- THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
Heat pump (air-to-water) · Modbus register map
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus register map
Updated 19 November 2026
The THERMA V monobloc can be run by a third-party controller over Modbus RTU wired to terminal block 3 (26 = A, 27 = B) on the indoor PCB, with no LG gateway. Coils switch space heating/cooling, hot water, silent mode and emergency functions; discrete inputs report pump, compressor, defrost, heater and error states; holding registers carry the operating mode, control method, setpoints and the smart-grid energy state; input registers give the error code, outdoor-unit cycle, flow rate and product type.
This page lists 35 Modbus registers for the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LG’s own free documentation (linked below) and checked against it.
- Manufacturer
- LG
- Model
- THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
- Equipment type
- Heat pump (air-to-water)
- Registers
- 35 (13 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615
Integration notes: LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
Wire RS-485 to terminals 26 (A) and 27 (B), set the unit's Modbus address, then read discrete inputs 10001-10017 and input registers 30001-30012 for status and write coils 00001/00002 plus holding registers 40001-40010 for control.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Enable/Disable (Heating/Cooling) | BIT | Space heating/cooling on/off | Read/write |
| CO 1 | Enable/Disable (DHW) | BIT | Hot water on/off | Read/write |
| HR 0 | Operation mode | UINT16 | Operation mode | Read/write |
| HR 2 | Target temp (heating/cooling) circuit 1 | UINT16 | Circuit 1 water setpoint | Read/write |
| HR 8 | DHW target temp. | UINT16 | DHW setpoint | Read/write |
| DI 3 | Compressor status | BIT | Compressor running | Read |
| DI 13 | Error status | BIT | Error flag | Read |
| IR 0 | Error code | UINT16 | Error code | Read |
Enable Modbus control & writes
Turn DIP switch No.1 of option switch 1 ON (Modbus function as slave for a 3rd-party controller), then set the Modbus address under Installer setting > Modbus Address on the LG controller.
Byte order & addressing
- Operation mode codes are 0 = cooling, 3 = auto, 4 = heating (not 0/1/2).
- Product group and product info sit at the top of the input-register range (39998/39999 = wire 9997/9998).
Network setup
- Serial settings are 9600 bps, no parity, 1 stop bit.
- The bus connects to terminal block 3 (26 = A, 27 = B); check the CN_MODBUS harness is fully seated in CN_COM on the indoor PCB. The LG meter interface uses the same terminals.
Watch out for
- While a 3rd-party Modbus controller is in use, the LG controller cannot run the unit at the same time.
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Enable/Disable (Heating/Cooling) | Space heating/cooling operation on or off. | BIT | Read/write | 0 = Operation off; 1 = Operation on | |||
| CO | 1doc 00002 | Enable/Disable (DHW) | Domestic hot water operation on or off. | BIT | Read/write | 0 = Operation off; 1 = Operation on | |||
| CO | 2doc 00003 | Silent Mode Set | BIT | Read/write | 0 = Silent mode off; 1 = Silent mode on | ||||
| CO | 4doc 00005 | Emergency Stop | BIT | Read/write | 0 = Normal operation; 1 = Emergency stop | ||||
| CO | 5doc 00006 | Trigger Emergency Operation | Write 1 to start emergency operation. | BIT | Read/write | 0 = Keep status; 1 = Operation start | |||
| DI | 0doc 10001 | Water flow status | BIT | Read | 0 = Flow rate OK; 1 = Flow rate too low | ||||
| DI | 1doc 10002 | Water pump status | BIT | Read | 0 = Water pump off; 1 = Water pump on | ||||
| DI | 2doc 10003 | Ext. water pump status | External water pump. | BIT | Read | 0 = Water pump off; 1 = Water pump on | |||
| DI | 3doc 10004 | Compressor status | BIT | Read | 0 = Compressor off; 1 = Compressor on | ||||
| DI | 4doc 10005 | Defrosting status | BIT | Read | 0 = Defrost off; 1 = Defrost on | ||||
| DI | 5doc 10006 | DHW heating status (DHW thermal on/off) | BIT | Read | 0 = DHW inactive; 1 = DHW active | ||||
| DI | 7doc 10008 | Silent mode status | BIT | Read | 0 = Silent mode inactive; 1 = Silent mode active | ||||
| DI | 8doc 10009 | Cooling status | BIT | Read | 0 = No cooling; 1 = Cooling operation | ||||
| DI | 9doc 10010 | Solar pump status | BIT | Read | 0 = Solar pump off; 1 = Solar pump on | ||||
| DI | 10doc 10011 | Backup heater (step 1) status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 11doc 10012 | Backup heater (step 2) status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 12doc 10013 | DHW boost heater status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 13doc 10014 | Error status | BIT | Read | 0 = No error; 1 = Error state | ||||
| DI | 14doc 10015 | Emergency operation available (space heating/cooling) | BIT | Read | 0 = Unavailable; 1 = Available | ||||
| DI | 15doc 10016 | Emergency operation available (DHW) | BIT | Read | 0 = Unavailable; 1 = Available | ||||
| DI | 16doc 10017 | Mix pump status | BIT | Read | 0 = Mix pump off; 1 = Mix pump on | ||||
| IR | 0doc 30001 | Error code | Active error code number. | UINT16 | Read | ||||
| IR | 1doc 30002 | ODU operation cycle | What the outdoor unit is doing. | UINT16 | Read | 0 = Standby (off); 1 = Cooling; 2 = Heating | |||
| IR | 8doc 30009 | Current flow rate | Water flow in tenths of a litre per minute. | UINT16 | × 0.1 | L/min | Read | ||
| IR | 11doc 30012 | Energy state input | Energy state currently in effect (0 = state 0, 1 = state 1 and so on). | UINT16 | Read | ||||
| IR | 9997doc 39998 | Product group | 0x8X: the manual lists 0x80, 0x83, 0x88 and 0x89. | UINT16 | Read | ||||
| IR | 9998doc 39999 | Product info | UINT16 | Read | 0 = Split; 3 = Monobloc; 4 = High temperature; 5 = Medium temperature; 6 = System boiler | ||||
| HR | 0doc 40001 | Operation mode | UINT16 | Read/write | 0 = Cooling; 3 = Auto; 4 = Heating | ||||
| HR | 1doc 40002 | Control method (circuit 1/2) | Which temperature the unit controls to. | UINT16 | Read/write | 0 = Water outlet temperature control; 1 = Water inlet temperature control; 2 = Room air control | |||
| HR | 2doc 40003 | Target temp (heating/cooling) circuit 1 | Water target for circuit 1, in tenths of a degree. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 3doc 40004 | Room air temp. circuit 1 | Room air target for circuit 1, in tenths of a degree. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 5doc 40006 | Target temp (heating/cooling) circuit 2 | Water target for circuit 2, in tenths of a degree. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 6doc 40007 | Room air temp. circuit 2 | Room air target for circuit 2, in tenths of a degree. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 8doc 40009 | DHW target temp. | Hot water tank target, in tenths of a degree. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 9doc 40010 | Energy state input | Smart-grid style energy state written by the BMS. | UINT16 | Read/write | 0 = Not used; 1 = Forced off (as TB_SG1 closed / TB_SG2 open); 2 = Normal operation (as TB_SG1 open / TB_SG2 open); 3 = On-recommendation (as TB_SG1 open / TB_SG2 closed); 4 = On-command (as TB_SG1 closed / TB_SG2 closed); 5 = On-command step 2 (++ energy use vs normal); 6 = On-recommendation step 1 (+ energy use vs normal); 7 = Energy saving mode (- energy use vs normal); 8 = Super energy saving mode (-- energy use vs normal) |
Notes on this map
- This file follows the North American Rev.02 edition, where holding registers (function 0x03) are numbered 40001- and input registers (0x04) 30001-.
- Left out: every measured temperature (input registers 30003-30008, 30010, 30011 and 30013: water inlet/outlet, backup heater outlet, DHW tank, solar collector, room air and outdoor air) and the auto-mode shift values 40005 and 40008, because the manual gives a x10 scale but never says whether these values are signed, and they can be negative.
- Setpoints 40003, 40004, 40006, 40007 and 40009 are listed as UINT16: the map prints only the x10 scale and no signedness, but these targets are always positive in the manual's setting ranges (for example leaving water 15-65 °C heating, 5-27 °C cooling), so signed and unsigned reads agree.
- The map skips coil 00004 and discrete input 10007; they are not listed in this edition.
- The error-code register returns LG's numeric error code; the code list is not part of this map.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
What Modbus registers does the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) have?
This map lists 35 registers: 5 coils, 16 discrete inputs, 6 input registers, 8 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The memory map prints Modicon numbers: coils 00001-, discrete inputs 10001-, input registers 30001-, holding registers 40001-. Drop the leading table digit and subtract one to get the wire address (40001 = holding register 0, 30009 = input register 8, 39999 = input register 9998).
What are the minimum Modbus registers to integrate the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)?
Start with CO 0 Enable/Disable (Heating/Cooling) (Space heating/cooling on/off); CO 1 Enable/Disable (DHW) (Hot water on/off); HR 0 Operation mode (Operation mode); HR 2 Target temp (heating/cooling) circuit 1 (Circuit 1 water setpoint); HR 8 DHW target temp. (DHW setpoint); DI 3 Compressor status (Compressor running); DI 13 Error status (Error flag); IR 0 Error code (Error code).
How do I enable Modbus control of the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)?
Turn DIP switch No.1 of option switch 1 ON (Modbus function as slave for a 3rd-party controller), then set the Modbus address under Installer setting > Modbus Address on the LG controller.
Where is the official LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus documentation?
The source is Installation Manual - Air-to-Water Heat Pump (THERMA V) (MFL68026615 Rev.02), revision 2024-03-27, published free by LG at https://media.us.lg.com/m/448e6747eb2bae77/original/IM_MFL68026615_02_240405_05_WEB-pdf.pdf.
More LG Modbus register maps
- Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
LG PAHCMR000 AHU Communication Kit (R32 and R410A Multi V / single split outdoor units with a PRLK EEV kit), installation manual IM_AHU_Comm_Kit_PAHCMR000_R32_06_26.
Also known as: PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus - Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
LG PAHCMS000 AHU Communication Kit for discharge (supply) air control with up to four LG outdoor units, installation manual IM_AHU_Comm_Kit_PAHCMS000_11_23.
Also known as: PAHCMS000, LG AHU Communication Kit discharge air, LG AHU comm kit PAHCMS000 Modbus
Other pumps register maps
- Heat pump / ventilation unit controller (air handler)
Nilan CTS602 controller with HMI350T panel (Modbus version 23)
Nilan ventilation, heat-recovery and compact heat pump units with the CTS602 board and HMI350T user panel, Modbus protocol version 23 (software 3.6.58/3.6.59).
Also known as: CTS 602, CTS602 HMI350T, CTS602 w. HMI350T - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit - Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080 - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+ - Heat pump (water-source heat pump controller)
First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
First Co. / AE-Air water-source heat pumps (WSV and related series) with the factory DDC controller CB900, without hot-gas reheat (IOM8083D02 rev. A).
Also known as: CB900, CB900-1, CB900-2, IOM8083D02, WSV series DDC, First Co. WSHP DDC controller, AE-Air WSHP DDC - Pump (submersible grinder pump pit)
Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)
Up to four Grundfos SEG AUTOADAPT grinder pumps in one or more pits, connected to a CIU 202 (Modbus RTU), CIU 262 (cellular) or CIU 502 (Modbus TCP); functional profile 96846341 (2019-01).
Also known as: SEG AUTOADAPT, CIU 202, CIU 262, CIU 502, 96846341
All pumps Modbus register maps →
Source: Installation Manual - Air-to-Water Heat Pump (THERMA V) · MFL68026615 Rev.02 · rev. 2024-03-27. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.