- FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Variable frequency drive · Modbus register map
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus register map
Updated 19 November 2026
Yaskawa's drive for industrial fans and pumps, with a built-in RS-485 port running MEMOBUS/Modbus RTU. Command registers (run bits, frequency reference, PID setpoints, digital outputs) start at 0001H, status and monitor registers at 0020H, and every parameter is reachable at the hex number printed under it. This map covers the command and status words, the key monitors, fault bits and the b1/H5 setup parameters.
This page lists 46 Modbus registers for the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 46 (25 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications
Integration notes: Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Set H5-01..H5-03, then b1-01 = 2 and b1-02 = 2 so the frequency reference and Run come from Modbus. Write 0001H (run bits) and 0002H (frequency reference) with function 10H and poll 0020H, 0021H and 002CH.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Run command / MFDI command | BITMAP16 | Run/stop, direction, fault reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference (o1-03 units) | Read/write |
| HR 32 | Drive status 1 | BITMAP16 | Drive status 1 | Read |
| HR 33 | Fault description 1 | BITMAP16 | Fault description 1 | Read |
| HR 36 | U1-02 Output frequency | UINT16 | U1-02 output frequency | Read |
| HR 44 | Drive status 2 | BITMAP16 | Drive status 2 incl. comm timeout | Read |
| HR 49 | U1-07 DC bus voltage | UINT16 | U1-07 DC bus voltage | Read |
Enable Modbus control & writes
Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then power-cycle or set H5-20 = 1. For control set b1-01 = 2 and b1-02 = 2 (or b1-15/b1-16 for external reference 2). H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.
Communication loss & watchdog
H5-05 = 1 (default) enables CE detection; H5-09 sets the timeout (0.0-10.0 s, default 2.0 s) and H5-04 the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at the H5-34 go-to frequency, with H5-35 as an optional timeout to a CE fault). Drive status 2 (002CH) bit F shows a timeout.
Byte order & addressing
- Registers are hex and 0-based: 0020H is sent as 00 20.
- No function 06H; use 10H.
- Parameter writes need the Enter command unless H5-11 = 1.
Network setup
- RS-485 is on the control terminal block; 8 data bits and 1 stop bit are fixed; up to 31 drives per line.
- Set DIP switch S2 ON only at the last drive on the line to enable its termination resistor.
- H5-01 = 0 makes the drive ignore Modbus.
Watch out for
- The EEPROM Enter command (0900H) is limited to about 100,000 writes; use 0910H for frequent changes.
- Network inputs in 0001H are ORed with the physical terminals.
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Run command / MFDI command | Run bits follow H5-12; bits 4-B drive multi-function inputs 1-8. | BITMAP16 | Read/write | bit 0 = H5-12=0: forward run (1) / stop; H5-12=1: run (1) / stop; bit 1 = H5-12=0: reverse run (1) / stop; H5-12=1: reverse (1) / forward; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Multi-function input 1 (ComRef when H1-01 = 40); bit 5 = Multi-function input 2 (ComCtrl when H1-02 = 41); bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7; bit 11 = Multi-function input 8 | |||
| HR | 2doc 0002H | Frequency reference | Unsigned; units set by o1-03. | UINT16 | Read/write | ||||
| HR | 3doc 0003H | Output voltage gain | 20-2000 (2.0-200.0 %), 1000 at power-up. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 4doc 0004H | Torque reference / torque limit | Enable with 000FH bit 2. | INT16 | × 0.1 | % | Read/write | ||
| HR | 5doc 0005H | Torque compensation | Enable with 000FH bit 3. | INT16 | × 0.1 | % | Read/write | ||
| HR | 6doc 0006H | PID setpoint | Enable with 000FH bit 1. | INT16 | × 0.01 | % | Read/write | ||
| HR | 9doc 0009H | MFDO setting | Drive the digital outputs from the network. | BITMAP16 | Read/write | bit 0 = MFDO M1-M2; bit 1 = MFDO M3-M4; bit 2 = MFDO MD-ME-MF; bit 6 = Enable bit 7; bit 7 = Fault relay MA/MB-MC | |||
| HR | 13doc 000DH | PI2 control setpoint | -100.00 to +100.00 %; enable with 000FH bit 4. | INT16 | × 0.01 | % | Read/write | ||
| HR | 15doc 000FH | Command selection setting | Enables network sources for setpoints and broadcast terminal inputs. | BITMAP16 | Read/write | bit 1 = PID target from Modbus; bit 2 = Torque reference/limit from Modbus; bit 3 = Torque compensation from Modbus; bit 4 = PI2 target from Modbus; bit 5 = PID feedback from Modbus (15FFH); bit 12 = Broadcast terminal S5 input; bit 13 = Broadcast terminal S6 input; bit 14 = Broadcast terminal S7 input; bit 15 = Broadcast terminal S8 input | |||
| HR | 32doc 0020H | Drive status 1 | BITMAP16 | Read | bit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error (oPExx); bit 5 = MFDO M1-M2 on; bit 6 = MFDO M3-M4 on; bit 7 = MFDO MD-ME-MF on; bit 12 = SToF: one safety input open; bit 13 = STo: both safety inputs open; bit 14 = ComRef enabled; bit 15 = ComCtrl enabled | ||||
| HR | 33doc 0021H | Fault description 1 | BITMAP16 | Read | bit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 heatsink / oH2 external overheat; bit 7 = EF0-EF7 external fault; bit 8 = CPFxx hardware fault (incl. oFx); bit 9 = oL1 motor overload, oL3/oL4 overtorque, UL3/UL4 undertorque; bit 10 = oS overspeed / dEv speed deviation; bit 11 = During Uv detection; bit 12 = Uv1/Uv2/Uv3 undervoltage; bit 13 = LF output / PF input phase loss; bit 14 = CE Modbus / bUS option communication error; bit 15 = oPr keypad connection fault | ||||
| HR | 34doc 0022H | Fault contents (data link) | Errors from the last write. | BITMAP16 | Read | bit 0 = During data write / motor switching; bit 3 = Upper/lower limit fault; bit 4 = Data integrity fault; bit 5 = During EEPROM write | |||
| HR | 35doc 0023H | U1-01 Frequency reference | Units set by o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | U1-02 Output frequency | Units set by o1-03. | UINT16 | Read | ||||
| HR | 41doc 0029H | Fault description 2 | BITMAP16 | Read | bit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 6 = oH4 motor overheat fault (PTC) | ||||
| HR | 42doc 002AH | Minor fault description 1 | Alarms that do not trip the drive. | BITMAP16 | Read | bit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 9 = CE: running at H5-34 go-to frequency; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat (PTC); bit 15 = CALL serial transmission error | |||
| HR | 43doc 002BH | U1-10 Input terminal status | BITMAP16 | Read | bit 0 = Terminal S1 on; bit 1 = Terminal S2 on; bit 2 = Terminal S3 on; bit 3 = Terminal S4 on; bit 4 = Terminal S5 on; bit 5 = Terminal S6 on; bit 6 = Terminal S7 on; bit 7 = Terminal S8 on | ||||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = During zero speed; bit 2 = Speed agree; bit 3 = User-defined speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Run ready; bit 7 = During low-voltage detection; bit 8 = During baseblock; bit 9 = Frequency reference mode (1 = not from communication option); bit 10 = Run command mode (1 = not from communication option); bit 11 = Over/undertorque 1/2 detected; bit 12 = Frequency reference loss; bit 13 = Auto-restart in progress; bit 14 = Fault; bit 15 = Modbus communication timeout (incl. CE go-to-frequency alarm) | ||||
| HR | 45doc 002DH | U1-11 Output terminal status | BITMAP16 | Read | bit 0 = MFDO M1-M2; bit 1 = MFDO M3-M4; bit 2 = MFDO MD-ME-MF; bit 7 = Fault relay MA/MB-MC | ||||
| HR | 49doc 0031H | U1-07 DC bus voltage | UINT16 | V | Read | ||||
| HR | 56doc 0038H | PID feedback | Unsigned; 100 % = maximum output frequency. | UINT16 | × 0.1 | % | Read | ||
| HR | 57doc 0039H | PID input | Signed; +/-100 % = +/- maximum output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 58doc 003AH | PID output | Signed; +/-100 % = +/- maximum output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 61doc 003DH | Communications error description | Kept until the fault is reset. | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | |||
| HR | 75doc 004BH | U1-12 Drive status | BITMAP16 | Read | bit 0 = During run; bit 1 = During zero speed; bit 2 = During reverse; bit 3 = During reset signal input; bit 4 = During speed agree; bit 5 = Drive ready; bit 6 = Minor fault; bit 7 = Fault; bit 8 = oPExx operation error; bit 9 = Momentary power loss recovery; bit 10 = Motor 2 selected; bit 14 = ComRef / NetRef status; bit 15 = ComCtrl / NetCtrl status | ||||
| HR | 152doc 0098H | U4-01 Cumulative operation time (tens) | U4-01 = 0098H x 10 + 0099H (manual example: 12345 h -> 1234 and 5). | UINT16 | × 10 | h | Read | ||
| HR | 153doc 0099H | U4-01 Cumulative operation time (1 h part) | Ones digit of U4-01. | UINT16 | h | Read | |||
| HR | 191doc 00BFH | Operation error number | The xx of the active oPExx. | UINT16 | Read | ||||
| HR | 192doc 00C0H | Fault description 3 | BITMAP16 | Read | bit 1 = Uv1 DC bus undervoltage; bit 2 = Uv2 control power undervoltage; bit 3 = Uv3 soft charge answerback; bit 4 = SC short circuit / IGBT; bit 5 = GF ground fault; bit 6 = oC overcurrent; bit 7 = ov overvoltage; bit 8 = oH heatsink overheat; bit 9 = oH1 heatsink overheat; bit 10 = oL1 motor overload; bit 11 = oL2 drive overload; bit 12 = oL3 overtorque 1; bit 13 = oL4 overtorque 2 | ||||
| HR | 193doc 00C1H | Fault description 4 | BITMAP16 | Read | bit 0 = EF3; bit 1 = EF4; bit 2 = EF5; bit 3 = EF6; bit 4 = EF7; bit 5 = EF8; bit 7 = oS overspeed; bit 8 = dEv speed deviation; bit 10 = PF input phase loss; bit 11 = LF output phase loss; bit 12 = oH3 motor overheat (PTC); bit 13 = oPr keypad connection; bit 14 = Err EEPROM write; bit 15 = oH4 motor overheat fault (PTC) | ||||
| HR | 384doc 0180H | b1-01 Frequency reference selection 1 | Set 2 to take the frequency reference from Modbus. | UINT16 | Read/write | 0 = Keypad; 1 = Analog input; 2 = Memobus/Modbus communications; 3 = Option PCB; 4 = Pulse train input | |||
| HR | 385doc 0181H | b1-02 Run command selection 1 | Set 2 to take Run from Modbus. | UINT16 | Read/write | 0 = Keypad; 1 = Digital input; 2 = Memobus/Modbus communications; 3 = Option PCB | |||
| HR | 1061doc 0425H | H5-01 Drive node address | 0-FFH, default 1FH; 0 = no response. Reload needed. | UINT16 | Read/write | ||||
| HR | 1062doc 0426H | H5-02 Communication speed selection | Default 3. | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps; 6 = 57.6 kbps; 7 = 76.8 kbps; 8 = 115.2 kbps | |||
| HR | 1063doc 0427H | H5-03 Communication parity selection | Default 0. | UINT16 | Read/write | 0 = No parity; 1 = Even parity; 2 = Odd parity | |||
| HR | 1064doc 0428H | H5-04 Communication error stop method | Reaction to CE; default 3. | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only; 4 = Run at H5-34 (CE go-to frequency) | |||
| HR | 1065doc 0429H | H5-05 Comm fault detection selection | Default 1. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 1066doc 042AH | H5-06 Drive transmit wait time | 0-65 ms, default 5 ms. | UINT16 | ms | Read/write | |||
| HR | 1077doc 0435H | H5-09 CE detection time | 0.0-10.0 s, default 2.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1078doc 0436H | H5-10 Modbus register 0025H unit selection | UINT16 | Read/write | 0 = 0.1 V units; 1 = 1 V units | ||||
| HR | 1084doc 043CH | H5-11 Comm ENTER command mode | Default 0. | UINT16 | Read/write | 0 = ENTER command required; 1 = ENTER command not required | |||
| HR | 1085doc 043DH | H5-12 Run command method selection | Meaning of 0001H bits 0/1; default 0. | UINT16 | Read/write | 0 = FWD/Stop, REV/Stop; 1 = Run/Stop, FWD/REV | |||
| HR | 2304doc 0900H | Enter command (save to EEPROM) | Write 0 to store written parameters; EEPROM limited to 100,000 writes. | UINT16 | Write | ||||
| HR | 2320doc 0910H | Enter command (RAM only) | Write 0 to apply written parameters without saving. | UINT16 | Write | ||||
| HR | 2903doc 0B57H | H5-20 Communication parameters reload | Apply H5 changes without a power cycle. | UINT16 | Read/write | 0 = Reload at next power cycle; 1 = Reload now | |||
| HR | 5631doc 15FFH | PID setpoint | Signed 0.01 %. The 000FH bit 5 text calls 15FFH the PID feedback input. | INT16 | × 0.01 | % | Read/write |
Notes on this map
- Frequency registers 0002H, 0023H and 0024H use the units chosen in o1-03, so they are left unscaled.
- Left out: 0025H output voltage (unit switched by H5-10), 0026H output current and 00ABH rated current (the manual says the rated-current unit differs by model), 0027H output power and 0028H/0032H torque reference (unit/sign not fixed in the table), 003EH/003FH and 00B5H-00B8H speed/frequency monitors in r/min or 0.01 % (sign not stated), the U-monitor, fault-trace and fault-history blocks from 0040H, the FP605 smart-network block 1A7FH-1AA0H, the real-time-clock registers 3004H-3030H and the emergency-override registers 3A93H-3A96H.
- Supported function codes are 03H, 08H, 10H, 5AH and 67H (non-consecutive read/write); there is no 06H, so use 10H even for a single register.
- U4-01 cumulative operation time is split over two 16-bit registers (0098H = value / 10, 0099H = last digit), not a 32-bit value.
- With H5-11 = 0, parameters written over Modbus take effect only after the Enter command (0900H or 0910H). Command registers 0001H-001FH do not need Enter.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
What Modbus registers does the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) have?
This map lists 46 registers: 46 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example (Table 6.7) asks slave 2 for starting register 0020H as bytes 00 20. Parameters use the hex number printed under each parameter (H5-01 = 0425H).
What are the minimum Modbus registers to integrate the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)?
Start with HR 1 Run command / MFDI command (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 32 Drive status 1 (Drive status 1); HR 33 Fault description 1 (Fault description 1); HR 36 U1-02 Output frequency (U1-02 output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout); HR 49 U1-07 DC bus voltage (U1-07 DC bus voltage).
How do I enable Modbus control of the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)?
Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then power-cycle or set H5-20 = 1. For control set b1-01 = 2 and b1-02 = 2 (or b1-15/b1-16 for external reference 2). H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.
What happens when the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) loses Modbus communication?
H5-05 = 1 (default) enables CE detection; H5-09 sets the timeout (0.0-10.0 s, default 2.0 s) and H5-04 the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at the H5-34 go-to frequency, with H5-35 as an optional timeout to a CE fault). Drive status 2 (002CH) bit F shows a timeout.
Where is the official Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus documentation?
The source is FP605 Drive AC Drive for Industrial Fan and Pump Applications Technical Reference (SIEPC7106171FE), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPC7106171F&cmd=documents&documentName=SIEPC7106171F.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Variable frequency drive
Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)
Bonfiglioli ACTIVE (ACT) and ACTIVE Cube (ACU 201/401/210/410) inverters with a CM-232 or CM-485 communication module set to Modbus, per manual VEC 383 R4 (04/23).
Also known as: ACTIVE Cube, ACU, ACU 201, ACU 401, ACU 210, ACU 410, ACTIVE, ACT, CM-232, CM-485, CM-MODBUS - Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Hitachi SJ700-2 series inverter (Modbus RTU)
Hitachi SJ700-2 series inverters using the built-in RS485 port (TM2) in Modbus-RTU mode (C079), per instruction manual NT204DX.
Also known as: SJ700, SJ700-2, SJ700 series
All variable frequency drives Modbus register maps →
Source: FP605 Drive AC Drive for Industrial Fan and Pump Applications Technical Reference · SIEPC7106171FE. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.