Heat pump (integral ventilation unit, via ISG Modbus TCP gateway) · Modbus register map
Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus register map
Updated 17 November 2026
Stiebel Eltron's LWZ integral units combine ventilation with heat recovery, an exhaust-air heat pump and DHW. Over Modbus they are reached through the Internet Service Gateway (ISG) with the Modbus TCP/IP extension, which serves single 16-bit registers with fixed scaling per data type. The map covers system values (input registers 1-33), operating mode, heating/DHW/cooling setpoints and fan stages (holding 1001-1027), status flags (2001-2005), heat, energy and runtime counters (3001-3032) and the shared SG Ready registers.
This page lists 99 Modbus registers for the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP — 30 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Stiebel Eltron’s own free documentation (linked below) and checked against it.
- Manufacturer
- Stiebel Eltron
- Model
- Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP
- Registers
- 99 (30 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- LWZ 303 Integral, LWZ 403 SOL, LWA 403, LWZ 304 Trend, LWZ 404 Trend, LWZ 304 SOL, LWZ 404 SOL, LWZ 504, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus, LWZ 5 S Trend, LWZ 8 S Trend, LWZ 5 S Smart, LWZ 5 CS Premium, LWZ 8 CS Premium
Integration notes: Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP
Poll the ISG on TCP port 502, unit ID 1. Read input registers (FC 04) for temperatures, fan speeds, status flags 2001 and fault status 2002; write holding registers (FC 06/16) for operating mode 1001, room/DHW setpoints and the ventilation stages 1018-1021. Subtract 1 from every printed register number.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 6 | Outside temperature | INT16 | Outside temperature (offset check) | Read |
| IR 15 | Actual DHW temperature | INT16 | Actual DHW temperature | Read |
| IR 0 | Actual room T HC1 | INT16 | Actual room temperature HC1 | Read |
| IR 2000 | Operating status | BITMAP16 | Operating status flags | Read |
| IR 2001 | Fault status | UINT16 | Fault status | Read |
| HR 1000 | Operating mode | UINT16 | Operating mode | Read/write |
| HR 1001 | Room temperature day HC1 | INT16 | Day room setpoint HC1 | Read/write |
| HR 1017 | Day stage | UINT16 | Ventilation day stage | Read/write |
Enable Modbus control & writes
The ISG web or ISG plus needs the Modbus TCP/IP software extension and, for the ISG web, the Basic service package. With an integral ventilation unit connected, check for it in SERVICEWELT under DIAGNOSIS > BUS SUBSCRIBER > ISG; if Modbus TCP/IP is not listed, update the ISG firmware or contact Stiebel Eltron service.
Byte order & addressing
- All points are 16-bit; totals use paired kWh/MWh registers.
- Operating mode codes are not contiguous: 11 = automatic, 14 = manual.
- Faults cannot be acknowledged over Modbus, only in SERVICEWELT.
- The Modbus interface cannot run alongside other ISG software interfaces (read-only use with EMI excepted).
Network setup
- Default ISG IP 192.168.0.126 on a direct PC link; DHCP behind a router. Change it on the Profile tab in SERVICEWELT.
- Unit ID fixed at 1, port 502.
Watch out for
- Do not run the ISG on the same CAN bus as a DCo-aktiv GSM module.
Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 1 | Actual room T HC1 | Room temperature, heating circuit 1 (remote control value). | INT16 | × 0.1 | °C | Read | ||
| IR | 1doc 2 | Set room temperature HC1 | Room setpoint, heating circuit 1. | INT16 | × 0.1 | °C | Read | ||
| IR | 2doc 3 | Relative humidity HC1 | Room humidity, heating circuit 1 (remote control value). | INT16 | × 0.1 | % | Read | ||
| IR | 3doc 4 | Actual room T HC2 | Room temperature, heating circuit 2 (remote control value). | INT16 | × 0.1 | °C | Read | ||
| IR | 4doc 5 | Set room temperature HC2 | Room setpoint, heating circuit 2. | INT16 | × 0.1 | °C | Read | ||
| IR | 5doc 6 | Relative humidity HC2 | Room humidity, heating circuit 2 (remote control value). | INT16 | × 0.1 | % | Read | ||
| IR | 6doc 7 | Outside temperature | Outdoor air temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 7doc 8 | Actual value HC1 | Heating circuit 1 actual temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 8doc 9 | Set value HC1 | Heating circuit 1 setpoint. | INT16 | × 0.1 | °C | Read | ||
| IR | 9doc 10 | Actual value HC2 | Heating circuit 2 actual temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 10doc 11 | Set value HC2 | Heating circuit 2 setpoint. | INT16 | × 0.1 | °C | Read | ||
| IR | 11doc 12 | Flow temperature | Heating flow temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 12doc 13 | Return temperature | Heating return temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 13doc 14 | Pressure heating circuit | Heating circuit pressure; LWZ 304/404/504/Trend only. | INT16 | × 0.1 | bar | Read | ||
| IR | 14doc 15 | Flow rate | Heating water flow rate; LWZ 304/404/504/Trend only. | INT16 | × 0.1 | l/min | Read | ||
| IR | 15doc 16 | Actual DHW temperature | Hot water cylinder temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 16doc 17 | DHW set temperature | Hot water setpoint. | INT16 | × 0.1 | °C | Read | ||
| IR | 17doc 18 | Ventilation air actual fan speed | Supply (ventilation) air fan speed. | UINT16 | Hz | Read | |||
| IR | 18doc 19 | Ventilation air set flow rate | Supply air flow setpoint. | UINT16 | m³/h | Read | |||
| IR | 19doc 20 | Extract air actual fan speed | Extract air fan speed. | UINT16 | Hz | Read | |||
| IR | 20doc 21 | Extract air set flow rate | Extract air flow setpoint. | UINT16 | m³/h | Read | |||
| IR | 21doc 22 | Extract air humidity | Extract air relative humidity; LWZ 304/404/504/Trend only. | UINT16 | % | Read | |||
| IR | 24doc 25 | Dew point temp. HC1 | Dew point, heating circuit 1; units with cooling only. | INT16 | × 0.1 | °C | Read | ||
| IR | 25doc 26 | Dew point temp. HC2 | Dew point, heating circuit 2; units with cooling only. | INT16 | × 0.1 | °C | Read | ||
| IR | 26doc 27 | Collector temperature | Solar collector temperature; units with solar only. | INT16 | × 0.1 | °C | Read | ||
| IR | 27doc 28 | Hot gas temperature | Compressor discharge temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 28doc 29 | High pressure | Refrigerant high pressure. | INT16 | × 0.01 | bar | Read | ||
| IR | 29doc 30 | Low pressure | Refrigerant low pressure. | INT16 | × 0.01 | bar | Read | ||
| IR | 30doc 31 | Compressor starts | Number of compressor starts. | UINT16 | Read | ||||
| IR | 31doc 32 | Compressor speed | Compressor speed; LWZ 504 only. | INT16 | × 0.1 | Hz | Read | ||
| IR | 32doc 33 | Mixed water amount | Available mixed hot water volume; LWZ 504 only. | UINT16 | l | Read | |||
| IR | 2000doc 2001 | Operating status | Packed status flags of the unit. | BITMAP16 | Read | bit 0 = Switching program enabled; bit 1 = Compressor; bit 2 = Heating; bit 3 = Cooling; bit 4 = DHW; bit 5 = Electric reheating; bit 6 = Service; bit 7 = Power-off (utility block); bit 8 = Filter; bit 9 = Ventilation; bit 10 = Heating circuit pump; bit 11 = Evaporator defrost; bit 12 = Filter extract air; bit 13 = Filter ventilation air; bit 14 = Heat-up program | |||
| IR | 2001doc 2002 | Fault status | 1 = system fault; acknowledge only via SERVICEWELT. | UINT16 | Read | 0 = No fault; 1 = Fault | |||
| IR | 2003doc 2004 | Defrost initiated | 1 = defrost signal active. | UINT16 | Read | 0 = Off; 1 = Initiated | |||
| IR | 2004doc 2005 | Operating status-2 | Further packed status flags. | BITMAP16 | Read | bit 0 = Summer mode active; bit 1 = Oven/fireplace mode active | |||
| IR | 3000doc 3001 | Heat meter htg day | Heat delivered for heating today. | UINT16 | kWh | Read | |||
| IR | 3001doc 3002 | Heat meter htg total kWh | Total heat for heating, kWh part (0-999). | UINT16 | kWh | Read | |||
| IR | 3002doc 3003 | Heat meter htg total MWh | Total heat for heating, MWh part. | UINT16 | MWh | Read | |||
| IR | 3003doc 3004 | Heat meter DHW day | Heat delivered for DHW today. | UINT16 | kWh | Read | |||
| IR | 3004doc 3005 | Heat meter DHW total kWh | Total heat for DHW, kWh part. | UINT16 | kWh | Read | |||
| IR | 3005doc 3006 | Heat meter DHW total MWh | Total heat for DHW, MWh part. | UINT16 | MWh | Read | |||
| IR | 3006doc 3007 | Heat M boost htg total kWh | Heat from the electric booster for heating, kWh part. | UINT16 | kWh | Read | |||
| IR | 3007doc 3008 | Heat M boost htg total MWh | Heat from the electric booster for heating, MWh part. | UINT16 | MWh | Read | |||
| IR | 3008doc 3009 | Heat M boost DHW total kWh | Heat from the electric booster for DHW, kWh part. | UINT16 | kWh | Read | |||
| IR | 3009doc 3010 | Heat M boost DHW total MWh | Heat from the electric booster for DHW, MWh part. | UINT16 | MWh | Read | |||
| IR | 3010doc 3011 | Heat M recovery day | Heat recovered by the heat exchanger today. | UINT16 | kWh | Read | |||
| IR | 3011doc 3012 | Heat M recovery total kWh | Total recovered heat, kWh part. | UINT16 | kWh | Read | |||
| IR | 3012doc 3013 | Heat M recovery total MWh | Total recovered heat, MWh part. | UINT16 | MWh | Read | |||
| IR | 3013doc 3014 | HM solar htg day | Solar heat for heating today; solar units only. | UINT16 | kWh | Read | |||
| IR | 3014doc 3015 | HM solar htg total kWh | Solar heat for heating, kWh part; solar units only. | UINT16 | kWh | Read | |||
| IR | 3015doc 3016 | HM solar htg total MWh | Solar heat for heating, MWh part; solar units only. | UINT16 | MWh | Read | |||
| IR | 3016doc 3017 | HM solar DHW day | Solar heat for DHW today; solar units only. | UINT16 | kWh | Read | |||
| IR | 3017doc 3018 | HM solar DHW total kWh | Solar heat for DHW, kWh part; solar units only. | UINT16 | kWh | Read | |||
| IR | 3018doc 3019 | HM solar DHW total MWh | Solar heat for DHW, MWh part; solar units only. | UINT16 | MWh | Read | |||
| IR | 3019doc 3020 | HM cooling total kWh | Cooling energy, kWh part; units with cooling only. | UINT16 | kWh | Read | |||
| IR | 3020doc 3021 | HM cooling total MWh | Cooling energy, MWh part; units with cooling only. | UINT16 | MWh | Read | |||
| IR | 3021doc 3022 | Pwr con htg day | Electricity used for heating today. | UINT16 | kWh | Read | |||
| IR | 3022doc 3023 | Pwr con htg total kWh | Electricity used for heating, kWh part. | UINT16 | kWh | Read | |||
| IR | 3023doc 3024 | Pwr con htg total MWh | Electricity used for heating, MWh part. | UINT16 | MWh | Read | |||
| IR | 3024doc 3025 | Pwr con DHW day | Electricity used for DHW today. | UINT16 | kWh | Read | |||
| IR | 3025doc 3026 | Pwr con DHW total kWh | Electricity used for DHW, kWh part. | UINT16 | kWh | Read | |||
| IR | 3026doc 3027 | Pwr con DHW total MWh | Electricity used for DHW, MWh part. | UINT16 | MWh | Read | |||
| IR | 3027doc 3028 | Compressor heating hours | Compressor operating hours in heating. | UINT16 | h | Read | |||
| IR | 3028doc 3029 | Compressor cooling hours | Compressor operating hours in cooling; units with cooling only. | UINT16 | h | Read | |||
| IR | 3029doc 3030 | Compressor DHW hours | Compressor operating hours in DHW mode. | UINT16 | h | Read | |||
| IR | 3030doc 3031 | Elec booster heating hours | Electric booster operating hours for heating. | UINT16 | h | Read | |||
| IR | 3031doc 3032 | Elec booster DHW hours | Electric booster operating hours for DHW. | UINT16 | h | Read | |||
| IR | 5000doc 5001 | SG Ready operating state | Resulting SG Ready state 1-4. | UINT16 | Read | 1 = State 1: heating must not start, frost protection only; 2 = State 2: normal automatic/programmed operation; 3 = State 3: accelerated mode with raised heating/DHW setpoints; 4 = State 4: immediate switch to maximum heating/DHW setpoints | |||
| IR | 5001doc 5002 | Controller identification | Type code of the connected controller. | UINT16 | Read | 103 = LWZ 303/403 Integral/SOL, LWA 403, LWZ 304/404 Trend/FLEX, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus/Trend/Smart, LWZ 8 S Trend; 104 = LWZ 304/404 SOL, LWZ 504, LWZ 5/8 CS Premium, VCR-I 8 CS Premium CN; 390 = WPM 3; 391 = WPM 3i; 449 = WPMsystem | |||
| HR | 1000doc 1001 | Operating mode | Selects the unit operating mode. | UINT16 | Read/write | 0 = Emergency operation; 1 = Standby; 3 = Day mode; 4 = Setback mode; 5 = DHW; 11 = Automatic; 14 = Manual mode | |||
| HR | 1001doc 1002 | Room temperature day HC1 | Day (comfort) room heating setpoint, heating circuit 1. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1002doc 1003 | Room temp. night HC1 | Night (setback) room heating setpoint, heating circuit 1. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1003doc 1004 | Manual set HC1 | Heating circuit 1 setpoint in manual mode. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1004doc 1005 | Room temperature day HC2 | Day room heating setpoint, heating circuit 2. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1005doc 1006 | Room temp. night HC2 | Night room heating setpoint, heating circuit 2. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1006doc 1007 | Manual set HC2 | Heating circuit 2 setpoint in manual mode. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1007doc 1008 | Gradient HC1 | Heating curve slope, heating circuit 1. | INT16 | × 0.01 | Read/write | |||
| HR | 1008doc 1009 | Low end HC1 | Heating curve base point, heating circuit 1. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1009doc 1010 | Gradient HC2 | Heating curve slope, heating circuit 2. | INT16 | × 0.01 | Read/write | |||
| HR | 1010doc 1011 | Low end HC2 | Heating curve base point, heating circuit 2. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1011doc 1012 | DHW set day | Day hot water setpoint. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1012doc 1013 | DHW set night | Night hot water setpoint. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1013doc 1014 | DHW set manual | Hot water setpoint in manual mode. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1014doc 1015 | MWM set day | Mixed water volume setpoint, day; LWZ 504 only. | UINT16 | l | Read/write | |||
| HR | 1015doc 1016 | MWM set night | Mixed water volume setpoint, night; LWZ 504 only. | UINT16 | l | Read/write | |||
| HR | 1016doc 1017 | MWM set manual | Mixed water volume setpoint, manual mode; LWZ 504 only. | UINT16 | l | Read/write | |||
| HR | 1017doc 1018 | Day stage | Ventilation fan stage in day mode (0-3). | UINT16 | Read/write | ||||
| HR | 1018doc 1019 | Night stage | Ventilation fan stage in night mode (0-3). | UINT16 | Read/write | ||||
| HR | 1019doc 1020 | Party stage | Ventilation fan stage in party mode (0-3). | UINT16 | Read/write | ||||
| HR | 1020doc 1021 | Manual stage | Ventilation fan stage in manual mode (0-3). | UINT16 | Read/write | ||||
| HR | 1021doc 1022 | Room temperature day HC1 cooling | Day room cooling setpoint, HC 1; units with cooling only. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1022doc 1023 | Room temp. night HC1 cooling | Night room cooling setpoint, HC 1; units with cooling only. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1023doc 1024 | Room temperature day HC2 cooling | Day room cooling setpoint, HC 2; units with cooling only. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1024doc 1025 | Room temp. night HC2 cooling | Night room cooling setpoint, HC 2; units with cooling only. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1025doc 1026 | Reset | Reset command; LWZ 504 only. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 1026doc 1027 | Restart ISG | ISG restart command; codes as published. | UINT16 | Read/write | 0 = Off; 1 = Reset; 2 = Menu | |||
| HR | 4000doc 4001 | Switch SG Ready on and off | Enables or disables SG Ready. Language tables disagree on which code means on; check on site. | UINT16 | Read/write | ||||
| HR | 4001doc 4002 | SG Ready input 1 | Virtual SG Ready contact written by the BMS. | UINT16 | Read/write | 0 = Switched off; 1 = Switched on | |||
| HR | 4002doc 4003 | SG Ready input 2 | Virtual SG Ready contact written by the BMS. | UINT16 | Read/write | 0 = Switched off; 1 = Switched on |
Notes on this map
- Stiebel Eltron does not host this software documentation publicly (its own download path returns 404). The linked copy is a retailer mirror of the unchanged Stiebel Eltron document with one shop cover page added in front.
- Data types: type 2 = signed, value x 0.1; type 6 = unsigned, x 1; type 7 = signed, value x 0.01; type 8 = unsigned 0-255, x 1. Unavailable objects return 32768 (0x8000).
- For LWZ units the controller reports -60 for a missing or open sensor lead and -50 for a shorted sensor lead.
- Energy totals are split into a kWh register (0-999) and an MWh register: total = MWh x 1000 + kWh.
- Rows marked '(x)' in the table apply only to the listed sub-models (LWZ 504, units with cooling, units with solar, LWZ 304/404/504/Trend); this is noted in the descriptions. Registers 18 and 19 (supply air fan) are listed for LWZ only, not LWA.
- Left out: extract air temperature (23) and extract air dew point (24), because they are typed as signed x 0.1 values but given a 0-65535 range; BUS-STATUS (2003), typed unsigned but coded with negative values.
- Holding registers 1016-1027 sit on a continuation page without a repeated table header in the English section; their values were checked against the German table.
- SG Ready on/off (4001): the language tables of the same document disagree on the coding (German and Italian: 0 = off, 1 = on; English: 0 = on, 1 = off). No value labels are given here; test on site which code switches the function on.
- WPM-managed heat pumps use another register set: see stiebel-eltron/isg-modbus-wpm-heat-pumps.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP
What Modbus registers does the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP have?
This map lists 99 registers: 69 input registers, 30 holding registers. 30 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document states that ISG addressing is 1-based (its example: register 30501 is reached as address 501 with function code 04), so subtract one from the printed register number: outside temperature, printed 7, is requested at input register address 6. The document also warns that, depending on the configuration, an offset of 1 may have to be allowed for; confirm with outside temperature against the unit display.
What are the minimum Modbus registers to integrate the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP?
Start with IR 6 Outside temperature (Outside temperature (offset check)); IR 15 Actual DHW temperature (Actual DHW temperature); IR 0 Actual room T HC1 (Actual room temperature HC1); IR 2000 Operating status (Operating status flags); IR 2001 Fault status (Fault status); HR 1000 Operating mode (Operating mode); HR 1001 Room temperature day HC1 (Day room setpoint HC1); HR 1017 Day stage (Ventilation day stage).
How do I enable Modbus control of the Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP?
The ISG web or ISG plus needs the Modbus TCP/IP software extension and, for the ISG web, the Basic service package. With an integral ventilation unit connected, check for it in SERVICEWELT under DIAGNOSIS > BUS SUBSCRIBER > ISG; if Modbus TCP/IP is not listed, update the ISG firmware or contact Stiebel Eltron service.
Where is the official Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP Modbus documentation?
The source is Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP (A 321798-44755-9770). Stiebel Eltron doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.heizungsdiscount24.de/pdf/Stiebel-Eltron-Internet-Service-Gateway-ISG-Connect-Software-Dokumentation.pdf. It may be an older revision, so check it against the live unit.
More Stiebel Eltron Modbus register maps
Other ac & vrf gateways register maps
- Gateway for Bender BMS-bus devices (insulation monitors, RCMs, changeover modules) - sensor/alarm data
Bender COM461MT BMS-to-Modbus/TCP gateway
COM461MT software D402 V1.0x; the map is the gateway's process image, shown here for BMS device address 1 plus the built-in test record.
Also known as: COM461MT, B95061021 - Split AC unit (VRF / split AC gateway built in)
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.
Also known as: Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus
All ac & vrf gateways Modbus register maps →
Source: Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP · A 321798-44755-9770 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.