- P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
Variable frequency drive (HVAC bypass package) · Modbus register map
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU) Modbus register map
Updated 19 November 2026
The P1000 Bypass pairs the drive with a bypass controller board that has its own RS-485 port. Over Modbus RTU the bypass passes through the drive command and monitor registers and adds a bypass command word (run, AUTO select, BYPASS select, smoke purge, Motor AND/OR, fault reset), a bypass frequency reference, network control of the bypass inputs and outputs, and UB bypass monitors.
This page lists 36 Modbus registers for the Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
- Equipment type
- Variable frequency drive (HVAC bypass package)
- Registers
- 36 (16 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- P1000 Bypass, P1B
Integration notes: Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
Set Z3-01 = 0 (Modbus), Z3-02 address, Z3-03/Z3-04 line settings and restart. Set Z1-07 = 2 and Z1-08 = 2 to take speed and run from the bypass serial port, then write 8401H (frequency) and 8400H (run bit 0, AUTO select bit 10, BYPASS select bit 12); poll 0020H, 0021H, 0024H and UB-09 (8788H).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 33792 | Bypass command (BYP Command) | BITMAP16 | Bypass command 8400H | Read/write |
| HR 33793 | Bypass frequency reference | UINT16 | Bypass frequency reference 8401H | Read/write |
| HR 32 | Drive status 1 | BITMAP16 | Drive status 1 | Read |
| HR 33 | Fault contents 1 | BITMAP16 | Fault contents 1 | Read |
| HR 36 | Output frequency | UINT16 | Output frequency | Read |
| HR 34696 | UB-09 bypass current fault | UINT16 | Bypass current fault UB-09 | Read |
| HR 49 | DC bus voltage | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
Set Z3-01 = 0, then Z1-07 = 2 [Bypass Serial] for the speed reference and Z1-08 = 2 [Bypass Serial] for the AUTO run command. Set Z3-12 = 1 if the bypass digital inputs are to be driven from 8402H.
Communication loss & watchdog
Z3-11 enables comm-fault detection and Z3-06 sets the timeout (default 2.0 s); Z3-05 sets the action (see notes).
Byte order & addressing
- 8400H bits are OR-ed with the physical bypass inputs; clear them to release a command.
- There is no function 06H; write single registers with 10H.
Network setup
- Z3-02 node address 0-127 (default 1); Z3-03 baud 0-8 (default 3 = 9600); Z3-04 parity (default none). Z3-07 adds a reply delay.
Watch out for
- Z3-05 = 3 opens the bypass contactor on a comm fault as well as faulting the drive.
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Drive operation command / multi-function inputs | Drive-level command word. | BITMAP16 | Read/write | bit 2 = External fault EF0; bit 3 = Fault reset; bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7 | |||
| HR | 6doc 0006H | PI target | 0.01 % units, signed. | INT16 | × 0.01 | % | Read/write | ||
| HR | 15doc 000FH | Control selection setting | BITMAP16 | Read/write | bit 1 = PI setpoint input from Modbus; bit 4 = PI2 target input from Modbus; bit 12 = Terminal S5 input for broadcast; bit 13 = Terminal S6 input for broadcast; bit 14 = Terminal S7 input for broadcast | ||||
| HR | 32doc 0020H | Drive status 1 | BITMAP16 | Read | bit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = MFDO M1-M2; bit 6 = MFDO M3-M4; bit 7 = MFDO M5-M6; bit 14 = ComRef status; bit 15 = ComCtrl status | ||||
| HR | 33doc 0021H | Fault contents 1 | BITMAP16 | Read | bit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 / oH2 overheat; bit 6 = FbL / FbH PI feedback loss; bit 7 = EF to EF7 external fault; bit 8 = CPF hardware fault (incl. oFx); bit 9 = oL1 / oL3 / UL3; bit 11 = Uv main circuit undervoltage; bit 12 = Uv1 / Uv2 / Uv3; bit 13 = LF / PF phase loss; bit 14 = CE / bUS communication error; bit 15 = oPr operator connection fault | ||||
| HR | 34doc 0022H | Data link status | BITMAP16 | Read | bit 0 = Writing data or switching motors; bit 3 = Upper or lower limit error; bit 4 = Data conformity error; bit 5 = Writing to EEPROM | ||||
| HR | 35doc 0023H | Frequency reference | Units set by o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | Output frequency | Units set by o1-03. | UINT16 | Read | ||||
| HR | 42doc 002AH | Alarm contents 1 | BITMAP16 | Read | bit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 8 = FAn cooling fan error; bit 9 = CE Modbus communication error; bit 10 = bUS option communication error; bit 11 = UL3 undertorque 1; bit 12 = oH3 motor overheat; bit 13 = FbL / FbH PI feedback loss; bit 15 = CALL transmission error | ||||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = User speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = During undervoltage; bit 8 = During baseblock; bit 9 = Frequency reference from keypad; bit 10 = Run command from keypad; bit 11 = Over/undertorque 1; bit 12 = Frequency reference loss; bit 13 = During fault restart; bit 14 = Fault; bit 15 = Communication timeout | ||||
| HR | 49doc 0031H | DC bus voltage | UINT16 | V | Read | ||||
| HR | 52doc 0034H | Product code 1 | ASCII product type code. | UINT16 | Read | ||||
| HR | 56doc 0038H | PI feedback | Unsigned; 100 % = maximum output frequency. | UINT16 | × 0.1 | % | Read | ||
| HR | 57doc 0039H | PI input | Signed. | INT16 | × 0.1 | % | Read | ||
| HR | 58doc 003AH | PI output | Signed. | INT16 | × 0.1 | % | Read | ||
| HR | 61doc 003DH | Communications error contents | Held until the fault is reset. | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | |||
| HR | 75doc 004BH | Drive status (U1-12) | BITMAP16 | Read | bit 0 = During run; bit 1 = Zero speed; bit 2 = Reverse run; bit 3 = Fault reset signal input; bit 4 = Speed agree; bit 5 = Drive ready; bit 6 = Alarm; bit 7 = Fault; bit 8 = Operation error oPE; bit 9 = Momentary power loss; bit 14 = ComRef / NetRef; bit 15 = ComCtrl / NetCtrl | ||||
| HR | 127doc 007FH | Alarm code | Code list in the manual's alarm register table. | UINT16 | Read | ||||
| HR | 152doc 0098H | Accumulated operation time, high word (U4-01) | 10 h units; total = high x 10 + low. | UINT16 | × 10 | h | Read | ||
| HR | 153doc 0099H | Accumulated operation time, low word (U4-01) | 1 h units. | UINT16 | h | Read | |||
| HR | 33792doc 8400H | Bypass command (BYP Command) | OR-ed with the physical inputs. | BITMAP16 | Read/write | bit 0 = Run; bit 1 = Run reverse; bit 3 = Transfer to bypass; bit 4 = Smoke purge bypass; bit 5 = Smoke purge drive; bit 6 = Motor OR select; bit 7 = Motor AND select; bit 10 = AUTO select; bit 12 = BYPASS select; bit 13 = Fault reset; bit 14 = External fault (EFB) | |||
| HR | 33793doc 8401H | Bypass frequency reference | Sent to the drive when Z1-07 = 2; units set by o1-03. | UINT16 | Read/write | ||||
| HR | 33794doc 8402H | Bypass digital input command | OR-ed with DI-1 to DI-8; needs Z3-12 = 1. | BITMAP16 | Read/write | bit 0 = DI-1; bit 1 = DI-2; bit 2 = DI-3; bit 3 = DI-4; bit 4 = DI-5; bit 5 = DI-6; bit 6 = DI-7; bit 7 = DI-8 | |||
| HR | 33795doc 8403H | Bypass digital output command | Only outputs whose function is unused. | BITMAP16 | Read/write | bit 6 = DO-7; bit 7 = DO-8; bit 8 = DO-9; bit 9 = DO-10 | |||
| HR | 34048doc 8500H | Z3-01 serial communications protocol | Default 3 (BACnet). | UINT16 | Read/write | 0 = Modbus; 1 = N2; 2 = P1; 3 = BACnet | |||
| HR | 34049doc 8501H | Z3-02 serial communications node address | 0-127, default 1. | UINT16 | Read/write | ||||
| HR | 34050doc 8502H | Z3-03 baud rate | Default 3. | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps; 7 = 76800 bps; 8 = 115200 bps | |||
| HR | 34051doc 8503H | Z3-04 parity | Default 0. | UINT16 | Read/write | 0 = No parity; 1 = Even parity; 2 = Odd parity | |||
| HR | 34053doc 8505H | Z3-06 serial communications fault time | 0.0-99.9 s, default 2.0 s; 0.0 = never. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 34054doc 8506H | Z3-07 receive-to-transmit wait time | 0-99 ms, default 5 ms. | UINT16 | ms | Read/write | |||
| HR | 34059doc 850BH | Z3-12 network digital input select | 1 enables 8402H. | UINT16 | Read/write | 0 = Disable; 1 = Enable | |||
| HR | 34252doc 85CCH | Z1-07 speed reference select | Default 1. | UINT16 | Read/write | 0 = Operator; 1 = Analog input; 2 = Bypass serial; 3 = Option board (CN5) | |||
| HR | 34253doc 85CDH | Z1-08 run command select | Default 1. | UINT16 | Read/write | 0 = Operator; 1 = Bypass controller digital input; 2 = Bypass serial; 3 = Option board (CN5) | |||
| HR | 34696doc 8788H | UB-09 bypass current fault | Bypass fault code. | UINT16 | Read | ||||
| HR | 34700doc 878CH | UB-13 bypass previous fault | Bypass fault code. | UINT16 | Read | ||||
| HR | 34705doc 8791H | UB-18 bypass software version | UINT16 | Read |
Notes on this map
- All registers are 16-bit; signed values are noted per register.
- Frequency registers 8401H, 0023H and 0024H use the units chosen in drive parameter o1-03, so they are left unscaled.
- Bypass status and fault words UB-02 to UB-08 (8781H-8787H) are left out because the source shows their bits as display digits without a stated bit order.
- Left out: 0025H-0027H output voltage, current and power (unit switches or depends on model), 00ABH rated current, speed monitors in r/min, fault-trace blocks from 0080H and the fault/alarm description words from 00C0H.
- Function codes are 03H (read up to 16 registers), 08H (loopback) and 10H (write); there is no 06H.
- Z3-01 defaults to 3 (BACnet); select 0 for Modbus. Changes to the Z3 settings take effect after restarting.
- UB-17 contactor voltage is left out: the monitor table prints it at 878FH (the same number as UB-16) while the BACnet table puts it at 8790H.
- Z3-05 (comm fault action) is left out: its detail page gives range 0-3 but the parameter list adds setting 4 (run at Z3-10).
- 8400H bits 9 and 11 are left out: the register table's row order gives HAND select and DRIVE select, but the BACnet object table in the same manual maps bit 9 to 'Drive Select' and bit 11 to 'Not Used'. The other 8400H bit numbers come from that BACnet table and agree with the row order.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
What Modbus registers does the Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU) have?
This map lists 36 registers: 36 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example asks for starting register 0020H as 00 20. Bypass parameters and monitors use the hex number printed under each one (Z3-01 = 8500H, UB-09 = 8788H).
What are the minimum Modbus registers to integrate the Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)?
Start with HR 33792 Bypass command (BYP Command) (Bypass command 8400H); HR 33793 Bypass frequency reference (Bypass frequency reference 8401H); HR 32 Drive status 1 (Drive status 1); HR 33 Fault contents 1 (Fault contents 1); HR 36 Output frequency (Output frequency); HR 34696 UB-09 bypass current fault (Bypass current fault UB-09); HR 49 DC bus voltage (DC bus voltage).
How do I enable Modbus control of the Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)?
Set Z3-01 = 0, then Z1-07 = 2 [Bypass Serial] for the speed reference and Z1-08 = 2 [Bypass Serial] for the AUTO run command. Set Z3-12 = 1 if the bypass digital inputs are to be driven from 8402H.
What happens when the Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU) loses Modbus communication?
Z3-11 enables comm-fault detection and Z3-06 sets the timeout (default 2.0 s); Z3-05 sets the action (see notes).
Where is the official Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU) Modbus documentation?
The source is P1000 Bypass for industrial fans and pumps Technical Manual (SIEP YAIP1B 01D), revision 2023-04, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIP1B01&cmd=documents&documentName=SIEPYAIP1B01.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Pump (circulator / E-pump / pump drive)
Grundfos E-pumps (MAGNA3, TPE, CRE, CUE) via CIM 200 / CIM 500
Grundfos E-pumps (CRE/CRNE/CRIE, MTRE, CHIE, CME, TPE, TPE Series 2000, NBE/NKE), CUE drives and MAGNA3 with a CIM/CIU 200, CIM/CIU 500 or built-in SoftCIM.
Also known as: MAGNA3, TPE, TPE Series 2000, CRE, CRNE, CRIE, MTRE, CHIE, CME, NBE, NKE, CUE, MGE, CIM 200, CIU 200, CIM 500, CIU 500, SoftCIM Modbus RTU
All variable frequency drives Modbus register maps →
Source: P1000 Bypass for industrial fans and pumps Technical Manual · SIEP YAIP1B 01D · rev. 2023-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.