- UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
VRF / split AC gateway (built-in indoor-unit Modbus) · Modbus register map
Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus register map
Updated 17 November 2026
Sinclair's UNI SPLIT DC inverter indoor units have a Modbus RTU slave built into the indoor controller, so no separate gateway is needed; up to 255 units share one RS-485 line. Settings and analog values are 16-bit words (holding registers) and flags are coils. This map covers on/off, mode, fan, setpoint, swing, temperatures, remote locks and shields, feature flags, and the indoor, outdoor and inverter-drive fault bits.
This page lists 115 Modbus registers for the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Sinclair’s own free documentation (linked below) and checked against it.
- Manufacturer
- Sinclair
- Model
- UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
- Equipment type
- VRF / split AC gateway (built-in indoor-unit Modbus)
- Registers
- 115 (31 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- Sinclair UNI SPLIT, UNI SPLIT Modbus, All DC Inverter UNI SPLIT
- Source document
- User's manual UNI SPLIT Modbus
Integration notes: Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
Set the indoor unit to PC/Modbus address mode on the wired controller, then poll holding registers 0-83 with function 03 and coils 0-215 with function 01. Control by writing words 2, 17, 19 and 20 with function 16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | Unit on/off | UINT16 | Unit on/off (0xAA on, 0x55 off) | Read/write |
| HR 4 | Ambient temperature | INT16 | Ambient temperature | Read |
| HR 17 | Set mode | UINT16 | Mode | Read/write |
| HR 19 | Set fan speed | UINT16 | Fan speed | Read/write |
| HR 20 | Set temperature | UINT16 | Setpoint | Read/write |
| CO 151 | Compressor status | BIT | Compressor running | Read |
| CO 122 | Comms failure with ODU | BIT | ODU communication failure | Read |
Enable Modbus control & writes
The Modbus interface is built into the indoor unit controller. Select the address mode and set the unit address on the wired controller (see the unit's service manual).
Byte order & addressing
- Writes must use function 16 (registers) or 15 (coils); function 06/05 are not listed.
- On/off uses 0xAA (on) and 0x55 (off), not 1/0.
- The BMS and the unit's own controls act equally: the most recent command wins.
Network setup
- RS-485 at 9600 baud, 8 data bits, no parity, 1 stop bit.
- Up to 255 indoor units per RS-485 port; use another port for more.
- Use twisted pair and keep it at least 15 cm from power cables.
Watch out for
- Exception 04 means the Modbus module can't reach the air conditioner, including right after power-up.
- Heating commands are ignored on cooling-only units (check coil 177).
Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 8doc Bit8 | ODU present flag | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 9doc Bit9 | Master wired controller present flag | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 13doc Bit13 | Slave wired controller present flag | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 17doc Bit17 | Remote lock | BIT | Read/write | 0 = Not locked; 1 = Locked by remote monitoring | ||||
| CO | 18doc Bit18 | Remote temperature shield | BIT | Read/write | 0 = No shield; 1 = Shield | ||||
| CO | 19doc Bit19 | Remote mode shield | BIT | Read/write | 0 = No shield; 1 = Shield | ||||
| CO | 20doc Bit20 | Remote on/off shield | BIT | Read/write | 0 = No shield; 1 = Shield | ||||
| CO | 21doc Bit21 | Remote energy-saving shield | BIT | Read/write | 0 = No shield; 1 = Shield | ||||
| CO | 24doc Bit24 | Absence mode | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 25doc Bit25 | Healthy function | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 26doc Bit26 | I-Demand (comfort energy saving) | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 27doc Bit27 | Turbo | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 28doc Bit28 | Electric heating permission | BIT | Read/write | 0 = E-heating permitted; 1 = E-heating not permitted | ||||
| CO | 29doc Bit29 | X-fan | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 30doc Bit30 | Silent | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 31doc Bit31 | Low-temperature drying mode | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 32doc Bit32 | Energy saving in cooling active | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 33doc Bit33 | Energy saving in heating active | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 34doc Bit34 | Button lock (child lock) | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 35doc Bit35 | On/off memory | BIT | Read/write | 0 = Memorise; 1 = Do not memorise | ||||
| CO | 36doc Bit36 | Temperature unit flag | BIT | Read/write | 0 = °C; 1 = °F | ||||
| CO | 40doc Bit40 | Timer status | BIT | Read | 0 = No timer; 1 = Timer set | ||||
| CO | 46doc Bit46 | Gate control system fitted | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 47doc Bit47 | Presence sensor module fitted | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 49doc Bit49 | Timer on flag | BIT | Read | 0 = Not active; 1 = Active | ||||
| CO | 50doc Bit50 | Timer off flag | BIT | Read | 0 = Not active; 1 = Active | ||||
| CO | 51doc Bit51 | Indoor temperature source in current mode | BIT | Read | 0 = Return-air temperature; 1 = Wired controller temperature | ||||
| CO | 55doc Bit55 | Low standby power (1 W) mode | BIT | Read | 0 = Mode 1; 1 = Mode 2 | ||||
| CO | 65doc Bit65 | Wired controller temp sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 70doc Bit70 | Wired controller memory chip error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 72doc Bit72 | Cancel timer | BIT | Read/write | 0 = Do not cancel; 1 = Cancel | ||||
| CO | 74doc Bit74 | Up/down swing mode | BIT | Read/write | 0 = Mode 1: simple swing; 1 = Mode 2: fixed angle and small-area swing | ||||
| CO | 91doc Bit91 | Electric heating | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 92doc Bit92 | Water pump | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 93doc Bit93 | Fresh air valve switch | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 94doc Bit94 | Cold plasma generator | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 95doc Bit95 | Error output status | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 97doc Bit97 | Indoor evaporator temp sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 98doc Bit98 | Indoor return-air temp sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 99doc Bit99 | Light-board ambient temp sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 101doc Bit101 | Water overflow protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 102doc Bit102 | IDU memory chip error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 104doc Bit104 | Jumper cap error (IDU) | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 105doc Bit105 | Indoor fan error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 112doc Bit112 | Key card status | BIT | Read | 0 = Card out; 1 = Card in | ||||
| CO | 113doc Bit113 | Room occupied | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 114doc Bit114 | Static pressure type | BIT | Read | 0 = Low static; 1 = High static | ||||
| CO | 120doc Bit120 | Comms failure with master wired controller | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 121doc Bit121 | Comms failure with slave wired controller | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 122doc Bit122 | Comms failure with ODU | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 147doc Bit147 | Outdoor fan status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 150doc Bit150 | 4-way valve status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 151doc Bit151 | Compressor status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 152doc Bit152 | Discharge temperature protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 153doc Bit153 | Refrigerant shortage protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 154doc Bit154 | DC fan motor protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 155doc Bit155 | 4-way valve reversing error protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 156doc Bit156 | Over-power protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 157doc Bit157 | Overload protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 158doc Bit158 | Low pressure protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 159doc Bit159 | High pressure protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 160doc Bit160 | Evaporator anti-freeze protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 161doc Bit161 | Outdoor ambient temp sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 162doc Bit162 | Discharge temp sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 163doc Bit163 | Condenser temp sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 164doc Bit164 | Outdoor coil pipe temp sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 165doc Bit165 | Jumper cap error (ODU) | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 166doc Bit166 | ODU memory chip error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 174doc Bit174 | Drive communication failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 176doc Bit176 | SAVE status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 177doc Bit177 | Cooling-only flag | BIT | Read | 0 = Heat pump (cool and heat); 1 = Cooling only | ||||
| CO | 179doc Bit179 | System defrosting | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 182doc Bit182 | Low power consumption status | BIT | Read | 0 = Not ready; 1 = Ready | ||||
| CO | 183doc Bit183 | AC input phase sequence protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 184doc Bit184 | Drive DC bus undervoltage / voltage drop | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 185doc Bit185 | Drive DC bus overvoltage | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 186doc Bit186 | Drive AC input current protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 187doc Bit187 | Drive IPM protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 188doc Bit188 | Drive PFC protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 189doc Bit189 | Compressor startup failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 190doc Bit190 | Compressor phase loss protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 191doc Bit191 | Drive module reset | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 192doc Bit192 | Compressor over-current protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 193doc Bit193 | Compressor power protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 194doc Bit194 | Drive current detection circuit failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 195doc Bit195 | Compressor out-of-step protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 196doc Bit196 | Compressor stalling | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 198doc Bit198 | Drive module high temperature protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 199doc Bit199 | Drive module temperature sensor failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 205doc Bit205 | Drive under-charge | BIT | Read | 0 = Charged; 1 = Under charge | ||||
| CO | 208doc Bit208 | Drive storage chip failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 210doc Bit210 | Drive charging circuit failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 211doc Bit211 | Drive AC input voltage abnormal | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 212doc Bit212 | Drive electric box temp sensor failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 213doc Bit213 | Drive AC input zero-cross protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 214doc Bit214 | Temperature drift protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 215doc Bit215 | Current sensor connection protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| HR | 2doc Word 2 | Unit on/off | UINT16 | Read/write | 85 = 0x55: off; 170 = 0xAA: on | ||||
| HR | 4doc Word 4 | Ambient temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 5doc Word 5 | IDU address | 1-16 with a central controller, 1-255 in PC address mode. | UINT16 | Read | ||||
| HR | 17doc Word 17 | Set mode | Heating is ignored on cooling-only units. | UINT16 | Read/write | 1 = Cooling; 2 = Heating; 3 = Drying; 4 = Fan only; 5 = Auto | |||
| HR | 19doc Word 19 | Set fan speed | UINT16 | Read/write | 0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Turbo | ||||
| HR | 20doc Word 20 | Set temperature | 16-30 °C; reads 12 in low-temp drying and 8 in absence mode. | UINT16 | °C | Read/write | |||
| HR | 22doc Word 22 | Up/down swing | UINT16 | Read/write | 0 = Off; 1 = Swing 1-5; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 7 = Swing 3-5; 8 = Swing 2-5; 9 = Swing 2-4; 10 = Swing 1-4; 11 = Swing 1-3 | ||||
| HR | 23doc Word 23 | Left/right swing | UINT16 | Read/write | 0 = Off (default after power-on); 1 = Swing, same direction; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 12 = Positions 1-5; 13 = Swing, opposite direction | ||||
| HR | 24doc Word 24 | Fresh air valve | 0-10; the manual lists 10 fresh-air modes but the meaning of 0 is cut short. | UINT16 | Read/write | ||||
| HR | 25doc Word 25 | Sleep mode | Ignored in fan or auto mode. | UINT16 | Read/write | 0 = No sleep; 1 = Sleep 1; 2 = Sleep 2; 3 = Sleep 3 | |||
| HR | 34doc Word 34 | Clean function | 0 = no clean function; 10-39 = contamination grade. | UINT16 | Read/write | ||||
| HR | 35doc Word 35 | Energy-saving lower limit, cooling | 16-30 °C. | UINT16 | °C | Read/write | |||
| HR | 36doc Word 36 | Energy-saving upper limit, heating | 16-30 °C. | UINT16 | °C | Read/write | |||
| HR | 39doc Word 39 | Ambient temperature sensor selection | UINT16 | Read | 1 = Return-air sensor; 2 = Wired controller sensor; 3 = Return air for cool/dry/fan, wired controller for heat/auto | ||||
| HR | 49doc Word 49 | Outdoor ambient temperature | -100 to 155 °C. | INT16 | °C | Read | |||
| HR | 77doc Word 77 | DRED function | UINT16 | Read | 0 = No DRED; 1 = DRED1; 2 = DRED2; 3 = DRED3 | ||||
| HR | 82doc Word 82 | Return-air temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 83doc Word 83 | Light-board ambient temperature | INT16 | × 0.1 | °C | Read |
Notes on this map
- All values are 16-bit words or single bits; there are no 32-bit values.
- Function codes listed: 01 read coils, 03 read registers, 0F write coils and 10 write registers. Single-write codes 05 and 06 are not listed.
- Reserved words and bits are left out, as are a few bits printed with no name (for example Bit125 and Bits 201-204 and 207, which have no value meaning).
- When energy saving is active in cooling (or heating), a remote setpoint below the cooling lower limit (or above the heating upper limit) is ignored. The two energy-saving bits (32 and 33) must be set or cleared together.
- After power-up, the module answers with exception 04 until it has valid data from the unit; 04 later means the module has lost contact with the air conditioner.
- Several fault bits are printed with '1: yes 0: on', which reads as a typo for '0: no'; they are given here as 1 = fault.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
What Modbus registers does the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) have?
This map lists 115 registers: 97 coils, 18 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Word and bit addresses start at 0 and go on the wire unchanged: 'Word 20' is holding register address 20 and 'Bit17' is coil address 17. The manual's read example (start address 00 01 for words 1-2) confirms the numbering.
What are the minimum Modbus registers to integrate the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)?
Start with HR 2 Unit on/off (Unit on/off (0xAA on, 0x55 off)); HR 4 Ambient temperature (Ambient temperature); HR 17 Set mode (Mode); HR 19 Set fan speed (Fan speed); HR 20 Set temperature (Setpoint); CO 151 Compressor status (Compressor running); CO 122 Comms failure with ODU (ODU communication failure).
How do I enable Modbus control of the Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)?
The Modbus interface is built into the indoor unit controller. Select the address mode and set the unit address on the wired controller (see the unit's service manual).
Where is the official Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU) Modbus documentation?
The source is User's manual UNI SPLIT Modbus, published free by Sinclair at https://www.sinclair-solutions.com/files/user-manual-en/accessories/sinclair-um-uni-split-modbus-protocol-en.pdf.
Other ac & vrf gateways register maps
- Split AC unit (VRF / split AC gateway built in)
Aermec LPG series DC inverter air conditioners (built-in Modbus)
Aermec LPG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; ModBus Protocol LPG series 5385759_02 (EN 25.05).
Also known as: LPG - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus
All ac & vrf gateways Modbus register maps →
Source: User's manual UNI SPLIT Modbus. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.