Gateway for Bender BMS-bus devices (insulation monitors, RCMs, changeover modules) - sensor/alarm data · Modbus register map

Bender COM461MT BMS-to-Modbus/TCP gateway Modbus register map

Updated 17 November 2026

Short answer

The COM461MT sits on a Bender internal BMS bus (RS-485) and republishes the data of up to 150 BMS devices (ISOMETER, RCMS, EDS, MK800, PRC changeover modules) as Modbus/TCP input registers. Each BMS address gets its own 256-register block: device name, timestamp, alarm flags, then 4 registers per channel (float value, alarm/unit byte pair, text code). This map shows the block for BMS address 1 (channels 1-12), the test record at address 0 and the command interface.

This page lists 50 Modbus registers for the Bender COM461MT BMS-to-Modbus/TCP gateway — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Bender’s own free documentation (linked below) and checked against it.

Manufacturer
Bender
Model
COM461MT BMS-to-Modbus/TCP gateway
Equipment type
Gateway for Bender BMS-bus devices (insulation monitors, RCMs, changeover modules) - sensor/alarm data
Registers
50 (4 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Firmware
D402 V1.0x
Also known as
COM461MT, B95061021
Source document
COM461MT Operating Manual - BMS Ethernet gateway for the connection of Bender devices with BMS support to Ethernet (TCP/IP) using the Modbus/TCP protocol · COM461MT_D00011_01_M_XXEN/08.2020 · rev. 2020-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Bender COM461MT BMS-to-Modbus/TCP gateway

Integration in brief

Read input registers (FC4) at BMS address x 0x100: register +0x0E tells you if the device has an alarm or has dropped off the bus, and each channel's float value sits at +0x10 + 4 x (channel-1). First read the test record at 0x0010/0x0014 (230.0 and 12.34) to prove your float word order.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 20Reference: channel 2 valueFLOAT32 ABCDTest value 12.34 - check word order onceRead
IR 270Device 1: common alarm / device lostBITMAP16Common alarm and device-lost flagsRead
IR 272Device 1: channel 1 valueFLOAT32 ABCDChannel 1 measured valueRead
IR 274Device 1: channel 1 AT&T / R&UUINT16Channel 1 alarm type and unitRead
IR 275Device 1: channel 1 description codeUINT16Channel 1 text codeRead
IR 64516Command statusUINT16Status of the last commandRead

Enable Modbus control & writes

Set IP address, subnet mask, BMS address and 'Modbus control' (on/off) on the gateway's web page (factory IP 192.168.0.254, mask 255.255.0.0). Commands only work while Modbus control is enabled.

Byte order & addressing

Network setup

Watch out for

Bender COM461MT BMS-to-Modbus/TCP gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Bender COM461MT BMS-to-Modbus/TCP gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 0x0000Reference: device type textTest record at virtual BMS address 0; reads the text TEST.STRING[20]Read
IR14doc 0x000EReference: common alarm / device lostTest record; common alarm bit is set.BITMAP16Readbit 0 = Device lost (LSB of low byte); bit 8 = Common alarm (LSB of high byte)
IR16doc 0x0010Reference: channel 1 valueTest value 230.0 (undervoltage). Use it to check your float word order.FLOAT32ABCDVRead
IR20doc 0x0014Reference: channel 2 valueTest value 12.34 (overcurrent); raw words 0x4145 0x70A4.FLOAT32ABCDARead
IR256doc 0x0100Device 1: device nameDevice type text learned by the gateway's BMS bus scan.STRING[20]Read
IR266doc 0x010ADevice 1: timestamp year / monthHigh byte = year (YY), low byte = month.UINT16Read
IR267doc 0x010BDevice 1: timestamp day / hourHigh byte = day, low byte = hour.UINT16Read
IR268doc 0x010CDevice 1: timestamp minute / secondHigh byte = minute, low byte = second.UINT16Read
IR270doc 0x010EDevice 1: common alarm / device lostAlarm summary and communication-loss flag for this BMS device.BITMAP16Readbit 0 = Device lost / no communication (LSB of low byte); bit 8 = Common alarm (LSB of high byte)
IR272doc 0x0110Device 1: channel 1 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR274doc 0x0112Device 1: channel 1 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR275doc 0x0113Device 1: channel 1 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR276doc 0x0114Device 1: channel 2 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR278doc 0x0116Device 1: channel 2 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR279doc 0x0117Device 1: channel 2 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR280doc 0x0118Device 1: channel 3 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR282doc 0x011ADevice 1: channel 3 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR283doc 0x011BDevice 1: channel 3 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR284doc 0x011CDevice 1: channel 4 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR286doc 0x011EDevice 1: channel 4 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR287doc 0x011FDevice 1: channel 4 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR288doc 0x0120Device 1: channel 5 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR290doc 0x0122Device 1: channel 5 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR291doc 0x0123Device 1: channel 5 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR292doc 0x0124Device 1: channel 6 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR294doc 0x0126Device 1: channel 6 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR295doc 0x0127Device 1: channel 6 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR296doc 0x0128Device 1: channel 7 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR298doc 0x012ADevice 1: channel 7 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR299doc 0x012BDevice 1: channel 7 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR300doc 0x012CDevice 1: channel 8 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR302doc 0x012EDevice 1: channel 8 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR303doc 0x012FDevice 1: channel 8 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR304doc 0x0130Device 1: channel 9 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR306doc 0x0132Device 1: channel 9 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR307doc 0x0133Device 1: channel 9 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR308doc 0x0134Device 1: channel 10 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR310doc 0x0136Device 1: channel 10 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR311doc 0x0137Device 1: channel 10 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR312doc 0x0138Device 1: channel 11 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR314doc 0x013ADevice 1: channel 11 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR315doc 0x013BDevice 1: channel 11 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR316doc 0x013CDevice 1: channel 12 valueIEEE 754 float; unit given by the R&U byte of the next-but-one word.FLOAT32ABCDRead
IR318doc 0x013EDevice 1: channel 12 AT&T / R&UHigh byte = alarm/test type, low byte = range and unit code.UINT16Read
IR319doc 0x013FDevice 1: channel 12 description codeBender text code for the channel, e.g. 71 = insulation fault, 76 = voltage.UINT16Read
IR64516doc 0xFC04Command statusResult of the last command, read with FC4.UINT16Read0 = Busy; 1 = Error; 2 = Ready (done)
HR64512doc 0xFC00Command: external BMS bus addressEnter 1 when there is no external BMS bus.UINT16Write
HR64513doc 0xFC01Command: internal BMS bus addressTarget device 1-150, or 0 for broadcast commands.UINT16Write
HR64514doc 0xFC02Command: BMS channelChannel 1-12 for relay commands, otherwise 0.UINT16Write
HR64515doc 0xFC03Command: command codeWriting all four words with FC16 sends the command.UINT16Write1 = Test ISOMETER; 2 = Test changeover device PRC; 3 = Start automatic changeover test 1->2, end after T(test); 4 = Start test generator without changeover; 5 = Switch over to line 1; 6 = Switch over to line 2; 7 = Reset alarm (broadcast); 8 = Reset alarm EDS (broadcast); 9 = Buzzer off for alarm address; 10 = Switch on relay/switch; 11 = Switch off relay/switch

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Bender COM461MT BMS-to-Modbus/TCP gateway

What Modbus registers does the Bender COM461MT BMS-to-Modbus/TCP gateway have?

This map lists 50 registers: 46 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Bender COM461MT BMS-to-Modbus/TCP gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and go on the wire as-is: the manual's example request for BMS device 1 puts 0x0100 in the start-address field. Block start = BMS address x 0x100; channel n of that device starts at block + 0x10 + 4 x (n-1). Bender notes that some clients need 1 added (process image then starts at 0x0101).

What byte order does the Bender COM461MT BMS-to-Modbus/TCP gateway use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Bender COM461MT BMS-to-Modbus/TCP gateway?

Start with IR 20 Reference: channel 2 value (Test value 12.34 - check word order once); IR 270 Device 1: common alarm / device lost (Common alarm and device-lost flags); IR 272 Device 1: channel 1 value (Channel 1 measured value); IR 274 Device 1: channel 1 AT&T / R&U (Channel 1 alarm type and unit); IR 275 Device 1: channel 1 description code (Channel 1 text code); IR 64516 Command status (Status of the last command).

How do I enable Modbus control of the Bender COM461MT BMS-to-Modbus/TCP gateway?

Set IP address, subnet mask, BMS address and 'Modbus control' (on/off) on the gateway's web page (factory IP 192.168.0.254, mask 255.255.0.0). Commands only work while Modbus control is enabled.

Where is the official Bender COM461MT BMS-to-Modbus/TCP gateway Modbus documentation?

The source is COM461MT Operating Manual - BMS Ethernet gateway for the connection of Bender devices with BMS support to Ethernet (TCP/IP) using the Modbus/TCP protocol (COM461MT_D00011_01_M_XXEN/08.2020), revision 2020-08, published free by Bender at https://www.bender.de/fileadmin/content/Products/m/e/COM461MT_D00011_M_XXEN.pdf.

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: COM461MT Operating Manual - BMS Ethernet gateway for the connection of Bender devices with BMS support to Ethernet (TCP/IP) using the Modbus/TCP protocol · COM461MT_D00011_01_M_XXEN/08.2020 · rev. 2020-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.