Variable frequency drive (HVAC) · Modbus register map

Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus register map

Updated 17 November 2026

Short answer

The E7 is Yaskawa's legacy HVAC fan/pump drive with a built-in RS-422/485 port that speaks Memobus/Modbus RTU (or Metasys N2 / APOGEE FLN). All registers are hex: commands at 0001h-000Fh, detailed fault and alarm words from 0010h, status from 0020h, U1/U2/U3 monitors from 0040h, and every parameter at its own address. This map covers the command block, all status/fault words, the main monitors with their published units, and the b1/H5 communication parameters.

This page lists 66 Modbus registers for the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
E7 HVAC drive (CIMR-E7U) - Modbus RTU
Equipment type
Variable frequency drive (HVAC)
Registers
66 (21 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Firmware
Manual revision 3016
Also known as
CIMR-E7U, E7U, E7 Drive
Source document
E7 Drive Parameter Access Technical Manual · TM.E7.11 · rev. 2004-05-31
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU

Integration in brief

Set H5-08 = 0, H5-01..H5-03 at the keypad and power-cycle; set b1-01 = 2 and b1-02 = 2 to take reference and run from Modbus. Write 0001h/0002h together with function 10h and poll 0020h-002Dh plus 0042h-0046h.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1CommandBITMAP16Run/stop, direction, resetRead/write
HR 2Frequency referenceUINT16Frequency referenceRead/write
HR 32Inverter status (0020h)BITMAP16Run/ready/faultRead
HR 33Fault contents (summary)BITMAP16Fault summaryRead
HR 44Inverter status (002Ch)BITMAP16Status incl. comm timeoutRead
HR 65Output frequency (U1-02)UINT16Output frequencyRead
HR 66Output current (U1-03)UINT16Output currentRead
HR 128Current fault (U2-01)UINT16Current fault codeRead

Enable Modbus control & writes

H5-08 = 0 selects Memobus/Modbus (1 = Metasys N2, 2 = APOGEE FLN). Set H5-01 (default 1Fh), H5-02 (default 3 = 9600) and H5-03 (default none) and cycle power. b1-01 = 2 and b1-02 = 2 hand reference and run to serial communications.

Communication loss & watchdog

H5-05 = 1 (default) enables CE detection after H5-09 (default 2.0 s); H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default), 4 run at d1-04. 002Ch bit F flags a comm timeout.

Byte order & addressing

Network setup

Watch out for

Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

66 of 66 shown
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001hCommandRun/stop, direction, external fault, reset, network multi-function inputs.BITMAP16Read/writebit 0 = Run (0 = stop); bit 1 = Reverse (0 = forward); bit 2 = External fault; bit 3 = Fault reset; bit 4 = ComNet; bit 5 = ComCtrl; bit 6 = Multi-function input 1 (S3, H1-01); bit 7 = Multi-function input 2 (S4, H1-02); bit 8 = Multi-function input 3 (S5, H1-03); bit 9 = Multi-function input 4 (S6, H1-04); bit 10 = Multi-function input 5 (S7, H1-05)
HR2doc 0002hFrequency referenceUnits depend on the display-unit setting; unscaled here.UINT16Read/write
HR6doc 0006hPID setpointUsed when 000Fh bit 1 is set.UINT16Read/write
HR7doc 0007hAnalog output 1 settingRange -11 to 11 V as -726 to 726.INT16Read/write
HR8doc 0008hAnalog output 2 settingRange -11 to 11 V as -726 to 726.INT16Read/write
HR9doc 0009hOutputsNetwork control of digital and fault outputs.BITMAP16Read/writebit 0 = Multi-function output 1; bit 1 = Multi-function output 2; bit 2 = Multi-function output 3; bit 6 = Fault relay output; bit 7 = Fault relay N.C.
HR15doc 000FhCommand selectionEnables 0006h PID value and broadcast S5-S7 inputs.BITMAP16Read/writebit 1 = PID value 0006h is used; bit 12 = Broadcast terminal S5 enable; bit 13 = Broadcast terminal S6 enable; bit 14 = Broadcast terminal S7 enable
HR16doc 0010hInverter status (0010h)BITMAP16Readbit 0 = Run; bit 3 = Reset signal; bit 4 = Speed agree; bit 5 = Inverter ready; bit 6 = Minor fault; bit 7 = Major fault; bit 14 = ComRef; bit 15 = ComCtrl
HR20doc 0014hFault contents 1BITMAP16Readbit 0 = PUF fuse; bit 1 = UV1 main circuit undervoltage; bit 2 = UV2 control circuit undervoltage; bit 3 = UV3 MC error; bit 5 = GF ground fault; bit 6 = OC overcurrent; bit 7 = OV overvoltage; bit 8 = OH inverter overheat; bit 9 = OH1 inverter overheat warning; bit 10 = OL1 motor overload; bit 11 = OL2 inverter overload; bit 12 = OL3 overtorque 1; bit 13 = OL4 overtorque 2; bit 14 = RR braking resistor fault; bit 15 = RH braking resistor overheat
HR21doc 0015hFault contents 2BITMAP16Readbit 0 = EF3 external fault 3; bit 1 = EF4 external fault 4; bit 2 = EF5 external fault 5; bit 3 = EF6 external fault 6; bit 4 = EF7 external fault 7; bit 7 = OS overspeed; bit 8 = DEV excessive speed bias; bit 9 = PGO PG line interruption; bit 10 = PF input phase fault; bit 11 = LF output phase fault; bit 12 = OH3 overheat; bit 13 = OPR operator bypass fault; bit 14 = ERR EEPROM write fault; bit 15 = OH4 motor overheat fault
HR22doc 0016hFault contents 3BITMAP16Readbit 0 = CE communications fault; bit 1 = BUS communications option fault; bit 2 = E-15 SI-F/G communication fault; bit 3 = E-10 SI-F/G fault; bit 4 = CF control fault; bit 5 = SVE zero servo fault; bit 6 = EF0 communications option external fault; bit 7 = FBL PID feedback error; bit 8 = UL3 undertorque 1; bit 9 = UL4 undertorque 2; bit 10 = OL7 high slip braking overload
HR23doc 0017hCPF contents 1BITMAP16Readbit 2 = CPF02 base block circuit error; bit 3 = CPF03 EEPROM error; bit 4 = CPF04 CPU internal A/D error; bit 5 = CPF05 CPU external A/D error; bit 6 = CPF06 option card connection error
HR24doc 0018hCPF contents 2BITMAP16Readbit 0 = CPF20 option card A/D error; bit 1 = CPF21 option card self-diagnostic error; bit 2 = CPF22 option card code error; bit 3 = CPF23 option card DP-RAM error
HR25doc 0019hMinor fault contents 1Alarms.BITMAP16Readbit 0 = UV undervoltage; bit 1 = OV overvoltage; bit 2 = OH inverter overheat; bit 3 = OH2 inverter overheat warning; bit 4 = OL3 overtorque 1; bit 5 = OL4 overtorque 2; bit 6 = EF 2-wire sequence input fault; bit 7 = BB baseblock; bit 8 = EF3 external fault 3; bit 9 = EF4 external fault 4; bit 10 = EF5 external fault 5; bit 11 = EF6 external fault 6; bit 12 = EF7 external fault 7; bit 15 = OS overspeed
HR26doc 001AhMinor fault contents 2Alarms.BITMAP16Readbit 0 = DEV excessive speed bias; bit 1 = PGO PG line interruption; bit 2 = OPR operator bypass fault; bit 3 = CE communications fault; bit 4 = BUS communications option fault; bit 5 = CALL waiting for communications; bit 6 = OL1 motor overload; bit 7 = OL2 inverter overload; bit 8 = E-15 SI-F/G communication fault; bit 9 = E-10 SI-F/G fault; bit 10 = Motor switch; bit 11 = FBL PID feedback error; bit 12 = CALL waiting for communications; bit 13 = UL3 undertorque 1; bit 14 = UL4 undertorque 2; bit 15 = Communication test fault
HR27doc 001BhMinor fault contents 3Alarms.BITMAP16Readbit 0 = OH3 motor overheat alarm; bit 1 = DNE drive not enabled
HR32doc 0020hInverter status (0020h)BITMAP16Readbit 0 = Run; bit 1 = Reverse; bit 2 = Inverter ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Multi-function output 1; bit 6 = Multi-function output 2; bit 7 = Multi-function output 3
HR33doc 0021hFault contents (summary)BITMAP16Readbit 0 = OC or GF overcurrent/ground fault; bit 1 = OV overvoltage; bit 2 = OL2 inverter overload; bit 3 = OH1 or OH2 overheat; bit 4 = RR or RH braking resistor fault; bit 5 = PUF fuse fault; bit 6 = FBL PID feedback fault; bit 7 = EF external fault; bit 8 = CPF hardware fault; bit 9 = OL1, OL3 or OL4 overload/overtorque; bit 10 = PGO, OS or DEV speed deviation; bit 11 = UV undervoltage; bit 12 = UV1, UV2, UV3 or power off; bit 13 = SPI or SPO input/output phase fault; bit 14 = CE communications error; bit 15 = OPR operator error
HR34doc 0022hData link statusBITMAP16Readbit 0 = Data writing; bit 3 = Data limit fault; bit 4 = Data compatibility fault
HR43doc 002BhSequence input statusTerminals 1-7 closed.BITMAP16Readbit 0 = Terminal 1 closed; bit 1 = Terminal 2 closed; bit 2 = Terminal 3 closed; bit 3 = Terminal 4 closed; bit 4 = Terminal 5 closed; bit 5 = Terminal 6 closed; bit 6 = Terminal 7 closed
HR44doc 002ChInverter status (002Ch)BITMAP16Readbit 0 = Run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = Random speed agree; bit 4 = Frequency detect 1; bit 5 = Frequency detect 2; bit 6 = Inverter ready; bit 7 = Undervoltage; bit 8 = Baseblock; bit 9 = Frequency reference not from communications; bit 10 = Run command not from communications; bit 11 = Overtorque; bit 12 = Loss of frequency reference; bit 13 = Fault retry; bit 14 = Fault; bit 15 = Communications timeout
HR45doc 002DhMulti-function output statusBITMAP16Readbit 0 = Multi-function output 1; bit 1 = Multi-function output 2; bit 2 = Multi-function output 3
HR59doc 003BhCPU revisionUINT16Read
HR60doc 003ChFlash ID (software revision)UINT16Read
HR61doc 003DhCommunications errorBITMAP16Readbit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout
HR62doc 003EhkVA settingSee parameter o2-04.UINT16Read
HR64doc 0040hFrequency reference (U1-01)Listed in 0.01 Hz; see notes on display units.UINT16Read
HR65doc 0041hOutput frequency (U1-02)Listed in 0.01 Hz; see notes on display units.UINT16Read
HR66doc 0042hOutput current (U1-03)UINT16× 0.1ARead
HR69doc 0045hOutput voltage (U1-06)UINT16× 0.1VRead
HR70doc 0046hDC bus voltage (U1-07)UINT16VRead
HR73doc 0049hInput terminal status (U1-10)BITMAP16Readbit 0 = Fwd run (S1); bit 1 = Rev run (S2); bit 2 = S3; bit 3 = S4; bit 4 = S5; bit 5 = S6; bit 6 = S7
HR74doc 004AhOutput terminal status (U1-11)BITMAP16Readbit 0 = Multi-function output 1; bit 1 = Multi-function output 2; bit 2 = Multi-function output 3; bit 7 = Fault output
HR75doc 004BhDrive operation status (U1-12)BITMAP16Readbit 0 = FWD run; bit 1 = Zero speed; bit 2 = REV run; bit 3 = Reset; bit 4 = Speed agree; bit 5 = Drive ready; bit 6 = Minor fault; bit 7 = Major fault
HR76doc 004ChElapsed time (U1-13)UINT16hRead
HR77doc 004DhFlash ID (U1-14)Software revision.UINT16Read
HR78doc 004EhTerminal A1 input level (U1-15)Percent of 10 V.UINT16× 0.1%Read
HR79doc 04FhTerminal A2 input level (U1-16)Percent of 20 mA (or 10 V).UINT16× 0.1%Read
HR92doc 005ChkWh (U1-29)Low part of energy count.UINT16kWhRead
HR93doc 005DhMWh (U1-30)High part of energy count.UINT16MWhRead
HR97doc 0061hFirst parameter causing OPE (U1-34)UINT16Read
HR103doc 0067hFAN elapsed time (U1-40)UINT16hRead
HR128doc 0080hCurrent fault (U2-01)UINT16Read
HR129doc 0081hPrevious fault (U2-02)UINT16Read
HR132doc 0084hOutput current at previous fault (U2-05)UINT16× 0.1ARead
HR134doc 0086hOutput voltage at previous fault (U2-07)UINT16× 0.1VRead
HR135doc 0087hDC bus voltage at previous fault (U2-08)UINT16VRead
HR141doc 008DhElapsed time at previous fault (U2-14)UINT16hRead
HR384doc 0180hb1-01 Reference sourceUINT16Read/write0 = Operator; 1 = Terminals; 2 = Serial com; 3 = Option PCB
HR385doc 0181hb1-02 Run sourceUINT16Read/write0 = Operator; 1 = Terminals; 2 = Serial com; 3 = Option PCB
HR386doc 0182hb1-03 Stopping methodUINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = DC injection to stop; 3 = Coast with timer (C1-09)
HR1061doc 0425hH5-01 Serial comm address0h-20h; default 1Fh.UINT16Read/write
HR1062doc 0426hH5-02 Serial baud rateUINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200
HR1063doc 0427hH5-03 Serial parityUINT16Read/write0 = None; 1 = Even; 2 = Odd
HR1064doc 0428hH5-04 Serial fault selectReaction to a CE communication fault.UINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = Fast-stop; 3 = Alarm only; 4 = Run at d1-04
HR1065doc 0429hH5-05 Serial fault detectUINT16Read/write0 = Disabled; 1 = Enabled
HR1066doc 042AhH5-06 Transmit wait time5-65 ms.UINT16msRead/write
HR1067doc 042BhH5-07 RTS controlUINT16Read/write0 = Disabled; 1 = Enabled
HR1076doc 0434hH5-08 Protocol selectUINT16Read/write0 = Memobus (Modbus); 1 = N2 (Metasys); 2 = FLN (APOGEE)
HR1077doc 0435hH5-09 CE detect time0.0-10.0 s.UINT16× 0.1sRead/write
HR2048doc 0800hMost recent fault (U3-01)Also readable at 0090h.UINT16Read
HR2049doc 0801h2nd most recent fault (U3-02)UINT16Read
HR2050doc 0802h3rd most recent fault (U3-03)UINT16Read
HR2051doc 0803h4th most recent fault (U3-04)UINT16Read
HR2304doc 900ENTERWrite 0 to copy RAM parameters to non-volatile memory.UINT16Write
HR2320doc 910ACCEPTWrite 0 to move run-locked parameter writes into active RAM.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU

What Modbus registers does the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU have?

This map lists 66 registers: 66 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. All addresses are hex and go into the request unchanged: the manual's read example sets starting register 00h 20h to read 0020h-0023h. Parameters use the hex address in the parameter table (b1-01 = 0180h, H5-01 = 0425h). ENTER/ACCEPT are printed as 900/910, i.e. 0900h/0910h.

What are the minimum Modbus registers to integrate the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU?

Start with HR 1 Command (Run/stop, direction, reset); HR 2 Frequency reference (Frequency reference); HR 32 Inverter status (0020h) (Run/ready/fault); HR 33 Fault contents (summary) (Fault summary); HR 44 Inverter status (002Ch) (Status incl. comm timeout); HR 65 Output frequency (U1-02) (Output frequency); HR 66 Output current (U1-03) (Output current); HR 128 Current fault (U2-01) (Current fault code).

How do I enable Modbus control of the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU?

H5-08 = 0 selects Memobus/Modbus (1 = Metasys N2, 2 = APOGEE FLN). Set H5-01 (default 1Fh), H5-02 (default 3 = 9600) and H5-03 (default none) and cycle power. b1-01 = 2 and b1-02 = 2 hand reference and run to serial communications.

What happens when the Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU loses Modbus communication?

H5-05 = 1 (default) enables CE detection after H5-09 (default 2.0 s); H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default), 4 run at d1-04. 002Ch bit F flags a comm timeout.

Where is the official Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU Modbus documentation?

The source is E7 Drive Parameter Access Technical Manual (TM.E7.11), revision 2004-05-31, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.E7.11&cmd=documents&documentName=TM.E7.11.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: E7 Drive Parameter Access Technical Manual · TM.E7.11 · rev. 2004-05-31. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.