Easy Modbus
  1. Home
  2. Modbus register maps
  3. Sinclair
  4. UNI SPLIT DC inverter indoor units (integrated Modbus RTU)

VRF / split AC gateway (built-in indoor-unit Modbus) · Modbus register map

Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Sinclair's UNI SPLIT DC inverter indoor units have a Modbus RTU slave built into the indoor controller, so no separate gateway is needed; up to 255 units share one RS-485 line. Settings and analog values are 16-bit words (holding registers) and flags are coils. This map covers on/off, mode, fan, setpoint, swing, temperatures, remote locks and shields, feature flags, and the indoor, outdoor and inverter-drive fault bits.

This page lists 115 Modbus registers for the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Sinclair’s own free documentation (linked below) and checked against it.

Manufacturer
Sinclair
Model
UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
Equipment type
VRF / split AC gateway (built-in indoor-unit Modbus)
Registers
115 (31 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
Sinclair UNI SPLIT, UNI SPLIT Modbus, All DC Inverter UNI SPLIT
Source document
User's manual UNI SPLIT Modbus
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)

Integration in brief

Set the indoor unit to PC/Modbus address mode on the wired controller, then poll holding registers 0-83 with function 03 and coils 0-215 with function 01. Control by writing words 2, 17, 19 and 20 with function 16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2Unit on/offUINT16Unit on/off (0xAA on, 0x55 off)Read/write
HR 4Ambient temperatureINT16Ambient temperatureRead
HR 17Set modeUINT16ModeRead/write
HR 19Set fan speedUINT16Fan speedRead/write
HR 20Set temperatureUINT16SetpointRead/write
CO 151Compressor statusBITCompressor runningRead
CO 122Comms failure with ODUBITODU communication failureRead

Enable Modbus control & writes

The Modbus interface is built into the indoor unit controller. Select the address mode and set the unit address on the wired controller (see the unit's service manual).

Byte order & addressing

Network setup

Watch out for

Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

115 of 115 shown
Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO8doc Bit8ODU present flagBITRead0 = No; 1 = Yes
CO9doc Bit9Master wired controller present flagBITRead0 = No; 1 = Yes
CO13doc Bit13Slave wired controller present flagBITRead0 = No; 1 = Yes
CO17doc Bit17Remote lockBITRead/write0 = Not locked; 1 = Locked by remote monitoring
CO18doc Bit18Remote temperature shieldBITRead/write0 = No shield; 1 = Shield
CO19doc Bit19Remote mode shieldBITRead/write0 = No shield; 1 = Shield
CO20doc Bit20Remote on/off shieldBITRead/write0 = No shield; 1 = Shield
CO21doc Bit21Remote energy-saving shieldBITRead/write0 = No shield; 1 = Shield
CO24doc Bit24Absence modeBITRead/write0 = Off; 1 = On
CO25doc Bit25Healthy functionBITRead/write0 = Off; 1 = On
CO26doc Bit26I-Demand (comfort energy saving)BITRead/write0 = Off; 1 = On
CO27doc Bit27TurboBITRead/write0 = Off; 1 = On
CO28doc Bit28Electric heating permissionBITRead/write0 = E-heating permitted; 1 = E-heating not permitted
CO29doc Bit29X-fanBITRead/write0 = Off; 1 = On
CO30doc Bit30SilentBITRead/write0 = Off; 1 = On
CO31doc Bit31Low-temperature drying modeBITRead/write0 = Off; 1 = On
CO32doc Bit32Energy saving in cooling activeBITRead/write0 = Off; 1 = On
CO33doc Bit33Energy saving in heating activeBITRead/write0 = Off; 1 = On
CO34doc Bit34Button lock (child lock)BITRead/write0 = Off; 1 = On
CO35doc Bit35On/off memoryBITRead/write0 = Memorise; 1 = Do not memorise
CO36doc Bit36Temperature unit flagBITRead/write0 = °C; 1 = °F
CO40doc Bit40Timer statusBITRead0 = No timer; 1 = Timer set
CO46doc Bit46Gate control system fittedBITRead0 = No; 1 = Yes
CO47doc Bit47Presence sensor module fittedBITRead0 = No; 1 = Yes
CO49doc Bit49Timer on flagBITRead0 = Not active; 1 = Active
CO50doc Bit50Timer off flagBITRead0 = Not active; 1 = Active
CO51doc Bit51Indoor temperature source in current modeBITRead0 = Return-air temperature; 1 = Wired controller temperature
CO55doc Bit55Low standby power (1 W) modeBITRead0 = Mode 1; 1 = Mode 2
CO65doc Bit65Wired controller temp sensor errorBITRead0 = Normal; 1 = Fault
CO70doc Bit70Wired controller memory chip errorBITRead0 = Normal; 1 = Fault
CO72doc Bit72Cancel timerBITRead/write0 = Do not cancel; 1 = Cancel
CO74doc Bit74Up/down swing modeBITRead/write0 = Mode 1: simple swing; 1 = Mode 2: fixed angle and small-area swing
CO91doc Bit91Electric heatingBITRead0 = Off; 1 = On
CO92doc Bit92Water pumpBITRead0 = Off; 1 = On
CO93doc Bit93Fresh air valve switchBITRead0 = Off; 1 = On
CO94doc Bit94Cold plasma generatorBITRead0 = Off; 1 = On
CO95doc Bit95Error output statusBITRead0 = No; 1 = Yes
CO97doc Bit97Indoor evaporator temp sensor errorBITRead0 = Normal; 1 = Fault
CO98doc Bit98Indoor return-air temp sensor errorBITRead0 = Normal; 1 = Fault
CO99doc Bit99Light-board ambient temp sensor errorBITRead0 = Normal; 1 = Fault
CO101doc Bit101Water overflow protectionBITRead0 = Normal; 1 = Fault
CO102doc Bit102IDU memory chip errorBITRead0 = Normal; 1 = Fault
CO104doc Bit104Jumper cap error (IDU)BITRead0 = Normal; 1 = Fault
CO105doc Bit105Indoor fan errorBITRead0 = Normal; 1 = Fault
CO112doc Bit112Key card statusBITRead0 = Card out; 1 = Card in
CO113doc Bit113Room occupiedBITRead0 = No; 1 = Yes
CO114doc Bit114Static pressure typeBITRead0 = Low static; 1 = High static
CO120doc Bit120Comms failure with master wired controllerBITRead0 = Normal; 1 = Fault
CO121doc Bit121Comms failure with slave wired controllerBITRead0 = Normal; 1 = Fault
CO122doc Bit122Comms failure with ODUBITRead0 = Normal; 1 = Fault
CO147doc Bit147Outdoor fan statusBITRead0 = Off; 1 = On
CO150doc Bit1504-way valve statusBITRead0 = Off; 1 = On
CO151doc Bit151Compressor statusBITRead0 = Off; 1 = On
CO152doc Bit152Discharge temperature protectionBITRead0 = Normal; 1 = Fault
CO153doc Bit153Refrigerant shortage protectionBITRead0 = Normal; 1 = Fault
CO154doc Bit154DC fan motor protectionBITRead0 = Normal; 1 = Fault
CO155doc Bit1554-way valve reversing error protectionBITRead0 = Normal; 1 = Fault
CO156doc Bit156Over-power protectionBITRead0 = Normal; 1 = Fault
CO157doc Bit157Overload protectionBITRead0 = Normal; 1 = Fault
CO158doc Bit158Low pressure protectionBITRead0 = Normal; 1 = Fault
CO159doc Bit159High pressure protectionBITRead0 = Normal; 1 = Fault
CO160doc Bit160Evaporator anti-freeze protectionBITRead0 = Normal; 1 = Fault
CO161doc Bit161Outdoor ambient temp sensor errorBITRead0 = Normal; 1 = Fault
CO162doc Bit162Discharge temp sensor errorBITRead0 = Normal; 1 = Fault
CO163doc Bit163Condenser temp sensor errorBITRead0 = Normal; 1 = Fault
CO164doc Bit164Outdoor coil pipe temp sensor errorBITRead0 = Normal; 1 = Fault
CO165doc Bit165Jumper cap error (ODU)BITRead0 = Normal; 1 = Fault
CO166doc Bit166ODU memory chip errorBITRead0 = Normal; 1 = Fault
CO174doc Bit174Drive communication failureBITRead0 = Normal; 1 = Fault
CO176doc Bit176SAVE statusBITRead0 = Off; 1 = On
CO177doc Bit177Cooling-only flagBITRead0 = Heat pump (cool and heat); 1 = Cooling only
CO179doc Bit179System defrostingBITRead0 = No; 1 = Yes
CO182doc Bit182Low power consumption statusBITRead0 = Not ready; 1 = Ready
CO183doc Bit183AC input phase sequence protectionBITRead0 = Normal; 1 = Fault
CO184doc Bit184Drive DC bus undervoltage / voltage dropBITRead0 = Normal; 1 = Fault
CO185doc Bit185Drive DC bus overvoltageBITRead0 = Normal; 1 = Fault
CO186doc Bit186Drive AC input current protectionBITRead0 = Normal; 1 = Fault
CO187doc Bit187Drive IPM protectionBITRead0 = Normal; 1 = Fault
CO188doc Bit188Drive PFC protectionBITRead0 = Normal; 1 = Fault
CO189doc Bit189Compressor startup failureBITRead0 = Normal; 1 = Fault
CO190doc Bit190Compressor phase loss protectionBITRead0 = Normal; 1 = Fault
CO191doc Bit191Drive module resetBITRead0 = Normal; 1 = Fault
CO192doc Bit192Compressor over-current protectionBITRead0 = Normal; 1 = Fault
CO193doc Bit193Compressor power protectionBITRead0 = Normal; 1 = Fault
CO194doc Bit194Drive current detection circuit failureBITRead0 = Normal; 1 = Fault
CO195doc Bit195Compressor out-of-step protectionBITRead0 = Normal; 1 = Fault
CO196doc Bit196Compressor stallingBITRead0 = Normal; 1 = Fault
CO198doc Bit198Drive module high temperature protectionBITRead0 = Normal; 1 = Fault
CO199doc Bit199Drive module temperature sensor failureBITRead0 = Normal; 1 = Fault
CO205doc Bit205Drive under-chargeBITRead0 = Charged; 1 = Under charge
CO208doc Bit208Drive storage chip failureBITRead0 = Normal; 1 = Fault
CO210doc Bit210Drive charging circuit failureBITRead0 = Normal; 1 = Fault
CO211doc Bit211Drive AC input voltage abnormalBITRead0 = Normal; 1 = Fault
CO212doc Bit212Drive electric box temp sensor failureBITRead0 = Normal; 1 = Fault
CO213doc Bit213Drive AC input zero-cross protectionBITRead0 = Normal; 1 = Fault
CO214doc Bit214Temperature drift protectionBITRead0 = Normal; 1 = Fault
CO215doc Bit215Current sensor connection protectionBITRead0 = Normal; 1 = Fault
HR2doc Word 2Unit on/offUINT16Read/write85 = 0x55: off; 170 = 0xAA: on
HR4doc Word 4Ambient temperatureINT16× 0.1°CRead
HR5doc Word 5IDU address1-16 with a central controller, 1-255 in PC address mode.UINT16Read
HR17doc Word 17Set modeHeating is ignored on cooling-only units.UINT16Read/write1 = Cooling; 2 = Heating; 3 = Drying; 4 = Fan only; 5 = Auto
HR19doc Word 19Set fan speedUINT16Read/write0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Turbo
HR20doc Word 20Set temperature16-30 °C; reads 12 in low-temp drying and 8 in absence mode.UINT16°CRead/write
HR22doc Word 22Up/down swingUINT16Read/write0 = Off; 1 = Swing 1-5; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 7 = Swing 3-5; 8 = Swing 2-5; 9 = Swing 2-4; 10 = Swing 1-4; 11 = Swing 1-3
HR23doc Word 23Left/right swingUINT16Read/write0 = Off (default after power-on); 1 = Swing, same direction; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 12 = Positions 1-5; 13 = Swing, opposite direction
HR24doc Word 24Fresh air valve0-10; the manual lists 10 fresh-air modes but the meaning of 0 is cut short.UINT16Read/write
HR25doc Word 25Sleep modeIgnored in fan or auto mode.UINT16Read/write0 = No sleep; 1 = Sleep 1; 2 = Sleep 2; 3 = Sleep 3
HR34doc Word 34Clean function0 = no clean function; 10-39 = contamination grade.UINT16Read/write
HR35doc Word 35Energy-saving lower limit, cooling16-30 °C.UINT16°CRead/write
HR36doc Word 36Energy-saving upper limit, heating16-30 °C.UINT16°CRead/write
HR39doc Word 39Ambient temperature sensor selectionUINT16Read1 = Return-air sensor; 2 = Wired controller sensor; 3 = Return air for cool/dry/fan, wired controller for heat/auto
HR49doc Word 49Outdoor ambient temperature-100 to 155 °C.INT16°CRead
HR77doc Word 77DRED functionUINT16Read0 = No DRED; 1 = DRED1; 2 = DRED2; 3 = DRED3
HR82doc Word 82Return-air temperatureINT16× 0.1°CRead
HR83doc Word 83Light-board ambient temperatureINT16× 0.1°CRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)

What Modbus registers does the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) have?

This map lists 115 registers: 97 coils, 18 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Word and bit addresses start at 0 and go on the wire unchanged: 'Word 20' is holding register address 20 and 'Bit17' is coil address 17. The manual's read example (start address 00 01 for words 1-2) confirms the numbering.

What are the minimum Modbus registers to integrate the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)?

Start with HR 2 Unit on/off (Unit on/off (0xAA on, 0x55 off)); HR 4 Ambient temperature (Ambient temperature); HR 17 Set mode (Mode); HR 19 Set fan speed (Fan speed); HR 20 Set temperature (Setpoint); CO 151 Compressor status (Compressor running); CO 122 Comms failure with ODU (ODU communication failure).

How do I enable Modbus control of the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)?

The Modbus interface is built into the indoor unit controller. Select the address mode and set the unit address on the wired controller (see the unit's service manual).

Where is the official Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus documentation?

The source is User's manual UNI SPLIT Modbus, published free by Sinclair at https://www.sinclair-solutions.com/files/user-manual-en/accessories/sinclair-um-uni-split-modbus-protocol-en.pdf.

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: User's manual UNI SPLIT Modbus. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.