  4. THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)

Heat pump (air-to-water) · Modbus register map

LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The THERMA V monobloc can be run by a third-party controller over Modbus RTU wired to terminal block 3 (26 = A, 27 = B) on the indoor PCB, with no LG gateway. Coils switch space heating/cooling, hot water, silent mode and emergency functions; discrete inputs report pump, compressor, defrost, heater and error states; holding registers carry the operating mode, control method, setpoints and the smart-grid energy state; input registers give the error code, outdoor-unit cycle, flow rate and product type.

This page lists 35 Modbus registers for the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LG’s own free documentation (linked below) and checked against it.

Manufacturer
LG
Model
THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
Equipment type
Heat pump (air-to-water)
Registers
35 (13 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615
Source document
Installation Manual - Air-to-Water Heat Pump (THERMA V) · MFL68026615 Rev.02 · rev. 2024-03-27
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)

Integration in brief

Wire RS-485 to terminals 26 (A) and 27 (B), set the unit's Modbus address, then read discrete inputs 10001-10017 and input registers 30001-30012 for status and write coils 00001/00002 plus holding registers 40001-40010 for control.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0Enable/Disable (Heating/Cooling)BITSpace heating/cooling on/offRead/write
CO 1Enable/Disable (DHW)BITHot water on/offRead/write
HR 0Operation modeUINT16Operation modeRead/write
HR 2Target temp (heating/cooling) circuit 1UINT16Circuit 1 water setpointRead/write
HR 8DHW target temp.UINT16DHW setpointRead/write
DI 3Compressor statusBITCompressor runningRead
DI 13Error statusBITError flagRead
IR 0Error codeUINT16Error codeRead

Enable Modbus control & writes

Turn DIP switch No.1 of option switch 1 ON (Modbus function as slave for a 3rd-party controller), then set the Modbus address under Installer setting > Modbus Address on the LG controller.

Byte order & addressing

Network setup

Watch out for

LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

35 of 35 shown
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Enable/Disable (Heating/Cooling)Space heating/cooling operation on or off.BITRead/write0 = Operation off; 1 = Operation on
CO1doc 00002Enable/Disable (DHW)Domestic hot water operation on or off.BITRead/write0 = Operation off; 1 = Operation on
CO2doc 00003Silent Mode SetBITRead/write0 = Silent mode off; 1 = Silent mode on
CO4doc 00005Emergency StopBITRead/write0 = Normal operation; 1 = Emergency stop
CO5doc 00006Trigger Emergency OperationWrite 1 to start emergency operation.BITRead/write0 = Keep status; 1 = Operation start
DI0doc 10001Water flow statusBITRead0 = Flow rate OK; 1 = Flow rate too low
DI1doc 10002Water pump statusBITRead0 = Water pump off; 1 = Water pump on
DI2doc 10003Ext. water pump statusExternal water pump.BITRead0 = Water pump off; 1 = Water pump on
DI3doc 10004Compressor statusBITRead0 = Compressor off; 1 = Compressor on
DI4doc 10005Defrosting statusBITRead0 = Defrost off; 1 = Defrost on
DI5doc 10006DHW heating status (DHW thermal on/off)BITRead0 = DHW inactive; 1 = DHW active
DI7doc 10008Silent mode statusBITRead0 = Silent mode inactive; 1 = Silent mode active
DI8doc 10009Cooling statusBITRead0 = No cooling; 1 = Cooling operation
DI9doc 10010Solar pump statusBITRead0 = Solar pump off; 1 = Solar pump on
DI10doc 10011Backup heater (step 1) statusBITRead0 = Off; 1 = On
DI11doc 10012Backup heater (step 2) statusBITRead0 = Off; 1 = On
DI12doc 10013DHW boost heater statusBITRead0 = Off; 1 = On
DI13doc 10014Error statusBITRead0 = No error; 1 = Error state
DI14doc 10015Emergency operation available (space heating/cooling)BITRead0 = Unavailable; 1 = Available
DI15doc 10016Emergency operation available (DHW)BITRead0 = Unavailable; 1 = Available
DI16doc 10017Mix pump statusBITRead0 = Mix pump off; 1 = Mix pump on
IR0doc 30001Error codeActive error code number.UINT16Read
IR1doc 30002ODU operation cycleWhat the outdoor unit is doing.UINT16Read0 = Standby (off); 1 = Cooling; 2 = Heating
IR8doc 30009Current flow rateWater flow in tenths of a litre per minute.UINT16× 0.1L/minRead
IR11doc 30012Energy state inputEnergy state currently in effect (0 = state 0, 1 = state 1 and so on).UINT16Read
IR9997doc 39998Product group0x8X: the manual lists 0x80, 0x83, 0x88 and 0x89.UINT16Read
IR9998doc 39999Product infoUINT16Read0 = Split; 3 = Monobloc; 4 = High temperature; 5 = Medium temperature; 6 = System boiler
HR0doc 40001Operation modeUINT16Read/write0 = Cooling; 3 = Auto; 4 = Heating
HR1doc 40002Control method (circuit 1/2)Which temperature the unit controls to.UINT16Read/write0 = Water outlet temperature control; 1 = Water inlet temperature control; 2 = Room air control
HR2doc 40003Target temp (heating/cooling) circuit 1Water target for circuit 1, in tenths of a degree.UINT16× 0.1°CRead/write
HR3doc 40004Room air temp. circuit 1Room air target for circuit 1, in tenths of a degree.UINT16× 0.1°CRead/write
HR5doc 40006Target temp (heating/cooling) circuit 2Water target for circuit 2, in tenths of a degree.UINT16× 0.1°CRead/write
HR6doc 40007Room air temp. circuit 2Room air target for circuit 2, in tenths of a degree.UINT16× 0.1°CRead/write
HR8doc 40009DHW target temp.Hot water tank target, in tenths of a degree.UINT16× 0.1°CRead/write
HR9doc 40010Energy state inputSmart-grid style energy state written by the BMS.UINT16Read/write0 = Not used; 1 = Forced off (as TB_SG1 closed / TB_SG2 open); 2 = Normal operation (as TB_SG1 open / TB_SG2 open); 3 = On-recommendation (as TB_SG1 open / TB_SG2 closed); 4 = On-command (as TB_SG1 closed / TB_SG2 closed); 5 = On-command step 2 (++ energy use vs normal); 6 = On-recommendation step 1 (+ energy use vs normal); 7 = Energy saving mode (- energy use vs normal); 8 = Super energy saving mode (-- energy use vs normal)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)

What Modbus registers does the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) have?

This map lists 35 registers: 5 coils, 16 discrete inputs, 6 input registers, 8 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The memory map prints Modicon numbers: coils 00001-, discrete inputs 10001-, input registers 30001-, holding registers 40001-. Drop the leading table digit and subtract one to get the wire address (40001 = holding register 0, 30009 = input register 8, 39999 = input register 9998).

What are the minimum Modbus registers to integrate the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)?

Start with CO 0 Enable/Disable (Heating/Cooling) (Space heating/cooling on/off); CO 1 Enable/Disable (DHW) (Hot water on/off); HR 0 Operation mode (Operation mode); HR 2 Target temp (heating/cooling) circuit 1 (Circuit 1 water setpoint); HR 8 DHW target temp. (DHW setpoint); DI 3 Compressor status (Compressor running); DI 13 Error status (Error flag); IR 0 Error code (Error code).

How do I enable Modbus control of the LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)?

Turn DIP switch No.1 of option switch 1 ON (Modbus function as slave for a 3rd-party controller), then set the Modbus address under Installer setting > Modbus Address on the LG controller.

Where is the official LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU) Modbus documentation?

The source is Installation Manual - Air-to-Water Heat Pump (THERMA V) (MFL68026615 Rev.02), revision 2024-03-27, published free by LG at https://media.us.lg.com/m/448e6747eb2bae77/original/IM_MFL68026615_02_240405_05_WEB-pdf.pdf.

More LG Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Installation Manual - Air-to-Water Heat Pump (THERMA V) · MFL68026615 Rev.02 · rev. 2024-03-27. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.