Chiller · Modbus register map

Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module) Modbus register map

Updated 19 November 2026

Short answer

Older McQuay centrifugal chillers whose MicroTech II controller takes a plug-in Modbus RTU module. The map is a small fixed set of coils and 16-bit holding registers: start/stop, setpoints, water and refrigerant temperatures and pressures, flows, motor values for a selectable compressor, run hours and a 16-word alarm bitmap.

This page lists 63 Modbus registers for the Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin Applied
Model
MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
Equipment type
Chiller
Registers
63 (9 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063
Source document
MicroTech II Chiller Unit Controller Protocol Information, Modbus Protocol · ED 15063-2 · rev. 2005-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)

Integration in brief

Read the shaded minimum points (status, water temperatures, capacity, alarm coil) and write Chiller Enable (coil 2) and Cool Setpoint (40002) once the unit's setpoint source is switched to the network.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 146Chiller StatusUINT16Chiller statusRead
HR 1Cool SetpointINT16Cool setpointRead/write
HR 6Evaporator Leaving Water Temperature for UnitINT16Evaporator leaving water temperatureRead
HR 4Evaporator Entering Water TemperatureINT16Evaporator entering water temperatureRead
HR 10Actual CapacityUINT16Actual capacityRead
CO 1Chiller EnableBITChiller enable (start/stop)Read/write
CO 3Alarm Digital OutputBITAlarm presentRead
CO 24Clear AlarmsBITClear alarmsRead/write

Enable Modbus control & writes

At the touch-screen interface panel set SETPOINTS MODE #9 'BAS Protocol' to Modbus (operator password 2001), then set #3 'Control Source' to BAS once communication is confirmed.

Byte order & addressing

Network setup

Watch out for

Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

63 of 63 shown
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1doc 2Chiller EnableNetwork start/stop of the chiller.BITRead/write0 = Off (disable); 1 = On (enable)
CO2doc 3Chiller On Off / Run EnabledPrinted under two point names that share coil 3.BITRead0 = Off; 1 = On / run allowed
CO3doc 4Alarm Digital OutputAny alarm active; poll it, then read the alarm words.BITRead0 = No alarm; 1 = Alarm
CO5doc 6Chiller Local/RemoteBITRead0 = Remote; 1 = Local
CO6doc 7Chiller LimitedConditions may stop the chiller reaching setpoint.BITRead0 = Not limited; 1 = Limited
CO7doc 8Evaporator Flow Switch StatusBITRead0 = No flow; 1 = Flow
CO8doc 9Condenser Flow Switch StatusBITRead0 = No flow; 1 = Flow
CO19doc 20Pump SelectChooses the pump reported by the pump run-hour registers.BITRead/write0 = Pump #1; 1 = Pump #2
CO24doc 25Clear AlarmsClears clearable alarms; shutdown faults need the panel.BITRead/write0 = Normal; 1 = Clear alarm
CO29doc 30Evaporator Water Pump StatusBITRead0 = Pump off request; 1 = Pump on request
CO31doc 32Condenser Water Pump StatusBITRead0 = Pump off request; 1 = Pump on request
HR1doc 40002Cool SetpointLeaving chilled water setpoint in cooling mode.INT16× 0.1°FRead/write
HR2doc 40003Active SetpointLeaving water setpoint in use.INT16× 0.1°FRead
HR3doc 40004Capacity Limit SetpointMaximum capacity set by the network (0-160 %).UINT16× 0.1%Write
HR4doc 40005Evaporator Entering Water TemperatureINT16× 0.1°FRead
HR5doc 40006Heat SetpointUsed only in heat mode.INT16× 0.1°FRead/write
HR6doc 40007Evaporator Leaving Water Temperature for UnitINT16× 0.1°FRead
HR7doc 40008Condenser Entering Water TemperatureINT16× 0.1°FRead
HR8doc 40009Condenser Leaving Water TemperatureINT16× 0.1°FRead
HR10doc 40011Actual CapacityPercent of nominal capacity (0-160 %).UINT16× 0.1%Read
HR14doc 40015Evaporator Leaving Water Temperature for CompressorFor the compressor chosen in Compressor Select.INT16× 0.1°FRead
HR15doc 40016Compressor Suction Line TemperatureFor the compressor chosen in Compressor Select.INT16× 0.1°FRead
HR16doc 40017Evaporator Saturated Refrigerant TemperatureFor the compressor/circuit chosen in Compressor Select.INT16× 0.1°FRead
HR17doc 40018Evaporator Refrigerant PressureGauge pressure, selected compressor/circuit.INT16× 0.1psiRead
HR18doc 40019Evaporator Water Flow RateUINT16gpmRead
HR19doc 40020Compressor Discharge TemperatureFor the compressor chosen in Compressor Select.INT16× 0.1°FRead
HR20doc 40021Condenser Saturated Refrigerant TemperatureFor the compressor/circuit chosen in Compressor Select.INT16× 0.1°FRead
HR21doc 40022Condenser Refrigerant PressureGauge pressure, selected compressor/circuit.INT16× 0.1psiRead
HR22doc 40023Heat Recovery Entering Water TemperatureINT16× 0.1°FRead
HR23doc 40024Heat Recovery Leaving Water TemperatureINT16× 0.1°FRead
HR24doc 40025Condenser Water Flow RateUINT16gpmRead
HR25doc 40026Compressor Percent RLAMotor current as % of rated load amps, selected compressor.UINT16× 0.1%Read
HR26doc 40027Compressor CurrentSelected compressor; needs the solid-state starter option.UINT16ARead
HR27doc 40028Compressor PowerSelected compressor; needs the solid-state starter option.UINT16kWRead
HR29doc 40030Compressor VoltageSelected compressor; needs the solid-state starter option.UINT16VRead
HR33doc 40034Oil Sump PressureSelected compressor (not on WMC).INT16× 0.1psiRead
HR34doc 40035Oil Feed TemperatureSelected compressor (not on WMC).INT16× 0.1°FRead
HR35doc 40036Oil Sump TemperatureSelected compressor (not on WMC).INT16× 0.1°FRead
HR36doc 40037Liquid Line Refrigerant TemperatureINT16× 0.1°FRead
HR42doc 40043Capacity Limit OutputCapacity limit currently applied (0-160 %).UINT16× 0.1%Read
HR50doc 40051Ice SetpointLeaving water setpoint in ice mode (15-35 °F).INT16× 0.1°FRead/write
HR129doc 40130Active Alarms word 1 (alarms 1-15)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 1 = 1 Entering Condenser Water Temperature Sensor Fault; bit 2 = 2 Entering Evaporator Water Temperature Sensor Fault; bit 3 = 3 Liquid Line Refrigerant Temperature Sensor Fault; bit 4 = 4 Leaving Condenser Water Temperature Sensor Fault; bit 5 = 5 Repower After Power Loss 1; bit 6 = 6 Repower After Power Loss 2; bit 7 = 7 Repower After Power Loss 3; bit 8 = 8 Repower After Power Loss 4; bit 9 = 9 (Expansion Alarm - Warning); bit 10 = 10 Low Ambient Temperature Lockout; bit 11 = 11 High Condenser Pressure - Inhibit Loading Circuit 1; bit 12 = 12 High Condenser Pressure - Inhibit Loading Circuit 2; bit 13 = 13 High Condenser Pressure - Inhibit Loading Circuit 3; bit 14 = 14 High Condenser Pressure - Inhibit Loading Circuit 4; bit 15 = 15 High Condenser Pressure - Unload
HR130doc 40131Active Alarms word 2 (alarms 16-31)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 16 High Condenser Pressure - Unload Circuit 1; bit 1 = 17 High Condenser Pressure - Unload Circuit 2; bit 2 = 18 High Condenser Pressure - Unload Circuit 3; bit 3 = 19 High Condenser Pressure - Unload Circuit 4; bit 4 = 20 Condenser Water Freeze Protect Comp 1; bit 5 = 21 Condenser Water Freeze Protect Comp 2; bit 6 = 22 Condenser Water Freeze Protect Comp 3; bit 7 = 23 Condenser Water Freeze Protect Comp 4; bit 8 = 24 Condenser Pump #1 Fault; bit 9 = 25 Condenser Pump #2 Fault; bit 10 = 26 High Discharge Temperature Comp 1; bit 11 = 27 High Discharge Temperature Comp 2; bit 12 = 28 High Discharge Temperature Comp 3; bit 13 = 29 High Discharge Temperature Comp 4; bit 14 = 30 Entering Evap Temperature Sensor Fault (EWT reset active); bit 15 = 31 Low Evaporator Pressure - Inhibit Loading
HR131doc 40132Active Alarms word 3 (alarms 32-47)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 32 Low Evaporator Pressure - Inhibit Loading Circuit 1; bit 1 = 33 Low Evaporator Pressure - Inhibit Loading Circuit 2; bit 2 = 34 Low Evaporator Pressure - Inhibit Loading Circuit 3; bit 3 = 35 Low Evaporator Pressure - Inhibit Loading Circuit 4; bit 4 = 36 Low Evaporator Pressure - Unload; bit 5 = 37 Low Evaporator Pressure - Unload Circuit 1; bit 6 = 38 Low Evaporator Pressure - Unload Circuit 2; bit 7 = 39 Low Evaporator Pressure - Unload Circuit 3; bit 8 = 40 Low Evaporator Pressure - Unload Circuit 4; bit 9 = 41 High Motor Current On Compressor #1; bit 10 = 42 High Motor Current On Compressor #2; bit 11 = 43 High Motor Current On Compressor #3; bit 12 = 44 High Motor Current On Compressor #4; bit 13 = 45 Evaporator Freeze Protect Comp 1; bit 14 = 46 Evaporator Freeze Protect Comp 2; bit 15 = 47 Evaporator Freeze Protect Comp 3
HR132doc 40133Active Alarms word 4 (alarms 48-63)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 48 Evaporator Freeze Protect Comp 4; bit 1 = 49 Evaporator Pump #1 Fault; bit 2 = 50 Evaporator Pump #2 Fault; bit 3 = 51 (Expansion Alarm - Problem); bit 4 = 52 Outside Ambient Temperature Sensor Fault; bit 5 = 53 Compressor Current Overload Trip #1; bit 6 = 54 Compressor Current Overload Trip #2; bit 7 = 55 Compressor Current Overload Trip #3; bit 8 = 56 Compressor Current Overload Trip #4; bit 9 = 57 Motor Current Imbalance On Compressor #1; bit 10 = 58 Motor Current Imbalance On Compressor #2; bit 11 = 59 Motor Current Imbalance On Compressor #3; bit 12 = 60 Motor Current Imbalance On Compressor #4; bit 13 = 61 Low Motor Current Comp 1; bit 14 = 62 Low Motor Current Comp 2; bit 15 = 63 Low Motor Current Comp 3
HR133doc 40134Active Alarms word 5 (alarms 64-79)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 64 Low Motor Current Comp 4; bit 1 = 65 Motor Protection; bit 2 = 66 Motor Protection Circuit 1; bit 3 = 67 Motor Protection Circuit 2; bit 4 = 68 High Motor Temperature Comp 1; bit 5 = 69 High Motor Temperature Comp 2; bit 6 = 70 High Motor Temperature Comp 3; bit 7 = 71 High Motor Temperature Comp 4; bit 8 = 72 Phase Loss At Compressor 1; bit 9 = 73 Phase Loss At Compressor 2; bit 10 = 74 Phase Loss At Compressor 3; bit 11 = 75 Phase Loss At Compressor 4; bit 12 = 76 Phase Reversal At Compressor 1; bit 13 = 77 Phase Reversal At Compressor 2; bit 14 = 78 Phase Reversal At Compressor 3; bit 15 = 79 Phase Reversal At Compressor 4
HR134doc 40135Active Alarms word 6 (alarms 80-95)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 80 Overvoltage On Compressor 1; bit 1 = 81 Overvoltage On Compressor 2; bit 2 = 82 Overvoltage On Compressor 3; bit 3 = 83 Overvoltage On Compressor 4; bit 4 = 84 Undervoltage On Compressor 1; bit 5 = 85 Undervoltage On Compressor 2; bit 6 = 86 Undervoltage On Compressor 3; bit 7 = 87 Undervoltage On Compressor 4; bit 8 = 88 Condenser Pressure Sensor Fault; bit 9 = 89 Condenser Pressure Sensor Fault Circuit 1; bit 10 = 90 Condenser Pressure Sensor Fault Circuit 2; bit 11 = 91 Condenser Pressure Sensor Fault Circuit 3; bit 12 = 92 Condenser Pressure Sensor Fault Circuit 4; bit 13 = 93 No Condenser Water Flow; bit 14 = 94 High Condenser Pressure; bit 15 = 95 High Condenser Pressure Circuit 1
HR135doc 40136Active Alarms word 7 (alarms 96-111)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 96 High Condenser Pressure Circuit 2; bit 1 = 97 High Condenser Pressure Circuit 3; bit 2 = 98 High Condenser Pressure Circuit 4; bit 3 = 99 No Compressor Stop Comp 1; bit 4 = 100 No Compressor Stop Comp 2; bit 5 = 101 No Compressor Stop Comp 3; bit 6 = 102 No Compressor Stop Comp 4; bit 7 = 103 Discharge Temperature Sensor Fault Circuit 1; bit 8 = 104 Discharge Temperature Sensor Fault Circuit 2; bit 9 = 105 Discharge Temperature Sensor Fault Circuit 3; bit 10 = 106 Discharge Temperature Sensor Fault Circuit 4; bit 11 = 107 High Discharge Temperature Circuit 1; bit 12 = 108 High Discharge Temperature Circuit 2; bit 13 = 109 High Discharge Temperature Circuit 3; bit 14 = 110 High Discharge Temperature Circuit 4; bit 15 = 111 Entering Condenser Water Temperature Sensor Fault
HR136doc 40137Active Alarms word 8 (alarms 112-127)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 112 No Evaporator Water Flow; bit 1 = 113 Evaporator Water Freeze Protect; bit 2 = 114 Low Evaporator Pressure; bit 3 = 115 Low Evaporator Pressure Circuit 1; bit 4 = 116 Low Evaporator Pressure Circuit 2; bit 5 = 117 Low Evaporator Pressure Circuit 3; bit 6 = 118 Low Evaporator Pressure Circuit 4; bit 7 = 119 Evaporator Pressure Sensor Fault; bit 8 = 120 Evaporator Pressure Sensor Fault Circuit 1; bit 9 = 121 Evaporator Pressure Sensor Fault Circuit 2; bit 10 = 122 Evaporator Pressure Sensor Fault Circuit 3; bit 11 = 123 Evaporator Pressure Sensor Fault Circuit 4; bit 12 = 124 Ground Fault Protection 1; bit 13 = 125 Ground Fault Protection 2; bit 14 = 126 Ground Fault Protection 3; bit 15 = 127 Ground Fault Protection 4
HR137doc 40138Active Alarms word 9 (alarms 128-143)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 128 Below Minimum Lift Pressure Circuit 1; bit 1 = 129 Below Minimum Lift Pressure Circuit 2; bit 2 = 130 Below Minimum Lift Pressure Circuit 3; bit 3 = 131 Below Minimum Lift Pressure Circuit 4; bit 4 = 132 Liquid Line Pressure Sensor Fault Circuit 1; bit 5 = 133 Liquid Line Pressure Sensor Fault Circuit 2; bit 6 = 134 Liquid Line Pressure Sensor Fault Circuit 3; bit 7 = 135 Liquid Line Pressure Sensor Fault Circuit 4; bit 8 = 136 Liquid Line Refrigerant Temperature Sensor Fault Circuit 1; bit 9 = 137 Liquid Line Refrigerant Temperature Sensor Fault Circuit 2; bit 10 = 138 Liquid Line Refrigerant Temperature Sensor Fault Circuit 3; bit 11 = 139 Liquid Line Refrigerant Temperature Sensor Fault Circuit 4; bit 12 = 140 Re-Start Fault; bit 13 = 141 Re-Start Fault Circuit 1; bit 14 = 142 Re-Start Fault Circuit 2; bit 15 = 143 Re-Start Fault Circuit 3
HR138doc 40139Active Alarms word 10 (alarms 144-159)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 144 Re-Start Fault Circuit 4; bit 1 = 145 Leaving Evaporator Water Temperature Sensor Fault; bit 2 = 146 Leaving Evaporator Water Temperature Sensor Fault Comp 1; bit 3 = 147 Leaving Evaporator Water Temperature Sensor Fault Comp 2; bit 4 = 148 Leaving Evaporator Water Temperature Sensor Fault Comp 3; bit 5 = 149 Leaving Evaporator Water Temperature Sensor Fault Comp 4; bit 6 = 150 Mechanical High Pressure; bit 7 = 151 Mechanical High Pressure Circuit 1; bit 8 = 152 Mechanical High Pressure Circuit 2; bit 9 = 153 Mechanical High Pressure Circuit 3; bit 10 = 154 Mechanical High Pressure Circuit 4; bit 11 = 155 Low Oil Net Pressure Comp 1; bit 12 = 156 Low Oil Net Pressure Comp 2; bit 13 = 157 Low Oil Net Pressure Comp 3; bit 14 = 158 Low Oil Net Pressure Comp 4; bit 15 = 159 High Oil Feed Temperature Comp 1
HR139doc 40140Active Alarms word 11 (alarms 160-175)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 160 High Oil Feed Temperature Comp 2; bit 1 = 161 High Oil Feed Temperature Comp 3; bit 2 = 162 High Oil Feed Temperature Comp 4; bit 3 = 163 Low Oil Feed Temperature Comp 1; bit 4 = 164 Low Oil Feed Temperature Comp 2; bit 5 = 165 Low Oil Feed Temperature Comp 3; bit 6 = 166 Low Oil Feed Temperature Comp 4; bit 7 = 167 Oil Feed Temperature Sensor Fault Comp 1; bit 8 = 168 Oil Feed Temperature Sensor Fault Comp 2; bit 9 = 169 Oil Feed Temperature Sensor Fault Comp 3; bit 10 = 170 Oil Feed Temperature Sensor Fault Comp 4; bit 11 = 171 Low Oil Level Circuit 1; bit 12 = 172 Low Oil Level Circuit 2; bit 13 = 173 Low Oil Level Circuit 3; bit 14 = 174 Low Oil Level Circuit 4; bit 15 = 175 High Oil Pressure Difference Circuit 1
HR140doc 40141Active Alarms word 12 (alarms 176-191)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 176 High Oil Pressure Difference Circuit 2; bit 1 = 177 High Oil Pressure Difference Circuit 3; bit 2 = 178 High Oil Pressure Difference Circuit 4; bit 3 = 179 Oil Feed Pressure Sensor Fault Comp 1; bit 4 = 180 Oil Feed Pressure Sensor Fault Comp 2; bit 5 = 181 Oil Feed Pressure Sensor Fault Comp 3; bit 6 = 182 Oil Feed Pressure Sensor Fault Comp 4; bit 7 = 183 Oil Sump Pressure Sensor Fault Comp 1; bit 8 = 184 Oil Sump Pressure Sensor Fault Comp 2; bit 9 = 185 Oil Sump Pressure Sensor Fault Comp 3; bit 10 = 186 Oil Sump Pressure Sensor Fault Comp 4; bit 11 = 187 Oil Sump Temperature Sensor Fault Comp 1; bit 12 = 188 Oil Sump Temperature Sensor Fault Comp 2; bit 13 = 189 Oil Sump Temperature Sensor Fault Comp 3; bit 14 = 190 Oil Sump Temperature Sensor Fault Comp 4; bit 15 = 191 Phase Voltage Protection
HR141doc 40142Active Alarms word 13 (alarms 192-207)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 192 Starter Fault Compressor 1; bit 1 = 193 Starter Fault Compressor 2; bit 2 = 194 Starter Fault Compressor 3; bit 3 = 195 Starter Fault Compressor 4; bit 4 = 196 No Starter Transition Comp 1; bit 5 = 197 No Starter Transition Comp 2; bit 6 = 198 No Starter Transition Comp 3; bit 7 = 199 No Starter Transition Comp 4; bit 8 = 200 No Oil Pressure Start Comp 1; bit 9 = 201 No Oil Pressure Start Comp 2; bit 10 = 202 No Oil Pressure Start Comp 3; bit 11 = 203 No Oil Pressure Start Comp 4; bit 12 = 204 Low Subcooling Circuit 1; bit 13 = 205 Low Subcooling Circuit 2; bit 14 = 206 Low Subcooling Circuit 3; bit 15 = 207 Low Subcooling Circuit 4
HR142doc 40143Active Alarms word 14 (alarms 208-223)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 208 Surge High Suct SH-Running Comp 1; bit 1 = 209 Surge High Suct SH-Running Comp 2; bit 2 = 210 Surge High Suct SH-Running Comp 3; bit 3 = 211 Surge High Suct SH-Running Comp 4; bit 4 = 212 Surge High Suct SH-Starting Comp 1; bit 5 = 213 Surge High Suct SH-Starting Comp 2; bit 6 = 214 Surge High Suct SH-Starting Comp 3; bit 7 = 215 Surge High Suct SH-Starting Comp 4; bit 8 = 216 Suction Temperature Sensor Fault Circuit 1; bit 9 = 217 Suction Temperature Sensor Fault Circuit 2; bit 10 = 218 Suction Temperature Sensor Fault Circuit 3; bit 11 = 219 Suction Temperature Sensor Fault Circuit 4; bit 12 = 220 Vanes Open No Start Comp 1; bit 13 = 221 Vanes Open No Start Comp 2; bit 14 = 222 Vanes Open No Start Comp 3; bit 15 = 223 Vanes Open No Start Comp 4
HR143doc 40144Active Alarms word 15 (alarms 224-228)1 = alarm active. Bit text gives the alarm number and name.BITMAP16Readbit 0 = 224 (Expansion Alarm- Fault); bit 1 = 225 COMP SHUTDOWN - Comp Fault #1; bit 2 = 226 COMP SHUTDOWN - Comp Fault #2; bit 3 = 227 COMP SHUTDOWN - Comp Fault #3; bit 4 = 228 COMP SHUTDOWN - Comp Fault #4
HR145doc 40146Chiller Mode SetpointUINT16Read/write1 = Ice; 2 = Cool; 3 = Heat
HR146doc 40147Chiller StatusUINT16Read1 = Off; 2 = Start; 3 = Run; 4 = Pre-shutdown; 5 = Service
HR160doc 40161Compressor SelectCompressor number 1-4 whose values the per-compressor registers return.UINT16Read/write
HR173doc 40174Compressor StartsStart count of the selected compressor.UINT16Read
HR174doc 40175Compressor Run HoursSelected compressor; raw value x 10 = hours.UINT16× 10hRead
HR175doc 40176Evaporator Pump Run HoursPump chosen with Pump Select.UINT16hRead
HR176doc 40177Condenser Pump Run HoursPump chosen with Pump Select.UINT16hRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)

What Modbus registers does the Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module) have?

This map lists 63 registers: 11 coils, 52 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document states that data element 1 is sent as index 0 in the PDU. Holding registers are printed in 4xxxx form (Cool Setpoint 40002 = wire address 1) and coils as plain element numbers (Chiller Enable coil 2 = wire address 1). The point tags confirm it: Active Setpoint 40003 is tagged A2 and Chiller Enable coil 2 is tagged D1.

What are the minimum Modbus registers to integrate the Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)?

Start with HR 146 Chiller Status (Chiller status); HR 1 Cool Setpoint (Cool setpoint); HR 6 Evaporator Leaving Water Temperature for Unit (Evaporator leaving water temperature); HR 4 Evaporator Entering Water Temperature (Evaporator entering water temperature); HR 10 Actual Capacity (Actual capacity); CO 1 Chiller Enable (Chiller enable (start/stop)); CO 3 Alarm Digital Output (Alarm present); CO 24 Clear Alarms (Clear alarms).

How do I enable Modbus control of the Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)?

At the touch-screen interface panel set SETPOINTS MODE #9 'BAS Protocol' to Modbus (operator password 2001), then set #3 'Control Source' to BAS once communication is confirmed.

Where is the official Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module) Modbus documentation?

The source is MicroTech II Chiller Unit Controller Protocol Information, Modbus Protocol (ED 15063-2), revision 2005-12, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED15063-2.pdf.

More Daikin Applied Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: MicroTech II Chiller Unit Controller Protocol Information, Modbus Protocol · ED 15063-2 · rev. 2005-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.