Air handler DX kit (VRF / split AC gateway built in) · Modbus register map

LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus register map

Updated 19 November 2026

Short answer

The PAHCMR000 kit lets a third-party air handler use an LG Multi V or single-split outdoor unit, and its RS485 CH1 port talks Modbus RTU directly to a DDC controller. Coils switch the unit and lock wired-controller functions, holding registers set mode, fan speed, target temperature and its limits, and discrete inputs and input registers report compressor, defrost and oil-return status, error code, return-air and coil temperatures.

This page lists 19 Modbus registers for the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LG’s own free documentation (linked below) and checked against it.

Manufacturer
LG
Model
PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
Equipment type
Air handler DX kit (VRF / split AC gateway built in)
Registers
19 (10 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus
Source document
Communications Kit Installation Manual for LG R32 Air Handler Unit (AHU) - PAHCMR000 · IM_AHU_Comm_Kit_PAHCMR000_R32_06_26 · rev. 2025
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)

Integration in brief

Set DIP SW1-2 to ON (communication), wire the DDC to RS485 CH1, then write coil 00001 for on/off and holding registers 40001-40003 for mode, fan and target temperature; read 30002 for return-air temperature and 30001 / coil 00007 for errors.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0Operating On/OffBITOn/offRead/write
HR 0Operation modeUINT16Operation modeRead/write
HR 1Fan speedUINT16Fan speedRead/write
HR 2Target temperatureINT16Target temperatureRead/write
IR 1Return air temperatureINT16Return air temperatureRead
IR 0Error codeUINT16Error codeRead
DI 0Compressor statusBITCompressor statusRead
DI 1Defrost statusBITDefrost statusRead

Enable Modbus control & writes

DIP switch SW1-2 ON selects control by DDC Modbus (or LG remote / central controllers); OFF selects contact-signal control, where an LG central controller can only monitor.

Byte order & addressing

Network setup

Watch out for

LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

19 of 19 shown
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Operating On/OffBITRead/write0 = Off; 1 = On
CO2doc 00003All button lockLocks the LG wired controller keys.BITRead/write0 = Unlock; 1 = Lock
CO3doc 00004Mode lockBITRead/write0 = Unlock; 1 = Lock
CO4doc 00005Fan speed lockBITRead/write0 = Unlock; 1 = Lock
CO5doc 00006Target temperature lockBITRead/write0 = Unlock; 1 = Lock
CO6doc 00007ErrorRead only (function 01).BITRead0 = Normal; 1 = Error
DI0doc 10001Compressor statusBITRead0 = Off; 1 = On
DI1doc 10002Defrost statusBITRead0 = Normal; 1 = Defrost
DI2doc 10003Oil returnBITRead0 = Normal; 1 = Oil return
IR0doc 30001Error codeLG error code 0-255.UINT16Read
IR1doc 30002Return air temperatureRange -50 to 100 °C, sent x10.INT16× 0.1°CRead
IR3doc 30004Pipe in temperatureRange -50 to 100 °C, sent x10.INT16× 0.1°CRead
IR4doc 30005Pipe out temperatureRange -50 to 100 °C, sent x10.INT16× 0.1°CRead
IR5doc 30006CapacityAHU capacity setting, 0-255.UINT16kBtuRead
HR0doc 40001Operation modeUINT16Read/write0 = Cooling; 2 = Fan; 4 = Heating
HR1doc 40002Fan speedUINT16Read/write1 = Low; 2 = Middle; 3 = High
HR2doc 40003Target temperatureRange -10 to 100 °C, sent x10.INT16× 0.1°CRead/write
HR3doc 40004Target temperature upper range15.6-30 °C, sent x10, in 1.0 °C steps.INT16× 0.1°CRead/write
HR4doc 40005Target temperature lower range15.6-30 °C, sent x10, in 1.0 °C steps.INT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)

What Modbus registers does the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) have?

This map lists 19 registers: 6 coils, 3 discrete inputs, 5 input registers, 5 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Points are printed as 00001/10001/30001/40001-style registers together with the function codes for each block (01/05 coils 00001-00008, 02 inputs 10001-10008, 04 input registers 30001-30008, 03/06 holding registers 40001-40010). The wire address is the printed number minus the block base: 40003 is holding register 2.

What are the minimum Modbus registers to integrate the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)?

Start with CO 0 Operating On/Off (On/off); HR 0 Operation mode (Operation mode); HR 1 Fan speed (Fan speed); HR 2 Target temperature (Target temperature); IR 1 Return air temperature (Return air temperature); IR 0 Error code (Error code); DI 0 Compressor status (Compressor status); DI 1 Defrost status (Defrost status).

How do I enable Modbus control of the LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)?

DIP switch SW1-2 ON selects control by DDC Modbus (or LG remote / central controllers); OFF selects contact-signal control, where an LG central controller can only monitor.

Where is the official LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC) Modbus documentation?

The source is Communications Kit Installation Manual for LG R32 Air Handler Unit (AHU) - PAHCMR000 (IM_AHU_Comm_Kit_PAHCMR000_R32_06_26), revision 2025, published free by LG at https://media.us.lg.com/m/d2725fbeddc5be9/original/IM_AHU_Comm_Kit_PAHCMR000-pdf.pdf.

More LG Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Communications Kit Installation Manual for LG R32 Air Handler Unit (AHU) - PAHCMR000 · IM_AHU_Comm_Kit_PAHCMR000_R32_06_26 · rev. 2025. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.