Variable frequency drive · Modbus register map

Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus register map

Updated 17 November 2026

Short answer

The F7 is Yaskawa's legacy general-purpose vector drive with an embedded Modbus RTU slave on terminals R+/R-/S+/S-. Commands are written to hex registers 0001H-000FH, detailed fault/alarm words sit at 0010H-001AH, status and PID levels at 0020H-003FH, and each parameter has a hex address. This map covers the full Appendix D reference and monitor data plus fault codes and the b1/H5 setup parameters.

This page lists 50 Modbus registers for the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
F7 drive (CIMR-F7U, legacy) - Modbus RTU
Equipment type
Variable frequency drive
Registers
50 (18 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
CIMR-F7U, F7U, F7 Drive
Source document
F7 Drive User Manual (Appendix D Communications) · TM.F7.01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU

Integration in brief

Set H5-01..H5-03 at the keypad and power-cycle, set b1-01 = 2 and b1-02 = 2, then write 0001H and 0002H with function 10H and poll 0020H-002DH for status and faults.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Operation commandBITMAP16Run/stop and resetRead/write
HR 2Frequency referenceUINT16Frequency referenceRead/write
HR 32Drive statusBITMAP16Drive statusRead
HR 33Fault details (0021H)BITMAP16Fault detailsRead
HR 36Output frequency (U1-02)UINT16Output frequencyRead
HR 44Drive status 2BITMAP16Drive status 2 incl. comm timeoutRead
HR 128Current fault (U2-01)UINT16Current fault codeRead
HR 25Alarm content 1BITMAP16Alarm content 1Read

Enable Modbus control & writes

H5-01 address (default 1Fh, 0-20h), H5-02 baud (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 select serial communication for reference and run.

Communication loss & watchdog

H5-05 = 1 (default) enables communication fault (CE) detection; H5-04 selects the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002CH bit F shows a comm time-out. No detection-time parameter is listed for the F7.

Byte order & addressing

Network setup

Watch out for

Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HOperation commandRun forward/reverse, external fault, reset, network inputs S3-S8.BITMAP16Read/writebit 0 = Run forward; bit 1 = Run reverse; bit 2 = External fault (EFO); bit 3 = Fault reset; bit 4 = ComNet; bit 5 = ComCtrl; bit 6 = Multi-function input command 3 (S3); bit 7 = Multi-function input command 4 (S4); bit 8 = Multi-function input command 5 (S5); bit 9 = Multi-function input command 6 (S6); bit 10 = Multi-function input command 7 (S7); bit 11 = Multi-function input command 8 (S8)
HR2doc 0002HFrequency referenceUnits set by o1-03; unscaled here.UINT16Read/write
HR6doc 0006HPID setpointUsed when 000FH bit 1 is set.UINT16Read/write
HR7doc 0007HAnalog output 1 (FM) setting-11 V = -726 ... 11 V = 726 (10 V = 660).INT16Read/write
HR8doc 0008HAnalog output 2 (AM) setting-11 V = -726 ... 11 V = 726 (10 V = 660).INT16Read/write
HR9doc 0009HMulti-function contact output settingsBITMAP16Read/writebit 0 = Digital output 1 (M1-M2) on; bit 1 = Digital output 2 (M3-M4) on; bit 2 = Digital output 3 (M5-M6) on; bit 6 = Use bit 7 for fault contact MA-MC; bit 7 = Fault contact (MA-MC) on
HR15doc 000FHReference selection settingsBITMAP16Read/writebit 1 = Input PID setpoint enabled; bit 12 = Broadcast terminal S5 input enabled; bit 13 = Broadcast terminal S6 input enabled; bit 14 = Broadcast terminal S7 input enabled; bit 15 = Broadcast terminal S8 input enabled
HR16doc 0010HStatus signalBITMAP16Readbit 0 = Run command; bit 1 = At zero speed; bit 2 = Reverse operation; bit 3 = Fault reset signal; bit 4 = Speed agree; bit 5 = Drive ready; bit 6 = Alarm; bit 7 = Fault; bit 14 = ComRef; bit 15 = ComCtrl
HR17doc 0011HFault details (0011H)BITMAP16Readbit 0 = OPE error; bit 1 = Err error; bit 2 = Program mode
HR18doc 0012HoPE detailsoPE error code.UINT16Read1 = OPE01; 2 = OPE02; 3 = OPE03; 6 = OPE06; 10 = OPE10; 11 = OPE11
HR20doc 0014HFault content 1BITMAP16Readbit 0 = Fuse blown (FU); bit 1 = DC bus undervoltage (UV1); bit 2 = Control power supply undervoltage (UV2); bit 3 = Main circuit answerback (UV3); bit 5 = Ground fault (GF); bit 6 = Overcurrent (OC); bit 7 = Overvoltage (OV); bit 8 = Heatsink overtemperature (OH); bit 9 = Drive overheat (OH1); bit 10 = Motor overload (OL1); bit 11 = Drive overload (OL2); bit 12 = Overtorque 1 (OL3); bit 13 = Overtorque 2 (OL4); bit 14 = Dynamic braking transistor (RR); bit 15 = Dynamic braking resistor (RH)
HR21doc 0015HFault content 2BITMAP16Readbit 0 = External fault 3 (EF3); bit 1 = External fault 4 (EF4); bit 2 = External fault 5 (EF5); bit 3 = External fault 6 (EF6); bit 4 = External fault 7 (EF7); bit 5 = External fault 8 (EF8); bit 7 = Overspeed (OS); bit 8 = Speed deviation (DEV); bit 9 = PG open (PGO); bit 10 = Input phase loss (PF); bit 11 = Output phase loss (LF); bit 12 = DCCT fault (CF); bit 13 = Operator disconnect (OPR); bit 14 = EEPROM write-in fault (ERR)
HR22doc 0016HFault content 3BITMAP16Readbit 0 = Modbus communication error (CE); bit 1 = Bus error (BUS); bit 2 = SI-F/G communications error (E-15); bit 3 = SI-F/G fail (E-10); bit 4 = Control fault (CF); bit 5 = Zero servo fault (SVE); bit 6 = External fault (EF0)
HR23doc 0017HCPF content 1BITMAP16Readbit 2 = CPF02; bit 3 = CPF03; bit 4 = CPF04; bit 5 = CPF05; bit 6 = CPF06
HR24doc 0018HCPF content 2BITMAP16Readbit 0 = CPF20; bit 1 = CPF21; bit 2 = CPF22; bit 3 = CPF23
HR25doc 0019HAlarm content 1BITMAP16Readbit 0 = Undervoltage (UV); bit 1 = Overvoltage (OV); bit 2 = Heatsink overtemperature (OH); bit 3 = Drive overheat fault (OH1); bit 4 = Overtorque 1 (OL3); bit 5 = Overtorque 2 (OL4); bit 6 = 2-wire sequence input (EF); bit 7 = External baseblock (BB); bit 8 = External fault 3 (EF3); bit 9 = External fault 4 (EF4); bit 10 = External fault 5 (EF5); bit 11 = External fault 6 (EF6); bit 12 = External fault 7 (EF7); bit 13 = External fault 8 (EF8); bit 14 = Cooling fan (FAN); bit 15 = Overspeed (OS)
HR26doc 001AHAlarm content 2BITMAP16Readbit 0 = Speed deviation (DEV); bit 1 = PG open (PGO); bit 2 = Operator disconnected (OPR); bit 3 = Modbus communication (CE); bit 4 = Bus error (BUS); bit 5 = Waiting for transmission (CALL); bit 6 = Motor overload (OL1); bit 7 = Drive overload (OL2); bit 8 = SI-R/G alarm (E-15); bit 9 = External fault (EF0)
HR32doc 0020HDrive statusBITMAP16Readbit 0 = Operating; bit 1 = Reverse operation; bit 2 = Drive start-up complete; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Multi-function output 1 (M1-M2) on; bit 6 = Multi-function output 2 (M3-M4) on; bit 7 = Multi-function output 3 (M5-M6) on
HR33doc 0021HFault details (0021H)BITMAP16Readbit 0 = Overcurrent (OC) or ground fault (GF); bit 1 = Main circuit overvoltage (OV); bit 2 = Drive overload (OL2); bit 3 = Drive overheat (OH1, OH2); bit 5 = Fuse blown (PUF); bit 6 = PID feedback reference lost (FbL); bit 7 = External error (EF, EFO); bit 8 = Hardware error (CPF); bit 9 = Motor overload (OL1) or overtorque 1 (OL3); bit 10 = PG open (PGO), overspeed (OS) or speed deviation (DEV); bit 11 = Main circuit undervoltage (UV) alarm; bit 12 = UV1, UV2 or UV3; bit 13 = Output phase loss (LF); bit 14 = Modbus communication error (CE); bit 15 = Operator disconnected (OPR)
HR34doc 0022HData link statusBITMAP16Readbit 0 = Writing data; bit 3 = Upper/lower limit errors; bit 4 = Data integrity error
HR35doc 0023HFrequency reference (U1-01)Raw; units follow o1-03.UINT16Read
HR36doc 0024HOutput frequency (U1-02)Raw; units follow o1-03.UINT16Read
HR43doc 002BHSequence input statusBITMAP16Readbit 0 = S1 on; bit 1 = S2 on; bit 2 = S3 on; bit 3 = S4 on; bit 4 = S5 on; bit 5 = S6 on; bit 6 = S7 on; bit 7 = S8 on
HR44doc 002CHDrive status 2BITMAP16Readbit 0 = Operating; bit 1 = Zero speed; bit 2 = Frequency agree; bit 3 = Desired frequency agree; bit 4 = Frequency detection 1 (<= L4-01); bit 5 = Frequency detection 2 (>= L4-01); bit 6 = Drive start-up completed; bit 7 = Low voltage detected; bit 8 = Baseblock; bit 9 = Frequency reference not from communication; bit 10 = Run command not from communication; bit 11 = Overtorque detected; bit 12 = Frequency reference lost; bit 13 = Retrying error; bit 14 = Error (incl. Modbus time-out); bit 15 = Modbus communications time-out
HR45doc 002DHMulti-function digital output statusBITMAP16Readbit 0 = Output 1 (M1-M2) on; bit 1 = Output 2 (M3-M4) on; bit 2 = Output 3 (M5-M6) on
HR56doc 0038HPID feedback levelUnsigned; 10 = 1 % of max output frequency.UINT16× 0.1%Read
HR57doc 0039HPID input levelSigned; 10 = 1 % of max output frequency.INT16× 0.1%Read
HR58doc 003AHPID output levelSigned; 10 = 1 % of max output frequency.INT16× 0.1%Read
HR59doc 003BHCPU software numberUINT16Read
HR60doc 003CHFlash software numberUINT16Read
HR61doc 003DHCommunication error detailsLatched until reset.BITMAP16Readbit 0 = CRC error; bit 1 = Invalid data length; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Time-out
HR62doc 003EHkVA settingUINT16Read
HR63doc 003FHControl methodUINT16Read
HR128doc 0080hCurrent fault (U2-01)UINT16Read
HR129doc 0081hLast fault (U2-02)UINT16Read
HR144doc 0090hLast fault (U3-01)UINT16Read
HR145doc 0091hFault message 2 (U3-02)UINT16Read
HR146doc 0092hFault message 3 (U3-03)UINT16Read
HR147doc 0093hFault message 4 (U3-04)UINT16Read
HR384doc 0180hb1-01 Reference sourceUINT16Read/write0 = Operator; 1 = Terminals; 2 = Serial com; 3 = Option PCB
HR385doc 0181hb1-02 Run sourceUINT16Read/write0 = Operator; 1 = Terminals; 2 = Serial com; 3 = Option PCB
HR1061doc 0425hH5-01 Serial comm address0h-20h; default 1Fh.UINT16Read/write
HR1062doc 0426hH5-02 Serial baud rateUINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200
HR1063doc 0427hH5-03 Serial parityUINT16Read/write0 = None; 1 = Even; 2 = Odd
HR1064doc 0428hH5-04 Serial fault selectReaction to a CE fault.UINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = Fast-stop; 3 = Alarm only
HR1065doc 0429hH5-05 Serial fault detectUINT16Read/write0 = Disabled; 1 = Enabled
HR1066doc 042AhH5-06 Transmit wait time5-65 ms.UINT16msRead/write
HR1067doc 042BhH5-07 RTS controlUINT16Read/write0 = Disabled; 1 = Enabled
HR2304doc 0900HEnter command (EEPROM)Write 0 to store parameters in EEPROM and RAM.UINT16Write
HR2320doc 0910HEnter command (RAM only)Write 0 to activate parameters in RAM only.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU

What Modbus registers does the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU have?

This map lists 50 registers: 50 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and go on the wire unchanged: the 03H message example reads starting address 00 20 (drive status). Parameter addresses are the hex values in the TM.F7.11 parameter tables (b1-01 = 0180h, H5-01 = 0425h).

What are the minimum Modbus registers to integrate the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU?

Start with HR 1 Operation command (Run/stop and reset); HR 2 Frequency reference (Frequency reference); HR 32 Drive status (Drive status); HR 33 Fault details (0021H) (Fault details); HR 36 Output frequency (U1-02) (Output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout); HR 128 Current fault (U2-01) (Current fault code); HR 25 Alarm content 1 (Alarm content 1).

How do I enable Modbus control of the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU?

H5-01 address (default 1Fh, 0-20h), H5-02 baud (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 select serial communication for reference and run.

What happens when the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU loses Modbus communication?

H5-05 = 1 (default) enables communication fault (CE) detection; H5-04 selects the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002CH bit F shows a comm time-out. No detection-time parameter is listed for the F7.

Where is the official Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus documentation?

The source is F7 Drive User Manual (Appendix D Communications) (TM.F7.01), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.F7.01&cmd=documents&documentName=TM.F7.01.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: F7 Drive User Manual (Appendix D Communications) · TM.F7.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.