- Home
- Modbus register maps
- Mitsubishi Electric
- MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
VRF / split AC gateway · Modbus register map
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units Modbus register map
Updated 19 November 2026
Procon protocol converter that plugs into the CN105/CN92 connector of one Mitsubishi Electric split indoor unit and serves Modbus RTU or BACnet MS/TP on RS-485. For Air-To-Air units it exposes mode, setpoint, fan, vane and on/off, room temperature and fault code, the BMS room-sensor setpoint offset and deadband auto-changeover settings.
This page lists 33 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
- Equipment type
- VRF / split AC gateway
- Registers
- 33 (19 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- 3.0.28 / 3.1.1
- Also known as
- MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI
Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Set DIP 7 ON for Modbus RTU, choose the slave ID on DIP 1-5 and set DIP 6 ON for 9600 / no parity. Write mode, setpoint, fan, vane and on/off at holding 0-3 and 7, and poll room temperature (8) and fault code (12).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 7 | Drive On/Off | UINT16 | On/off | Read/write |
| HR 0 | Drive mode | UINT16 | Mode | Read/write |
| HR 1 | Temperature setpoint | UINT16 | Setpoint (x10) | Read/write |
| HR 2 | Fan speed | UINT16 | Fan speed | Read/write |
| HR 8 | Room temperature | UINT16 | Room temperature (x10) | Read |
| HR 12 | Fault code (decimal) | UINT16 | Fault code (8000 = none) | Read |
Enable Modbus control & writes
DIP 7 ON = Modbus RTU (OFF = BACnet MS/TP).
Byte order & addressing
- Node address on DIP 1-5 (1-30, binary); all ON = address from holding 4; all OFF = address 1.
- DIP 6 ON = 9600 baud, no parity; OFF = holding 5 and 6. Data bits 8 and stop bits 1 are fixed.
- Setting the BMS room temperature to 0 °C turns the setpoint offset feature off.
Network setup
- Plug the flying lead into CN105/CN92 on the indoor unit PCB; it is powered from there (12 V DC).
- Use one A1M per indoor unit if the fault register is used; with MXZ multi-splits one A1M per indoor unit is required.
Watch out for
- The RS-485 ACK LED flashes on valid Modbus or BACnet traffic; if it stays lit without flashing, check the RS-485 wiring and the protocol / baud / parity settings.
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Drive On/Off | Same as holding register 7. | BIT | Read/write | 0 = Drive off; 1 = Drive on | |||
| IR | 0doc 30001 | Room temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 1doc 30002 | Fault code (hex) | 0x8000 = no error, 0x6999 = no comms with indoor unit. | UINT16 | Read | 27033 = Bad communication with indoor unit; 32768 = No error | |||
| IR | 3doc 30004 | Firmware version | MelcoBEMS MINI (A1M) firmware version. | UINT16 | Read | ||||
| IR | 5doc 30006 | Modbus comms counter | Counts valid Modbus commands; wraps after 65535. | UINT16 | Read | ||||
| IR | 8doc 30009 | Fault code (decimal) | UINT16 | Read | 6999 = Bad communication with indoor unit; 8000 = No error | ||||
| IR | 9doc 30010 | System type detected | UINT16 | Read | 0 = Air-to-air; 1 = Air-to-water; 2 = Lossnay; 255 = Undetermined (no unit detected yet) | ||||
| IR | 10doc 30011 | Deadband enabled state | UINT16 | Read | 0 = Deadband disabled (DIP 8 off); 1 = Deadband enabled (DIP 8 on) | ||||
| HR | 0doc 40001 | Drive mode | i-see codes are read only. | UINT16 | Read/write | 1 = Heating; 2 = Humidity reduction; 3 = Cooling; 7 = Ventilation / clean air; 8 = Auto; 9 = i-see heating (read only); 10 = i-see humidity reduction (read only); 11 = i-see cooling (read only) | |||
| HR | 1doc 40002 | Temperature setpoint | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 2doc 40003 | Fan speed | UINT16 | Read/write | 0 = Auto; 2 = Quiet; 3 = Weak; 5 = Strong; 6 = Very strong (SH i) | ||||
| HR | 3doc 40004 | Air direction | UINT16 | Read/write | 0 = Auto; 1 = Position 1; 2 = Position 2; 3 = Position 3; 4 = Position 4; 5 = Position 5; 7 = Swing | ||||
| HR | 4doc 40005 | Modbus slave ID / BACnet station ID | Modbus 1-247, BACnet 1-127; used when DIP 1-5 are all ON. | UINT16 | Read/write | ||||
| HR | 5doc 40006 | RS-485 baud rate | Used when DIP 6 is OFF. BACnet allows only 0, 4, 6, 8, 10. | UINT16 | Read/write | 0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200 | |||
| HR | 6doc 40007 | RS-485 parity | Used when DIP 6 is OFF. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 7doc 40008 | Drive On/Off | UINT16 | Read/write | 0 = Drive off; 1 = Drive on | ||||
| HR | 8doc 40009 | Room temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 9doc 40010 | Fault code (hex) | 0x8000 = no error. | UINT16 | Read | 27033 = Bad communication with indoor unit; 32768 = No error | |||
| HR | 10doc 40011 | Firmware version | UINT16 | Read | |||||
| HR | 11doc 40012 | Modbus comms counter | UINT16 | Read | |||||
| HR | 12doc 40013 | Fault code (decimal) | UINT16 | Read | 6999 = Bad communication with indoor unit; 8000 = No error | ||||
| HR | 13doc 40014 | System type detected | UINT16 | Read | 0 = Air-to-air; 1 = Air-to-water; 2 = Lossnay; 255 = Undetermined (no unit detected yet) | ||||
| HR | 14doc 40015 | Deadband enabled state | UINT16 | Read | 0 = Deadband disabled (DIP 8 off); 1 = Deadband enabled (DIP 8 on) | ||||
| HR | 15doc 40016 | BMS room temperature (signed) | Room reading from the BMS for the setpoint offset feature. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 16doc 40017 | BMS room temperature | Unsigned version, 0-50 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 17doc 40018 | BMS virtual setpoint | 10-40 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 18doc 40019 | Deadband heating setpoint | Whole degrees, default 19 °C; at least 2 °C below the cooling setpoint. | UINT16 | °C | Read/write | |||
| HR | 19doc 40020 | Deadband cooling setpoint | Whole degrees, default 23 °C; at least 2 °C above the heating setpoint. | UINT16 | °C | Read/write | |||
| HR | 272doc 40273 / 40274 | BACnet device instance | Most significant 16 bits at 272, least significant at 273. | UINT32 | ABCD | Read/write | |||
| HR | 274doc 40275 | BACnet max master | UINT16 | Read/write | |||||
| HR | 275doc 40276 | BACnet max info frames | UINT16 | Read/write | |||||
| HR | 276doc 40277 | BACnet APDU timeout | UINT16 | ms | Read/write | ||||
| HR | 277doc 40278 | BACnet APDU retries | UINT16 | Read/write |
Notes on this map
- This file covers only the Air-To-Air tables (section 11). The same manual has Lossnay tables (section 13); the Air-To-Water tables are in a separate register-table document.
- Input values and the coil are mirrored as read-only holding registers for BMSs that only read holding registers. There are no discrete inputs for Air-To-Air systems.
- BMS room temperature is given signed (40016) and unsigned (40017). Deadband setpoints (40019/40020) are whole °C, unlike the x10 setpoint and temperatures.
- Holding 4 and 5 serve as the Modbus slave ID / baud rate or the BACnet station ID / baud rate, depending on the protocol chosen on DIP 7.
- The BACnet device instance is a 32-bit value: the manual names 272 the most significant and 273 the least significant 16 bits, so it is listed as UINT32 high word first.
- Fault codes other than 8000 / 0x8000 and 6999 / 0x6999 are the indoor unit's own codes.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units have?
This map lists 33 registers: 1 coil, 7 input registers, 25 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row prints a 0-based 'Address' next to the Modicon address (40001 = holding 0, 30001 = input 0, 00001 = coil 0). The 0-based address is the wire address.
What byte order does the Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units?
Start with HR 7 Drive On/Off (On/off); HR 0 Drive mode (Mode); HR 1 Temperature setpoint (Setpoint (x10)); HR 2 Fan speed (Fan speed); HR 8 Room temperature (Room temperature (x10)); HR 12 Fault code (decimal) (Fault code (8000 = none)).
How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units?
DIP 7 ON = Modbus RTU (OFF = BACnet MS/TP).
Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units Modbus documentation?
The source is Procon MelcoBEMS MINI (A1M) Installation Manual (Manual version 1.1.11), revision 2024-03-14, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5186.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other ac & vrf gateways register maps
- VRF / split AC gateway
Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners
RTD-RA plugged into the S21 port of a Daikin room air conditioner (split) indoor unit, installation instructions 21070-1.07.04.
Also known as: RTD-RA, Daikin RTD-RA - Heat pump (integral ventilation unit, via ISG Modbus TCP gateway)
Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP
Stiebel Eltron LWZ / LWA integral ventilation and heat pump units reached through an ISG web or ISG plus with the Modbus TCP/IP software extension.
Also known as: LWZ 303 Integral, LWZ 403 SOL, LWA 403, LWZ 304 Trend, LWZ 404 Trend, LWZ 304 SOL, LWZ 404 SOL, LWZ 504, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus, LWZ 5 S Trend, LWZ 8 S Trend, LWZ 5 S Smart, LWZ 5 CS Premium, LWZ 8 CS Premium - Gateway for Bender BMS-bus devices (insulation monitors, RCMs, changeover modules) - sensor/alarm data
Bender COM461MT BMS-to-Modbus/TCP gateway
COM461MT software D402 V1.0x; the map is the gateway's process image, shown here for BMS device address 1 plus the built-in test record.
Also known as: COM461MT, B95061021 - Split AC unit (VRF / split AC gateway built in)
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.
Also known as: Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway
All ac & vrf gateways Modbus register maps →
Source: Procon MelcoBEMS MINI (A1M) Installation Manual · Manual version 1.1.11 · rev. 2024-03-14. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.