- PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
Air handler DX kit (VRF / split AC gateway built in) · Modbus register map
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus register map
Updated 19 November 2026
The PAHCMR000 kit lets a third-party air handler use an LG Multi V or single-split outdoor unit, and its RS485 CH1 port talks Modbus RTU directly to a DDC controller. Coils switch the unit and lock wired-controller functions, holding registers set mode, fan speed, target temperature and its limits, and discrete inputs and input registers report compressor, defrost and oil-return status, error code, return-air and coil temperatures.
This page lists 19 Modbus registers for the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LG’s own free documentation (linked below) and checked against it.
- Manufacturer
- LG
- Model
- PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
- Equipment type
- Air handler DX kit (VRF / split AC gateway built in)
- Registers
- 19 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus
Integration notes: LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
Set DIP SW1-2 to ON (communication), wire the DDC to RS485 CH1, then write coil 00001 for on/off and holding registers 40001-40003 for mode, fan and target temperature; read 30002 for return-air temperature and 30001 / coil 00007 for errors.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Operating On/Off | BIT | On/off | Read/write |
| HR 0 | Operation mode | UINT16 | Operation mode | Read/write |
| HR 1 | Fan speed | UINT16 | Fan speed | Read/write |
| HR 2 | Target temperature | INT16 | Target temperature | Read/write |
| IR 1 | Return air temperature | INT16 | Return air temperature | Read |
| IR 0 | Error code | UINT16 | Error code | Read |
| DI 0 | Compressor status | BIT | Compressor status | Read |
| DI 1 | Defrost status | BIT | Defrost status | Read |
Enable Modbus control & writes
DIP switch SW1-2 ON selects control by DDC Modbus (or LG remote / central controllers); OFF selects contact-signal control, where an LG central controller can only monitor.
Byte order & addressing
- Operation mode uses 0 = cooling, 2 = fan, 4 = heating (no auto value).
- Only function 06 is listed for writing holding registers and 05 for coils.
Network setup
- RS485 CH1 to the DDC: 2-core 1.0-1.5 mm2 shielded cable, up to 500 m.
- 9600 bps, no parity, 1 stop bit.
- The Modbus slave (sub) address follows the main module address setting described in the manual.
Watch out for
- Discharge-air temperature control, forced thermal on/off and capacity control are not available over Modbus with this kit.
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Operating On/Off | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 2doc 00003 | All button lock | Locks the LG wired controller keys. | BIT | Read/write | 0 = Unlock; 1 = Lock | |||
| CO | 3doc 00004 | Mode lock | BIT | Read/write | 0 = Unlock; 1 = Lock | ||||
| CO | 4doc 00005 | Fan speed lock | BIT | Read/write | 0 = Unlock; 1 = Lock | ||||
| CO | 5doc 00006 | Target temperature lock | BIT | Read/write | 0 = Unlock; 1 = Lock | ||||
| CO | 6doc 00007 | Error | Read only (function 01). | BIT | Read | 0 = Normal; 1 = Error | |||
| DI | 0doc 10001 | Compressor status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 1doc 10002 | Defrost status | BIT | Read | 0 = Normal; 1 = Defrost | ||||
| DI | 2doc 10003 | Oil return | BIT | Read | 0 = Normal; 1 = Oil return | ||||
| IR | 0doc 30001 | Error code | LG error code 0-255. | UINT16 | Read | ||||
| IR | 1doc 30002 | Return air temperature | Range -50 to 100 °C, sent x10. | INT16 | × 0.1 | °C | Read | ||
| IR | 3doc 30004 | Pipe in temperature | Range -50 to 100 °C, sent x10. | INT16 | × 0.1 | °C | Read | ||
| IR | 4doc 30005 | Pipe out temperature | Range -50 to 100 °C, sent x10. | INT16 | × 0.1 | °C | Read | ||
| IR | 5doc 30006 | Capacity | AHU capacity setting, 0-255. | UINT16 | kBtu | Read | |||
| HR | 0doc 40001 | Operation mode | UINT16 | Read/write | 0 = Cooling; 2 = Fan; 4 = Heating | ||||
| HR | 1doc 40002 | Fan speed | UINT16 | Read/write | 1 = Low; 2 = Middle; 3 = High | ||||
| HR | 2doc 40003 | Target temperature | Range -10 to 100 °C, sent x10. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 3doc 40004 | Target temperature upper range | 15.6-30 °C, sent x10, in 1.0 °C steps. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 4doc 40005 | Target temperature lower range | 15.6-30 °C, sent x10, in 1.0 °C steps. | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- Reserved points (coils 00002 and 00008, inputs 10004-10008, input registers 30003, 30007-30008, holding 40006-40010) are left out.
- Access follows the function-code columns of the memory map: coil 00007 (Error) is read with 01 only; the other coils accept 01 and 05. Holding registers accept 03 and 06.
- Temperatures are sent multiplied by 10 and cover negative ranges, so they are listed as signed 16-bit.
- The manual does not print the data-bit setting; only 9600 bps, no parity and 1 stop bit are stated.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
What Modbus registers does the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) have?
This map lists 19 registers: 6 coils, 3 discrete inputs, 5 input registers, 5 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Points are printed as 00001/10001/30001/40001-style registers together with the function codes for each block (01/05 coils 00001-00008, 02 inputs 10001-10008, 04 input registers 30001-30008, 03/06 holding registers 40001-40010). The wire address is the printed number minus the block base: 40003 is holding register 2.
What are the minimum Modbus registers to integrate the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)?
Start with CO 0 Operating On/Off (On/off); HR 0 Operation mode (Operation mode); HR 1 Fan speed (Fan speed); HR 2 Target temperature (Target temperature); IR 1 Return air temperature (Return air temperature); IR 0 Error code (Error code); DI 0 Compressor status (Compressor status); DI 1 Defrost status (Defrost status).
How do I enable Modbus control of the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)?
DIP switch SW1-2 ON selects control by DDC Modbus (or LG remote / central controllers); OFF selects contact-signal control, where an LG central controller can only monitor.
Where is the official LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus documentation?
The source is Communications Kit Installation Manual for LG R32 Air Handler Unit (AHU) - PAHCMR000 (IM_AHU_Comm_Kit_PAHCMR000_R32_06_26), revision 2025, published free by LG at https://media.us.lg.com/m/d2725fbeddc5be9/original/IM_AHU_Comm_Kit_PAHCMR000-pdf.pdf.
More LG Modbus register maps
- Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
LG PAHCMS000 AHU Communication Kit for discharge (supply) air control with up to four LG outdoor units, installation manual IM_AHU_Comm_Kit_PAHCMS000_11_23.
Also known as: PAHCMS000, LG AHU Communication Kit discharge air, LG AHU comm kit PAHCMS000 Modbus - Heat pump (air-to-water)
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
LG THERMA V R32 Monobloc air-to-water heat pumps covered by installation manual MFL68026615 Rev.02 (North American models ZHBW041GA0 / ZHBW048GA0 / ZHBW055GA0), using the indoor PCB's own Modbus RTU slave port.
Also known as: ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615
Other ac & vrf gateways register maps
- VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - VRF / split AC gateway (built-in indoor-unit Modbus)
Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
Sinclair All DC Inverter UNI SPLIT indoor units with the built-in Modbus RTU interface, per the UNI SPLIT Modbus user's manual.
Also known as: Sinclair UNI SPLIT, UNI SPLIT Modbus, All DC Inverter UNI SPLIT - Split AC unit (VRF / split AC gateway built in)
Aermec LPG series DC inverter air conditioners (built-in Modbus)
Aermec LPG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; ModBus Protocol LPG series 5385759_02 (EN 25.05).
Also known as: LPG - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus
All ac & vrf gateways Modbus register maps →
Source: Communications Kit Installation Manual for LG R32 Air Handler Unit (AHU) - PAHCMR000 · IM_AHU_Comm_Kit_PAHCMR000_R32_06_26 · rev. 2025. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.