Chiller · Modbus register map

Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus register map

Updated 17 November 2026

Short answer

The Trane RTAC is an air-cooled helical-rotary (screw) chiller. With a Symbio 800 controller it serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, pressures, temperatures, run hours, starter and drive values), BAS setpoints, binary status and diagnostic flags, and the multi-state mode points.

This page lists 406 Modbus registers for the Trane RTAC air-cooled helical-rotary chiller (Symbio 800) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
RTAC air-cooled helical-rotary chiller (Symbio 800)
Equipment type
Chiller
Registers
406 (8 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RTAC, Series R RTAC
Source document
Symbio 800 Integration Points List, BACnet/Modbus, RTAC · BAS-PTS023A-EN · rev. 2024-11-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane RTAC air-cooled helical-rotary chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Chilled Water SetpointFLOAT32 ABCDActive chilled water setpointRead
IR 56Evaporator Leaving Water TemperatureFLOAT32 ABCDEvaporator leaving water temperatureRead
IR 54Evaporator Entering Water TemperatureFLOAT32 ABCDEvaporator entering water temperatureRead
IR 14Actual Running CapacityFLOAT32 ABCDActual running capacityRead
IR 74Outdoor Air TemperatureFLOAT32 ABCDOutdoor air temperatureRead
IR 3010Run EnabledUINT16Run enabledRead
HR 3010Reset DiagnosticUINT16Reset diagnosticRead/write
HR 2010Chiller Mode Command BASUINT16Chiller mode commandRead/write

Enable Modbus control & writes

On the Symbio 800 web interface (USB connection) go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP; for TCP set the IP address on the IP Configuration tab.

Byte order & addressing

Network setup

Watch out for

Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

406 of 406 shown
Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Chilled Water SetpointTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Active Demand Limit SetpointFLOAT32ABCD%Read
IR14doc 30015Actual Running CapacityFLOAT32ABCD%Read
IR16doc 30017Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR18doc 30019Evaporator Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR20doc 30021Evaporator Saturated Refrigerant Temperature Circuit 1Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR22doc 30023Evaporator Saturated Refrigerant Temperature Circuit 2Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR24doc 30025Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR26doc 30027Condenser Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR28doc 30029Condenser Saturated Refrigerant Temperature Circuit 1Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR30doc 30031Condenser Saturated Refrigerant Temperature Circuit 2Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR32doc 30033Local Atmospheric PressurePressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR34doc 30035Starts - Compressor 1AFLOAT32ABCDRead
IR36doc 30037Run Time- Compressor 1A (in seconds)FLOAT32ABCDsRead
IR38doc 30039Starts- Compressor 1BNeeds: Compressor 1BFLOAT32ABCDRead
IR40doc 30041Run Time- Compressor 1B (in seconds)Needs: Compressor 1BFLOAT32ABCDsRead
IR42doc 30043Starts- Compressor 2AFLOAT32ABCDRead
IR44doc 30045Run Time- Compressor 2A (in seconds)FLOAT32ABCDsRead
IR46doc 30047Starts - Compressor 2BNeeds: Compressor 2BFLOAT32ABCDRead
IR48doc 30049Run Time- Compressor 2B (in seconds)Needs: Compressor 2BFLOAT32ABCDsRead
IR50doc 30051Air Flow Percentage Circuit 1FLOAT32ABCD%Read
IR52doc 30053Air Flow Percentage Circuit 2FLOAT32ABCD%Read
IR54doc 30055Evaporator Entering Water TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR56doc 30057Evaporator Leaving Water TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR58doc 30059Oil Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR60doc 30061Oil Pressure - Compressor 1BPressure in the factory unit system (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR62doc 30063Oil Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR64doc 30065Oil Pressure - Compressor 2BPressure in the factory unit system (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR66doc 30067Oil Temperature - Compressor 1ATemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR68doc 30069Oil Temperature - Compressor 1BTemperature in the unit system set at the factory (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR70doc 30071Oil Temperature - Compressor 2ATemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR72doc 30073Oil Temperature - Compressor 2BTemperature in the unit system set at the factory (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR74doc 30075Outdoor Air TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR76doc 30077Phase AB Voltage - Compressor 1AVoltage. Needs: EM Starter 1AFLOAT32ABCDRead
IR78doc 30079Phase AB Voltage - Compressor 1BVoltage. Needs: TR200 Modbus AFD 1A and Number of Compressors = 3 or 4FLOAT32ABCDRead
IR80doc 30081Phase AB Voltage - Compressor 2AVoltage. Needs: TR200 Modbus AFD 1A, EM Starter 2A and Number of Compressors = 2FLOAT32ABCDRead
IR82doc 30083Line 1 Current - Compressor 1ACurrent. Needs: EM Starter 1AFLOAT32ABCDRead
IR84doc 30085Line 2 Current - Compressor 1ACurrent. Needs: EM Starter 1AFLOAT32ABCDRead
IR86doc 30087Line 3 Current - Compressor 1ACurrent. Needs: EM Starter 1AFLOAT32ABCDRead
IR88doc 30089Line 1 Current - Compressor 1BCurrent. Needs: EM Starter 1BFLOAT32ABCDRead
IR90doc 30091Line 2 Current - Compressor 1BCurrent. Needs: EM Starter 1BFLOAT32ABCDRead
IR92doc 30093Line 3 Current - Compressor 1BCurrent. Needs: EM Starter 1BFLOAT32ABCDRead
IR94doc 30095Line 1 Current - Compressor 2ACurrent. Needs: EM Starter 2AFLOAT32ABCDRead
IR96doc 30097Line 2 Current - Compressor 2ACurrent. Needs: EM Starter 2AFLOAT32ABCDRead
IR98doc 30099Line 3 Current - Compressor 2ACurrent. Needs: EM Starter 2AFLOAT32ABCDRead
IR100doc 30101Line 1 Current - Compressor 2BCurrent. Needs: EM Starter 2BFLOAT32ABCDRead
IR102doc 30103Line 2 Current - Compressor 2BCurrent. Needs: EM Starter 2BFLOAT32ABCDRead
IR104doc 30105Line 3 Current - Compressor 2BCurrent. Needs: EM Starter 2BFLOAT32ABCDRead
IR106doc 30107Line 1 Current RLA - Compressor 1ANeeds: EM Starter 1AFLOAT32ABCD%Read
IR108doc 30109Line 2 Current RLA - Compressor 1ANeeds: EM Starter 1AFLOAT32ABCD%Read
IR110doc 30111Line 3 Current RLA - Compressor 1ANeeds: EM Starter 1AFLOAT32ABCD%Read
IR112doc 30113Line 1 Current RLA - Compressor 1BNeeds: EM Starter 1BFLOAT32ABCD%Read
IR114doc 30115Line 2 Current RLA - Compressor 1BNeeds: EM Starter 1BFLOAT32ABCD%Read
IR116doc 30117Line 3 Current RLA - Compressor 1BNeeds: EM Starter 1BFLOAT32ABCD%Read
IR118doc 30119Line 1 Current RLA - Compressor 2ANeeds: EM Starter 2AFLOAT32ABCD%Read
IR120doc 30121Line 2 Current RLA - Compressor 2ANeeds: EM Starter 2AFLOAT32ABCD%Read
IR122doc 30123Line 3 Current RLA - Compressor 2ANeeds: EM Starter 2AFLOAT32ABCD%Read
IR124doc 30125Line 1 Current RLA - Compressor 2BNeeds: EM Starter 2BFLOAT32ABCD%Read
IR126doc 30127Line 2 Current RLA - Compressor 2BNeeds: EM Starter 2BFLOAT32ABCD%Read
IR128doc 30129Line 3 Current RLA - Compressor 2BNeeds: EM Starter 2BFLOAT32ABCD%Read
IR130doc 30131Number of CircuitsFLOAT32ABCDRead
IR132doc 30133Number of Compressors Circuit 1FLOAT32ABCDRead
IR134doc 30135Number of Compressors Circuit 2FLOAT32ABCDRead
IR136doc 30137Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR138doc 30139Drive Output Power Circuit 1Electrical power. Needs: TR200 Modbus AFD 1AFLOAT32ABCDRead
IR140doc 30141Drive Output Power Circuit 2Electrical power. Needs: TR200 Modbus AFD 2AFLOAT32ABCDRead
IR142doc 30143Refrigerant Discharge Temperature - Compressor 1ANeeds: TR200 Modbus AFD 1AFLOAT32ABCDRead
IR144doc 30145Refrigerant Discharge Temperature - Compressor 2ANeeds: TR200 Modbus AFD 1AFLOAT32ABCDRead
IR146doc 30147AFD Frequency Circuit 1Needs: TR200 Modbus AFD 1AFLOAT32ABCDRead
IR148doc 30149AFD Frequency Circuit 2Needs: TR200 Modbus AFD 2AFLOAT32ABCDRead
IR150doc 30151Drive Motor Average Current RLA Circuit 1Needs: TR200 Modbus AFD 1AFLOAT32ABCD%Read
IR152doc 30153Drive Motor Average Current RLA Circuit 2Needs: TR200 Modbus AFD 2AFLOAT32ABCD%Read
IR154doc 30155Evaporator Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR156doc 30157Evaporator Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR158doc 30159Condenser Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR160doc 30161Condenser Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR162doc 30163Oil Absolute Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR164doc 30165Oil Absolute Pressure - Compressor 1BPressure in the factory unit system (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR166doc 30167Oil Absolute Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR168doc 30169Oil Absolute Pressure - Compressor 2BPressure in the factory unit system (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR170doc 30171Average Line Current Circuit 1Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR172doc 30173Average Line Current Circuit 2Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR174doc 30175Average Line Voltage Circuit 1Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR176doc 30177Average Line Voltage Circuit 2Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR178doc 30179Line Current L1 Circuit 1Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR180doc 30181Line Current L2 Circuit 1Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR182doc 30183Line Current L3 Circuit 1Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR184doc 30185Line Current L1 Circuit 2Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR186doc 30187Line Current L2 Circuit 2Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR188doc 30189Line Current L3 Circuit 2Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR190doc 30191Voltage L1-L2 Circuit 1Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR192doc 30193Voltage L2-L3 Circuit 1Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR194doc 30195Voltage L1-L3 Circuit 1Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR196doc 30197Voltage L1-L2 Circuit 2Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR198doc 30199Voltage L2-L1 Circuit 2Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR200doc 30201Voltage L1-L3 Circuit 2Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR202doc 30203Line Frequency Circuit 1Needs: Two Energy MetersFLOAT32ABCDRead
IR204doc 30205Line Frequency Circuit 2Needs: Two Energy MetersFLOAT32ABCDRead
IR206doc 30207Power Factor Circuit 1Needs: Two Energy MetersFLOAT32ABCDRead
IR208doc 30209Power Factor Circuit 2Needs: Two Energy MetersFLOAT32ABCDRead
IR210doc 30211Power Demand Circuit 1Electrical power. Needs: Two Energy MetersFLOAT32ABCDRead
IR212doc 30213Power Demand Circuit 2Electrical power. Needs: Two Energy MetersFLOAT32ABCDRead
IR214doc 30215Power FactorNeeds: One Energy MeterFLOAT32ABCDRead
IR216doc 30217Current L1Current. Needs: One Energy MeterFLOAT32ABCDRead
IR218doc 30219Current L2Current. Needs: One Energy MeterFLOAT32ABCDRead
IR220doc 30221Current L3Current. Needs: One Energy MeterFLOAT32ABCDRead
IR222doc 30223Average CurrentCurrent. Needs: One Energy MeterFLOAT32ABCDRead
IR224doc 30225Voltage L1-L2Voltage. Needs: One Energy MeterFLOAT32ABCDRead
IR226doc 30227Voltage L2-L3Voltage. Needs: One Energy MeterFLOAT32ABCDRead
IR228doc 30229Voltage L1-L3Voltage. Needs: One Energy MeterFLOAT32ABCDRead
IR230doc 30231Average Voltage L-LVoltage. Needs: One Energy MeterFLOAT32ABCDRead
IR232doc 30233Line FrequencyNeeds: One Energy MeterFLOAT32ABCDRead
IR234doc 30235Unit Power DemandElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR236doc 30237Unit Source IDFLOAT32ABCDRead
IR238doc 30239Unit Power ConsumptionElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR240doc 30241Evaporator Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR242doc 30243Evaporator Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR244doc 30245Active Cool/Heat Setpoint TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR2010doc 32011Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR3010doc 33011Run EnabledUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3011doc 33012Local Setpoint ControlUINT16Read0 = Remote Control; 1 = Local Control
IR3012doc 33013Capacity LimitedUINT16Read0 = Not Limited; 1 = Limited
IR3013doc 33014Chiller Running StateUINT16Read0 = Off; 1 = On
IR3014doc 33015Maximum CapacityUINT16Read0 = Off; 1 = On
IR3015doc 33016Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3016doc 33017Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop - Manual Reset Required
IR3017doc 33018Compressor 1A StatusUINT16Read0 = Off; 1 = Running
IR3018doc 33019Compressor 1B StatusUINT16Read0 = Off; 1 = Running
IR3019doc 33020Compressor 2A StatusUINT16Read0 = Off; 1 = Running
IR3020doc 33021Compressor 2B StatusUINT16Read0 = Off; 1 = Running
IR3021doc 33022Evaporator Water Pump RequestUINT16Read0 = Off; 1 = On
IR3022doc 33023Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3023doc 33024Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3024doc 33025Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3025doc 33026Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3026doc 33027Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3027doc 33028Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3028doc 33029Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3029doc 33030Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3030doc 33031Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3031doc 33032External Auto Stop Input StatusUINT16Read0 = Stop; 1 = Auto
IR3032doc 33033Front Panel Auto Stop StatusUINT16Read0 = Stop; 1 = Auto
IR3033doc 33034Limit Mode Relay StatusUINT16Read0 = Off; 1 = On
IR4000doc 34001Diagnostic:MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Diagnostic:MP: Non-Volatile Memory ReformattedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Diagnostic:Check ClockDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Diagnostic:MP: Could not Store Starts and HoursDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Diagnostic:MP: Non-Volatile Block Test ErrorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Diagnostic:MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Comm Loss: Electronic Expansion Valve 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Comm Loss: Electronic Expansion Valve 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Diagnostic:Low Evaporator Rfgt Temperature - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Diagnostic:Low Evaporator Liquid Level - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Diagnostic:Low Suction Rfgt Pressure - Ckt 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Diagnostic:High Evaporator Liquid Level - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Diagnostic:Evaporator Liquid Level Sensor - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Comm Loss: Evap Rfgt Liquid Level - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Diagnostic:Low Evaporator Temp (Unit Off) - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Diagnostic:Very Low Evaporator Rfgt Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Evaporator Water Flow (High Approach Temperature) - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Diagnostic:Low Evaporator Rfgt Temperature - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Diagnostic:Low Evaporator Liquid Level - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Diagnostic:Low Suction Rfgt Pressure - Ckt 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Diagnostic:High Evaporator Liquid Level - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Diagnostic:Evaporator Liquid Level Sensor - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Comm Loss: Evap Rfgt Liquid Level - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Diagnostic:Low Evaporator Temp (Unit Off) - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Diagnostic:Very Low Evaporator Rfgt Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Evaporator Water Flow (High Approach Temperature) - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Comm Loss: Slide Valve Unload - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Comm Loss: Step Load - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Comm Loss: Slide Valve Load - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Comm Loss: Suction Rfgt Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Diagnostic:Suction Refrigerant Pressure Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Diagnostic:AFD Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Diagnostic:AFD Motor Current Overload - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Comm Loss: Slide Valve Unload - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Comm Loss: Step Load - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Comm Loss: Slide Valve Load - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Comm Loss: Suction Rfgt Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Diagnostic:Suction Refrigerant Pressure Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Diagnostic:AFD Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Diagnostic:AFD Motor Current Overload - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Comm Loss: Slide Valve Unload - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Comm Loss: Step Load - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Comm Loss: Slide Valve Load - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Comm Loss: Suction Rfgt Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Diagnostic:Suction Refrigerant Pressure Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Comm Loss: Slide Valve Unload - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Comm Loss: Step Load - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Comm Loss: Slide Valve Load - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Comm Loss: Suction Rfgt Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Diagnostic:Suction Refrigerant Pressure Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Diagnostic:Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Comm Loss: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Comm Loss: Ext Chilled Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Comm Loss: Ext Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Diagnostic:External Chilled Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Diagnostic:External Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Comm Loss: Programmable Relay Board 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Diagnostic:Condenser Fan VFD Fault - Ckt1 Drive 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Diagnostic:Condenser Fan VFD Fault - Ckt1 Drive 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Comm Loss: Fan Control Ckt1, Stage 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Comm Loss: Fan Control Ckt1, Stage 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Comm Loss: Fan Control Ckt1, Stage 3Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Comm Loss: Fan Control Ckt1, Stage 4Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Comm Loss: Fan Inverter Power - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Comm Loss: Fan Inverter Speed Cmd - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Comm Loss: Fan Inv Fault, Ckt1, Dr 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Comm Loss: Fan Inv Fault, Ckt1, Dr 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Diagnostic:Condenser Fan VFD Fault - Ckt2 Drive 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Diagnostic:Condenser Fan VFD Fault - Ckt2 Drive 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Comm Loss: Fan Control Ckt2, Stage 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Comm Loss: Fan Control Ckt2, Stage 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Comm Loss: Fan Control Ckt2, Stage 3Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Comm Loss: Fan Control Ckt2, Stage 4Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Comm Loss: Fan Inverter Power - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Comm Loss: Fan Inverter Speed Cmd - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Comm Loss: Fan Inv Fault, Ckt2, Dr 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Comm Loss: Fan Inv Fault, Ckt2, Dr 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Comm Loss: Outdoor Air TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Diagnostic:Excessive IPC Comm LossDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Comm Loss: External Ckt Lockout - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Comm Loss: External Ckt Lockout - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Diagnostic:Low Evap Leaving Water Temp: Unit OnDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Diagnostic:Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Diagnostic:Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Diagnostic:Outdoor Air Temperature SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Diagnostic:Low Evaporator Water Temp (Unit Off)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Diagnostic:Evap Water Flow (Entering Water Temp)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Diagnostic:High Pressure Cutout - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Diagnostic:Low Oil Flow - Cprsr 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Diagnostic:Intermediate Oil Press Xdcr - Cprsr 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Diagnostic:High Oil Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Diagnostic:Oil Temperature Sensor - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Comm Loss: High Pressure Cutout Sw - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Comm Loss: Intermediate Oil Pressure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Comm Loss: Oil Temperature - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Comm Loss: Oil Return Solenoid Valve - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Diagnostic:Oil Flow Protection Fault - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Comm Loss: Cprsr Disch Rfgt Temp - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Diagnostic:Cprsr Disch Rfgt Temp Sensor -1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Diagnostic: Low Discharge Superheat - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Diagnostic:High Pressure Cutout - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Diagnostic:Low Oil Flow - Cprsr 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Diagnostic:Intermediate Oil Press Xdcr - Cprsr 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Diagnostic:High Oil Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Diagnostic:Oil Temperature Sensor - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Comm Loss: High Pressure Cutout Sw - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Comm Loss: Intermediate Oil Pressure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Comm Loss: Oil Temperature - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Comm Loss: Oil Return Solenoid Valve - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Diagnostic:Oil Flow Protection Fault - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Comm Loss: Cprsr Disch Rfgt Temp - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Diagnostic:Cprsr Disch Rfgt Temp Sensor -2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Diagnostic: Low Discharge Superheat - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Diagnostic:High Pressure Cutout - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Diagnostic:Low Oil Flow - Cprsr 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Diagnostic:Intermediate Oil Press Xdcr - Cprsr 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Diagnostic:High Oil Temperature - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Diagnostic:Oil Temperature Sensor - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Comm Loss: High Pressure Cutout Sw - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Comm Loss: Intermediate Oil Pressure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Comm Loss: Oil Temperature - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Comm Loss: Oil Return Solenoid Valve - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Diagnostic:Oil Flow Protection Fault - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Diagnostic:High Pressure Cutout - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Diagnostic:Low Oil Flow - Cprsr 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Diagnostic:Intermediate Oil Press Xdcr - Cprsr 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Diagnostic:High Oil Temperature - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Diagnostic:Oil Temperature Sensor - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Comm Loss: High Pressure Cutout Sw - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Comm Loss: Intermediate Oil Pressure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Comm Loss: Oil Temperature - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Comm Loss: Oil Return Solenoid Valve - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Diagnostic:Oil Flow Protection Fault - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Comm Loss: Condenser Rfgt Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Diagnostic:Condenser Rfgt Pressure Transducer - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Comm Loss: Condenser Rfgt Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Diagnostic:Condenser Rfgt Pressure Transducer - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Comm Loss: Starter 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Diagnostic:Starter Failed to Arm/Start - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Diagnostic:AFD Interrupt Failure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Comm Loss: AFD 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Comm Loss: Starter 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Diagnostic:Starter Failed to Arm/Start - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Diagnostic:AFD Interrupt Failure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Comm Loss: AFD 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Comm Loss: Starter 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Diagnostic:Starter Failed to Arm/Start - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Comm Loss: Starter 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Diagnostic:Starter Failed to Arm/Start - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Diagnostic:Starter 1A Loss of Comm with MPDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Diagnostic:Starter Fault Type I - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Diagnostic:Starter Fault Type II - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Diagnostic:Starter Fault Type III - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Diagnostic:Starter Contactor Interrupt Failure - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Diagnostic:Starter Did Not Transition - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Diagnostic:Transition Complete Input Shorted - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Diagnostic:Phase Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Diagnostic:Phase Reversal - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Diagnostic:Severe Current Imbalance - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Diagnostic:Power Loss - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Diagnostic:Motor Current Overload - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Cprsr Did Not Accel: Shutdown - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Cprsr Did Not Accel: Transition - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Diagnostic:Transition Complete Input Opened - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Diagnostic:Starter Module Memory Error Type 1 - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Diagnostic:Starter Module Memory Error Type 2 - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Diagnostic:Starter Dry Run Test - 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Diagnostic:Over VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Diagnostic:Under VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Diagnostic:Starter 2A Loss of Comm with MPDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Diagnostic:Starter Fault Type I - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Diagnostic:Starter Fault Type II - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Diagnostic:Starter Fault Type III - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Diagnostic:Starter Contactor Interrupt Failure - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Diagnostic:Starter Did Not Transition - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Diagnostic:Transition Complete Input Shorted - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Diagnostic:Phase Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Diagnostic:Phase Reversal - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Diagnostic:Severe Current Imbalance - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4182doc 34183Diagnostic:Power Loss - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4183doc 34184Diagnostic:Motor Current Overload - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4184doc 34185Cprsr Did Not Accel: Shutdown - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4185doc 34186Cprsr Did Not Accel: Transition - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4186doc 34187Diagnostic:Transition Complete Input Opened - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4187doc 34188Diagnostic:Starter Module Memory Error Type 1 - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4188doc 34189Diagnostic:Starter Module Memory Error Type 2 - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4189doc 34190Diagnostic:Starter Dry Run Test - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4190doc 34191Diagnostic:Starter Panel Thermostat Cutout - 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4191doc 34192Diagnostic:Starter Panel Thermostat Comm Loss 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4192doc 34193Diagnostic:Starter 1B Loss of Comm with MPDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4193doc 34194Diagnostic:Starter Fault Type I - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4194doc 34195Diagnostic:Starter Fault Type II - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4195doc 34196Diagnostic:Starter Fault Type III - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4196doc 34197Diagnostic:Starter Contactor Interrupt Failure - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4197doc 34198Diagnostic:Starter Did Not Transition - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4198doc 34199Diagnostic:Transition Complete Input Shorted - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4199doc 34200Diagnostic:Transition Complete Input Shorted - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4200doc 34201Diagnostic:Phase Loss - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4201doc 34202Diagnostic:Phase Reversal - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4202doc 34203Diagnostic:Severe Current Imbalance - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4203doc 34204Diagnostic:Power Loss - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4204doc 34205Diagnostic:Motor Current Overload - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4205doc 34206Cprsr Did Not Accel: Shutdown - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4206doc 34207Cprsr Did Not Accel: Transition - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4207doc 34208Diagnostic:Transition Complete Input Opened - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4208doc 34209Diagnostic:Starter Module Memory Error Type 1 - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4209doc 34210Diagnostic:Starter Module Memory Error Type 2 - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4210doc 34211Diagnostic:Starter Dry Run Test - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4211doc 34212Diagnostic:Starter Panel Thermostat Cutout - 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4212doc 34213Diagnostic:Starter Panel Thermostat Comm Loss 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4213doc 34214Diagnostic:Starter 2B Loss of Comm with MPDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4214doc 34215Diagnostic:Starter Fault Type I - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4215doc 34216Diagnostic:Starter Fault Type II - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4216doc 34217Diagnostic:Starter Fault Type III - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4217doc 34218Diagnostic:Starter Contactor Interrupt Failure - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4218doc 34219Diagnostic:Starter Did Not Transition - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4219doc 34220Diagnostic:Phase Loss - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4220doc 34221Diagnostic:Phase Reversal - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4221doc 34222Diagnostic:Severe Current Imbalance - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4222doc 34223Diagnostic:Power Loss - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4223doc 34224Diagnostic:Motor Current Overload - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4224doc 34225Cprsr Did Not Accel: Shutdown - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4225doc 34226Cprsr Did Not Accel: Transition - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4226doc 34227Diagnostic:Transition Complete Input Opened - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4227doc 34228Diagnostic:Starter Module Memory Error Type 1 - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4228doc 34229Diagnostic:Starter Module Memory Error Type 2 - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4229doc 34230Diagnostic:Starter Dry Run Test - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4230doc 34231Diagnostic:Starter Panel Thermostat Cutout - 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4231doc 34232Diagnostic:Starter Panel Thermostat Comm Loss 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4232doc 34233Diagnostic:Low Differential Rfgt Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4233doc 34234Diagnostic:High Differential Rfgt Pressure - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4234doc 34235Diagnostic:Pumpdown Terminated - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4235doc 34236Comm Loss: Evap Rfgt Drain Valve - Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4236doc 34237Diagnostic:Evaporator Rfgt Drain - Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4237doc 34238Diagnostic:Low Differential Rfgt Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4238doc 34239Diagnostic:High Differential Rfgt Pressure - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4239doc 34240Diagnostic:Pumpdown Terminated - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4240doc 34241Comm Loss: Evap Rfgt Drain Valve - Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4241doc 34242Diagnostic:Evaporator Rfgt Drain - Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4242doc 34243Comm Loss: Evaporator Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4243doc 34244Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4244doc 34245Diagnostic:Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4245doc 34246Diagnostic:Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4246doc 34247Diagnostic:High Evaporator PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4247doc 34248Diagnostic:High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4248doc 34249Diagnostic:Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4249doc 34250Diagnostic:Software Error 1002: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4250doc 34251Diagnostic:Software Error 1003: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4251doc 34252Comm Loss: External Ice Building CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4252doc 34253Comm Loss: Ice Building Status RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4253doc 34254Comm Loss: Local BAS InterfaceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR2010doc 42011Chiller Mode Command BASUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
HR3010doc 43011Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3011doc 43012Chiller Auto Stop Command BASUINT16Read/write0 = Stop; 1 = Auto
HR3012doc 43013Circuit 1 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3013doc 43014Circuit 2 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3014doc 43015Energy Consumption ResetNeeds: Power MonitorUINT16Read/write0 = Accumulating; 1 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane RTAC air-cooled helical-rotary chiller (Symbio 800)

What Modbus registers does the Trane RTAC air-cooled helical-rotary chiller (Symbio 800) have?

This map lists 406 registers: 398 input registers, 8 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane RTAC air-cooled helical-rotary chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane RTAC air-cooled helical-rotary chiller (Symbio 800)?

Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 56 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 54 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 14 Actual Running Capacity (Actual running capacity); IR 74 Outdoor Air Temperature (Outdoor air temperature); IR 3010 Run Enabled (Run enabled); HR 3010 Reset Diagnostic (Reset diagnostic); HR 2010 Chiller Mode Command BAS (Chiller mode command).

How do I enable Modbus control of the Trane RTAC air-cooled helical-rotary chiller (Symbio 800)?

On the Symbio 800 web interface (USB connection) go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP; for TCP set the IP address on the IP Configuration tab.

Where is the official Trane RTAC air-cooled helical-rotary chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, RTAC (BAS-PTS023A-EN), revision 2024-11-08, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS023A-EN_11082024.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, RTAC · BAS-PTS023A-EN · rev. 2024-11-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.