Variable frequency drive (HVAC bypass package) · Modbus register map
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus register map
Updated 19 November 2026
The HV600 Bypass wraps an HV600 HVAC drive with a bypass contactor board that carries its own RS-485 port. In Modbus mode it exposes the drive command and monitor registers plus bypass-only registers: a bypass command word (drive/bypass select, emergency override, Motor AND/OR), network control of the bypass digital inputs and outputs, and status bits for bypass run and bypass faults.
This page lists 38 Modbus registers for the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
- Equipment type
- Variable frequency drive (HVAC bypass package)
- Registers
- 38 (22 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass
Integration notes: Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Set H5-08 = 0 (Modbus), H5-01/H5-02/H5-03 for the line, then reload (power cycle or H5-20 = 1). Set b1-01 = 2 and b1-02 = 2 for comms control, write the frequency to 0002H and run with 0001H bit 0; use 8400H to select drive or bypass and for emergency override, and poll 0020H, 0021H and 004BH.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Run command / drive MFDI command | BITMAP16 | Run command | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference | Read/write |
| HR 33792 | Bypass command word | BITMAP16 | Bypass command word 8400H | Read/write |
| HR 32 | Drive status 1 | BITMAP16 | Drive/bypass status 0020H | Read |
| HR 33 | Fault description 1 | BITMAP16 | Fault description 1 | Read |
| HR 36 | U1-02 output frequency | UINT16 | Output frequency | Read |
| HR 75 | U1-12 drive status | BITMAP16 | U1-12 drive status (HAND/AUTO) | Read |
| HR 49 | U1-07 DC bus voltage | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
Select Modbus with H5-08 = 0 and give the bypass a node address (H5-01 not 0). Set b1-01 = 2 and b1-02 = 2 (or 8 for AUTO command + serial run). Set Z3-12 = 1 to let Modbus drive the digital inputs. Communication parameters take effect after a power cycle or H5-20 = 1.
Communication loss & watchdog
H5-05 = 1 enables CE detection after H5-09 (default 2.0 s) without messages; H5-04 sets the action (ramp, coast, fast stop, alarm only, or run at H5-34).
Byte order & addressing
- There is no function 06H; write single registers with 10H.
- Parameter writes need an Enter command (write 0 to 0900H or 0910H) unless H5-11 says otherwise; command registers do not.
- With H5-04 = 0 (ramp to stop), a motor running in bypass mode coasts to stop instead.
Network setup
- RS-485 on bypass terminal TB3 (2 TXRX+, 3 TXRX-, 1 IG5); up to 31 bypasses per line.
- 8 data bits and 1 stop bit are fixed; speeds 1.2-115.2 kbps; parity none, even or odd.
- Turn DIP switch S1 on the bypass control board ON only at the end of the line (termination).
Watch out for
- Bypass faults (FBxx) are not cleared by the drive fault reset; the manual resets all faults through a bypass digital input set to Z2-0x = 34 (8400H bit 13 is also labelled fault reset).
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Run command / drive MFDI command | Bits 4-B drive the drive digital inputs when Z3-12 = 1. | BITMAP16 | Read/write | bit 0 = Run (1 = run, 0 = stop); bit 2 = External fault EF0; bit 3 = Fault reset | |||
| HR | 2doc 0002H | Frequency reference | Units set by o1-03. | UINT16 | Read/write | ||||
| HR | 3doc 0003H | Output voltage gain | 20-2000 = 2.0-200.0 %, 1000 at power-up. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 6doc 0006H | PID setpoint | Signed, 0.01 %; enable with 000FH bit 1. | INT16 | × 0.01 | % | Read/write | ||
| HR | 13doc 000DH | PI2 control setpoint | -100.00 to +100.00 %; enable with 000FH bit 4. | INT16 | × 0.01 | % | Read/write | ||
| HR | 15doc 000FH | Command selection setting | Selects which values come from Modbus. | BITMAP16 | Read/write | bit 1 = PID setpoint from Modbus (0006H); bit 4 = PI2 setpoint from Modbus (000DH); bit 5 = PID feedback from Modbus (15FFH); bit 12 = Terminal S5 input for broadcast; bit 13 = Terminal S6 input for broadcast; bit 14 = Terminal S7 input for broadcast | |||
| HR | 32doc 0020H | Drive status 1 | BITMAP16 | Read | bit 0 = Drive run or bypass run; bit 1 = Reverse; bit 2 = System ready; bit 3 = Drive or bypass faulted; bit 4 = oPE error on drive or bypass; bit 5 = MFDO M1-M2 on; bit 6 = MFDO M3-M4 on; bit 7 = MFDO M5-M6 on; bit 12 = Safe Torque Off hardware; bit 13 = Safe Torque Off; bit 14 = Bypass ComRef enabled; bit 15 = Bypass ComCtrl enabled | ||||
| HR | 33doc 0021H | Fault description 1 | BITMAP16 | Read | bit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 / oH2 overheat; bit 7 = EF0-EF7 external fault; bit 8 = CPFxx hardware fault (incl. oFx); bit 9 = oL1 / oL3 / oL4 / UL3 / UL4; bit 10 = oS overspeed / dEv; bit 11 = Undervoltage detection; bit 12 = Uv1 / Uv2 / Uv3; bit 13 = LF / PF phase loss; bit 14 = CE / bUS communication error; bit 15 = oPr keypad connection fault | ||||
| HR | 34doc 0022H | Fault contents (data link) | BITMAP16 | Read | bit 0 = Data writing / motor switching; bit 3 = Upper/lower limit fault; bit 4 = Data integrity fault; bit 5 = EEPROM writing | ||||
| HR | 35doc 0023H | U1-01 frequency reference | Units set by o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | U1-02 output frequency | Units set by o1-03. | UINT16 | Read | ||||
| HR | 42doc 002AH | Minor fault description 1 | BITMAP16 | Read | bit 2 = EF FWD/REV input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 9 = CE run at H5-34; bit 10 = bUS option comm error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat (PTC); bit 15 = CALL serial transmission error | ||||
| HR | 43doc 002BH | Drive input terminal status | Bits 0-6 = drive inputs S1-S7. | BITMAP16 | Read | bit 0 = Drive input S1 on; bit 1 = Drive input S2 on; bit 2 = Drive input S3 on; bit 3 = Drive input S4 on; bit 4 = Drive input S5 on; bit 5 = Drive input S6 on; bit 6 = Drive input S7 on | |||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agreement; bit 3 = User-defined speed agreement; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = Low voltage detection; bit 8 = Baseblock; bit 11 = Overtorque/undertorque detection; bit 12 = Frequency reference loss; bit 13 = Auto-restart executing; bit 14 = Fault; bit 15 = Modbus communication timeout | ||||
| HR | 45doc 002DH | Drive output terminal status | BITMAP16 | Read | bit 0 = MFDO M1-M2; bit 1 = MFDO M3-M4; bit 2 = MFDO M5-M6; bit 7 = Fault relay MA/MB-MC | ||||
| HR | 49doc 0031H | U1-07 DC bus voltage | UINT16 | V | Read | ||||
| HR | 56doc 0038H | PID feedback | Unsigned; 100 % = maximum output frequency. | UINT16 | × 0.1 | % | Read | ||
| HR | 57doc 0039H | PID input | Signed, +/-100 % of maximum output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 58doc 003AH | PID output | Signed, +/-100 % of maximum output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 61doc 003DH | Bypass serial communication error description | Held until fault reset. | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | |||
| HR | 75doc 004BH | U1-12 drive status | BITMAP16 | Read | bit 0 = During run; bit 1 = Zero speed; bit 2 = Reverse; bit 3 = Reset signal input; bit 4 = Speed agreement; bit 5 = Drive ready; bit 6 = Minor fault; bit 7 = Fault; bit 8 = oPExx error; bit 9 = Momentary power loss recovery; bit 12 = AUTO mode; bit 13 = HAND mode; bit 14 = ComRef / NetRef; bit 15 = ComCtrl / NetCtrl | ||||
| HR | 127doc 007FH | Minor fault code | Code list in the troubleshooting chapter. | UINT16 | Read | ||||
| HR | 384doc 0180H | b1-01 frequency reference selection 1 | 2 = serial communications. | UINT16 | Read/write | ||||
| HR | 385doc 0181H | b1-02 run command selection 1 | 2 = serial, 8 = AUTO command + serial run. | UINT16 | Read/write | ||||
| HR | 1061doc 0425H | H5-01 drive node address | 0-FFH for Modbus, default 1FH; 0 = no response. | UINT16 | Read/write | ||||
| HR | 1062doc 0426H | H5-02 communication speed | Default 3. | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps; 6 = 57.6 kbps; 7 = 76.8 kbps; 8 = 115.2 kbps | |||
| HR | 1063doc 0427H | H5-03 communication parity | Default 0. | UINT16 | Read/write | 0 = No parity; 1 = Even parity; 2 = Odd parity | |||
| HR | 1064doc 0428H | H5-04 communication error stop method | Default 3. | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only; 4 = Run at H5-34 (CE go-to-frequency) | |||
| HR | 1065doc 0429H | H5-05 comm fault detection | Default 1. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 1066doc 042AH | H5-06 drive transmit wait time | 0-65 ms, default 5 ms. | UINT16 | ms | Read/write | |||
| HR | 1077doc 0435H | H5-09 CE detection time | 0.0-10.0 s, default 2.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1581doc 062DH | H5-08 communication protocol selection | Default 3 (BACnet); set 0 for Modbus. | UINT16 | Read/write | 0 = Modbus/MEMOBUS; 1 = Metasys/N2; 2 = Apogee/P1; 3 = BACnet | |||
| HR | 2304doc 0900H | Enter command (write to EEPROM) | Write 0 to apply and store parameter writes. | UINT16 | Write | ||||
| HR | 2320doc 0910H | Enter command (write to RAM only) | Write 0 to apply parameter writes without storing. | UINT16 | Write | ||||
| HR | 5631doc 15FFH | PID feedback over comms | Used when 000FH bit 5 = 1. | UINT16 | Read/write | ||||
| HR | 33792doc 8400H | Bypass command word | BITMAP16 | Read/write | bit 3 = Remote transfer; bit 4 = Emergency override bypass; bit 5 = Emergency override (FWD); bit 6 = Motor OR; bit 7 = Motor AND; bit 11 = Drive select (Z1-39); bit 12 = Bypass select (Z1-39); bit 13 = Fault reset; bit 14 = EFB; bit 15 = Emergency override drive (REV) | ||||
| HR | 33794doc 8402H | Bypass MFDI command | Bypass inputs TB2-1 to TB2-8 when Z3-12 = 1. | BITMAP16 | Read/write | bit 0 = Bypass DI 1 (TB2-1); bit 1 = Bypass DI 2 (TB2-2); bit 2 = Bypass DI 3 (TB2-3); bit 3 = Bypass DI 4 (TB2-4); bit 4 = Bypass DI 5 (TB2-5); bit 5 = Bypass DI 6 (TB2-6); bit 6 = Bypass DI 7 (TB2-7); bit 7 = Bypass DI 8 (TB2-8) | |||
| HR | 33795doc 8403H | Bypass MFDO command | Outputs whose Z2 function is set to 99 (not used). | BITMAP16 | Read/write | bit 6 = MFDO 7 (TB1 1-3); bit 7 = MFDO 8 (TB1 4-6); bit 8 = MFDO 9 (TB1 7-9); bit 9 = MFDO 10 (TB1 10-12) |
Notes on this map
- All registers are 16-bit; signed values are noted per register.
- Frequency registers 0002H, 0023H and 0024H use the units chosen in o1-03, so they are left unscaled.
- Left out: 0025H output voltage (unit switched by H5-10), 0026H/0027H output current and power (resolution or unit not fixed in the table), 00ABH/00FBH currents (unit depends on drive model), 003EH/003FH speed values, the fault-trace blocks from 0080H and the long fault/minor-fault description words from 00C0H.
- Date/time registers 3004H-3030H, emergency-override references 3A93H-3A96H and bypass clock monitors 8440H-8442H are not listed.
- Supported function codes are 03H, 08H, 10H, 5AH and 67H; there is no 06H, so use 10H even for one register. A 03H read returns at most 16 registers.
- H5-08 defaults to 3 (BACnet) on the bypass, so select Modbus (0) first.
- 0001H bits 0 and 1 are printed with two meanings each (forward run / run, and reverse run / reverse direction) without saying which applies, so bit 1 is left out; bit 0 = 1 runs the motor either way.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
What Modbus registers does the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) have?
This map lists 38 registers: 38 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example asks for starting register 0020H as 00 20. Parameters use the hex number printed under each parameter (H5-01 = 0425H).
What are the minimum Modbus registers to integrate the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)?
Start with HR 1 Run command / drive MFDI command (Run command); HR 2 Frequency reference (Frequency reference); HR 33792 Bypass command word (Bypass command word 8400H); HR 32 Drive status 1 (Drive/bypass status 0020H); HR 33 Fault description 1 (Fault description 1); HR 36 U1-02 output frequency (Output frequency); HR 75 U1-12 drive status (U1-12 drive status (HAND/AUTO)); HR 49 U1-07 DC bus voltage (DC bus voltage).
How do I enable Modbus control of the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)?
Select Modbus with H5-08 = 0 and give the bypass a node address (H5-01 not 0). Set b1-01 = 2 and b1-02 = 2 (or 8 for AUTO command + serial run). Set Z3-12 = 1 to let Modbus drive the digital inputs. Communication parameters take effect after a power cycle or H5-20 = 1.
What happens when the Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) loses Modbus communication?
H5-05 = 1 enables CE detection after H5-09 (default 2.0 s) without messages; H5-04 sets the action (ramp, coast, fast stop, alarm only, or run at H5-34).
Where is the official Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU) Modbus documentation?
The source is HV600 Narrow & Enclosed Bypass Technical Reference (SIEPYAIH6B01F), revision 2025-09, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIH6B01&cmd=documents&documentName=SIEPYAIH6B01.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Variable frequency drive
AutomationDirect GS2 series AC drive
All GS2 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-23P0, GS2-25P0, GS2-27P5, GS2-41P0, GS2-42P0, GS2-43P0, GS2-45P0, GS2-47P5 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Hitachi SJ-P1 inverters on the built-in RS485 port in Modbus-RTU mode, register layout of firmware Ver. 2.00 (User's Guide NT251BX-2, Rev. 6).
Also known as: SJ-P1, P1-xxxxx-L, P1-xxxxx-H
All variable frequency drives Modbus register maps →
Source: HV600 Narrow & Enclosed Bypass Technical Reference · SIEPYAIH6B01F · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.