VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway Modbus register map

Updated 17 November 2026

Short answer

Dual-protocol gateway (BACnet MS/TP or Modbus RTU, chosen by DIP switch) for Samsung air conditioners on the F3F4 remote-controller bus. In Modbus mode, holding registers cover on/off, mode, fan, vanes, setpoints including dual setpoint, thermistor input, window contact logic, filter status, WindFree/AirClean, errors and firmware version.

This page lists 47 Modbus registers for the Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway — 26 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Equipment type
VRF / split AC gateway
Registers
47 (26 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
2400 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus
Source document
IN485SAM001R000 User Manual · User Manual Version 1.0.0
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway

Integration in brief

Set SW1-5 ON for Modbus, choose baud on SW1-6..8 and address on SW2-1..6, reboot, then write 0-4 and poll 5, 10, 11, 44 and 66.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0On/OffUINT16On/offRead/write
HR 1Operation modeUINT16ModeRead/write
HR 4Temperature (user) setpointINT16SetpointRead/write
HR 5Indoor unit reference temperatureINT16Reference temperatureRead
HR 10Alarm statusUINT16Alarm flagRead
HR 11Error codeUINT16Error codeRead
HR 44Filter statusUINT16Filter signRead

Enable Modbus control & writes

Select Modbus RTU with SW1-5 ON (default is BACnet MS/TP), then reboot. If the gateway ignores commands, check register 7 is 0.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

47 of 47 shown
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0On/OffUINT16Read/write0 = Off; 1 = On
HR1Operation modeUINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2Fan speedUINT16Read/write0 = Auto; 1 = Fan speed 1; 2 = Fan speed 2; 3 = Fan speed 3; 4 = Fan speed 4
HR3Vane U/D positionCassette 360 uses register 139 instead.UINT16Read/write0 = Auto/Stop; 10 = Swing
HR4Temperature (user) setpointSetpoint requested by the BMS. SW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead/write-32768 = Initialisation value / no value (0x8000)
HR5Indoor unit reference temperatureSW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead-32768 = Initialisation value / no value (0x8000)
HR6Window contact protocol input0 = all closed; any bit set = its window contact is open.UINT16Read/write0 = All window contacts closed
HR7Control objects disablement1 = BMS commands ignored, remote controller only.UINT16Read/write0 = Objects enabled; 1 = Objects disabled
HR8Remote control disablement1 = remote controller ignored, BMS only.UINT16Read/write0 = RC enabled; 1 = RC disabled
HR9Operation timeAccumulated running hours.UINT16hRead/write
HR10Alarm statusUINT16Read0 = No error present; 1 = Error present
HR11Error codeSee the manual's error code list.UINT16Read
HR13Open window timeout0..30 minutes.UINT16minRead/write
HR14Baud rateUINT16Read1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps (printed 38500); 6 = 57600 bps; 7 = 76800 bps; 8 = 115200 bps
HR15Modbus slave address1..63, set on SW2.UINT16Read
HR21Maximum number of fan speedsUINT16Read
HR22Input sensor temperatureRoom temperature from a BMS thermistor; 0x8000 = none. SW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead/write-32768 = Initialisation value / no value (0x8000)
HR23AC real setpointSetpoint sent to the indoor unit. SW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead
HR24Current AC maximum setpointSW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead
HR25Current AC minimum setpointSW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead
HR26Vane L/R positionUINT16Read/write0 = Auto/Stop; 10 = Swing
HR31Window contact functional statusUINT16Read0 = Not active; 1 = Active (window open)
HR40Window contact On/Off disablementUINT16Read0 = Not disabling on/off; 1 = Disabling on/off now
HR43Filter resetUINT16Write1 = Reset
HR44Filter statusUINT16Read0 = Off; 1 = Lit
HR48Switch valueDIP-switch positions of SW1 and SW2 as bits.UINT16Read
HR66Return path temperatureSW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead-32768 = Initialisation value / no value (0x8000)
HR67Number of IU connectedIndoor units on the RC bus.UINT16Read
HR68IU # status reportedPosition in the sorted unit list of the unit being reported.UINT16Read/write
HR69IU address status reportedAddress of the unit whose status is reported.UINT16Read
HR81Error addressIndoor unit reporting the error.UINT16Read
HR86Filter signal addressIndoor unit reporting the filter sign.UINT16Read
HR94FW version MSBFirst two firmware numbers in hex (1.2.3.4 shows 1.2).UINT16Read
HR95FW version LSBLast two firmware numbers in hex.UINT16Read
HR99ResetUINT16Write1 = Reset
HR130Window contact stepUINT16Read0 = Contact weak (window closed); 1 = Contact strong (no action executed); 2 = Contact strong (action executed); 3 = Contact strong (action executed)
HR137WindFreeCool, fan and dry modes only.UINT16Read/write0 = Off; 1 = On
HR138AirCleanUINT16Read/write0 = Off; 1 = On
HR139360° air flow directionCassette 360 up/down air flow.UINT16Read/write0 = Spot; 1 = Mid; 2 = Wide; 3 = Swing; 4 = Other
HR140Dual setpointUINT16Read/write0 = Off; 1 = On
HR141Dual setpoint heat temperatureSW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead/write
HR142Dual setpoint cool temperatureSW2-7/8 default x1 °C (x10: 0.1; or °F).INT16°CRead/write
HR1000Window contact reload last valueUINT16Read/write0 = No; 1 = Yes
HR1001Window contact lock when openUINT16Read/write0 = No; 1 = Yes
HR1002Window timeout0..30 minutes.UINT16minRead/write
HR1150Machine mode2 = custom limits 1153-1156 apply.UINT16Read/write0 = Normal; 1 = NA; 2 = Limited setpoint
HR1220Remote lock kept after reset1 = register 8 keeps its value through a reset.UINT16Read/write0 = RC enabled after reset; 1 = Register 8 value kept after reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway

What Modbus registers does the Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway have?

This map lists 47 registers: 47 holding registers. 26 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give 'Modbus address (base 0)' and 'PLC address (base 1)'; the base-0 address is the wire address and is used for 'documented'.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway?

Start with HR 0 On/Off (On/off); HR 1 Operation mode (Mode); HR 4 Temperature (user) setpoint (Setpoint); HR 5 Indoor unit reference temperature (Reference temperature); HR 10 Alarm status (Alarm flag); HR 11 Error code (Error code); HR 44 Filter status (Filter sign).

How do I enable Modbus control of the Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway?

Select Modbus RTU with SW1-5 ON (default is BACnet MS/TP), then reboot. If the gateway ignores commands, check register 7 is 0.

Where is the official Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway Modbus documentation?

The source is IN485SAM001R000 User Manual (User Manual Version 1.0.0), published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in485sam001r000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: IN485SAM001R000 User Manual · User Manual Version 1.0.0. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.