Easy Modbus
  1. Home
  2. Modbus register maps
  3. Yaskawa
  4. HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)

Variable frequency drive (HVAC bypass package) · Modbus register map

Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The HV600 Bypass wraps an HV600 HVAC drive with a bypass contactor board that carries its own RS-485 port. In Modbus mode it exposes the drive command and monitor registers plus bypass-only registers: a bypass command word (drive/bypass select, emergency override, Motor AND/OR), network control of the bypass digital inputs and outputs, and status bits for bypass run and bypass faults.

This page lists 38 Modbus registers for the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Equipment type
Variable frequency drive (HVAC bypass package)
Registers
38 (22 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass
Source document
HV600 Narrow & Enclosed Bypass Technical Reference · SIEPYAIH6B01F · rev. 2025-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)

Integration in brief

Set H5-08 = 0 (Modbus), H5-01/H5-02/H5-03 for the line, then reload (power cycle or H5-20 = 1). Set b1-01 = 2 and b1-02 = 2 for comms control, write the frequency to 0002H and run with 0001H bit 0; use 8400H to select drive or bypass and for emergency override, and poll 0020H, 0021H and 004BH.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Run command / drive MFDI commandBITMAP16Run commandRead/write
HR 2Frequency referenceUINT16Frequency referenceRead/write
HR 33792Bypass command wordBITMAP16Bypass command word 8400HRead/write
HR 32Drive status 1BITMAP16Drive/bypass status 0020HRead
HR 33Fault description 1BITMAP16Fault description 1Read
HR 36U1-02 output frequencyUINT16Output frequencyRead
HR 75U1-12 drive statusBITMAP16U1-12 drive status (HAND/AUTO)Read
HR 49U1-07 DC bus voltageUINT16DC bus voltageRead

Enable Modbus control & writes

Select Modbus with H5-08 = 0 and give the bypass a node address (H5-01 not 0). Set b1-01 = 2 and b1-02 = 2 (or 8 for AUTO command + serial run). Set Z3-12 = 1 to let Modbus drive the digital inputs. Communication parameters take effect after a power cycle or H5-20 = 1.

Communication loss & watchdog

H5-05 = 1 enables CE detection after H5-09 (default 2.0 s) without messages; H5-04 sets the action (ramp, coast, fast stop, alarm only, or run at H5-34).

Byte order & addressing

Network setup

Watch out for

Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

38 of 38 shown
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HRun command / drive MFDI commandBits 4-B drive the drive digital inputs when Z3-12 = 1.BITMAP16Read/writebit 0 = Run (1 = run, 0 = stop); bit 2 = External fault EF0; bit 3 = Fault reset
HR2doc 0002HFrequency referenceUnits set by o1-03.UINT16Read/write
HR3doc 0003HOutput voltage gain20-2000 = 2.0-200.0 %, 1000 at power-up.UINT16× 0.1%Read/write
HR6doc 0006HPID setpointSigned, 0.01 %; enable with 000FH bit 1.INT16× 0.01%Read/write
HR13doc 000DHPI2 control setpoint-100.00 to +100.00 %; enable with 000FH bit 4.INT16× 0.01%Read/write
HR15doc 000FHCommand selection settingSelects which values come from Modbus.BITMAP16Read/writebit 1 = PID setpoint from Modbus (0006H); bit 4 = PI2 setpoint from Modbus (000DH); bit 5 = PID feedback from Modbus (15FFH); bit 12 = Terminal S5 input for broadcast; bit 13 = Terminal S6 input for broadcast; bit 14 = Terminal S7 input for broadcast
HR32doc 0020HDrive status 1BITMAP16Readbit 0 = Drive run or bypass run; bit 1 = Reverse; bit 2 = System ready; bit 3 = Drive or bypass faulted; bit 4 = oPE error on drive or bypass; bit 5 = MFDO M1-M2 on; bit 6 = MFDO M3-M4 on; bit 7 = MFDO M5-M6 on; bit 12 = Safe Torque Off hardware; bit 13 = Safe Torque Off; bit 14 = Bypass ComRef enabled; bit 15 = Bypass ComCtrl enabled
HR33doc 0021HFault description 1BITMAP16Readbit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 / oH2 overheat; bit 7 = EF0-EF7 external fault; bit 8 = CPFxx hardware fault (incl. oFx); bit 9 = oL1 / oL3 / oL4 / UL3 / UL4; bit 10 = oS overspeed / dEv; bit 11 = Undervoltage detection; bit 12 = Uv1 / Uv2 / Uv3; bit 13 = LF / PF phase loss; bit 14 = CE / bUS communication error; bit 15 = oPr keypad connection fault
HR34doc 0022HFault contents (data link)BITMAP16Readbit 0 = Data writing / motor switching; bit 3 = Upper/lower limit fault; bit 4 = Data integrity fault; bit 5 = EEPROM writing
HR35doc 0023HU1-01 frequency referenceUnits set by o1-03.UINT16Read
HR36doc 0024HU1-02 output frequencyUnits set by o1-03.UINT16Read
HR42doc 002AHMinor fault description 1BITMAP16Readbit 2 = EF FWD/REV input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 9 = CE run at H5-34; bit 10 = bUS option comm error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat (PTC); bit 15 = CALL serial transmission error
HR43doc 002BHDrive input terminal statusBits 0-6 = drive inputs S1-S7.BITMAP16Readbit 0 = Drive input S1 on; bit 1 = Drive input S2 on; bit 2 = Drive input S3 on; bit 3 = Drive input S4 on; bit 4 = Drive input S5 on; bit 5 = Drive input S6 on; bit 6 = Drive input S7 on
HR44doc 002CHDrive status 2BITMAP16Readbit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agreement; bit 3 = User-defined speed agreement; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = Low voltage detection; bit 8 = Baseblock; bit 11 = Overtorque/undertorque detection; bit 12 = Frequency reference loss; bit 13 = Auto-restart executing; bit 14 = Fault; bit 15 = Modbus communication timeout
HR45doc 002DHDrive output terminal statusBITMAP16Readbit 0 = MFDO M1-M2; bit 1 = MFDO M3-M4; bit 2 = MFDO M5-M6; bit 7 = Fault relay MA/MB-MC
HR49doc 0031HU1-07 DC bus voltageUINT16VRead
HR56doc 0038HPID feedbackUnsigned; 100 % = maximum output frequency.UINT16× 0.1%Read
HR57doc 0039HPID inputSigned, +/-100 % of maximum output frequency.INT16× 0.1%Read
HR58doc 003AHPID outputSigned, +/-100 % of maximum output frequency.INT16× 0.1%Read
HR61doc 003DHBypass serial communication error descriptionHeld until fault reset.BITMAP16Readbit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout
HR75doc 004BHU1-12 drive statusBITMAP16Readbit 0 = During run; bit 1 = Zero speed; bit 2 = Reverse; bit 3 = Reset signal input; bit 4 = Speed agreement; bit 5 = Drive ready; bit 6 = Minor fault; bit 7 = Fault; bit 8 = oPExx error; bit 9 = Momentary power loss recovery; bit 12 = AUTO mode; bit 13 = HAND mode; bit 14 = ComRef / NetRef; bit 15 = ComCtrl / NetCtrl
HR127doc 007FHMinor fault codeCode list in the troubleshooting chapter.UINT16Read
HR384doc 0180Hb1-01 frequency reference selection 12 = serial communications.UINT16Read/write
HR385doc 0181Hb1-02 run command selection 12 = serial, 8 = AUTO command + serial run.UINT16Read/write
HR1061doc 0425HH5-01 drive node address0-FFH for Modbus, default 1FH; 0 = no response.UINT16Read/write
HR1062doc 0426HH5-02 communication speedDefault 3.UINT16Read/write0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps; 6 = 57.6 kbps; 7 = 76.8 kbps; 8 = 115.2 kbps
HR1063doc 0427HH5-03 communication parityDefault 0.UINT16Read/write0 = No parity; 1 = Even parity; 2 = Odd parity
HR1064doc 0428HH5-04 communication error stop methodDefault 3.UINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only; 4 = Run at H5-34 (CE go-to-frequency)
HR1065doc 0429HH5-05 comm fault detectionDefault 1.UINT16Read/write0 = Disabled; 1 = Enabled
HR1066doc 042AHH5-06 drive transmit wait time0-65 ms, default 5 ms.UINT16msRead/write
HR1077doc 0435HH5-09 CE detection time0.0-10.0 s, default 2.0 s.UINT16× 0.1sRead/write
HR1581doc 062DHH5-08 communication protocol selectionDefault 3 (BACnet); set 0 for Modbus.UINT16Read/write0 = Modbus/MEMOBUS; 1 = Metasys/N2; 2 = Apogee/P1; 3 = BACnet
HR2304doc 0900HEnter command (write to EEPROM)Write 0 to apply and store parameter writes.UINT16Write
HR2320doc 0910HEnter command (write to RAM only)Write 0 to apply parameter writes without storing.UINT16Write
HR5631doc 15FFHPID feedback over commsUsed when 000FH bit 5 = 1.UINT16Read/write
HR33792doc 8400HBypass command wordBITMAP16Read/writebit 3 = Remote transfer; bit 4 = Emergency override bypass; bit 5 = Emergency override (FWD); bit 6 = Motor OR; bit 7 = Motor AND; bit 11 = Drive select (Z1-39); bit 12 = Bypass select (Z1-39); bit 13 = Fault reset; bit 14 = EFB; bit 15 = Emergency override drive (REV)
HR33794doc 8402HBypass MFDI commandBypass inputs TB2-1 to TB2-8 when Z3-12 = 1.BITMAP16Read/writebit 0 = Bypass DI 1 (TB2-1); bit 1 = Bypass DI 2 (TB2-2); bit 2 = Bypass DI 3 (TB2-3); bit 3 = Bypass DI 4 (TB2-4); bit 4 = Bypass DI 5 (TB2-5); bit 5 = Bypass DI 6 (TB2-6); bit 6 = Bypass DI 7 (TB2-7); bit 7 = Bypass DI 8 (TB2-8)
HR33795doc 8403HBypass MFDO commandOutputs whose Z2 function is set to 99 (not used).BITMAP16Read/writebit 6 = MFDO 7 (TB1 1-3); bit 7 = MFDO 8 (TB1 4-6); bit 8 = MFDO 9 (TB1 7-9); bit 9 = MFDO 10 (TB1 10-12)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)

What Modbus registers does the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) have?

This map lists 38 registers: 38 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example asks for starting register 0020H as 00 20. Parameters use the hex number printed under each parameter (H5-01 = 0425H).

What are the minimum Modbus registers to integrate the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)?

Start with HR 1 Run command / drive MFDI command (Run command); HR 2 Frequency reference (Frequency reference); HR 33792 Bypass command word (Bypass command word 8400H); HR 32 Drive status 1 (Drive/bypass status 0020H); HR 33 Fault description 1 (Fault description 1); HR 36 U1-02 output frequency (Output frequency); HR 75 U1-12 drive status (U1-12 drive status (HAND/AUTO)); HR 49 U1-07 DC bus voltage (DC bus voltage).

How do I enable Modbus control of the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)?

Select Modbus with H5-08 = 0 and give the bypass a node address (H5-01 not 0). Set b1-01 = 2 and b1-02 = 2 (or 8 for AUTO command + serial run). Set Z3-12 = 1 to let Modbus drive the digital inputs. Communication parameters take effect after a power cycle or H5-20 = 1.

What happens when the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) loses Modbus communication?

H5-05 = 1 enables CE detection after H5-09 (default 2.0 s) without messages; H5-04 sets the action (ramp, coast, fast stop, alarm only, or run at H5-34).

Where is the official Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus documentation?

The source is HV600 Narrow & Enclosed Bypass Technical Reference (SIEPYAIH6B01F), revision 2025-09, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIH6B01&cmd=documents&documentName=SIEPYAIH6B01.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: HV600 Narrow & Enclosed Bypass Technical Reference · SIEPYAIH6B01F · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.