- E7 HVAC drive (CIMR-E7U) - Modbus RTU
Variable frequency drive (HVAC) · Modbus register map
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus register map
Updated 17 November 2026
The E7 is Yaskawa's legacy HVAC fan/pump drive with a built-in RS-422/485 port that speaks Memobus/Modbus RTU (or Metasys N2 / APOGEE FLN). All registers are hex: commands at 0001h-000Fh, detailed fault and alarm words from 0010h, status from 0020h, U1/U2/U3 monitors from 0040h, and every parameter at its own address. This map covers the command block, all status/fault words, the main monitors with their published units, and the b1/H5 communication parameters.
This page lists 66 Modbus registers for the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- E7 HVAC drive (CIMR-E7U) - Modbus RTU
- Equipment type
- Variable frequency drive (HVAC)
- Registers
- 66 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Firmware
- Manual revision 3016
- Also known as
- CIMR-E7U, E7U, E7 Drive
Integration notes: Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Set H5-08 = 0, H5-01..H5-03 at the keypad and power-cycle; set b1-01 = 2 and b1-02 = 2 to take reference and run from Modbus. Write 0001h/0002h together with function 10h and poll 0020h-002Dh plus 0042h-0046h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Command | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference | Read/write |
| HR 32 | Inverter status (0020h) | BITMAP16 | Run/ready/fault | Read |
| HR 33 | Fault contents (summary) | BITMAP16 | Fault summary | Read |
| HR 44 | Inverter status (002Ch) | BITMAP16 | Status incl. comm timeout | Read |
| HR 65 | Output frequency (U1-02) | UINT16 | Output frequency | Read |
| HR 66 | Output current (U1-03) | UINT16 | Output current | Read |
| HR 128 | Current fault (U2-01) | UINT16 | Current fault code | Read |
Enable Modbus control & writes
H5-08 = 0 selects Memobus/Modbus (1 = Metasys N2, 2 = APOGEE FLN). Set H5-01 (default 1Fh), H5-02 (default 3 = 9600) and H5-03 (default none) and cycle power. b1-01 = 2 and b1-02 = 2 hand reference and run to serial communications.
Communication loss & watchdog
H5-05 = 1 (default) enables CE detection after H5-09 (default 2.0 s); H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default), 4 run at d1-04. 002Ch bit F flags a comm timeout.
Byte order & addressing
- Registers and the slave address are hex.
- Function codes 03h, 06h, 08h and 10h; the parameter manual allows 1-8 registers per read.
- Serial parameter writes go to RAM; write 0 to 0900h (ENTER) to keep them over power loss (100,000 write limit). Run-locked parameters need 0910h (ACCEPT).
- Network multi-function inputs are ORed with the terminals.
Network setup
- RS-485: jumper S+ to R+ and S- to R-; up to 31 drives.
- Slave address 1-20h (1-32), default 1Fh; 0 is broadcast.
- 8 data bits, 1 stop bit; 1200-19200 baud.
Watch out for
- H5-08 must be 0; an E7 left on N2 or FLN will not answer Modbus.
- Fault trace values are not stored for CPF00/CPF01/CPF03, UV1 and UV2.
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001h | Command | Run/stop, direction, external fault, reset, network multi-function inputs. | BITMAP16 | Read/write | bit 0 = Run (0 = stop); bit 1 = Reverse (0 = forward); bit 2 = External fault; bit 3 = Fault reset; bit 4 = ComNet; bit 5 = ComCtrl; bit 6 = Multi-function input 1 (S3, H1-01); bit 7 = Multi-function input 2 (S4, H1-02); bit 8 = Multi-function input 3 (S5, H1-03); bit 9 = Multi-function input 4 (S6, H1-04); bit 10 = Multi-function input 5 (S7, H1-05) | |||
| HR | 2doc 0002h | Frequency reference | Units depend on the display-unit setting; unscaled here. | UINT16 | Read/write | ||||
| HR | 6doc 0006h | PID setpoint | Used when 000Fh bit 1 is set. | UINT16 | Read/write | ||||
| HR | 7doc 0007h | Analog output 1 setting | Range -11 to 11 V as -726 to 726. | INT16 | Read/write | ||||
| HR | 8doc 0008h | Analog output 2 setting | Range -11 to 11 V as -726 to 726. | INT16 | Read/write | ||||
| HR | 9doc 0009h | Outputs | Network control of digital and fault outputs. | BITMAP16 | Read/write | bit 0 = Multi-function output 1; bit 1 = Multi-function output 2; bit 2 = Multi-function output 3; bit 6 = Fault relay output; bit 7 = Fault relay N.C. | |||
| HR | 15doc 000Fh | Command selection | Enables 0006h PID value and broadcast S5-S7 inputs. | BITMAP16 | Read/write | bit 1 = PID value 0006h is used; bit 12 = Broadcast terminal S5 enable; bit 13 = Broadcast terminal S6 enable; bit 14 = Broadcast terminal S7 enable | |||
| HR | 16doc 0010h | Inverter status (0010h) | BITMAP16 | Read | bit 0 = Run; bit 3 = Reset signal; bit 4 = Speed agree; bit 5 = Inverter ready; bit 6 = Minor fault; bit 7 = Major fault; bit 14 = ComRef; bit 15 = ComCtrl | ||||
| HR | 20doc 0014h | Fault contents 1 | BITMAP16 | Read | bit 0 = PUF fuse; bit 1 = UV1 main circuit undervoltage; bit 2 = UV2 control circuit undervoltage; bit 3 = UV3 MC error; bit 5 = GF ground fault; bit 6 = OC overcurrent; bit 7 = OV overvoltage; bit 8 = OH inverter overheat; bit 9 = OH1 inverter overheat warning; bit 10 = OL1 motor overload; bit 11 = OL2 inverter overload; bit 12 = OL3 overtorque 1; bit 13 = OL4 overtorque 2; bit 14 = RR braking resistor fault; bit 15 = RH braking resistor overheat | ||||
| HR | 21doc 0015h | Fault contents 2 | BITMAP16 | Read | bit 0 = EF3 external fault 3; bit 1 = EF4 external fault 4; bit 2 = EF5 external fault 5; bit 3 = EF6 external fault 6; bit 4 = EF7 external fault 7; bit 7 = OS overspeed; bit 8 = DEV excessive speed bias; bit 9 = PGO PG line interruption; bit 10 = PF input phase fault; bit 11 = LF output phase fault; bit 12 = OH3 overheat; bit 13 = OPR operator bypass fault; bit 14 = ERR EEPROM write fault; bit 15 = OH4 motor overheat fault | ||||
| HR | 22doc 0016h | Fault contents 3 | BITMAP16 | Read | bit 0 = CE communications fault; bit 1 = BUS communications option fault; bit 2 = E-15 SI-F/G communication fault; bit 3 = E-10 SI-F/G fault; bit 4 = CF control fault; bit 5 = SVE zero servo fault; bit 6 = EF0 communications option external fault; bit 7 = FBL PID feedback error; bit 8 = UL3 undertorque 1; bit 9 = UL4 undertorque 2; bit 10 = OL7 high slip braking overload | ||||
| HR | 23doc 0017h | CPF contents 1 | BITMAP16 | Read | bit 2 = CPF02 base block circuit error; bit 3 = CPF03 EEPROM error; bit 4 = CPF04 CPU internal A/D error; bit 5 = CPF05 CPU external A/D error; bit 6 = CPF06 option card connection error | ||||
| HR | 24doc 0018h | CPF contents 2 | BITMAP16 | Read | bit 0 = CPF20 option card A/D error; bit 1 = CPF21 option card self-diagnostic error; bit 2 = CPF22 option card code error; bit 3 = CPF23 option card DP-RAM error | ||||
| HR | 25doc 0019h | Minor fault contents 1 | Alarms. | BITMAP16 | Read | bit 0 = UV undervoltage; bit 1 = OV overvoltage; bit 2 = OH inverter overheat; bit 3 = OH2 inverter overheat warning; bit 4 = OL3 overtorque 1; bit 5 = OL4 overtorque 2; bit 6 = EF 2-wire sequence input fault; bit 7 = BB baseblock; bit 8 = EF3 external fault 3; bit 9 = EF4 external fault 4; bit 10 = EF5 external fault 5; bit 11 = EF6 external fault 6; bit 12 = EF7 external fault 7; bit 15 = OS overspeed | |||
| HR | 26doc 001Ah | Minor fault contents 2 | Alarms. | BITMAP16 | Read | bit 0 = DEV excessive speed bias; bit 1 = PGO PG line interruption; bit 2 = OPR operator bypass fault; bit 3 = CE communications fault; bit 4 = BUS communications option fault; bit 5 = CALL waiting for communications; bit 6 = OL1 motor overload; bit 7 = OL2 inverter overload; bit 8 = E-15 SI-F/G communication fault; bit 9 = E-10 SI-F/G fault; bit 10 = Motor switch; bit 11 = FBL PID feedback error; bit 12 = CALL waiting for communications; bit 13 = UL3 undertorque 1; bit 14 = UL4 undertorque 2; bit 15 = Communication test fault | |||
| HR | 27doc 001Bh | Minor fault contents 3 | Alarms. | BITMAP16 | Read | bit 0 = OH3 motor overheat alarm; bit 1 = DNE drive not enabled | |||
| HR | 32doc 0020h | Inverter status (0020h) | BITMAP16 | Read | bit 0 = Run; bit 1 = Reverse; bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Multi-function output 1; bit 6 = Multi-function output 2; bit 7 = Multi-function output 3 | ||||
| HR | 33doc 0021h | Fault contents (summary) | BITMAP16 | Read | bit 0 = OC or GF overcurrent/ground fault; bit 1 = OV overvoltage; bit 2 = OL2 inverter overload; bit 3 = OH1 or OH2 overheat; bit 4 = RR or RH braking resistor fault; bit 5 = PUF fuse fault; bit 6 = FBL PID feedback fault; bit 7 = EF external fault; bit 8 = CPF hardware fault; bit 9 = OL1, OL3 or OL4 overload/overtorque; bit 10 = PGO, OS or DEV speed deviation; bit 11 = UV undervoltage; bit 12 = UV1, UV2, UV3 or power off; bit 13 = SPI or SPO input/output phase fault; bit 14 = CE communications error; bit 15 = OPR operator error | ||||
| HR | 34doc 0022h | Data link status | BITMAP16 | Read | bit 0 = Data writing; bit 3 = Data limit fault; bit 4 = Data compatibility fault | ||||
| HR | 43doc 002Bh | Sequence input status | Terminals 1-7 closed. | BITMAP16 | Read | bit 0 = Terminal 1 closed; bit 1 = Terminal 2 closed; bit 2 = Terminal 3 closed; bit 3 = Terminal 4 closed; bit 4 = Terminal 5 closed; bit 5 = Terminal 6 closed; bit 6 = Terminal 7 closed | |||
| HR | 44doc 002Ch | Inverter status (002Ch) | BITMAP16 | Read | bit 0 = Run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = Random speed agree; bit 4 = Frequency detect 1; bit 5 = Frequency detect 2; bit 6 = Inverter ready; bit 7 = Undervoltage; bit 8 = Baseblock; bit 9 = Frequency reference not from communications; bit 10 = Run command not from communications; bit 11 = Overtorque; bit 12 = Loss of frequency reference; bit 13 = Fault retry; bit 14 = Fault; bit 15 = Communications timeout | ||||
| HR | 45doc 002Dh | Multi-function output status | BITMAP16 | Read | bit 0 = Multi-function output 1; bit 1 = Multi-function output 2; bit 2 = Multi-function output 3 | ||||
| HR | 59doc 003Bh | CPU revision | UINT16 | Read | |||||
| HR | 60doc 003Ch | Flash ID (software revision) | UINT16 | Read | |||||
| HR | 61doc 003Dh | Communications error | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | ||||
| HR | 62doc 003Eh | kVA setting | See parameter o2-04. | UINT16 | Read | ||||
| HR | 64doc 0040h | Frequency reference (U1-01) | Listed in 0.01 Hz; see notes on display units. | UINT16 | Read | ||||
| HR | 65doc 0041h | Output frequency (U1-02) | Listed in 0.01 Hz; see notes on display units. | UINT16 | Read | ||||
| HR | 66doc 0042h | Output current (U1-03) | UINT16 | × 0.1 | A | Read | |||
| HR | 69doc 0045h | Output voltage (U1-06) | UINT16 | × 0.1 | V | Read | |||
| HR | 70doc 0046h | DC bus voltage (U1-07) | UINT16 | V | Read | ||||
| HR | 73doc 0049h | Input terminal status (U1-10) | BITMAP16 | Read | bit 0 = Fwd run (S1); bit 1 = Rev run (S2); bit 2 = S3; bit 3 = S4; bit 4 = S5; bit 5 = S6; bit 6 = S7 | ||||
| HR | 74doc 004Ah | Output terminal status (U1-11) | BITMAP16 | Read | bit 0 = Multi-function output 1; bit 1 = Multi-function output 2; bit 2 = Multi-function output 3; bit 7 = Fault output | ||||
| HR | 75doc 004Bh | Drive operation status (U1-12) | BITMAP16 | Read | bit 0 = FWD run; bit 1 = Zero speed; bit 2 = REV run; bit 3 = Reset; bit 4 = Speed agree; bit 5 = Drive ready; bit 6 = Minor fault; bit 7 = Major fault | ||||
| HR | 76doc 004Ch | Elapsed time (U1-13) | UINT16 | h | Read | ||||
| HR | 77doc 004Dh | Flash ID (U1-14) | Software revision. | UINT16 | Read | ||||
| HR | 78doc 004Eh | Terminal A1 input level (U1-15) | Percent of 10 V. | UINT16 | × 0.1 | % | Read | ||
| HR | 79doc 04Fh | Terminal A2 input level (U1-16) | Percent of 20 mA (or 10 V). | UINT16 | × 0.1 | % | Read | ||
| HR | 92doc 005Ch | kWh (U1-29) | Low part of energy count. | UINT16 | kWh | Read | |||
| HR | 93doc 005Dh | MWh (U1-30) | High part of energy count. | UINT16 | MWh | Read | |||
| HR | 97doc 0061h | First parameter causing OPE (U1-34) | UINT16 | Read | |||||
| HR | 103doc 0067h | FAN elapsed time (U1-40) | UINT16 | h | Read | ||||
| HR | 128doc 0080h | Current fault (U2-01) | UINT16 | Read | |||||
| HR | 129doc 0081h | Previous fault (U2-02) | UINT16 | Read | |||||
| HR | 132doc 0084h | Output current at previous fault (U2-05) | UINT16 | × 0.1 | A | Read | |||
| HR | 134doc 0086h | Output voltage at previous fault (U2-07) | UINT16 | × 0.1 | V | Read | |||
| HR | 135doc 0087h | DC bus voltage at previous fault (U2-08) | UINT16 | V | Read | ||||
| HR | 141doc 008Dh | Elapsed time at previous fault (U2-14) | UINT16 | h | Read | ||||
| HR | 384doc 0180h | b1-01 Reference source | UINT16 | Read/write | 0 = Operator; 1 = Terminals; 2 = Serial com; 3 = Option PCB | ||||
| HR | 385doc 0181h | b1-02 Run source | UINT16 | Read/write | 0 = Operator; 1 = Terminals; 2 = Serial com; 3 = Option PCB | ||||
| HR | 386doc 0182h | b1-03 Stopping method | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = DC injection to stop; 3 = Coast with timer (C1-09) | ||||
| HR | 1061doc 0425h | H5-01 Serial comm address | 0h-20h; default 1Fh. | UINT16 | Read/write | ||||
| HR | 1062doc 0426h | H5-02 Serial baud rate | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200 | ||||
| HR | 1063doc 0427h | H5-03 Serial parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 1064doc 0428h | H5-04 Serial fault select | Reaction to a CE communication fault. | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast-stop; 3 = Alarm only; 4 = Run at d1-04 | |||
| HR | 1065doc 0429h | H5-05 Serial fault detect | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1066doc 042Ah | H5-06 Transmit wait time | 5-65 ms. | UINT16 | ms | Read/write | |||
| HR | 1067doc 042Bh | H5-07 RTS control | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1076doc 0434h | H5-08 Protocol select | UINT16 | Read/write | 0 = Memobus (Modbus); 1 = N2 (Metasys); 2 = FLN (APOGEE) | ||||
| HR | 1077doc 0435h | H5-09 CE detect time | 0.0-10.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 2048doc 0800h | Most recent fault (U3-01) | Also readable at 0090h. | UINT16 | Read | ||||
| HR | 2049doc 0801h | 2nd most recent fault (U3-02) | UINT16 | Read | |||||
| HR | 2050doc 0802h | 3rd most recent fault (U3-03) | UINT16 | Read | |||||
| HR | 2051doc 0803h | 4th most recent fault (U3-04) | UINT16 | Read | |||||
| HR | 2304doc 900 | ENTER | Write 0 to copy RAM parameters to non-volatile memory. | UINT16 | Write | ||||
| HR | 2320doc 910 | ACCEPT | Write 0 to move run-locked parameter writes into active RAM. | UINT16 | Write |
Notes on this map
- 0040h/0041h frequency monitors are printed as 'Units 0.01Hz' in TM.E7.11, but the E7 user manual (TM.E7.01) says frequency monitor units change with o1-03; they are left unscaled here. 0002h frequency reference likewise depends on the display-unit setting.
- Left out because the sign is not stated: 0028h/0032h torque, 0047h/0033h output power, 0063h-0065h PID input/output/setpoint, 0068h heatsink temperature, 0051h Iq, and 0038h-003Ah PID levels (no units printed in TM.E7.11).
- 0011h operator status and 0012h OPE bits and 0013h product code are not included.
- Fault code numbers for U2-01/U3-01 are not tabulated in TM.E7.11, so no value list is given.
- Broadcast (slave 0): 0001h bit 0 run, bit 1 reverse, bits 5/6 multi-function inputs S3/S4, bits C-E S5-S7 (enabled by 000Fh bits C-E); 0002h frequency reference fixed at 30000 = 100 % of maximum frequency.
- The register map comes from TM.E7.11; the E7 user manual TM.E7.01 Appendix D gives the same data-table layout.
- From the free E7 user manual TM.E7.01 (Appendix D, https://www.yaskawa.com/delegate/getAttachment?documentId=TM.E7.01&cmd=documents&documentName=TM.E7.01.pdf): 8 data bits and 1 stop bit, up to 31 slaves, ENTER/RAM-only registers 0900H/0910H, and no fault trace for CPF00, CPF01, CPF03, UV1 and UV2.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
What Modbus registers does the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU have?
This map lists 66 registers: 66 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All addresses are hex and go into the request unchanged: the manual's read example sets starting register 00h 20h to read 0020h-0023h. Parameters use the hex address in the parameter table (b1-01 = 0180h, H5-01 = 0425h). ENTER/ACCEPT are printed as 900/910, i.e. 0900h/0910h.
What are the minimum Modbus registers to integrate the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU?
Start with HR 1 Command (Run/stop, direction, reset); HR 2 Frequency reference (Frequency reference); HR 32 Inverter status (0020h) (Run/ready/fault); HR 33 Fault contents (summary) (Fault summary); HR 44 Inverter status (002Ch) (Status incl. comm timeout); HR 65 Output frequency (U1-02) (Output frequency); HR 66 Output current (U1-03) (Output current); HR 128 Current fault (U2-01) (Current fault code).
How do I enable Modbus control of the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU?
H5-08 = 0 selects Memobus/Modbus (1 = Metasys N2, 2 = APOGEE FLN). Set H5-01 (default 1Fh), H5-02 (default 3 = 9600) and H5-03 (default none) and cycle power. b1-01 = 2 and b1-02 = 2 hand reference and run to serial communications.
What happens when the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU loses Modbus communication?
H5-05 = 1 (default) enables CE detection after H5-09 (default 2.0 s); H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default), 4 run at d1-04. 002Ch bit F flags a comm timeout.
Where is the official Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus documentation?
The source is E7 Drive Parameter Access Technical Manual (TM.E7.11), revision 2004-05-31, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.E7.11&cmd=documents&documentName=TM.E7.11.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
AutomationDirect DURApulse GS3 AC drive
All GS3 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: DURApulse GS3, GS3-21P0, GS3-22P0, GS3-23P0, GS3-25P0, GS3-27P5, GS3-2010, GS3-2015, GS3-2020, GS3-2025 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)
VACON 100 INDUSTRIAL, FLOW, HVAC and 100 X drives using the built-in RS-485 Modbus RTU or Ethernet Modbus TCP/UDP (manual DPD00156D); application IDs per the VACON 100 INDUSTRIAL application guide DPD00927L (FW0072V037).
Also known as: VACON 100 INDUSTRIAL, VACON 100 FLOW, VACON 100 HVAC, VACON 100 X, VACON0100 - Variable frequency drive (HVAC / pump)
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Fuji Electric FRENIC-HVAC (AR) and FRENIC-AQUA (AQ) inverters on the RS-485 port in Modbus RTU mode (y10 = 0); RS-485 Communication User's Manual 24A7-E-0021b.
Also known as: FRENIC-HVAC, FRENIC-AQUA, FRN-AR, FRN-AQ
All variable frequency drives Modbus register maps →
Source: E7 Drive Parameter Access Technical Manual · TM.E7.11 · rev. 2004-05-31. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.