Easy Modbus
  1. Home
  2. Modbus register maps
  3. Mitsubishi Electric
  4. FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)

Variable frequency drive · Modbus register map

Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Mitsubishi Electric's inverter for fans and pumps. Its RS-485 terminal block can speak Modbus RTU, exposing system variables (control word, operation mode, frequency command) at 40002-40015, a real-time monitor block from 40201, fault history at 40501, and parameters at 41000 + parameter number (Pr.1000 and up at 44000 + parameter number). This map covers control, status, the main monitors and the communication parameters.

This page lists 50 Modbus registers for the Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
Equipment type
Variable frequency drive
Registers
50 (21 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series
Source document
FR-F800 Instruction Manual (Detailed) · IB(NA)-0600547ENG-G · rev. 2024-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)

Integration in brief

Set Pr.549 = 1, give the drive a station number in Pr.331 (the initial 0 means broadcast, so it never answers) and reset. Put the drive in NET mode by writing H0014 to 40010, write the frequency to 40014 (0.01 Hz) and the run bits to 40009, then poll 40009, 40201 and 40224.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8Inverter status / control input commandBITMAP16Run/stop command and inverter statusRead/write
HR 9Operation mode / inverter settingUINT16Operation mode (write H0014 for NET)Read/write
HR 13Running frequency (RAM)UINT16Frequency command (RAM)Read/write
HR 200Output frequencyUINT16Output frequencyRead
HR 223Motor load factorUINT16Motor load factor (% of rated current)Read
HR 207Converter output voltageUINT16DC bus voltageRead
HR 500Fault record 1UINT16Latest fault codeRead/write

Enable Modbus control & writes

Pr.549 = 1 selects Modbus RTU on the RS-485 terminals; set Pr.331 (1-247), Pr.332 speed and Pr.334 parity, then reset or power-cycle. Run and frequency commands are taken in NET operation mode (write H0014 to 40010, or use Pr.79/Pr.340 so the drive starts in NET mode). If a communication option is installed and Pr.550 = 9999, commands via the RS-485 terminals are ignored.

Communication loss & watchdog

Pr.539 sets the Modbus communication check interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) disables the check, 0 lets Modbus run but shuts the output off in NET mode.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 40002Inverter resetWrite any value to reset the inverter.UINT16Write
HR2doc 40003Parameter clearWrite H965A to clear parameters.UINT16Write
HR3doc 40004All parameter clearWrite H99AA to clear all parameters.UINT16Write
HR5doc 40006Parameter clear (keep comm settings)Write H5A96; communication parameters are not cleared.UINT16Write
HR6doc 40007All parameter clear (keep comm settings)Write HAA99; communication parameters are not cleared.UINT16Write
HR8doc 40009Inverter status / control input commandWrite = control input command, read = inverter status.BITMAP16Read/writebit 0 = Write: stop command / Read: RUN (inverter running); bit 1 = Write: forward rotation command / Read: forward rotation output; bit 2 = Write: reverse rotation command / Read: reverse rotation output; bit 3 = Write: RH (high speed) / Read: SU (up to frequency); bit 4 = Write: RM (middle speed) / Read: OL (overload); bit 5 = Write: RL (low speed) / Read: IPF (instantaneous power failure); bit 6 = Write: JOG / Read: FU (frequency detection); bit 7 = Write: RT (second function) / Read: ABC1 (fault); bit 8 = Write: AU (current input selection) / Read: ABC2; bit 9 = Write: CS / Read: safety monitor output; bit 10 = Write: MRS (output stop) / Read: 0; bit 11 = Write: STP (start self-holding) / Read: 0; bit 12 = Write: RES (reset) / Read: 0; bit 15 = Read: fault occurrence
HR9doc 40010Operation mode / inverter settingRead returns the current mode; write H0010 EXT, H0011 PU, H0014 NET.UINT16Read/write0 = Read: EXT; 1 = Read: PU; 2 = Read: EXT JOG; 3 = Read: PU JOG; 4 = Read: NET; 5 = Read: PU + EXT; 16 = Write: EXT (H0010); 17 = Write: PU (H0011); 20 = Write: NET (H0014)
HR13doc 40014Running frequency (RAM)Frequency command, not stored in EEPROM.UINT16× 0.01HzRead/write
HR14doc 40015Running frequency (EEPROM)Frequency command, also stored in EEPROM.UINT16× 0.01HzWrite
HR200doc 40201Output frequencyUINT16× 0.01HzRead
HR202doc 40203Output voltageUINT16× 0.1VRead
HR204doc 40205Set frequencyUINT16× 0.01HzRead
HR205doc 40206Operation speedMotor speed per Pr.37/Pr.144.UINT16r/minRead
HR207doc 40208Converter output voltageDC bus voltage.UINT16× 0.1VRead
HR209doc 40210Electronic thermal O/L relay load factorMotor thermal accumulation, 100% = trip level.UINT16× 0.1%Read
HR211doc 40212Converter output voltage peakDC bus peak since power-up.UINT16× 0.1VRead
HR214doc 40215Input terminal status1 = terminal on.BITMAP16Readbit 0 = STF; bit 1 = STR; bit 2 = AU; bit 3 = RT; bit 4 = RL; bit 5 = RM; bit 6 = RH; bit 7 = JOG; bit 8 = MRS; bit 9 = STP (STOP); bit 10 = RES; bit 11 = CS; bit 14 = S2; bit 15 = S1
HR215doc 40216Output terminal status1 = terminal on.BITMAP16Readbit 0 = RUN; bit 1 = SU; bit 2 = IPF; bit 3 = OL; bit 4 = FU; bit 5 = ABC1; bit 6 = ABC2; bit 7 = So (SO)
HR216doc 40217Load meterTorque current as % of Pr.56.UINT16× 0.1%Read
HR219doc 40220Cumulative energization timeWraps at 65535 h.UINT16hRead
HR222doc 40223Actual operation timeWraps at 65535 h; reset with Pr.171.UINT16hRead
HR223doc 40224Motor load factorOutput current as % of inverter rated current.UINT16× 0.1%Read
HR251doc 40252PID set pointUINT16× 0.1%Read
HR252doc 40253PID measured valueUINT16× 0.1%Read
HR260doc 40261Motor thermal load factorE.THM trips at 100%.UINT16× 0.1%Read
HR261doc 40262Inverter thermal load factorE.THT trips at 100%.UINT16× 0.1%Read
HR266doc 40267PID measured value 2Shown whenever PID is enabled.UINT16× 0.1%Read
HR268doc 40269PID input pressure valueUINT16× 0.1%Read
HR291doc 40292Second PID set pointUINT16× 0.1%Read
HR292doc 40293Second PID measured valueUINT16× 0.1%Read
HR500doc 40501Fault record 1Low byte = error code. Write any value to 40501 to clear history.UINT16Read/write
HR501doc 40502Fault record 2Low byte = error code.UINT16Read
HR502doc 40503Fault record 3Low byte = error code.UINT16Read
HR503doc 40504Fault record 4Low byte = error code.UINT16Read
HR504doc 40505Fault record 5Low byte = error code.UINT16Read
HR505doc 40506Fault record 6Low byte = error code.UINT16Read
HR506doc 40507Fault record 7Low byte = error code.UINT16Read
HR507doc 40508Fault record 8Low byte = error code.UINT16Read
HR1000doc 41001Pr.1 Maximum frequencyUINT16× 0.01HzRead/write
HR1001doc 41002Pr.2 Minimum frequencyUINT16× 0.01HzRead/write
HR1003doc 41004Pr.4 Multi-speed setting (high speed)UINT16× 0.01HzRead/write
HR1004doc 41005Pr.5 Multi-speed setting (middle speed)UINT16× 0.01HzRead/write
HR1005doc 41006Pr.6 Multi-speed setting (low speed)UINT16× 0.01HzRead/write
HR1078doc 41079Pr.79 Operation mode selectionUINT16Read/write0 = External/PU switchover (External at power-on); 1 = Fixed PU operation; 2 = Fixed External operation (NET switchable); 3 = External/PU combined mode 1; 4 = External/PU combined mode 2; 6 = Switchover during operation; 7 = External operation (PU interlock)
HR1330doc 41331Pr.331 RS-485 communication station number0 = broadcast; 1-247 under Modbus RTU.UINT16Read/write
HR1331doc 41332Pr.332 RS-485 communication speedSetting x 100 = bps (96 = 9600).UINT16Read/write
HR1333doc 41334Pr.334 RS-485 communication parity check selectionUnder Modbus RTU this also sets the stop bits.UINT16Read/write0 = No parity (stop bits per Pr.333); 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit
HR1342doc 41343Pr.343 Communication error countModbus RTU error count.UINT16Read
HR1538doc 41539Pr.539 MODBUS RTU communication check time interval0 = Modbus allowed but output shut off in NET mode; 9999 = no check.UINT16× 0.1sRead/write
HR1548doc 41549Pr.549 Protocol selectionUINT16Read/write0 = Mitsubishi inverter protocol (computer link); 1 = MODBUS RTU; 2 = BACnet MS/TP

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)

What Modbus registers does the Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU) have?

This map lists 50 registers: 50 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modicon-style register numbers (40002, 41004). Its rule: starting address = register number - 40001, e.g. reading 41004 (Pr.4) sends start address H03EB (1003).

What are the minimum Modbus registers to integrate the Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)?

Start with HR 8 Inverter status / control input command (Run/stop command and inverter status); HR 9 Operation mode / inverter setting (Operation mode (write H0014 for NET)); HR 13 Running frequency (RAM) (Frequency command (RAM)); HR 200 Output frequency (Output frequency); HR 223 Motor load factor (Motor load factor (% of rated current)); HR 207 Converter output voltage (DC bus voltage); HR 500 Fault record 1 (Latest fault code).

How do I enable Modbus control of the Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)?

Pr.549 = 1 selects Modbus RTU on the RS-485 terminals; set Pr.331 (1-247), Pr.332 speed and Pr.334 parity, then reset or power-cycle. Run and frequency commands are taken in NET operation mode (write H0014 to 40010, or use Pr.79/Pr.340 so the drive starts in NET mode). If a communication option is installed and Pr.550 = 9999, commands via the RS-485 terminals are ignored.

What happens when the Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU) loses Modbus communication?

Pr.539 sets the Modbus communication check interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) disables the check, 0 lets Modbus run but shuts the output off in NET mode.

Where is the official Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU) Modbus documentation?

The source is FR-F800 Instruction Manual (Detailed) (IB(NA)-0600547ENG-G), revision 2024-10, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600547eng/ib0600547engg.pdf.

More Mitsubishi Electric Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: FR-F800 Instruction Manual (Detailed) · IB(NA)-0600547ENG-G · rev. 2024-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.