Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus register map

Updated 17 November 2026

Short answer

Interface that plugs into the S21 connector of a Daikin split / room air conditioner and exposes it as a Modbus RTU slave when its address is 1 or higher. Holding registers set setpoint, fan, mode, louvre, on/off, forced thermo-off and local limits; input registers report fault state, fault code, return-air and coil temperatures.

This page lists 17 Modbus registers for the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Realtime Control Systems’s own free documentation (linked below) and checked against it.

Manufacturer
Realtime Control Systems
Model
RTD-RA Modbus interface for Daikin room air conditioners
Equipment type
VRF / split AC gateway
Registers
17 (12 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
RTD-RA, Daikin RTD-RA
Source document
RTD-RA Installation Instructions · 21070-1.07.04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners

Integration in brief

Set an address of 1..63 on SW1 so the unit becomes a Modbus slave, then write H0001-H0005 and poll I0121-I0131. H0010 decides whether the IR remote stays usable.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 5OnOffUINT16On/offRead/write
HR 3ModeUINT16ModeRead/write
HR 1SetpointUINT16SetpointRead/write
HR 2FanspeedUINT16Fan speedRead/write
IR 123Return Air TemperatureINT16Return air temperatureRead
IR 121Is FaultUINT16Fault flagRead
IR 122Fault CodeUINT16Fault codeRead

Enable Modbus control & writes

Modbus slave mode is active whenever the SW1 address is 1 or higher; address 0 selects stand-alone mode. Closing input S2 in slave mode selects clone mode, which disables Modbus control.

Communication loss & watchdog

Optional via SW1: with no holding-register write for 120 s the unit is switched on with its current settings and local control is unlocked or left as is, depending on the switch.

Byte order & addressing

Network setup

Watch out for

Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

17 of 17 shown
Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR121doc I0121Is FaultUINT16Read0 = No unit fault; 1 = Unit in fault
IR122doc I0122Fault CodeTwo ASCII characters, high byte first.UINT16Read0 = Waiting for data; 255 = No fault; 14384 = 80 - group fault, no units found
IR123doc I0123Return Air TemperatureINT16× 0.01°CRead
IR130doc I0130Thermo OnUINT16Read0 = Idle/Fan; 1 = Heating; 2 = Cooling
IR131doc I0131Coil Inlet TemperatureINT16× 0.01°CRead
HR1doc H0001SetpointWhole degrees; heat 10..30, cool 18..32 (model dependent).UINT16°CRead/write
HR2doc H0002FanspeedSome models have fewer than 5 speeds.UINT16Read/write0 = Auto; 1 = Fan 1; 2 = Fan 2; 3 = Fan 3; 4 = Fan 4; 5 = Fan 5
HR3doc H0003ModeUINT16Read/write0 = Auto; 1 = Heat; 2 = Fan; 3 = Cool; 4 = Dry
HR4doc H0004LouvreUINT16Read/write0 = Stop; 1 = Swing
HR5doc H0005OnOffUINT16Read/write0 = Off; 1 = On
HR10doc H0010Global UpdateUINT16Read/write0 = Last Touch (unlocked); 1 = Central (local control locked); 2 = Local (writes not sent); 3 = On Change (sent only on change)
HR20doc H0020Setpoint Min16..32; 0 = no limit.UINT16°CRead/write
HR21doc H0021Setpoint Max16..32; 0 = no limit.UINT16°CRead/write
HR22doc H0022Fanspeed InhibitSet bits block those speeds; 0 = no inhibit.BITMAP16Read/writebit 0 = Auto (1); bit 1 = Fan 1 (2); bit 2 = Fan 2 (4); bit 3 = Fan 3 (8); bit 4 = Fan 4 (16); bit 5 = Fan 5 (32)
HR23doc H0023Mode InhibitSet bits block those modes; 0 = no inhibit.BITMAP16Read/writebit 0 = Auto (1); bit 1 = Heat (2); bit 2 = Fan (4); bit 3 = Cool (8); bit 4 = Dry (16)
HR24doc H0024Louvre InhibitSet bits block those louvre settings; 0 = no inhibit.BITMAP16Read/writebit 0 = Stop (1); bit 1 = Swing (2)
HR37doc H0037Force Thermo OffHolds the compressor off while the unit stays on.UINT16Read/write0 = Thermo enabled; 1 = Thermo off

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners

What Modbus registers does the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners have?

This map lists 17 registers: 5 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register base 0: H0005 is holding register wire address 5 and I0123 is input register wire address 123.

What are the minimum Modbus registers to integrate the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners?

Start with HR 5 OnOff (On/off); HR 3 Mode (Mode); HR 1 Setpoint (Setpoint); HR 2 Fanspeed (Fan speed); IR 123 Return Air Temperature (Return air temperature); IR 121 Is Fault (Fault flag); IR 122 Fault Code (Fault code).

How do I enable Modbus control of the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners?

Modbus slave mode is active whenever the SW1 address is 1 or higher; address 0 selects stand-alone mode. Closing input S2 in slave mode selects clone mode, which disables Modbus control.

What happens when the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners loses Modbus communication?

Optional via SW1: with no holding-register write for 120 s the unit is switched on with its current settings and local control is unlocked or left as is, depending on the switch.

Where is the official Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus documentation?

The source is RTD-RA Installation Instructions (21070-1.07.04), published free by Realtime Control Systems at https://www.daikin.es/content/dam/MDM/TechnicalDrawings/Split/EN/RTD-RA%20Installation%20Instructions%2021070-1.07_EN.pdf.

More Realtime Control Systems Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: RTD-RA Installation Instructions · 21070-1.07.04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.