- Home
- Modbus register maps
- Trane
- RTAC air-cooled helical-rotary chiller (Symbio 800)
Chiller · Modbus register map
Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus register map
Updated 17 November 2026
The Trane RTAC is an air-cooled helical-rotary (screw) chiller. With a Symbio 800 controller it serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, pressures, temperatures, run hours, starter and drive values), BAS setpoints, binary status and diagnostic flags, and the multi-state mode points.
This page lists 406 Modbus registers for the Trane RTAC air-cooled helical-rotary chiller (Symbio 800) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- RTAC air-cooled helical-rotary chiller (Symbio 800)
- Equipment type
- Chiller
- Registers
- 406 (8 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RTAC, Series R RTAC
Integration notes: Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Chilled Water Setpoint | FLOAT32 ABCD | Active chilled water setpoint | Read |
| IR 56 | Evaporator Leaving Water Temperature | FLOAT32 ABCD | Evaporator leaving water temperature | Read |
| IR 54 | Evaporator Entering Water Temperature | FLOAT32 ABCD | Evaporator entering water temperature | Read |
| IR 14 | Actual Running Capacity | FLOAT32 ABCD | Actual running capacity | Read |
| IR 74 | Outdoor Air Temperature | FLOAT32 ABCD | Outdoor air temperature | Read |
| IR 3010 | Run Enabled | UINT16 | Run enabled | Read |
| HR 3010 | Reset Diagnostic | UINT16 | Reset diagnostic | Read/write |
| HR 2010 | Chiller Mode Command BAS | UINT16 | Chiller mode command | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface (USB connection) go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP; for TCP set the IP address on the IP Configuration tab.
Byte order & addressing
- Analog values are 32-bit floats in two consecutive registers, high word first.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (001-247); 000 disables Modbus RTU. A change takes effect without a power cycle.
- Modbus TCP uses Ethernet port 1 (port 2 is reserved for the optional touch screen); the rotary address is not used for TCP and the Wi-Fi module does not support Modbus TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Chilled Water Setpoint | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Active Demand Limit Setpoint | FLOAT32 | ABCD | % | Read | |||
| IR | 14doc 30015 | Actual Running Capacity | FLOAT32 | ABCD | % | Read | |||
| IR | 16doc 30017 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | Evaporator Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 20doc 30021 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 22doc 30023 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 24doc 30025 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 26doc 30027 | Condenser Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 28doc 30029 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | Condenser Saturated Refrigerant Temperature Circuit 2 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Local Atmospheric Pressure | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Starts - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 36doc 30037 | Run Time- Compressor 1A (in seconds) | FLOAT32 | ABCD | s | Read | |||
| IR | 38doc 30039 | Starts- Compressor 1B | Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Run Time- Compressor 1B (in seconds) | Needs: Compressor 1B | FLOAT32 | ABCD | s | Read | ||
| IR | 42doc 30043 | Starts- Compressor 2A | FLOAT32 | ABCD | Read | ||||
| IR | 44doc 30045 | Run Time- Compressor 2A (in seconds) | FLOAT32 | ABCD | s | Read | |||
| IR | 46doc 30047 | Starts - Compressor 2B | Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 48doc 30049 | Run Time- Compressor 2B (in seconds) | Needs: Compressor 2B | FLOAT32 | ABCD | s | Read | ||
| IR | 50doc 30051 | Air Flow Percentage Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 52doc 30053 | Air Flow Percentage Circuit 2 | FLOAT32 | ABCD | % | Read | |||
| IR | 54doc 30055 | Evaporator Entering Water Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 56doc 30057 | Evaporator Leaving Water Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 58doc 30059 | Oil Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 60doc 30061 | Oil Pressure - Compressor 1B | Pressure in the factory unit system (I-P or SI). Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | Oil Pressure - Compressor 2A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 64doc 30065 | Oil Pressure - Compressor 2B | Pressure in the factory unit system (I-P or SI). Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 66doc 30067 | Oil Temperature - Compressor 1A | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 68doc 30069 | Oil Temperature - Compressor 1B | Temperature in the unit system set at the factory (I-P or SI). Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | Oil Temperature - Compressor 2A | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 72doc 30073 | Oil Temperature - Compressor 2B | Temperature in the unit system set at the factory (I-P or SI). Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 74doc 30075 | Outdoor Air Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 76doc 30077 | Phase AB Voltage - Compressor 1A | Voltage. Needs: EM Starter 1A | FLOAT32 | ABCD | Read | |||
| IR | 78doc 30079 | Phase AB Voltage - Compressor 1B | Voltage. Needs: TR200 Modbus AFD 1A and Number of Compressors = 3 or 4 | FLOAT32 | ABCD | Read | |||
| IR | 80doc 30081 | Phase AB Voltage - Compressor 2A | Voltage. Needs: TR200 Modbus AFD 1A, EM Starter 2A and Number of Compressors = 2 | FLOAT32 | ABCD | Read | |||
| IR | 82doc 30083 | Line 1 Current - Compressor 1A | Current. Needs: EM Starter 1A | FLOAT32 | ABCD | Read | |||
| IR | 84doc 30085 | Line 2 Current - Compressor 1A | Current. Needs: EM Starter 1A | FLOAT32 | ABCD | Read | |||
| IR | 86doc 30087 | Line 3 Current - Compressor 1A | Current. Needs: EM Starter 1A | FLOAT32 | ABCD | Read | |||
| IR | 88doc 30089 | Line 1 Current - Compressor 1B | Current. Needs: EM Starter 1B | FLOAT32 | ABCD | Read | |||
| IR | 90doc 30091 | Line 2 Current - Compressor 1B | Current. Needs: EM Starter 1B | FLOAT32 | ABCD | Read | |||
| IR | 92doc 30093 | Line 3 Current - Compressor 1B | Current. Needs: EM Starter 1B | FLOAT32 | ABCD | Read | |||
| IR | 94doc 30095 | Line 1 Current - Compressor 2A | Current. Needs: EM Starter 2A | FLOAT32 | ABCD | Read | |||
| IR | 96doc 30097 | Line 2 Current - Compressor 2A | Current. Needs: EM Starter 2A | FLOAT32 | ABCD | Read | |||
| IR | 98doc 30099 | Line 3 Current - Compressor 2A | Current. Needs: EM Starter 2A | FLOAT32 | ABCD | Read | |||
| IR | 100doc 30101 | Line 1 Current - Compressor 2B | Current. Needs: EM Starter 2B | FLOAT32 | ABCD | Read | |||
| IR | 102doc 30103 | Line 2 Current - Compressor 2B | Current. Needs: EM Starter 2B | FLOAT32 | ABCD | Read | |||
| IR | 104doc 30105 | Line 3 Current - Compressor 2B | Current. Needs: EM Starter 2B | FLOAT32 | ABCD | Read | |||
| IR | 106doc 30107 | Line 1 Current RLA - Compressor 1A | Needs: EM Starter 1A | FLOAT32 | ABCD | % | Read | ||
| IR | 108doc 30109 | Line 2 Current RLA - Compressor 1A | Needs: EM Starter 1A | FLOAT32 | ABCD | % | Read | ||
| IR | 110doc 30111 | Line 3 Current RLA - Compressor 1A | Needs: EM Starter 1A | FLOAT32 | ABCD | % | Read | ||
| IR | 112doc 30113 | Line 1 Current RLA - Compressor 1B | Needs: EM Starter 1B | FLOAT32 | ABCD | % | Read | ||
| IR | 114doc 30115 | Line 2 Current RLA - Compressor 1B | Needs: EM Starter 1B | FLOAT32 | ABCD | % | Read | ||
| IR | 116doc 30117 | Line 3 Current RLA - Compressor 1B | Needs: EM Starter 1B | FLOAT32 | ABCD | % | Read | ||
| IR | 118doc 30119 | Line 1 Current RLA - Compressor 2A | Needs: EM Starter 2A | FLOAT32 | ABCD | % | Read | ||
| IR | 120doc 30121 | Line 2 Current RLA - Compressor 2A | Needs: EM Starter 2A | FLOAT32 | ABCD | % | Read | ||
| IR | 122doc 30123 | Line 3 Current RLA - Compressor 2A | Needs: EM Starter 2A | FLOAT32 | ABCD | % | Read | ||
| IR | 124doc 30125 | Line 1 Current RLA - Compressor 2B | Needs: EM Starter 2B | FLOAT32 | ABCD | % | Read | ||
| IR | 126doc 30127 | Line 2 Current RLA - Compressor 2B | Needs: EM Starter 2B | FLOAT32 | ABCD | % | Read | ||
| IR | 128doc 30129 | Line 3 Current RLA - Compressor 2B | Needs: EM Starter 2B | FLOAT32 | ABCD | % | Read | ||
| IR | 130doc 30131 | Number of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 132doc 30133 | Number of Compressors Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 134doc 30135 | Number of Compressors Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 136doc 30137 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 138doc 30139 | Drive Output Power Circuit 1 | Electrical power. Needs: TR200 Modbus AFD 1A | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 | Drive Output Power Circuit 2 | Electrical power. Needs: TR200 Modbus AFD 2A | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | Refrigerant Discharge Temperature - Compressor 1A | Needs: TR200 Modbus AFD 1A | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 | Refrigerant Discharge Temperature - Compressor 2A | Needs: TR200 Modbus AFD 1A | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | AFD Frequency Circuit 1 | Needs: TR200 Modbus AFD 1A | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 | AFD Frequency Circuit 2 | Needs: TR200 Modbus AFD 2A | FLOAT32 | ABCD | Read | |||
| IR | 150doc 30151 | Drive Motor Average Current RLA Circuit 1 | Needs: TR200 Modbus AFD 1A | FLOAT32 | ABCD | % | Read | ||
| IR | 152doc 30153 | Drive Motor Average Current RLA Circuit 2 | Needs: TR200 Modbus AFD 2A | FLOAT32 | ABCD | % | Read | ||
| IR | 154doc 30155 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 156doc 30157 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 158doc 30159 | Condenser Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 | Condenser Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 162doc 30163 | Oil Absolute Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 164doc 30165 | Oil Absolute Pressure - Compressor 1B | Pressure in the factory unit system (I-P or SI). Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 166doc 30167 | Oil Absolute Pressure - Compressor 2A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 168doc 30169 | Oil Absolute Pressure - Compressor 2B | Pressure in the factory unit system (I-P or SI). Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 170doc 30171 | Average Line Current Circuit 1 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 172doc 30173 | Average Line Current Circuit 2 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 174doc 30175 | Average Line Voltage Circuit 1 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 176doc 30177 | Average Line Voltage Circuit 2 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 178doc 30179 | Line Current L1 Circuit 1 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 180doc 30181 | Line Current L2 Circuit 1 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 182doc 30183 | Line Current L3 Circuit 1 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 184doc 30185 | Line Current L1 Circuit 2 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 186doc 30187 | Line Current L2 Circuit 2 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 188doc 30189 | Line Current L3 Circuit 2 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 190doc 30191 | Voltage L1-L2 Circuit 1 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 192doc 30193 | Voltage L2-L3 Circuit 1 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 194doc 30195 | Voltage L1-L3 Circuit 1 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 196doc 30197 | Voltage L1-L2 Circuit 2 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 198doc 30199 | Voltage L2-L1 Circuit 2 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 200doc 30201 | Voltage L1-L3 Circuit 2 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 202doc 30203 | Line Frequency Circuit 1 | Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 204doc 30205 | Line Frequency Circuit 2 | Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 206doc 30207 | Power Factor Circuit 1 | Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 208doc 30209 | Power Factor Circuit 2 | Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 210doc 30211 | Power Demand Circuit 1 | Electrical power. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 212doc 30213 | Power Demand Circuit 2 | Electrical power. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 214doc 30215 | Power Factor | Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 216doc 30217 | Current L1 | Current. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 218doc 30219 | Current L2 | Current. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 220doc 30221 | Current L3 | Current. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 222doc 30223 | Average Current | Current. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 224doc 30225 | Voltage L1-L2 | Voltage. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 226doc 30227 | Voltage L2-L3 | Voltage. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 228doc 30229 | Voltage L1-L3 | Voltage. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 230doc 30231 | Average Voltage L-L | Voltage. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 232doc 30233 | Line Frequency | Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 234doc 30235 | Unit Power Demand | Electrical power. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 236doc 30237 | Unit Source ID | FLOAT32 | ABCD | Read | ||||
| IR | 238doc 30239 | Unit Power Consumption | Electrical power. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 240doc 30241 | Evaporator Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 242doc 30243 | Evaporator Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 244doc 30245 | Active Cool/Heat Setpoint Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 2010doc 32011 | Running Mode | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2011doc 32012 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| IR | 3010doc 33011 | Run Enabled | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3011doc 33012 | Local Setpoint Control | UINT16 | Read | 0 = Remote Control; 1 = Local Control | ||||
| IR | 3012doc 33013 | Capacity Limited | UINT16 | Read | 0 = Not Limited; 1 = Limited | ||||
| IR | 3013doc 33014 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3014doc 33015 | Maximum Capacity | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3015doc 33016 | Manual Override Exists | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3016doc 33017 | Emergency Stop | UINT16 | Read | 0 = Auto; 1 = Emergency Stop - Manual Reset Required | ||||
| IR | 3017doc 33018 | Compressor 1A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3018doc 33019 | Compressor 1B Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3019doc 33020 | Compressor 2A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3020doc 33021 | Compressor 2B Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3021doc 33022 | Evaporator Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3022doc 33023 | Evaporator Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3023doc 33024 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3024doc 33025 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3025doc 33026 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3026doc 33027 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3027doc 33028 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3028doc 33029 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3029doc 33030 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3030doc 33031 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3031doc 33032 | External Auto Stop Input Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3032doc 33033 | Front Panel Auto Stop Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3033doc 33034 | Limit Mode Relay Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 4000doc 34001 | Diagnostic:MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Diagnostic:MP: Non-Volatile Memory Reformatted | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Diagnostic:Check Clock | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Diagnostic:MP: Could not Store Starts and Hours | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Diagnostic:MP: Non-Volatile Block Test Error | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Diagnostic:MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Comm Loss: Electronic Expansion Valve 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Comm Loss: Electronic Expansion Valve 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Diagnostic:Low Evaporator Rfgt Temperature - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Diagnostic:Low Evaporator Liquid Level - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Diagnostic:Low Suction Rfgt Pressure - Ckt 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Diagnostic:High Evaporator Liquid Level - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Diagnostic:Evaporator Liquid Level Sensor - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Comm Loss: Evap Rfgt Liquid Level - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Diagnostic:Low Evaporator Temp (Unit Off) - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Diagnostic:Very Low Evaporator Rfgt Pressure - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Evaporator Water Flow (High Approach Temperature) - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Diagnostic:Low Evaporator Rfgt Temperature - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Diagnostic:Low Evaporator Liquid Level - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Diagnostic:Low Suction Rfgt Pressure - Ckt 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Diagnostic:High Evaporator Liquid Level - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Diagnostic:Evaporator Liquid Level Sensor - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Comm Loss: Evap Rfgt Liquid Level - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Diagnostic:Low Evaporator Temp (Unit Off) - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Diagnostic:Very Low Evaporator Rfgt Pressure - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Evaporator Water Flow (High Approach Temperature) - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Comm Loss: Slide Valve Unload - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Comm Loss: Step Load - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Comm Loss: Slide Valve Load - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Comm Loss: Suction Rfgt Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Diagnostic:Suction Refrigerant Pressure Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Diagnostic:AFD Fault - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Diagnostic:AFD Motor Current Overload - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Comm Loss: Slide Valve Unload - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Comm Loss: Step Load - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Comm Loss: Slide Valve Load - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4036doc 34037 | Comm Loss: Suction Rfgt Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4037doc 34038 | Diagnostic:Suction Refrigerant Pressure Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Diagnostic:AFD Fault - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Diagnostic:AFD Motor Current Overload - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Comm Loss: Slide Valve Unload - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Comm Loss: Step Load - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Comm Loss: Slide Valve Load - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Comm Loss: Suction Rfgt Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Diagnostic:Suction Refrigerant Pressure Sensor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Comm Loss: Slide Valve Unload - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Comm Loss: Step Load - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Comm Loss: Slide Valve Load - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Comm Loss: Suction Rfgt Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Diagnostic:Suction Refrigerant Pressure Sensor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Diagnostic:Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Comm Loss: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Comm Loss: Ext Chilled Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Comm Loss: Ext Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Diagnostic:External Chilled Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Diagnostic:External Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Comm Loss: Programmable Relay Board 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Diagnostic:Condenser Fan VFD Fault - Ckt1 Drive 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Diagnostic:Condenser Fan VFD Fault - Ckt1 Drive 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Comm Loss: Fan Control Ckt1, Stage 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Comm Loss: Fan Control Ckt1, Stage 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Comm Loss: Fan Control Ckt1, Stage 3 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Comm Loss: Fan Control Ckt1, Stage 4 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Comm Loss: Fan Inverter Power - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Comm Loss: Fan Inverter Speed Cmd - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Comm Loss: Fan Inv Fault, Ckt1, Dr 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Comm Loss: Fan Inv Fault, Ckt1, Dr 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Diagnostic:Condenser Fan VFD Fault - Ckt2 Drive 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Diagnostic:Condenser Fan VFD Fault - Ckt2 Drive 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Comm Loss: Fan Control Ckt2, Stage 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Comm Loss: Fan Control Ckt2, Stage 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4072doc 34073 | Comm Loss: Fan Control Ckt2, Stage 3 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Comm Loss: Fan Control Ckt2, Stage 4 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4074doc 34075 | Comm Loss: Fan Inverter Power - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4075doc 34076 | Comm Loss: Fan Inverter Speed Cmd - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Comm Loss: Fan Inv Fault, Ckt2, Dr 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Comm Loss: Fan Inv Fault, Ckt2, Dr 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Comm Loss: Outdoor Air Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Diagnostic:Excessive IPC Comm Loss | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Comm Loss: External Ckt Lockout - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Comm Loss: External Ckt Lockout - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Diagnostic:Low Evap Leaving Water Temp: Unit On | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Diagnostic:Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Diagnostic:Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Diagnostic:Outdoor Air Temperature Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Diagnostic:Low Evaporator Water Temp (Unit Off) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Diagnostic:Evap Water Flow (Entering Water Temp) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Diagnostic:High Pressure Cutout - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Diagnostic:Low Oil Flow - Cprsr 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Diagnostic:Intermediate Oil Press Xdcr - Cprsr 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Diagnostic:High Oil Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Diagnostic:Oil Temperature Sensor - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4095doc 34096 | Comm Loss: High Pressure Cutout Sw - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4096doc 34097 | Comm Loss: Intermediate Oil Pressure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Comm Loss: Oil Temperature - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Comm Loss: Oil Return Solenoid Valve - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Diagnostic:Oil Flow Protection Fault - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4100doc 34101 | Comm Loss: Cprsr Disch Rfgt Temp - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4101doc 34102 | Diagnostic:Cprsr Disch Rfgt Temp Sensor -1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Diagnostic: Low Discharge Superheat - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Diagnostic:High Pressure Cutout - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Diagnostic:Low Oil Flow - Cprsr 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Diagnostic:Intermediate Oil Press Xdcr - Cprsr 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Diagnostic:High Oil Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Diagnostic:Oil Temperature Sensor - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Comm Loss: High Pressure Cutout Sw - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4109doc 34110 | Comm Loss: Intermediate Oil Pressure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4110doc 34111 | Comm Loss: Oil Temperature - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4111doc 34112 | Comm Loss: Oil Return Solenoid Valve - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Diagnostic:Oil Flow Protection Fault - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Comm Loss: Cprsr Disch Rfgt Temp - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Diagnostic:Cprsr Disch Rfgt Temp Sensor -2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Diagnostic: Low Discharge Superheat - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Diagnostic:High Pressure Cutout - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Diagnostic:Low Oil Flow - Cprsr 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Diagnostic:Intermediate Oil Press Xdcr - Cprsr 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Diagnostic:High Oil Temperature - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Diagnostic:Oil Temperature Sensor - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4121doc 34122 | Comm Loss: High Pressure Cutout Sw - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Comm Loss: Intermediate Oil Pressure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Comm Loss: Oil Temperature - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Comm Loss: Oil Return Solenoid Valve - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Diagnostic:Oil Flow Protection Fault - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Diagnostic:High Pressure Cutout - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Diagnostic:Low Oil Flow - Cprsr 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Diagnostic:Intermediate Oil Press Xdcr - Cprsr 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Diagnostic:High Oil Temperature - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Diagnostic:Oil Temperature Sensor - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Comm Loss: High Pressure Cutout Sw - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Comm Loss: Intermediate Oil Pressure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Comm Loss: Oil Temperature - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Comm Loss: Oil Return Solenoid Valve - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Diagnostic:Oil Flow Protection Fault - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Comm Loss: Condenser Rfgt Pressure - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Diagnostic:Condenser Rfgt Pressure Transducer - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4138doc 34139 | Comm Loss: Condenser Rfgt Pressure - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4139doc 34140 | Diagnostic:Condenser Rfgt Pressure Transducer - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Comm Loss: Starter 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Diagnostic:Starter Failed to Arm/Start - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4142doc 34143 | Diagnostic:AFD Interrupt Failure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4143doc 34144 | Comm Loss: AFD 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Comm Loss: Starter 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Diagnostic:Starter Failed to Arm/Start - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4146doc 34147 | Diagnostic:AFD Interrupt Failure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Comm Loss: AFD 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Comm Loss: Starter 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Diagnostic:Starter Failed to Arm/Start - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4150doc 34151 | Comm Loss: Starter 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4151doc 34152 | Diagnostic:Starter Failed to Arm/Start - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4152doc 34153 | Diagnostic:Starter 1A Loss of Comm with MP | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4153doc 34154 | Diagnostic:Starter Fault Type I - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4154doc 34155 | Diagnostic:Starter Fault Type II - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4155doc 34156 | Diagnostic:Starter Fault Type III - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Diagnostic:Starter Contactor Interrupt Failure - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Diagnostic:Starter Did Not Transition - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Diagnostic:Transition Complete Input Shorted - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Diagnostic:Phase Loss - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Diagnostic:Phase Reversal - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Diagnostic:Severe Current Imbalance - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Diagnostic:Power Loss - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4163doc 34164 | Diagnostic:Motor Current Overload - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4164doc 34165 | Cprsr Did Not Accel: Shutdown - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4165doc 34166 | Cprsr Did Not Accel: Transition - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4166doc 34167 | Diagnostic:Transition Complete Input Opened - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4167doc 34168 | Diagnostic:Starter Module Memory Error Type 1 - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4168doc 34169 | Diagnostic:Starter Module Memory Error Type 2 - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4169doc 34170 | Diagnostic:Starter Dry Run Test - 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4170doc 34171 | Diagnostic:Over Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4171doc 34172 | Diagnostic:Under Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4172doc 34173 | Diagnostic:Starter 2A Loss of Comm with MP | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4173doc 34174 | Diagnostic:Starter Fault Type I - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4174doc 34175 | Diagnostic:Starter Fault Type II - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4175doc 34176 | Diagnostic:Starter Fault Type III - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4176doc 34177 | Diagnostic:Starter Contactor Interrupt Failure - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4177doc 34178 | Diagnostic:Starter Did Not Transition - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4178doc 34179 | Diagnostic:Transition Complete Input Shorted - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4179doc 34180 | Diagnostic:Phase Loss - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4180doc 34181 | Diagnostic:Phase Reversal - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4181doc 34182 | Diagnostic:Severe Current Imbalance - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4182doc 34183 | Diagnostic:Power Loss - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4183doc 34184 | Diagnostic:Motor Current Overload - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4184doc 34185 | Cprsr Did Not Accel: Shutdown - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4185doc 34186 | Cprsr Did Not Accel: Transition - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4186doc 34187 | Diagnostic:Transition Complete Input Opened - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4187doc 34188 | Diagnostic:Starter Module Memory Error Type 1 - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4188doc 34189 | Diagnostic:Starter Module Memory Error Type 2 - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4189doc 34190 | Diagnostic:Starter Dry Run Test - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4190doc 34191 | Diagnostic:Starter Panel Thermostat Cutout - 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4191doc 34192 | Diagnostic:Starter Panel Thermostat Comm Loss 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4192doc 34193 | Diagnostic:Starter 1B Loss of Comm with MP | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4193doc 34194 | Diagnostic:Starter Fault Type I - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4194doc 34195 | Diagnostic:Starter Fault Type II - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4195doc 34196 | Diagnostic:Starter Fault Type III - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4196doc 34197 | Diagnostic:Starter Contactor Interrupt Failure - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4197doc 34198 | Diagnostic:Starter Did Not Transition - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4198doc 34199 | Diagnostic:Transition Complete Input Shorted - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4199doc 34200 | Diagnostic:Transition Complete Input Shorted - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4200doc 34201 | Diagnostic:Phase Loss - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4201doc 34202 | Diagnostic:Phase Reversal - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4202doc 34203 | Diagnostic:Severe Current Imbalance - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4203doc 34204 | Diagnostic:Power Loss - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4204doc 34205 | Diagnostic:Motor Current Overload - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4205doc 34206 | Cprsr Did Not Accel: Shutdown - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4206doc 34207 | Cprsr Did Not Accel: Transition - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4207doc 34208 | Diagnostic:Transition Complete Input Opened - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4208doc 34209 | Diagnostic:Starter Module Memory Error Type 1 - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4209doc 34210 | Diagnostic:Starter Module Memory Error Type 2 - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4210doc 34211 | Diagnostic:Starter Dry Run Test - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4211doc 34212 | Diagnostic:Starter Panel Thermostat Cutout - 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4212doc 34213 | Diagnostic:Starter Panel Thermostat Comm Loss 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4213doc 34214 | Diagnostic:Starter 2B Loss of Comm with MP | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4214doc 34215 | Diagnostic:Starter Fault Type I - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4215doc 34216 | Diagnostic:Starter Fault Type II - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4216doc 34217 | Diagnostic:Starter Fault Type III - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4217doc 34218 | Diagnostic:Starter Contactor Interrupt Failure - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4218doc 34219 | Diagnostic:Starter Did Not Transition - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4219doc 34220 | Diagnostic:Phase Loss - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4220doc 34221 | Diagnostic:Phase Reversal - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4221doc 34222 | Diagnostic:Severe Current Imbalance - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4222doc 34223 | Diagnostic:Power Loss - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4223doc 34224 | Diagnostic:Motor Current Overload - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4224doc 34225 | Cprsr Did Not Accel: Shutdown - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4225doc 34226 | Cprsr Did Not Accel: Transition - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4226doc 34227 | Diagnostic:Transition Complete Input Opened - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4227doc 34228 | Diagnostic:Starter Module Memory Error Type 1 - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4228doc 34229 | Diagnostic:Starter Module Memory Error Type 2 - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4229doc 34230 | Diagnostic:Starter Dry Run Test - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4230doc 34231 | Diagnostic:Starter Panel Thermostat Cutout - 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4231doc 34232 | Diagnostic:Starter Panel Thermostat Comm Loss 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4232doc 34233 | Diagnostic:Low Differential Rfgt Pressure - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4233doc 34234 | Diagnostic:High Differential Rfgt Pressure - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4234doc 34235 | Diagnostic:Pumpdown Terminated - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4235doc 34236 | Comm Loss: Evap Rfgt Drain Valve - Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4236doc 34237 | Diagnostic:Evaporator Rfgt Drain - Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4237doc 34238 | Diagnostic:Low Differential Rfgt Pressure - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4238doc 34239 | Diagnostic:High Differential Rfgt Pressure - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4239doc 34240 | Diagnostic:Pumpdown Terminated - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4240doc 34241 | Comm Loss: Evap Rfgt Drain Valve - Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4241doc 34242 | Diagnostic:Evaporator Rfgt Drain - Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4242doc 34243 | Comm Loss: Evaporator Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4243doc 34244 | Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4244doc 34245 | Diagnostic:Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4245doc 34246 | Diagnostic:Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4246doc 34247 | Diagnostic:High Evaporator Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4247doc 34248 | Diagnostic:High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4248doc 34249 | Diagnostic:Software Error 1001: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4249doc 34250 | Diagnostic:Software Error 1002: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4250doc 34251 | Diagnostic:Software Error 1003: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4251doc 34252 | Comm Loss: External Ice Building Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4252doc 34253 | Comm Loss: Ice Building Status Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4253doc 34254 | Comm Loss: Local BAS Interface | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 2010doc 42011 | Chiller Mode Command BAS | UINT16 | Read/write | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| HR | 3010doc 43011 | Reset Diagnostic | UINT16 | Read/write | 0 = Normal; 1 = Reset | ||||
| HR | 3011doc 43012 | Chiller Auto Stop Command BAS | UINT16 | Read/write | 0 = Stop; 1 = Auto | ||||
| HR | 3012doc 43013 | Circuit 1 Lockout BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3013doc 43014 | Circuit 2 Lockout BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3014doc 43015 | Energy Consumption Reset | Needs: Power Monitor | UINT16 | Read/write | 0 = Accumulating; 1 = Reset |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Controller setup, serial defaults and the I-P/SI units statement come from Trane's Symbio 800 integration guide for Agility chillers, BAS-SVP047B-EN (Sept 2023, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP047B-EN_09092023.pdf), which describes the same Symbio 800 controller.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
What Modbus registers does the Trane RTAC air-cooled helical-rotary chiller (Symbio 800) have?
This map lists 406 registers: 398 input registers, 8 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane RTAC air-cooled helical-rotary chiller (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane RTAC air-cooled helical-rotary chiller (Symbio 800)?
Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 56 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 54 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 14 Actual Running Capacity (Actual running capacity); IR 74 Outdoor Air Temperature (Outdoor air temperature); IR 3010 Run Enabled (Run enabled); HR 3010 Reset Diagnostic (Reset diagnostic); HR 2010 Chiller Mode Command BAS (Chiller mode command).
How do I enable Modbus control of the Trane RTAC air-cooled helical-rotary chiller (Symbio 800)?
On the Symbio 800 web interface (USB connection) go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP; for TCP set the IP address on the IP Configuration tab.
Where is the official Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, RTAC (BAS-PTS023A-EN), revision 2024-11-08, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS023A-EN_11082024.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).
Also known as: WTX, TBX
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, RTAC · BAS-PTS023A-EN · rev. 2024-11-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.