Heat pump (integral ventilation unit, via ISG Modbus TCP gateway) · Modbus register map

Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus register map

Updated 17 November 2026

Short answer

Stiebel Eltron's LWZ integral units combine ventilation with heat recovery, an exhaust-air heat pump and DHW. Over Modbus they are reached through the Internet Service Gateway (ISG) with the Modbus TCP/IP extension, which serves single 16-bit registers with fixed scaling per data type. The map covers system values (input registers 1-33), operating mode, heating/DHW/cooling setpoints and fan stages (holding 1001-1027), status flags (2001-2005), heat, energy and runtime counters (3001-3032) and the shared SG Ready registers.

This page lists 99 Modbus registers for the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP — 30 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Stiebel Eltron’s own free documentation (linked below) and checked against it.

Manufacturer
Stiebel Eltron
Model
Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP
Equipment type
Heat pump (integral ventilation unit, via ISG Modbus TCP gateway)
Registers
99 (30 writable)
Transport
Modbus TCP
Default unit ID
1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
LWZ 303 Integral, LWZ 403 SOL, LWA 403, LWZ 304 Trend, LWZ 404 Trend, LWZ 304 SOL, LWZ 404 SOL, LWZ 504, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus, LWZ 5 S Trend, LWZ 8 S Trend, LWZ 5 S Smart, LWZ 5 CS Premium, LWZ 8 CS Premium
Source document
Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP · A 321798-44755-9770 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP

Integration in brief

Poll the ISG on TCP port 502, unit ID 1. Read input registers (FC 04) for temperatures, fan speeds, status flags 2001 and fault status 2002; write holding registers (FC 06/16) for operating mode 1001, room/DHW setpoints and the ventilation stages 1018-1021. Subtract 1 from every printed register number.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 6Outside temperatureINT16Outside temperature (offset check)Read
IR 15Actual DHW temperatureINT16Actual DHW temperatureRead
IR 0Actual room T HC1INT16Actual room temperature HC1Read
IR 2000Operating statusBITMAP16Operating status flagsRead
IR 2001Fault statusUINT16Fault statusRead
HR 1000Operating modeUINT16Operating modeRead/write
HR 1001Room temperature day HC1INT16Day room setpoint HC1Read/write
HR 1017Day stageUINT16Ventilation day stageRead/write

Enable Modbus control & writes

The ISG web or ISG plus needs the Modbus TCP/IP software extension and, for the ISG web, the Basic service package. With an integral ventilation unit connected, check for it in SERVICEWELT under DIAGNOSIS > BUS SUBSCRIBER > ISG; if Modbus TCP/IP is not listed, update the ISG firmware or contact Stiebel Eltron service.

Byte order & addressing

Network setup

Watch out for

Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

99 of 99 shown
Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 1Actual room T HC1Room temperature, heating circuit 1 (remote control value).INT16× 0.1°CRead
IR1doc 2Set room temperature HC1Room setpoint, heating circuit 1.INT16× 0.1°CRead
IR2doc 3Relative humidity HC1Room humidity, heating circuit 1 (remote control value).INT16× 0.1%Read
IR3doc 4Actual room T HC2Room temperature, heating circuit 2 (remote control value).INT16× 0.1°CRead
IR4doc 5Set room temperature HC2Room setpoint, heating circuit 2.INT16× 0.1°CRead
IR5doc 6Relative humidity HC2Room humidity, heating circuit 2 (remote control value).INT16× 0.1%Read
IR6doc 7Outside temperatureOutdoor air temperature.INT16× 0.1°CRead
IR7doc 8Actual value HC1Heating circuit 1 actual temperature.INT16× 0.1°CRead
IR8doc 9Set value HC1Heating circuit 1 setpoint.INT16× 0.1°CRead
IR9doc 10Actual value HC2Heating circuit 2 actual temperature.INT16× 0.1°CRead
IR10doc 11Set value HC2Heating circuit 2 setpoint.INT16× 0.1°CRead
IR11doc 12Flow temperatureHeating flow temperature.INT16× 0.1°CRead
IR12doc 13Return temperatureHeating return temperature.INT16× 0.1°CRead
IR13doc 14Pressure heating circuitHeating circuit pressure; LWZ 304/404/504/Trend only.INT16× 0.1barRead
IR14doc 15Flow rateHeating water flow rate; LWZ 304/404/504/Trend only.INT16× 0.1l/minRead
IR15doc 16Actual DHW temperatureHot water cylinder temperature.INT16× 0.1°CRead
IR16doc 17DHW set temperatureHot water setpoint.INT16× 0.1°CRead
IR17doc 18Ventilation air actual fan speedSupply (ventilation) air fan speed.UINT16HzRead
IR18doc 19Ventilation air set flow rateSupply air flow setpoint.UINT16m³/hRead
IR19doc 20Extract air actual fan speedExtract air fan speed.UINT16HzRead
IR20doc 21Extract air set flow rateExtract air flow setpoint.UINT16m³/hRead
IR21doc 22Extract air humidityExtract air relative humidity; LWZ 304/404/504/Trend only.UINT16%Read
IR24doc 25Dew point temp. HC1Dew point, heating circuit 1; units with cooling only.INT16× 0.1°CRead
IR25doc 26Dew point temp. HC2Dew point, heating circuit 2; units with cooling only.INT16× 0.1°CRead
IR26doc 27Collector temperatureSolar collector temperature; units with solar only.INT16× 0.1°CRead
IR27doc 28Hot gas temperatureCompressor discharge temperature.INT16× 0.1°CRead
IR28doc 29High pressureRefrigerant high pressure.INT16× 0.01barRead
IR29doc 30Low pressureRefrigerant low pressure.INT16× 0.01barRead
IR30doc 31Compressor startsNumber of compressor starts.UINT16Read
IR31doc 32Compressor speedCompressor speed; LWZ 504 only.INT16× 0.1HzRead
IR32doc 33Mixed water amountAvailable mixed hot water volume; LWZ 504 only.UINT16lRead
IR2000doc 2001Operating statusPacked status flags of the unit.BITMAP16Readbit 0 = Switching program enabled; bit 1 = Compressor; bit 2 = Heating; bit 3 = Cooling; bit 4 = DHW; bit 5 = Electric reheating; bit 6 = Service; bit 7 = Power-off (utility block); bit 8 = Filter; bit 9 = Ventilation; bit 10 = Heating circuit pump; bit 11 = Evaporator defrost; bit 12 = Filter extract air; bit 13 = Filter ventilation air; bit 14 = Heat-up program
IR2001doc 2002Fault status1 = system fault; acknowledge only via SERVICEWELT.UINT16Read0 = No fault; 1 = Fault
IR2003doc 2004Defrost initiated1 = defrost signal active.UINT16Read0 = Off; 1 = Initiated
IR2004doc 2005Operating status-2Further packed status flags.BITMAP16Readbit 0 = Summer mode active; bit 1 = Oven/fireplace mode active
IR3000doc 3001Heat meter htg dayHeat delivered for heating today.UINT16kWhRead
IR3001doc 3002Heat meter htg total kWhTotal heat for heating, kWh part (0-999).UINT16kWhRead
IR3002doc 3003Heat meter htg total MWhTotal heat for heating, MWh part.UINT16MWhRead
IR3003doc 3004Heat meter DHW dayHeat delivered for DHW today.UINT16kWhRead
IR3004doc 3005Heat meter DHW total kWhTotal heat for DHW, kWh part.UINT16kWhRead
IR3005doc 3006Heat meter DHW total MWhTotal heat for DHW, MWh part.UINT16MWhRead
IR3006doc 3007Heat M boost htg total kWhHeat from the electric booster for heating, kWh part.UINT16kWhRead
IR3007doc 3008Heat M boost htg total MWhHeat from the electric booster for heating, MWh part.UINT16MWhRead
IR3008doc 3009Heat M boost DHW total kWhHeat from the electric booster for DHW, kWh part.UINT16kWhRead
IR3009doc 3010Heat M boost DHW total MWhHeat from the electric booster for DHW, MWh part.UINT16MWhRead
IR3010doc 3011Heat M recovery dayHeat recovered by the heat exchanger today.UINT16kWhRead
IR3011doc 3012Heat M recovery total kWhTotal recovered heat, kWh part.UINT16kWhRead
IR3012doc 3013Heat M recovery total MWhTotal recovered heat, MWh part.UINT16MWhRead
IR3013doc 3014HM solar htg daySolar heat for heating today; solar units only.UINT16kWhRead
IR3014doc 3015HM solar htg total kWhSolar heat for heating, kWh part; solar units only.UINT16kWhRead
IR3015doc 3016HM solar htg total MWhSolar heat for heating, MWh part; solar units only.UINT16MWhRead
IR3016doc 3017HM solar DHW daySolar heat for DHW today; solar units only.UINT16kWhRead
IR3017doc 3018HM solar DHW total kWhSolar heat for DHW, kWh part; solar units only.UINT16kWhRead
IR3018doc 3019HM solar DHW total MWhSolar heat for DHW, MWh part; solar units only.UINT16MWhRead
IR3019doc 3020HM cooling total kWhCooling energy, kWh part; units with cooling only.UINT16kWhRead
IR3020doc 3021HM cooling total MWhCooling energy, MWh part; units with cooling only.UINT16MWhRead
IR3021doc 3022Pwr con htg dayElectricity used for heating today.UINT16kWhRead
IR3022doc 3023Pwr con htg total kWhElectricity used for heating, kWh part.UINT16kWhRead
IR3023doc 3024Pwr con htg total MWhElectricity used for heating, MWh part.UINT16MWhRead
IR3024doc 3025Pwr con DHW dayElectricity used for DHW today.UINT16kWhRead
IR3025doc 3026Pwr con DHW total kWhElectricity used for DHW, kWh part.UINT16kWhRead
IR3026doc 3027Pwr con DHW total MWhElectricity used for DHW, MWh part.UINT16MWhRead
IR3027doc 3028Compressor heating hoursCompressor operating hours in heating.UINT16hRead
IR3028doc 3029Compressor cooling hoursCompressor operating hours in cooling; units with cooling only.UINT16hRead
IR3029doc 3030Compressor DHW hoursCompressor operating hours in DHW mode.UINT16hRead
IR3030doc 3031Elec booster heating hoursElectric booster operating hours for heating.UINT16hRead
IR3031doc 3032Elec booster DHW hoursElectric booster operating hours for DHW.UINT16hRead
IR5000doc 5001SG Ready operating stateResulting SG Ready state 1-4.UINT16Read1 = State 1: heating must not start, frost protection only; 2 = State 2: normal automatic/programmed operation; 3 = State 3: accelerated mode with raised heating/DHW setpoints; 4 = State 4: immediate switch to maximum heating/DHW setpoints
IR5001doc 5002Controller identificationType code of the connected controller.UINT16Read103 = LWZ 303/403 Integral/SOL, LWA 403, LWZ 304/404 Trend/FLEX, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus/Trend/Smart, LWZ 8 S Trend; 104 = LWZ 304/404 SOL, LWZ 504, LWZ 5/8 CS Premium, VCR-I 8 CS Premium CN; 390 = WPM 3; 391 = WPM 3i; 449 = WPMsystem
HR1000doc 1001Operating modeSelects the unit operating mode.UINT16Read/write0 = Emergency operation; 1 = Standby; 3 = Day mode; 4 = Setback mode; 5 = DHW; 11 = Automatic; 14 = Manual mode
HR1001doc 1002Room temperature day HC1Day (comfort) room heating setpoint, heating circuit 1.INT16× 0.1°CRead/write
HR1002doc 1003Room temp. night HC1Night (setback) room heating setpoint, heating circuit 1.INT16× 0.1°CRead/write
HR1003doc 1004Manual set HC1Heating circuit 1 setpoint in manual mode.INT16× 0.1°CRead/write
HR1004doc 1005Room temperature day HC2Day room heating setpoint, heating circuit 2.INT16× 0.1°CRead/write
HR1005doc 1006Room temp. night HC2Night room heating setpoint, heating circuit 2.INT16× 0.1°CRead/write
HR1006doc 1007Manual set HC2Heating circuit 2 setpoint in manual mode.INT16× 0.1°CRead/write
HR1007doc 1008Gradient HC1Heating curve slope, heating circuit 1.INT16× 0.01Read/write
HR1008doc 1009Low end HC1Heating curve base point, heating circuit 1.INT16× 0.1°CRead/write
HR1009doc 1010Gradient HC2Heating curve slope, heating circuit 2.INT16× 0.01Read/write
HR1010doc 1011Low end HC2Heating curve base point, heating circuit 2.INT16× 0.1°CRead/write
HR1011doc 1012DHW set dayDay hot water setpoint.INT16× 0.1°CRead/write
HR1012doc 1013DHW set nightNight hot water setpoint.INT16× 0.1°CRead/write
HR1013doc 1014DHW set manualHot water setpoint in manual mode.INT16× 0.1°CRead/write
HR1014doc 1015MWM set dayMixed water volume setpoint, day; LWZ 504 only.UINT16lRead/write
HR1015doc 1016MWM set nightMixed water volume setpoint, night; LWZ 504 only.UINT16lRead/write
HR1016doc 1017MWM set manualMixed water volume setpoint, manual mode; LWZ 504 only.UINT16lRead/write
HR1017doc 1018Day stageVentilation fan stage in day mode (0-3).UINT16Read/write
HR1018doc 1019Night stageVentilation fan stage in night mode (0-3).UINT16Read/write
HR1019doc 1020Party stageVentilation fan stage in party mode (0-3).UINT16Read/write
HR1020doc 1021Manual stageVentilation fan stage in manual mode (0-3).UINT16Read/write
HR1021doc 1022Room temperature day HC1 coolingDay room cooling setpoint, HC 1; units with cooling only.INT16× 0.1°CRead/write
HR1022doc 1023Room temp. night HC1 coolingNight room cooling setpoint, HC 1; units with cooling only.INT16× 0.1°CRead/write
HR1023doc 1024Room temperature day HC2 coolingDay room cooling setpoint, HC 2; units with cooling only.INT16× 0.1°CRead/write
HR1024doc 1025Room temp. night HC2 coolingNight room cooling setpoint, HC 2; units with cooling only.INT16× 0.1°CRead/write
HR1025doc 1026ResetReset command; LWZ 504 only.UINT16Read/write0 = Off; 1 = On
HR1026doc 1027Restart ISGISG restart command; codes as published.UINT16Read/write0 = Off; 1 = Reset; 2 = Menu
HR4000doc 4001Switch SG Ready on and offEnables or disables SG Ready. Language tables disagree on which code means on; check on site.UINT16Read/write
HR4001doc 4002SG Ready input 1Virtual SG Ready contact written by the BMS.UINT16Read/write0 = Switched off; 1 = Switched on
HR4002doc 4003SG Ready input 2Virtual SG Ready contact written by the BMS.UINT16Read/write0 = Switched off; 1 = Switched on

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP

What Modbus registers does the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP have?

This map lists 99 registers: 69 input registers, 30 holding registers. 30 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document states that ISG addressing is 1-based (its example: register 30501 is reached as address 501 with function code 04), so subtract one from the printed register number: outside temperature, printed 7, is requested at input register address 6. The document also warns that, depending on the configuration, an offset of 1 may have to be allowed for; confirm with outside temperature against the unit display.

What are the minimum Modbus registers to integrate the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP?

Start with IR 6 Outside temperature (Outside temperature (offset check)); IR 15 Actual DHW temperature (Actual DHW temperature); IR 0 Actual room T HC1 (Actual room temperature HC1); IR 2000 Operating status (Operating status flags); IR 2001 Fault status (Fault status); HR 1000 Operating mode (Operating mode); HR 1001 Room temperature day HC1 (Day room setpoint HC1); HR 1017 Day stage (Ventilation day stage).

How do I enable Modbus control of the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP?

The ISG web or ISG plus needs the Modbus TCP/IP software extension and, for the ISG web, the Basic service package. With an integral ventilation unit connected, check for it in SERVICEWELT under DIAGNOSIS > BUS SUBSCRIBER > ISG; if Modbus TCP/IP is not listed, update the ISG firmware or contact Stiebel Eltron service.

Where is the official Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus documentation?

The source is Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP (A 321798-44755-9770). Stiebel Eltron doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.heizungsdiscount24.de/pdf/Stiebel-Eltron-Internet-Service-Gateway-ISG-Connect-Software-Dokumentation.pdf. It may be an older revision, so check it against the live unit.

More Stiebel Eltron Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP · A 321798-44755-9770 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.