Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus register map
Updated 17 November 2026
Interface that plugs into the S21 connector of a Daikin split / room air conditioner and exposes it as a Modbus RTU slave when its address is 1 or higher. Holding registers set setpoint, fan, mode, louvre, on/off, forced thermo-off and local limits; input registers report fault state, fault code, return-air and coil temperatures.
This page lists 17 Modbus registers for the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Realtime Control Systems’s own free documentation (linked below) and checked against it.
- Manufacturer
- Realtime Control Systems
- Model
- RTD-RA Modbus interface for Daikin room air conditioners
- Equipment type
- VRF / split AC gateway
- Registers
- 17 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- RTD-RA, Daikin RTD-RA
- Source document
- RTD-RA Installation Instructions · 21070-1.07.04
Integration notes: Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners
Set an address of 1..63 on SW1 so the unit becomes a Modbus slave, then write H0001-H0005 and poll I0121-I0131. H0010 decides whether the IR remote stays usable.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 5 | OnOff | UINT16 | On/off | Read/write |
| HR 3 | Mode | UINT16 | Mode | Read/write |
| HR 1 | Setpoint | UINT16 | Setpoint | Read/write |
| HR 2 | Fanspeed | UINT16 | Fan speed | Read/write |
| IR 123 | Return Air Temperature | INT16 | Return air temperature | Read |
| IR 121 | Is Fault | UINT16 | Fault flag | Read |
| IR 122 | Fault Code | UINT16 | Fault code | Read |
Enable Modbus control & writes
Modbus slave mode is active whenever the SW1 address is 1 or higher; address 0 selects stand-alone mode. Closing input S2 in slave mode selects clone mode, which disables Modbus control.
Communication loss & watchdog
Optional via SW1: with no holding-register write for 120 s the unit is switched on with its current settings and local control is unlocked or left as is, depending on the switch.
Byte order & addressing
- Readback temperatures above 32767 are negative: subtract 65536 then divide by 100.
- Repeated identical writes in Last Touch mode override the user's remote; use On Change (3) for cyclic writers.
Network setup
- 9600 baud, no parity, 1 stop bit by default.
- Address on SW1 (0..63; 0 = stand-alone).
- RS485 3-wire: DB(+), DA(-), GND, daisy-chained.
Watch out for
- Supported setpoint range and number of fan speeds vary by indoor unit model.
Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 121doc I0121 | Is Fault | UINT16 | Read | 0 = No unit fault; 1 = Unit in fault | ||||
| IR | 122doc I0122 | Fault Code | Two ASCII characters, high byte first. | UINT16 | Read | 0 = Waiting for data; 255 = No fault; 14384 = 80 - group fault, no units found | |||
| IR | 123doc I0123 | Return Air Temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 130doc I0130 | Thermo On | UINT16 | Read | 0 = Idle/Fan; 1 = Heating; 2 = Cooling | ||||
| IR | 131doc I0131 | Coil Inlet Temperature | INT16 | × 0.01 | °C | Read | |||
| HR | 1doc H0001 | Setpoint | Whole degrees; heat 10..30, cool 18..32 (model dependent). | UINT16 | °C | Read/write | |||
| HR | 2doc H0002 | Fanspeed | Some models have fewer than 5 speeds. | UINT16 | Read/write | 0 = Auto; 1 = Fan 1; 2 = Fan 2; 3 = Fan 3; 4 = Fan 4; 5 = Fan 5 | |||
| HR | 3doc H0003 | Mode | UINT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Fan; 3 = Cool; 4 = Dry | ||||
| HR | 4doc H0004 | Louvre | UINT16 | Read/write | 0 = Stop; 1 = Swing | ||||
| HR | 5doc H0005 | OnOff | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 10doc H0010 | Global Update | UINT16 | Read/write | 0 = Last Touch (unlocked); 1 = Central (local control locked); 2 = Local (writes not sent); 3 = On Change (sent only on change) | ||||
| HR | 20doc H0020 | Setpoint Min | 16..32; 0 = no limit. | UINT16 | °C | Read/write | |||
| HR | 21doc H0021 | Setpoint Max | 16..32; 0 = no limit. | UINT16 | °C | Read/write | |||
| HR | 22doc H0022 | Fanspeed Inhibit | Set bits block those speeds; 0 = no inhibit. | BITMAP16 | Read/write | bit 0 = Auto (1); bit 1 = Fan 1 (2); bit 2 = Fan 2 (4); bit 3 = Fan 3 (8); bit 4 = Fan 4 (16); bit 5 = Fan 5 (32) | |||
| HR | 23doc H0023 | Mode Inhibit | Set bits block those modes; 0 = no inhibit. | BITMAP16 | Read/write | bit 0 = Auto (1); bit 1 = Heat (2); bit 2 = Fan (4); bit 3 = Cool (8); bit 4 = Dry (16) | |||
| HR | 24doc H0024 | Louvre Inhibit | Set bits block those louvre settings; 0 = no inhibit. | BITMAP16 | Read/write | bit 0 = Stop (1); bit 1 = Swing (2) | |||
| HR | 37doc H0037 | Force Thermo Off | Holds the compressor off while the unit stays on. | UINT16 | Read/write | 0 = Thermo enabled; 1 = Thermo off |
Notes on this map
- All registers are 16 bits. Readback temperatures are signed and x100; setpoint and limits are whole °C.
- Fault codes pack two ASCII characters (high byte, low byte). Daikin code table is published separately by Realtime Controls.
- Function codes 03, 04, 06 and 16 supported, 1..10 registers per request.
- With the SW1 address set to 0 the RTD-RA runs stand-alone (inputs S1/S2 control it) and is not a Modbus slave.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners
What Modbus registers does the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners have?
This map lists 17 registers: 5 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register base 0: H0005 is holding register wire address 5 and I0123 is input register wire address 123.
What are the minimum Modbus registers to integrate the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners?
Start with HR 5 OnOff (On/off); HR 3 Mode (Mode); HR 1 Setpoint (Setpoint); HR 2 Fanspeed (Fan speed); IR 123 Return Air Temperature (Return air temperature); IR 121 Is Fault (Fault flag); IR 122 Fault Code (Fault code).
How do I enable Modbus control of the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners?
Modbus slave mode is active whenever the SW1 address is 1 or higher; address 0 selects stand-alone mode. Closing input S2 in slave mode selects clone mode, which disables Modbus control.
What happens when the Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners loses Modbus communication?
Optional via SW1: with no holding-register write for 120 s the unit is switched on with its current settings and local control is unlocked or left as is, depending on the switch.
Where is the official Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners Modbus documentation?
The source is RTD-RA Installation Instructions (21070-1.07.04), published free by Realtime Control Systems at https://www.daikin.es/content/dam/MDM/TechnicalDrawings/Split/EN/RTD-RA%20Installation%20Instructions%2021070-1.07_EN.pdf.
More Realtime Control Systems Modbus register maps
- Heat pump Modbus interface
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
RTD-LT/CA on the P1/P2 bus of Daikin Altherma Split LT CA hydroboxes (heating only and heating/cooling), with an EKRUCAL1 as main controller; all modes except Sequencer. Instructions 22570-2.09.12.
Also known as: RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA - VRF / split AC gateway
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
RTD-NET on the Daikin P1/P2 bus (VRV, Sky Air, VAM/VKM), up to 16 indoor units as one group; RTD-10 with the same firmware uses the same layout.
Also known as: RTD-NET, RTD-10, Daikin RTD-NET - Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W
Other ac & vrf gateways register maps
- Heat pump (integral ventilation unit, via ISG Modbus TCP gateway)
Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP
Stiebel Eltron LWZ / LWA integral ventilation and heat pump units reached through an ISG web or ISG plus with the Modbus TCP/IP software extension.
Also known as: LWZ 303 Integral, LWZ 403 SOL, LWA 403, LWZ 304 Trend, LWZ 404 Trend, LWZ 304 SOL, LWZ 404 SOL, LWZ 504, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus, LWZ 5 S Trend, LWZ 8 S Trend, LWZ 5 S Smart, LWZ 5 CS Premium, LWZ 8 CS Premium - Gateway for Bender BMS-bus devices (insulation monitors, RCMs, changeover modules) - sensor/alarm data
Bender COM461MT BMS-to-Modbus/TCP gateway
COM461MT software D402 V1.0x; the map is the gateway's process image, shown here for BMS device address 1 plus the built-in test record.
Also known as: COM461MT, B95061021 - Split AC unit (VRF / split AC gateway built in)
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.
Also known as: Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF
All ac & vrf gateways Modbus register maps →
Source: RTD-RA Installation Instructions · 21070-1.07.04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.