- Home
- Modbus register maps
- Yaskawa
- GA800 AC drive (MEMOBUS/Modbus RTU)
Variable frequency drive · Modbus register map
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU) Modbus register map
Updated 17 November 2026
Yaskawa's general-purpose industrial variable frequency drive with a built-in RS-485 MEMOBUS/Modbus RTU port. Commands go to hex registers 0001H-000FH, status, faults and monitors are read from 0020H onwards, and each parameter has its own hex register. This map covers the command block, status and fault words, the key monitors with fixed units and the b1/H5 communication parameters.
This page lists 34 Modbus registers for the Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU) — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- GA800 AC drive (MEMOBUS/Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 34 (23 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CIPR-GA80, GA800 Industrial AC Microdrive
Integration notes: Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Set H5-01..H5-03, then b1-01 = 2 and b1-02 = 2 so the frequency reference and Run come from Modbus. Write 0001H (run bits) and 0002H (frequency reference) with function 10H and poll 0020H-0021H and 002CH.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Run command / MFDI command | BITMAP16 | Run/stop, direction, fault reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference (o1-03 units) | Read/write |
| HR 32 | Drive status 1 | BITMAP16 | Drive status 1 | Read |
| HR 33 | Fault description 1 | BITMAP16 | Fault description 1 | Read |
| HR 36 | U1-02 Output frequency | UINT16 | U1-02 output frequency | Read |
| HR 44 | Drive status 2 | BITMAP16 | Drive status 2 incl. comm timeout | Read |
| HR 49 | U1-07 DC bus voltage | UINT16 | U1-07 DC bus voltage | Read |
Enable Modbus control & writes
Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps), H5-03 parity (default 0 = none), then power-cycle or set H5-20 = 1. For control set b1-01 = 2 and b1-02 = 2. H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.
Communication loss & watchdog
H5-05 = 1 (default) enables CE detection; H5-09 sets the timeout (0.0-10.0 s, default 2.0 s) and H5-04 the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default). Drive status 2 (002CH) bit F shows a timeout.
Byte order & addressing
- Registers are hex and 0-based: 0020H is sent as 00 20.
- No function 06H; use 10H.
- Parameter writes need the Enter command unless H5-11 = 1.
Network setup
- RS-485 on the control terminal block; 8 data bits and 1 stop bit are fixed.
- Set DIP switch S2 ON only at the last drive on the line to enable its termination resistor.
Watch out for
- The EEPROM Enter command (0900H) is limited to about 100,000 writes; use 0910H for frequent changes.
- Network inputs in 0001H are ORed with the physical terminals.
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Run command / MFDI command | Run bits follow H5-12; bits 4-B drive multi-function inputs 1-8. | BITMAP16 | Read/write | bit 0 = H5-12=0: forward run / H5-12=1: run; bit 1 = H5-12=0: reverse run / H5-12=1: reverse direction; bit 2 = External fault EF0; bit 3 = Fault reset; bit 4 = Multi-function input 1; bit 5 = Multi-function input 2; bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7; bit 11 = Multi-function input 8 | |||
| HR | 2doc 0002H | Frequency reference | Units set by o1-03. | UINT16 | Read/write | ||||
| HR | 3doc 0003H | Output voltage gain | 20-2000 (2.0-200.0 %), 1000 at power-up. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 4doc 0004H | Torque reference / torque limit | INT16 | × 0.1 | % | Read/write | |||
| HR | 5doc 0005H | Torque compensation | INT16 | × 0.1 | % | Read/write | |||
| HR | 6doc 0006H | PID setpoint | INT16 | × 0.01 | % | Read/write | |||
| HR | 9doc 0009H | MFDO setting | Drive digital outputs from the network. | BITMAP16 | Read/write | bit 0 = MFDO M1-M2; bit 1 = MFDO M3-M4; bit 2 = MFDO M5-M6; bit 6 = Enable bit 7; bit 7 = Fault relay MA/MB-MC | |||
| HR | 15doc 000FH | Command selection setting | Enables network sources for PID, torque and broadcast inputs. | BITMAP16 | Read/write | bit 1 = PID setpoint from Modbus; bit 2 = Torque reference/limit from Modbus; bit 3 = Torque compensation from Modbus; bit 5 = PID feedback from Modbus (15FFH); bit 12 = Broadcast terminal S5 input; bit 13 = Broadcast terminal S6 input; bit 14 = Broadcast terminal S7 input; bit 15 = Broadcast terminal S8 input | |||
| HR | 32doc 0020H | Drive status 1 | BITMAP16 | Read | bit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error (oPE); bit 5 = MFDO M1-M2; bit 6 = MFDO M3-M4; bit 7 = MFDO M5-M6; bit 12 = SToF (one safe input open); bit 13 = STo (both safe inputs open); bit 14 = ComRef enabled; bit 15 = ComCtrl enabled | ||||
| HR | 33doc 0021H | Fault description 1 | BITMAP16 | Read | bit 0 = oC overcurrent / GF ground fault; bit 1 = ov overvoltage; bit 2 = oL2 drive overload; bit 3 = oH1/oH2 overheat; bit 4 = rH/rr braking resistor or transistor; bit 6 = FbL/FbH PID feedback; bit 7 = EF0, EF1-EF8 external fault; bit 8 = CPFxx hardware fault (incl. oFx); bit 9 = oL1, oL3/oL4, UL3/UL4; bit 10 = PGo, PGoH, oS, dEv; bit 11 = During Uv detection; bit 12 = Uv1, Uv2, Uv3; bit 13 = LF/PF phase loss; bit 14 = CE/bUS communication error; bit 15 = oPr keypad connection fault | ||||
| HR | 34doc 0022H | Fault contents (data link) | Errors from the last write. | BITMAP16 | Read | bit 0 = During data write / motor switching; bit 3 = Upper/lower limit fault; bit 4 = Data integrity fault; bit 5 = During EEPROM write; bit 6 = Change data only in RAM (H5-17=1) | |||
| HR | 35doc 0023H | U1-01 Frequency reference | Units set by o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | U1-02 Output frequency | Units set by o1-03. | UINT16 | Read | ||||
| HR | 41doc 0029H | Fault description 2 | BITMAP16 | Read | bit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 4 = rH braking resistor overheat; bit 6 = oH4 motor overheat (PTC) | ||||
| HR | 42doc 002AH | Minor fault description 1 | Alarms that do not trip the drive. | BITMAP16 | Read | bit 2 = EF run command input error; bit 3 = bb baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 8 = FAn internal fan fault; bit 9 = CE Modbus communication error; bit 10 = bUS option communication error; bit 11 = UL3/UL4 undertorque; bit 12 = oH3 motor overheat (PTC); bit 13 = FbL/FbH PID feedback; bit 15 = CALL serial comm transmission error | |||
| HR | 43doc 002BH | U1-10 Input terminal status | BITMAP16 | Read | bit 0 = Terminal S1 ON; bit 1 = Terminal S2 ON; bit 2 = Terminal S3 ON; bit 3 = Terminal S4 ON; bit 4 = Terminal S5 ON; bit 5 = Terminal S6 ON; bit 6 = Terminal S7 ON; bit 7 = Terminal S8 ON | ||||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = During zero speed; bit 2 = Speed agree; bit 3 = User-defined speed agree; bit 4 = Frequency detection 1 (<= L4-01); bit 5 = Frequency detection 2 (>= L4-01); bit 6 = Run ready; bit 7 = During low voltage detection; bit 8 = During baseblock; bit 9 = Frequency reference not from comm option; bit 10 = Run command not from comm option; bit 11 = Overtorque/undertorque 1, 2; bit 12 = Frequency reference loss; bit 13 = Executing auto-restart; bit 14 = Fault; bit 15 = Modbus communications timeout | ||||
| HR | 45doc 002DH | U1-11 Output terminal status | BITMAP16 | Read | bit 0 = MFDO M1-M2; bit 1 = MFDO M3-M4; bit 2 = MFDO M5-M6; bit 7 = Fault relay MA/MB-MC | ||||
| HR | 49doc 0031H | U1-07 DC bus voltage | UINT16 | V | Read | ||||
| HR | 384doc 0180H | b1-01 Frequency reference selection 1 | Set 2 to take the frequency reference from Modbus. | UINT16 | Read/write | 0 = Keypad; 1 = Analog input; 2 = Memobus/Modbus communications; 3 = Option PCB; 4 = Pulse train input | |||
| HR | 385doc 0181H | b1-02 Run command selection 1 | Set 2 to take Run from Modbus. | UINT16 | Read/write | 0 = Keypad; 1 = Digital input (control circuit terminals); 2 = Memobus/Modbus communications; 3 = Option PCB | |||
| HR | 1061doc 0425H | H5-01 Drive node address | 0-FFH, default 1FH; reload needed. | UINT16 | Read/write | ||||
| HR | 1062doc 0426H | H5-02 Communication speed | Default 3. | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19.2 kbps; 5 = 38.4 kbps; 6 = 57.6 kbps; 7 = 76.8 kbps; 8 = 115.2 kbps | |||
| HR | 1063doc 0427H | H5-03 Communication parity | Default 0. | UINT16 | Read/write | 0 = No parity; 1 = Even parity; 2 = Odd parity | |||
| HR | 1064doc 0428H | H5-04 Communication error stop method | Reaction to CE; default 3. | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop (C1-09); 3 = Alarm only | |||
| HR | 1065doc 0429H | H5-05 Comm fault detection | Default 1. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 1066doc 042AH | H5-06 Drive transmit wait time | 0-65 ms, default 5 ms. | UINT16 | ms | Read/write | |||
| HR | 1077doc 0435H | H5-09 CE detection time | 0.0-10.0 s, default 2.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1078doc 0436H | H5-10 Modbus register 0025H unit | UINT16 | Read/write | 0 = 0.1 V units; 1 = 1 V units | ||||
| HR | 1084doc 043CH | H5-11 Comm ENTER command mode | Default 0. | UINT16 | Read/write | 0 = ENTER command required; 1 = ENTER command not required | |||
| HR | 1085doc 043DH | H5-12 Run command method | Meaning of 0001H bits 0/1; default 0. | UINT16 | Read/write | 0 = FWD/Stop, REV/Stop; 1 = Run/Stop, FWD/REV | |||
| HR | 2304doc 0900H | Enter command (save to EEPROM) | Write 0 to store written parameters; limited to 100,000 writes. | UINT16 | Write | ||||
| HR | 2320doc 0910H | Enter command (RAM only) | Write 0 to apply written parameters without saving. | UINT16 | Write | ||||
| HR | 2903doc 0B57H | H5-20 Communication parameters reload | Apply H5 changes without power cycling. | UINT16 | Read/write | 0 = Reload at next power cycle; 1 = Reload now |
Notes on this map
- Frequency registers 0002H, 0023H and 0024H use the units chosen in o1-03, so they are left unscaled.
- Left out: 0025H output voltage (unit switched by H5-10), 0026H output current (0.1 A in Table 6.16, but U1-03 resolution can depend on drive capacity), 0027H output power and 0028H/0032H torque reference (units/sign not fixed in the table), 002FH frequency reference bias, 0034H/0035H product codes, and the long fault-history and U-monitor blocks from 0040H.
- b1-02 option 1 is Digital Input in the parameter list; the detailed parameter section misprints it as Analog Input. It means the control circuit terminals.
- Supported function codes are 03H, 08H, 10H, 5AH and 67H (non-consecutive read/write); there is no 06H, so use 10H even for a single register. A 03H read returns at most 16 registers.
- With H5-11 = 0 parameter writes only take effect after writing 0 to 0900H (EEPROM) or 0910H (RAM). Command registers 0001H-000FH never need Enter. Reading 0900H/0910H returns error 02H.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
What Modbus registers does the Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU) have?
This map lists 34 registers: 34 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the manual's read example asks for starting register 0020H as 00 20. Parameters use the hex number printed under each parameter (H5-01 = 0425H).
What are the minimum Modbus registers to integrate the Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)?
Start with HR 1 Run command / MFDI command (Run/stop, direction, fault reset); HR 2 Frequency reference (Frequency reference (o1-03 units)); HR 32 Drive status 1 (Drive status 1); HR 33 Fault description 1 (Fault description 1); HR 36 U1-02 Output frequency (U1-02 output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout); HR 49 U1-07 DC bus voltage (U1-07 DC bus voltage).
How do I enable Modbus control of the Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)?
Set H5-01 node address (default 1FH), H5-02 speed (default 3 = 9600 bps), H5-03 parity (default 0 = none), then power-cycle or set H5-20 = 1. For control set b1-01 = 2 and b1-02 = 2. H5-12 decides whether 0001H bits 0/1 are FWD/REV run or Run plus direction.
What happens when the Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU) loses Modbus communication?
H5-05 = 1 (default) enables CE detection; H5-09 sets the timeout (0.0-10.0 s, default 2.0 s) and H5-04 the reaction (0 ramp, 1 coast, 2 fast stop, 3 alarm only - default). Drive status 2 (002CH) bit F shows a timeout.
Where is the official Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU) Modbus documentation?
The source is GA800 Drive Technical Reference (SIEPC71061737G), revision 2026-03, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPC71061737&cmd=documents&documentName=SIEPC71061737.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
AutomationDirect DURApulse GS20 / GS20X AC drive
GS20 and GS20X drives (built-in RS-485 port) per the GS20 & GS20X user manual, 1st edition rev. F, chapter 5.
Also known as: GS20X, DURApulse GS20, GS21-11P0 - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive
All variable frequency drives Modbus register maps →
Source: GA800 Drive Technical Reference · SIEPC71061737G · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.