  3. Yaskawa
  4. FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)

Variable frequency drive · Modbus register map

Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Yaskawa's drive for industrial fans and pumps, with a built-in RS-485 port running MEMOBUS/Modbus RTU. Command registers (run bits, frequency reference, PID setpoints, digital outputs) start at 0001H, status and monitor registers at 0020H, and every parameter is reachable at the hex number printed under it. This map covers the command and status words, the key monitors, fault bits and the b1/H5 setup parameters.

This page lists 46 Modbus registers for the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Equipment type
Variable frequency drive
Registers
46 (25 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications
Source document
FP605 Drive AC Drive for Industrial Fan and Pump Applications Technical Reference · SIEPC7106171FE
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)

Integration in brief

Set H5-01..H5-03, then b1-01 = 2 and b1-02 = 2 so the frequency reference and Run come from Modbus. Write 0001H (run bits) and 0002H (frequency reference) with function 10H and poll 0020H, 0021H and 002CH.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Run command / MFDI commandBITMAP16Run/stop, direction, fault resetRead/write
HR 2Frequency referenceUINT16Frequency reference (o1-03 units)Read/write
HR 32Drive status 1BITMAP16Drive status 1Read
HR 33Fault description 1BITMAP16Fault description 1Read
HR 36U1-02 Output frequencyUINT16U1-02 output frequencyRead
HR 44Drive status 2BITMAP16Drive status 2 incl. comm timeoutRead
HR 49U1-07 DC bus voltageUINT16U1-07 DC bus voltageRead

Enable Modbus control & writes

Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then power-cycle or set H5-20 = 1. For control set b1-01 = 2 and b1-02 = 2 (or b1-15/b1-16 for external reference 2). H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.

Communication loss & watchdog

H5-05 = 1 (default) enables CE detection; H5-09 sets the timeout (0.0-10.0 s, default 2.0 s) and H5-04 the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at the H5-34 go-to frequency, with H5-35 as an optional timeout to a CE fault). Drive status 2 (002CH) bit F shows a timeout.

Byte order & addressing

Network setup

Watch out for

Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

46 of 46 shown
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HRun command / MFDI commandRun bits follow H5-12; bits 4-B drive multi-function inputs 1-8.BITMAP16Read/writebit 0 = H5-12=0: forward run (1) / stop; H5-12=1: run (1) / stop; bit 1 = H5-12=0: reverse run (1) / stop; H5-12=1: reverse (1) / forward; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Multi-function input 1 (ComRef when H1-01 = 40); bit 5 = Multi-function input 2 (ComCtrl when H1-02 = 41); bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7; bit 11 = Multi-function input 8
HR2doc 0002HFrequency referenceUnsigned; units set by o1-03.UINT16Read/write
HR3doc 0003HOutput voltage gain20-2000 (2.0-200.0 %), 1000 at power-up.UINT16× 0.1%Read/write
HR4doc 0004HTorque reference / torque limitEnable with 000FH bit 2.INT16× 0.1%Read/write
HR5doc 0005HTorque compensationEnable with 000FH bit 3.INT16× 0.1%Read/write
HR6doc 0006HPID setpointEnable with 000FH bit 1.INT16× 0.01%Read/write
HR9doc 0009HMFDO settingDrive the digital outputs from the network.BITMAP16Read/writebit 0 = MFDO M1-M2; bit 1 = MFDO M3-M4; bit 2 = MFDO MD-ME-MF; bit 6 = Enable bit 7; bit 7 = Fault relay MA/MB-MC
HR13doc 000DHPI2 control setpoint-100.00 to +100.00 %; enable with 000FH bit 4.INT16× 0.01%Read/write
HR15doc 000FHCommand selection settingEnables network sources for setpoints and broadcast terminal inputs.BITMAP16Read/writebit 1 = PID target from Modbus; bit 2 = Torque reference/limit from Modbus; bit 3 = Torque compensation from Modbus; bit 4 = PI2 target from Modbus; bit 5 = PID feedback from Modbus (15FFH); bit 12 = Broadcast terminal S5 input; bit 13 = Broadcast terminal S6 input; bit 14 = Broadcast terminal S7 input; bit 15 = Broadcast terminal S8 input
HR32doc 0020HDrive status 1BITMAP16Readbit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error (oPExx); bit 5 = MFDO M1-M2 on; bit 6 = MFDO M3-M4 on; bit 7 = MFDO MD-ME-MF on; bit 12 = SToF: one safety input open; bit 13 = STo: both safety inputs open; bit 14 = ComRef enabled; bit 15 = ComCtrl enabled
HR33doc 0021HFault description 1BITMAP16Readbit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1 heatsink / oH2 external overheat; bit 7 = EF0-EF7 external fault; bit 8 = CPFxx hardware fault (incl. oFx); bit 9 = oL1 motor overload, oL3/oL4 overtorque, UL3/UL4 undertorque; bit 10 = oS overspeed / dEv speed deviation; bit 11 = During Uv detection; bit 12 = Uv1/Uv2/Uv3 undervoltage; bit 13 = LF output / PF input phase loss; bit 14 = CE Modbus / bUS option communication error; bit 15 = oPr keypad connection fault
HR34doc 0022HFault contents (data link)Errors from the last write.BITMAP16Readbit 0 = During data write / motor switching; bit 3 = Upper/lower limit fault; bit 4 = Data integrity fault; bit 5 = During EEPROM write
HR35doc 0023HU1-01 Frequency referenceUnits set by o1-03.UINT16Read
HR36doc 0024HU1-02 Output frequencyUnits set by o1-03.UINT16Read
HR41doc 0029HFault description 2BITMAP16Readbit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 6 = oH4 motor overheat fault (PTC)
HR42doc 002AHMinor fault description 1Alarms that do not trip the drive.BITMAP16Readbit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 9 = CE: running at H5-34 go-to frequency; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat (PTC); bit 15 = CALL serial transmission error
HR43doc 002BHU1-10 Input terminal statusBITMAP16Readbit 0 = Terminal S1 on; bit 1 = Terminal S2 on; bit 2 = Terminal S3 on; bit 3 = Terminal S4 on; bit 4 = Terminal S5 on; bit 5 = Terminal S6 on; bit 6 = Terminal S7 on; bit 7 = Terminal S8 on
HR44doc 002CHDrive status 2BITMAP16Readbit 0 = During run; bit 1 = During zero speed; bit 2 = Speed agree; bit 3 = User-defined speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Run ready; bit 7 = During low-voltage detection; bit 8 = During baseblock; bit 9 = Frequency reference mode (1 = not from communication option); bit 10 = Run command mode (1 = not from communication option); bit 11 = Over/undertorque 1/2 detected; bit 12 = Frequency reference loss; bit 13 = Auto-restart in progress; bit 14 = Fault; bit 15 = Modbus communication timeout (incl. CE go-to-frequency alarm)
HR45doc 002DHU1-11 Output terminal statusBITMAP16Readbit 0 = MFDO M1-M2; bit 1 = MFDO M3-M4; bit 2 = MFDO MD-ME-MF; bit 7 = Fault relay MA/MB-MC
HR49doc 0031HU1-07 DC bus voltageUINT16VRead
HR56doc 0038HPID feedbackUnsigned; 100 % = maximum output frequency.UINT16× 0.1%Read
HR57doc 0039HPID inputSigned; +/-100 % = +/- maximum output frequency.INT16× 0.1%Read
HR58doc 003AHPID outputSigned; +/-100 % = +/- maximum output frequency.INT16× 0.1%Read
HR61doc 003DHCommunications error descriptionKept until the fault is reset.BITMAP16Readbit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout
HR75doc 004BHU1-12 Drive statusBITMAP16Readbit 0 = During run; bit 1 = During zero speed; bit 2 = During reverse; bit 3 = During reset signal input; bit 4 = During speed agree; bit 5 = Drive ready; bit 6 = Minor fault; bit 7 = Fault; bit 8 = oPExx operation error; bit 9 = Momentary power loss recovery; bit 10 = Motor 2 selected; bit 14 = ComRef / NetRef status; bit 15 = ComCtrl / NetCtrl status
HR152doc 0098HU4-01 Cumulative operation time (tens)U4-01 = 0098H x 10 + 0099H (manual example: 12345 h -> 1234 and 5).UINT16× 10hRead
HR153doc 0099HU4-01 Cumulative operation time (1 h part)Ones digit of U4-01.UINT16hRead
HR191doc 00BFHOperation error numberThe xx of the active oPExx.UINT16Read
HR192doc 00C0HFault description 3BITMAP16Readbit 1 = Uv1 DC bus undervoltage; bit 2 = Uv2 control power undervoltage; bit 3 = Uv3 soft charge answerback; bit 4 = SC short circuit / IGBT; bit 5 = GF ground fault; bit 6 = oC overcurrent; bit 7 = ov overvoltage; bit 8 = oH heatsink overheat; bit 9 = oH1 heatsink overheat; bit 10 = oL1 motor overload; bit 11 = oL2 drive overload; bit 12 = oL3 overtorque 1; bit 13 = oL4 overtorque 2
HR193doc 00C1HFault description 4BITMAP16Readbit 0 = EF3; bit 1 = EF4; bit 2 = EF5; bit 3 = EF6; bit 4 = EF7; bit 5 = EF8; bit 7 = oS overspeed; bit 8 = dEv speed deviation; bit 10 = PF input phase loss; bit 11 = LF output phase loss; bit 12 = oH3 motor overheat (PTC); bit 13 = oPr keypad connection; bit 14 = Err EEPROM write; bit 15 = oH4 motor overheat fault (PTC)
HR384doc 0180Hb1-01 Frequency reference selection 1Set 2 to take the frequency reference from Modbus.UINT16Read/write0 = Keypad; 1 = Analog input; 2 = Memobus/Modbus communications; 3 = Option PCB; 4 = Pulse train input
HR385doc 0181Hb1-02 Run command selection 1Set 2 to take Run from Modbus.UINT16Read/write0 = Keypad; 1 = Digital input; 2 = Memobus/Modbus communications; 3 = Option PCB
HR1061doc 0425HH5-01 Drive node address0-FFH, default 1FH; 0 = no response. Reload needed.UINT16Read/write
HR1062doc 0426HH5-02 Communication speed selectionDefault 3.UINT16Read/write0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps; 6 = 57.6 kbps; 7 = 76.8 kbps; 8 = 115.2 kbps
HR1063doc 0427HH5-03 Communication parity selectionDefault 0.UINT16Read/write0 = No parity; 1 = Even parity; 2 = Odd parity
HR1064doc 0428HH5-04 Communication error stop methodReaction to CE; default 3.UINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only; 4 = Run at H5-34 (CE go-to frequency)
HR1065doc 0429HH5-05 Comm fault detection selectionDefault 1.UINT16Read/write0 = Disabled; 1 = Enabled
HR1066doc 042AHH5-06 Drive transmit wait time0-65 ms, default 5 ms.UINT16msRead/write
HR1077doc 0435HH5-09 CE detection time0.0-10.0 s, default 2.0 s.UINT16× 0.1sRead/write
HR1078doc 0436HH5-10 Modbus register 0025H unit selectionUINT16Read/write0 = 0.1 V units; 1 = 1 V units
HR1084doc 043CHH5-11 Comm ENTER command modeDefault 0.UINT16Read/write0 = ENTER command required; 1 = ENTER command not required
HR1085doc 043DHH5-12 Run command method selectionMeaning of 0001H bits 0/1; default 0.UINT16Read/write0 = FWD/Stop, REV/Stop; 1 = Run/Stop, FWD/REV
HR2304doc 0900HEnter command (save to EEPROM)Write 0 to store written parameters; EEPROM limited to 100,000 writes.UINT16Write
HR2320doc 0910HEnter command (RAM only)Write 0 to apply written parameters without saving.UINT16Write
HR2903doc 0B57HH5-20 Communication parameters reloadApply H5 changes without a power cycle.UINT16Read/write0 = Reload at next power cycle; 1 = Reload now
HR5631doc 15FFHPID setpointSigned 0.01 %. The 000FH bit 5 text calls 15FFH the PID feedback input.INT16× 0.01%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)

What Modbus registers does the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) have?

This map lists 46 registers: 46 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example (Table 6.7) asks slave 2 for starting register 0020H as bytes 00 20. Parameters use the hex number printed under each parameter (H5-01 = 0425H).

What are the minimum Modbus registers to integrate the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)?

Start with HR 1 Run command / MFDI command (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 32 Drive status 1 (Drive status 1); HR 33 Fault description 1 (Fault description 1); HR 36 U1-02 Output frequency (U1-02 output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout); HR 49 U1-07 DC bus voltage (U1-07 DC bus voltage).

How do I enable Modbus control of the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)?

Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps) and H5-03 parity (default 0 = none), then power-cycle or set H5-20 = 1. For control set b1-01 = 2 and b1-02 = 2 (or b1-15/b1-16 for external reference 2). H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.

What happens when the Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) loses Modbus communication?

H5-05 = 1 (default) enables CE detection; H5-09 sets the timeout (0.0-10.0 s, default 2.0 s) and H5-04 the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default, 4 run at the H5-34 go-to frequency, with H5-35 as an optional timeout to a CE fault). Drive status 2 (002CH) bit F shows a timeout.

Where is the official Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU) Modbus documentation?

The source is FP605 Drive AC Drive for Industrial Fan and Pump Applications Technical Reference (SIEPC7106171FE), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPC7106171F&cmd=documents&documentName=SIEPC7106171F.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: FP605 Drive AC Drive for Industrial Fan and Pump Applications Technical Reference · SIEPC7106171FE. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.