortedDiagnostic flag. Needs: Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Comm Loss: Motor Winding Temperature 1Diagnostic flag. Needs: Motor Winding TempUINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Comm Loss: Motor Winding Temperature 2Diagnostic flag. Needs: Motor Winding TempUINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Diagnostic: Cprsr Did Not Accelerate: TransitionDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Diagnostic: Compressor Did Not Accelerate FullyDiagnostic flag. Needs: Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Diagnostic: Compressor Did Not Accelerate: ShutdownDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Diagnostic: High Motor Winding TemperatureDiagnostic flag. Needs: Motor Winding TempUINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Diagnostic: High Pressure CutoutDiagnostic flag. Needs: Local Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Diagnostic: Momentary Power LossDiagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Diagnostic: Motor Current OverloadDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Diagnostic: Motor Winding Temp Sensor - Cprsr1ADiagnostic flag. Needs: Motor Winding TempUINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Diagnostic: Over VoltageDiagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Diagnostic: Phase LossDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Diagnostic: Phase ReversalDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Diagnostic: Power LossDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Diagnostic: Severe Current UnbalanceDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Starter Comm Loss: Main ProcessorDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Diagnostic: Starter Contactor Interrupt FailureDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Diagnostic: Starter Did Not TransitionDiagnostic flag. Needs: Wye-Delta StarterUINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Diagnostic: Starter Dry Run TestDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Diagnostic: Starter Fault Type IDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Diagnostic: Starter Fault Type IIDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Diagnostic: Starter Fault Type IIIDiagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Diagnostic: Starter Module Memory Error Type 1Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Diagnostic: Starter Module Memory Error Type 2Diagnostic flag. Needs: Wye-Delta Starter Solid State Starter Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Diagnostic: Transition Complete Input OpenedDiagnostic flag. Needs: Wye-Delta StarterUINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Diagnostic: Transition Complete Input ShortedDiagnostic flag. Needs: Wye-Delta StarterUINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Diagnostic: Under VoltageDiagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR16doc 40017Base Loading SetpointNeeds: Base LoadingFLOAT32ABCD%Read/write
HR18doc 40019Heat Recovery Water Tank Temperature Setpoint BASTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead/write
HR2010doc 42011Chiller Mode Command BASUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
HR3010doc 43011Chiller Auto Stop Command BASUINT16Read/write0 = Stop; 1 = Auto
HR3011doc 43012Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3012doc 43013Base Loading RequestNeeds: Base LoadingUINT16Read/write0 = Normal; 1 = Reduce Noise
HR3013doc 43014Heat Recovery Enable BASNeeds: Heat RecoveryUINT16Read/write0 = Off; 1 = On
HR3014doc 43015Evaporator Water Pump Request BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3015doc 43016Condenser Water Pump Request BASUINT16Read/write0 = Normal; 1 = Locked Out

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)

What Modbus registers does the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) have?

This map lists 275 registers: 263 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)?

Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 18 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 16 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 26 Actual Running Capacity (Actual running capacity); IR 2010 Running Mode (Running mode); IR 3010 Run Enabled (Run enabled); IR 3016 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3010 Chiller Auto Stop Command BAS (Chiller auto/stop command); HR 3011 Reset Diagnostic (Reset diagnostic).

How do I enable Modbus control of the Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)?

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Where is the official Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTHD (BAS-PTS015A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS015A-EN_11152024.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTHD · BAS-PTS015A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.