Variable frequency drive · Modbus register map
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus register map
Updated 17 November 2026
The F7 is Yaskawa's legacy general-purpose vector drive with an embedded Modbus RTU slave on terminals R+/R-/S+/S-. Commands are written to hex registers 0001H-000FH, detailed fault/alarm words sit at 0010H-001AH, status and PID levels at 0020H-003FH, and each parameter has a hex address. This map covers the full Appendix D reference and monitor data plus fault codes and the b1/H5 setup parameters.
This page lists 50 Modbus registers for the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- F7 drive (CIMR-F7U, legacy) - Modbus RTU
- Equipment type
- Variable frequency drive
- Registers
- 50 (18 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CIMR-F7U, F7U, F7 Drive
- Source document
- F7 Drive User Manual (Appendix D Communications) · TM.F7.01
Integration notes: Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Set H5-01..H5-03 at the keypad and power-cycle, set b1-01 = 2 and b1-02 = 2, then write 0001H and 0002H with function 10H and poll 0020H-002DH for status and faults.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Operation command | BITMAP16 | Run/stop and reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference | Read/write |
| HR 32 | Drive status | BITMAP16 | Drive status | Read |
| HR 33 | Fault details (0021H) | BITMAP16 | Fault details | Read |
| HR 36 | Output frequency (U1-02) | UINT16 | Output frequency | Read |
| HR 44 | Drive status 2 | BITMAP16 | Drive status 2 incl. comm timeout | Read |
| HR 128 | Current fault (U2-01) | UINT16 | Current fault code | Read |
| HR 25 | Alarm content 1 | BITMAP16 | Alarm content 1 | Read |
Enable Modbus control & writes
H5-01 address (default 1Fh, 0-20h), H5-02 baud (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 select serial communication for reference and run.
Communication loss & watchdog
H5-05 = 1 (default) enables communication fault (CE) detection; H5-04 selects the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002CH bit F shows a comm time-out. No detection-time parameter is listed for the F7.
Byte order & addressing
- Registers and addresses are hex and 0-based.
- Function codes 03H, 06H, 08H and 10H.
- Parameters written over Modbus need an Enter command: 0 to 0900H (EEPROM, 100,000 writes max) or 0910H (RAM only).
- Write 0 to unused bits and never write reserved registers.
Network setup
- Terminals S+, S-, R+, R-; for RS-485 jumper S+ to R+ and S- to R-. Up to 31 drives.
- 8 data bits, 1 stop bit; 1200-19200 baud; parity none/even/odd.
- Power-cycle after changing H5-01..H5-03.
Watch out for
- Fault trace data is not recorded for CPF00, CPF01, CPF03, UV1 and UV2.
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Operation command | Run forward/reverse, external fault, reset, network inputs S3-S8. | BITMAP16 | Read/write | bit 0 = Run forward; bit 1 = Run reverse; bit 2 = External fault (EFO); bit 3 = Fault reset; bit 4 = ComNet; bit 5 = ComCtrl; bit 6 = Multi-function input command 3 (S3); bit 7 = Multi-function input command 4 (S4); bit 8 = Multi-function input command 5 (S5); bit 9 = Multi-function input command 6 (S6); bit 10 = Multi-function input command 7 (S7); bit 11 = Multi-function input command 8 (S8) | |||
| HR | 2doc 0002H | Frequency reference | Units set by o1-03; unscaled here. | UINT16 | Read/write | ||||
| HR | 6doc 0006H | PID setpoint | Used when 000FH bit 1 is set. | UINT16 | Read/write | ||||
| HR | 7doc 0007H | Analog output 1 (FM) setting | -11 V = -726 ... 11 V = 726 (10 V = 660). | INT16 | Read/write | ||||
| HR | 8doc 0008H | Analog output 2 (AM) setting | -11 V = -726 ... 11 V = 726 (10 V = 660). | INT16 | Read/write | ||||
| HR | 9doc 0009H | Multi-function contact output settings | BITMAP16 | Read/write | bit 0 = Digital output 1 (M1-M2) on; bit 1 = Digital output 2 (M3-M4) on; bit 2 = Digital output 3 (M5-M6) on; bit 6 = Use bit 7 for fault contact MA-MC; bit 7 = Fault contact (MA-MC) on | ||||
| HR | 15doc 000FH | Reference selection settings | BITMAP16 | Read/write | bit 1 = Input PID setpoint enabled; bit 12 = Broadcast terminal S5 input enabled; bit 13 = Broadcast terminal S6 input enabled; bit 14 = Broadcast terminal S7 input enabled; bit 15 = Broadcast terminal S8 input enabled | ||||
| HR | 16doc 0010H | Status signal | BITMAP16 | Read | bit 0 = Run command; bit 1 = At zero speed; bit 2 = Reverse operation; bit 3 = Fault reset signal; bit 4 = Speed agree; bit 5 = Drive ready; bit 6 = Alarm; bit 7 = Fault; bit 14 = ComRef; bit 15 = ComCtrl | ||||
| HR | 17doc 0011H | Fault details (0011H) | BITMAP16 | Read | bit 0 = OPE error; bit 1 = Err error; bit 2 = Program mode | ||||
| HR | 18doc 0012H | oPE details | oPE error code. | UINT16 | Read | 1 = OPE01; 2 = OPE02; 3 = OPE03; 6 = OPE06; 10 = OPE10; 11 = OPE11 | |||
| HR | 20doc 0014H | Fault content 1 | BITMAP16 | Read | bit 0 = Fuse blown (FU); bit 1 = DC bus undervoltage (UV1); bit 2 = Control power supply undervoltage (UV2); bit 3 = Main circuit answerback (UV3); bit 5 = Ground fault (GF); bit 6 = Overcurrent (OC); bit 7 = Overvoltage (OV); bit 8 = Heatsink overtemperature (OH); bit 9 = Drive overheat (OH1); bit 10 = Motor overload (OL1); bit 11 = Drive overload (OL2); bit 12 = Overtorque 1 (OL3); bit 13 = Overtorque 2 (OL4); bit 14 = Dynamic braking transistor (RR); bit 15 = Dynamic braking resistor (RH) | ||||
| HR | 21doc 0015H | Fault content 2 | BITMAP16 | Read | bit 0 = External fault 3 (EF3); bit 1 = External fault 4 (EF4); bit 2 = External fault 5 (EF5); bit 3 = External fault 6 (EF6); bit 4 = External fault 7 (EF7); bit 5 = External fault 8 (EF8); bit 7 = Overspeed (OS); bit 8 = Speed deviation (DEV); bit 9 = PG open (PGO); bit 10 = Input phase loss (PF); bit 11 = Output phase loss (LF); bit 12 = DCCT fault (CF); bit 13 = Operator disconnect (OPR); bit 14 = EEPROM write-in fault (ERR) | ||||
| HR | 22doc 0016H | Fault content 3 | BITMAP16 | Read | bit 0 = Modbus communication error (CE); bit 1 = Bus error (BUS); bit 2 = SI-F/G communications error (E-15); bit 3 = SI-F/G fail (E-10); bit 4 = Control fault (CF); bit 5 = Zero servo fault (SVE); bit 6 = External fault (EF0) | ||||
| HR | 23doc 0017H | CPF content 1 | BITMAP16 | Read | bit 2 = CPF02; bit 3 = CPF03; bit 4 = CPF04; bit 5 = CPF05; bit 6 = CPF06 | ||||
| HR | 24doc 0018H | CPF content 2 | BITMAP16 | Read | bit 0 = CPF20; bit 1 = CPF21; bit 2 = CPF22; bit 3 = CPF23 | ||||
| HR | 25doc 0019H | Alarm content 1 | BITMAP16 | Read | bit 0 = Undervoltage (UV); bit 1 = Overvoltage (OV); bit 2 = Heatsink overtemperature (OH); bit 3 = Drive overheat fault (OH1); bit 4 = Overtorque 1 (OL3); bit 5 = Overtorque 2 (OL4); bit 6 = 2-wire sequence input (EF); bit 7 = External baseblock (BB); bit 8 = External fault 3 (EF3); bit 9 = External fault 4 (EF4); bit 10 = External fault 5 (EF5); bit 11 = External fault 6 (EF6); bit 12 = External fault 7 (EF7); bit 13 = External fault 8 (EF8); bit 14 = Cooling fan (FAN); bit 15 = Overspeed (OS) | ||||
| HR | 26doc 001AH | Alarm content 2 | BITMAP16 | Read | bit 0 = Speed deviation (DEV); bit 1 = PG open (PGO); bit 2 = Operator disconnected (OPR); bit 3 = Modbus communication (CE); bit 4 = Bus error (BUS); bit 5 = Waiting for transmission (CALL); bit 6 = Motor overload (OL1); bit 7 = Drive overload (OL2); bit 8 = SI-R/G alarm (E-15); bit 9 = External fault (EF0) | ||||
| HR | 32doc 0020H | Drive status | BITMAP16 | Read | bit 0 = Operating; bit 1 = Reverse operation; bit 2 = Drive start-up complete; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Multi-function output 1 (M1-M2) on; bit 6 = Multi-function output 2 (M3-M4) on; bit 7 = Multi-function output 3 (M5-M6) on | ||||
| HR | 33doc 0021H | Fault details (0021H) | BITMAP16 | Read | bit 0 = Overcurrent (OC) or ground fault (GF); bit 1 = Main circuit overvoltage (OV); bit 2 = Drive overload (OL2); bit 3 = Drive overheat (OH1, OH2); bit 5 = Fuse blown (PUF); bit 6 = PID feedback reference lost (FbL); bit 7 = External error (EF, EFO); bit 8 = Hardware error (CPF); bit 9 = Motor overload (OL1) or overtorque 1 (OL3); bit 10 = PG open (PGO), overspeed (OS) or speed deviation (DEV); bit 11 = Main circuit undervoltage (UV) alarm; bit 12 = UV1, UV2 or UV3; bit 13 = Output phase loss (LF); bit 14 = Modbus communication error (CE); bit 15 = Operator disconnected (OPR) | ||||
| HR | 34doc 0022H | Data link status | BITMAP16 | Read | bit 0 = Writing data; bit 3 = Upper/lower limit errors; bit 4 = Data integrity error | ||||
| HR | 35doc 0023H | Frequency reference (U1-01) | Raw; units follow o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | Output frequency (U1-02) | Raw; units follow o1-03. | UINT16 | Read | ||||
| HR | 43doc 002BH | Sequence input status | BITMAP16 | Read | bit 0 = S1 on; bit 1 = S2 on; bit 2 = S3 on; bit 3 = S4 on; bit 4 = S5 on; bit 5 = S6 on; bit 6 = S7 on; bit 7 = S8 on | ||||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = Operating; bit 1 = Zero speed; bit 2 = Frequency agree; bit 3 = Desired frequency agree; bit 4 = Frequency detection 1 (<= L4-01); bit 5 = Frequency detection 2 (>= L4-01); bit 6 = Drive start-up completed; bit 7 = Low voltage detected; bit 8 = Baseblock; bit 9 = Frequency reference not from communication; bit 10 = Run command not from communication; bit 11 = Overtorque detected; bit 12 = Frequency reference lost; bit 13 = Retrying error; bit 14 = Error (incl. Modbus time-out); bit 15 = Modbus communications time-out | ||||
| HR | 45doc 002DH | Multi-function digital output status | BITMAP16 | Read | bit 0 = Output 1 (M1-M2) on; bit 1 = Output 2 (M3-M4) on; bit 2 = Output 3 (M5-M6) on | ||||
| HR | 56doc 0038H | PID feedback level | Unsigned; 10 = 1 % of max output frequency. | UINT16 | × 0.1 | % | Read | ||
| HR | 57doc 0039H | PID input level | Signed; 10 = 1 % of max output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 58doc 003AH | PID output level | Signed; 10 = 1 % of max output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 59doc 003BH | CPU software number | UINT16 | Read | |||||
| HR | 60doc 003CH | Flash software number | UINT16 | Read | |||||
| HR | 61doc 003DH | Communication error details | Latched until reset. | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Invalid data length; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Time-out | |||
| HR | 62doc 003EH | kVA setting | UINT16 | Read | |||||
| HR | 63doc 003FH | Control method | UINT16 | Read | |||||
| HR | 128doc 0080h | Current fault (U2-01) | UINT16 | Read | |||||
| HR | 129doc 0081h | Last fault (U2-02) | UINT16 | Read | |||||
| HR | 144doc 0090h | Last fault (U3-01) | UINT16 | Read | |||||
| HR | 145doc 0091h | Fault message 2 (U3-02) | UINT16 | Read | |||||
| HR | 146doc 0092h | Fault message 3 (U3-03) | UINT16 | Read | |||||
| HR | 147doc 0093h | Fault message 4 (U3-04) | UINT16 | Read | |||||
| HR | 384doc 0180h | b1-01 Reference source | UINT16 | Read/write | 0 = Operator; 1 = Terminals; 2 = Serial com; 3 = Option PCB | ||||
| HR | 385doc 0181h | b1-02 Run source | UINT16 | Read/write | 0 = Operator; 1 = Terminals; 2 = Serial com; 3 = Option PCB | ||||
| HR | 1061doc 0425h | H5-01 Serial comm address | 0h-20h; default 1Fh. | UINT16 | Read/write | ||||
| HR | 1062doc 0426h | H5-02 Serial baud rate | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200 | ||||
| HR | 1063doc 0427h | H5-03 Serial parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 1064doc 0428h | H5-04 Serial fault select | Reaction to a CE fault. | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast-stop; 3 = Alarm only | |||
| HR | 1065doc 0429h | H5-05 Serial fault detect | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1066doc 042Ah | H5-06 Transmit wait time | 5-65 ms. | UINT16 | ms | Read/write | |||
| HR | 1067doc 042Bh | H5-07 RTS control | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 2304doc 0900H | Enter command (EEPROM) | Write 0 to store parameters in EEPROM and RAM. | UINT16 | Write | ||||
| HR | 2320doc 0910H | Enter command (RAM only) | Write 0 to activate parameters in RAM only. | UINT16 | Write |
Notes on this map
- Parameter addresses (b1, H5) and U2/U3 monitor addresses come from the free F7 Drive Parameter Access Technical Manual TM.F7.11 (2005-11-30): https://www.yaskawa.com/delegate/getAttachment?documentId=TM.F7.11&cmd=documents&documentName=TM.F7.11.pdf (Table 4.4 monitor registers, Tables 4.6 and 4.11 parameters).
- Left out because neither manual gives units or resolution for them: 0025H-0028H and 0031H, and the 0040H-006CH U1 monitor block.
- b1-01/b1-02 also accept codes beyond 3 (pulse input, CASE reference); only the common 0-3 selections are listed.
- Fault code numbers for U2/U3 registers are not tabulated, so no value list is given.
- The Modbus TCP/IP DPRAM table in TM.F7.11 (registers 2000h-2010h) applies only to the Ethernet option card and is not included.
- Broadcast (slave 0): 0001H bit 0 run, bit 1 reverse, bits 5/6 inputs S3/S4, bits C-F S5-S8 (enabled by 000FH bits C-F); 0002H = 30000 per 100 % of max frequency.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
What Modbus registers does the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU have?
This map lists 50 registers: 50 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and go on the wire unchanged: the 03H message example reads starting address 00 20 (drive status). Parameter addresses are the hex values in the TM.F7.11 parameter tables (b1-01 = 0180h, H5-01 = 0425h).
What are the minimum Modbus registers to integrate the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU?
Start with HR 1 Operation command (Run/stop and reset); HR 2 Frequency reference (Frequency reference); HR 32 Drive status (Drive status); HR 33 Fault details (0021H) (Fault details); HR 36 Output frequency (U1-02) (Output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout); HR 128 Current fault (U2-01) (Current fault code); HR 25 Alarm content 1 (Alarm content 1).
How do I enable Modbus control of the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU?
H5-01 address (default 1Fh, 0-20h), H5-02 baud (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 select serial communication for reference and run.
What happens when the Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU loses Modbus communication?
H5-05 = 1 (default) enables communication fault (CE) detection; H5-04 selects the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002CH bit F shows a comm time-out. No detection-time parameter is listed for the F7.
Where is the official Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU Modbus documentation?
The source is F7 Drive User Manual (Appendix D Communications) (TM.F7.01), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.F7.01&cmd=documents&documentName=TM.F7.01.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Pump (circulator / E-pump / pump drive)
Grundfos E-pumps (MAGNA3, TPE, CRE, CUE) via CIM 200 / CIM 500
Grundfos E-pumps (CRE/CRNE/CRIE, MTRE, CHIE, CME, TPE, TPE Series 2000, NBE/NKE), CUE drives and MAGNA3 with a CIM/CIU 200, CIM/CIU 500 or built-in SoftCIM.
Also known as: MAGNA3, TPE, TPE Series 2000, CRE, CRNE, CRIE, MTRE, CHIE, CME, NBE, NKE, CUE, MGE, CIM 200, CIU 200, CIM 500, CIU 500, SoftCIM Modbus RTU
All variable frequency drives Modbus register maps →
Source: F7 Drive User Manual (Appendix D Communications) · TM.F7.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.