Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus register map

Updated 17 November 2026

Short answer

The PowerXL DG1 and DH1 are Eaton variable frequency drives with on-board RS-485 (Modbus RTU, BACnet MS/TP) and Ethernet (Modbus TCP, EtherNet/IP, BACnet IP). Both expose the same Modbus layout: monitoring values by ID, a fixed process-data block for control and status, and parameters by ID. This map covers the control and status words, speed reference, default process data and the main monitoring IDs.

This page lists 25 Modbus registers for the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.

Manufacturer
Eaton
Model
PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
Equipment type
Variable frequency drive
Registers
25 (6 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive
Source document
PowerXL Series VFD Communication Manual · MN040010EN · rev. 2018-06 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)

Integration in brief

Write the control word at 2000 (bit 0 run, bit 1 reverse, bit 2 reset, bits 8-9 for fieldbus control and reference) and the speed reference at 2002, then read status 2100 and process data out 2103-2109.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2000FB control wordBITMAP16Control wordRead/write
HR 2002FB speed referenceUINT16Speed reference 0.01 %Read/write
HR 2100FB status wordBITMAP16Status wordRead
HR 2103Process data out 1 (output frequency)INT16Output frequencyRead
HR 2105Process data out 3 (motor current)INT16Motor currentRead
HR 27Latest fault codeUINT16Latest fault codeRead

Enable Modbus control & writes

Select Modbus RTU in RS485 comm set (DG1 P20.3.1.1 / DH1 P12.3.1.1, ID 586) and set slave address, baud rate and parity in the same group; set the control place and reference source to fieldbus.

Communication loss & watchdog

DG1 has a Modbus RTU communication time-out (P20.3.2.9, ID 593, printed default 10000 ms); P20.3.2.10 / P12.3.2.6 (ID 2516) chooses whether a comm loss faults only in fieldbus control or in all control places.

Byte order & addressing

Network setup

Watch out for

Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

25 of 25 shown
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc ID 1 (register 40001)Output frequencyMonitoring value read by ID.INT16× 0.01HzRead
HR1doc ID 2 (register 40002)Motor speedMonitoring value read by ID.INT16rpmRead
HR2doc ID 3 (register 40003)Motor currentMonitoring value read by ID.INT16× 0.1ARead
HR3doc ID 4 (register 40004)Motor torqueMonitoring value read by ID.INT16× 0.1%Read
HR4doc ID 5 (register 40005)Motor powerMonitoring value read by ID.INT16× 0.1%Read
HR5doc ID 6 (register 40006)Motor voltageMonitoring value read by ID.INT16× 0.1VRead
HR7doc ID 8 (register 40008)Unit temperatureMonitoring value read by ID.INT16× 0.1°CRead
HR8doc ID 9 (register 40009)Motor temperatureMonitoring value read by ID.INT16× 0.1%Read
HR23doc ID 24 (register 40024)Frequency referenceMonitoring value read by ID.INT16× 0.01HzRead
HR27doc ID 28 (register 40028)Latest fault codeCode of the most recent fault.UINT16Read
HR2000doc 42001FB control wordDrive command bits.BITMAP16Read/writebit 0 = Drive output on (run); bit 1 = Counter-clockwise (reverse); bit 2 = Fault reset; bit 3 = FB INDATA1; bit 4 = FB INDATA2; bit 5 = FB INDATA3; bit 6 = FB INDATA4; bit 7 = Bypass relay enable; bit 8 = FB control on; bit 9 = FB reference on
HR2002doc 42003FB speed reference0-10000 = 0.00-100.00 % between minimum and maximum frequency.UINT16× 0.01%Read/write
HR2003doc 42004Process data in 1 (fb torque reference)FB torque reference in the default process-data mapping.INT16× 0.01%Read/write
HR2006doc 42007Process data in 4 (accel time 1)Accel time 1 in the default process-data mapping.INT16× 0.1sRead/write
HR2007doc 42008Process data in 5 (decel time 1)Decel time 1 in the default process-data mapping.INT16× 0.1sRead/write
HR2008doc 42009Process data in 6 (current limit)Current limit in the default process-data mapping.INT16× 0.1ARead/write
HR2100doc 42101FB status wordDrive state bits.BITMAP16Readbit 0 = Ready; bit 1 = Running; bit 2 = Counterclockwise; bit 3 = Faulted; bit 4 = Warning; bit 5 = Reference frequency reached; bit 6 = Bypass activated; bit 7 = Run enabled
HR2102doc 42103FB actual speedActual motor speed, 0.01 % units.INT16× 0.01%Read
HR2103doc 42104Process data out 1 (output frequency)Output frequency in the default process-data mapping.INT16× 0.01HzRead
HR2104doc 42105Process data out 2 (motor speed)Motor speed in the default process-data mapping.INT16rpmRead
HR2105doc 42106Process data out 3 (motor current)Motor current in the default process-data mapping.INT16× 0.1ARead
HR2106doc 42107Process data out 4 (motor torque)Motor torque in the default process-data mapping.INT16× 0.1%Read
HR2107doc 42108Process data out 5 (motor power)Motor power in the default process-data mapping.INT16× 0.1%Read
HR2108doc 42109Process data out 6 (motor voltage)Motor voltage in the default process-data mapping.INT16× 0.1VRead
HR2109doc 42110Process data out 7 (dc link voltage)DC link voltage in the default process-data mapping.INT16VRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)

What Modbus registers does the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) have?

This map lists 25 registers: 25 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual pairs each drive ID with a 4x register (ID 2001 = 42001, ID 1 = 40001) and its frame examples read 'holding registers 2000-2003' with start address 07D0h, so ID n goes on the wire as n-1 (40001 = address 0).

What are the minimum Modbus registers to integrate the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)?

Start with HR 2000 FB control word (Control word); HR 2002 FB speed reference (Speed reference 0.01 %); HR 2100 FB status word (Status word); HR 2103 Process data out 1 (output frequency) (Output frequency); HR 2105 Process data out 3 (motor current) (Motor current); HR 27 Latest fault code (Latest fault code).

How do I enable Modbus control of the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)?

Select Modbus RTU in RS485 comm set (DG1 P20.3.1.1 / DH1 P12.3.1.1, ID 586) and set slave address, baud rate and parity in the same group; set the control place and reference source to fieldbus.

What happens when the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) loses Modbus communication?

DG1 has a Modbus RTU communication time-out (P20.3.2.9, ID 593, printed default 10000 ms); P20.3.2.10 / P12.3.2.6 (ID 2516) chooses whether a comm loss faults only in fieldbus control or in all control places.

Where is the official Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus documentation?

The source is PowerXL Series VFD Communication Manual (MN040010EN), revision 2018-06. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2020/12/PowerXL-Communication-Manual.pdf. It may be an older revision, so check it against the live unit.

More Eaton Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: PowerXL Series VFD Communication Manual · MN040010EN · rev. 2018-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.