Variable frequency drive · Modbus register map
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus register map
Updated 17 November 2026
The PowerXL DG1 and DH1 are Eaton variable frequency drives with on-board RS-485 (Modbus RTU, BACnet MS/TP) and Ethernet (Modbus TCP, EtherNet/IP, BACnet IP). Both expose the same Modbus layout: monitoring values by ID, a fixed process-data block for control and status, and parameters by ID. This map covers the control and status words, speed reference, default process data and the main monitoring IDs.
This page lists 25 Modbus registers for the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eaton
- Model
- PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
- Equipment type
- Variable frequency drive
- Registers
- 25 (6 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive
Integration notes: Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
Write the control word at 2000 (bit 0 run, bit 1 reverse, bit 2 reset, bits 8-9 for fieldbus control and reference) and the speed reference at 2002, then read status 2100 and process data out 2103-2109.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2000 | FB control word | BITMAP16 | Control word | Read/write |
| HR 2002 | FB speed reference | UINT16 | Speed reference 0.01 % | Read/write |
| HR 2100 | FB status word | BITMAP16 | Status word | Read |
| HR 2103 | Process data out 1 (output frequency) | INT16 | Output frequency | Read |
| HR 2105 | Process data out 3 (motor current) | INT16 | Motor current | Read |
| HR 27 | Latest fault code | UINT16 | Latest fault code | Read |
Enable Modbus control & writes
Select Modbus RTU in RS485 comm set (DG1 P20.3.1.1 / DH1 P12.3.1.1, ID 586) and set slave address, baud rate and parity in the same group; set the control place and reference source to fieldbus.
Communication loss & watchdog
DG1 has a Modbus RTU communication time-out (P20.3.2.9, ID 593, printed default 10000 ms); P20.3.2.10 / P12.3.2.6 (ID 2516) chooses whether a comm loss faults only in fieldbus control or in all control places.
Byte order & addressing
- Process data and IDs are Modicon-style: subtract 1 (and 40001) for the wire address.
- Holding and input registers are the same data (function 03 or 04).
Network setup
- Slave address range 1-247, default 1.
- Parity choice also sets stop bits: none = 2 stop bits, odd/even = 1 stop bit.
- Defaults: 19200 baud, even parity, 1 stop bit.
Watch out for
- Control word bits 8 (FB control) and 9 (FB reference) must be set for the drive to take run and speed from the bus.
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc ID 1 (register 40001) | Output frequency | Monitoring value read by ID. | INT16 | × 0.01 | Hz | Read | ||
| HR | 1doc ID 2 (register 40002) | Motor speed | Monitoring value read by ID. | INT16 | rpm | Read | |||
| HR | 2doc ID 3 (register 40003) | Motor current | Monitoring value read by ID. | INT16 | × 0.1 | A | Read | ||
| HR | 3doc ID 4 (register 40004) | Motor torque | Monitoring value read by ID. | INT16 | × 0.1 | % | Read | ||
| HR | 4doc ID 5 (register 40005) | Motor power | Monitoring value read by ID. | INT16 | × 0.1 | % | Read | ||
| HR | 5doc ID 6 (register 40006) | Motor voltage | Monitoring value read by ID. | INT16 | × 0.1 | V | Read | ||
| HR | 7doc ID 8 (register 40008) | Unit temperature | Monitoring value read by ID. | INT16 | × 0.1 | °C | Read | ||
| HR | 8doc ID 9 (register 40009) | Motor temperature | Monitoring value read by ID. | INT16 | × 0.1 | % | Read | ||
| HR | 23doc ID 24 (register 40024) | Frequency reference | Monitoring value read by ID. | INT16 | × 0.01 | Hz | Read | ||
| HR | 27doc ID 28 (register 40028) | Latest fault code | Code of the most recent fault. | UINT16 | Read | ||||
| HR | 2000doc 42001 | FB control word | Drive command bits. | BITMAP16 | Read/write | bit 0 = Drive output on (run); bit 1 = Counter-clockwise (reverse); bit 2 = Fault reset; bit 3 = FB INDATA1; bit 4 = FB INDATA2; bit 5 = FB INDATA3; bit 6 = FB INDATA4; bit 7 = Bypass relay enable; bit 8 = FB control on; bit 9 = FB reference on | |||
| HR | 2002doc 42003 | FB speed reference | 0-10000 = 0.00-100.00 % between minimum and maximum frequency. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 2003doc 42004 | Process data in 1 (fb torque reference) | FB torque reference in the default process-data mapping. | INT16 | × 0.01 | % | Read/write | ||
| HR | 2006doc 42007 | Process data in 4 (accel time 1) | Accel time 1 in the default process-data mapping. | INT16 | × 0.1 | s | Read/write | ||
| HR | 2007doc 42008 | Process data in 5 (decel time 1) | Decel time 1 in the default process-data mapping. | INT16 | × 0.1 | s | Read/write | ||
| HR | 2008doc 42009 | Process data in 6 (current limit) | Current limit in the default process-data mapping. | INT16 | × 0.1 | A | Read/write | ||
| HR | 2100doc 42101 | FB status word | Drive state bits. | BITMAP16 | Read | bit 0 = Ready; bit 1 = Running; bit 2 = Counterclockwise; bit 3 = Faulted; bit 4 = Warning; bit 5 = Reference frequency reached; bit 6 = Bypass activated; bit 7 = Run enabled | |||
| HR | 2102doc 42103 | FB actual speed | Actual motor speed, 0.01 % units. | INT16 | × 0.01 | % | Read | ||
| HR | 2103doc 42104 | Process data out 1 (output frequency) | Output frequency in the default process-data mapping. | INT16 | × 0.01 | Hz | Read | ||
| HR | 2104doc 42105 | Process data out 2 (motor speed) | Motor speed in the default process-data mapping. | INT16 | rpm | Read | |||
| HR | 2105doc 42106 | Process data out 3 (motor current) | Motor current in the default process-data mapping. | INT16 | × 0.1 | A | Read | ||
| HR | 2106doc 42107 | Process data out 4 (motor torque) | Motor torque in the default process-data mapping. | INT16 | × 0.1 | % | Read | ||
| HR | 2107doc 42108 | Process data out 5 (motor power) | Motor power in the default process-data mapping. | INT16 | × 0.1 | % | Read | ||
| HR | 2108doc 42109 | Process data out 6 (motor voltage) | Motor voltage in the default process-data mapping. | INT16 | × 0.1 | V | Read | ||
| HR | 2109doc 42110 | Process data out 7 (dc link voltage) | DC link voltage in the default process-data mapping. | INT16 | V | Read |
Notes on this map
- This copy is hosted by the US distributor Precision Electric; it is Eaton manual MN040010EN (June 2018).
- Scales come from the 'Display format' column of the parameter ID lists (x100 = two decimals, x10 = one decimal, x0 = none) and from the Appendix B process-data table. INTEGER items are typed INT16 here (the process-data range is printed -32768...32767).
- Process data out 8 is left out: the RTU chapter says it defaults to ID 28 (latest fault code) while Appendix B says FB Data Out 8 Sel defaults to ID 8 (unit temperature). Read ID 28 directly instead. Process data in 2-3 (setpoint/feedback) have no fixed unit and are left out.
- Left out: every 4-byte (DOUBLE) value such as energy counters, PID setpoints/feedback and instant motor power, because the manual only says data is big endian and does not state the word order of 32-bit values; the FB general status word 2102, whose 'not used' bit marks did not survive in the table.
- The DH1 menu codes are P12.3.x for RS-485 settings, the DG1 codes P20.3.x.
- Left out: monitoring IDs whose unit the manual does not settle: analog inputs 1-2 and analog output 1 (IDs 10, 11, 25; the BACnet object table calls them volts), PT100 temperature (ID 27) and the PID1/PID2 outputs (IDs 22, 38).
- RTU defaults from Table 8: slave address 1, baud rate code 1 (19200), parity code 2 (even, 1 stop bit). Data bits are not stated.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
What Modbus registers does the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) have?
This map lists 25 registers: 25 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual pairs each drive ID with a 4x register (ID 2001 = 42001, ID 1 = 40001) and its frame examples read 'holding registers 2000-2003' with start address 07D0h, so ID n goes on the wire as n-1 (40001 = address 0).
What are the minimum Modbus registers to integrate the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)?
Start with HR 2000 FB control word (Control word); HR 2002 FB speed reference (Speed reference 0.01 %); HR 2100 FB status word (Status word); HR 2103 Process data out 1 (output frequency) (Output frequency); HR 2105 Process data out 3 (motor current) (Motor current); HR 27 Latest fault code (Latest fault code).
How do I enable Modbus control of the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)?
Select Modbus RTU in RS485 comm set (DG1 P20.3.1.1 / DH1 P12.3.1.1, ID 586) and set slave address, baud rate and parity in the same group; set the control place and reference source to fieldbus.
What happens when the Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) loses Modbus communication?
DG1 has a Modbus RTU communication time-out (P20.3.2.9, ID 593, printed default 10000 ms); P20.3.2.10 / P12.3.2.6 (ID 2516) chooses whether a comm loss faults only in fieldbus control or in all control places.
Where is the official Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP) Modbus documentation?
The source is PowerXL Series VFD Communication Manual (MN040010EN), revision 2018-06. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2020/12/PowerXL-Communication-Manual.pdf. It may be an older revision, so check it against the live unit.
More Eaton Modbus register maps
- Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V - Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Power meter
Eaton IQ 250 / IQ 260 Electronic Power Meter
Eaton IQ 250 and IQ 260 meters (including the L logging versions), Modbus map Appendix B of IB02601006E.
Also known as: IQ 250, IQ 260, IQ 250L, IQ 260L, IQ250, IQ260 - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2 - Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34 - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V
Other variable frequency drives register maps
- Variable frequency drive
Inovance MD500-PLUS series AC drive
Inovance MD500-PLUS drives with the MD38TX1 RS-485 extension card, Modbus RTU slave, per software guide 19011580 rev. A04.
Also known as: MD500-PLUS, MD500 PLUS, MD500T-PLUS, Inovance MD500-PLUS - Variable frequency drive
INVT Goodrive20 (GD20) general-purpose VFD
INVT Goodrive20 drives using the built-in RS-485 Modbus port, per the GD20 VFD manual V2.1 (chapter 7, communication protocol).
Also known as: GD20, Goodrive20, GD20-EU, GD20-UL, GD20 vector VFD - Variable frequency drive
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.
Also known as: VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68 - Variable frequency drive
LS Electric LSLV-S100 AC drive (built-in RS-485 Modbus RTU)
LS Electric S100 drives (0.4-75 kW, including IP66) using the built-in RS-485 terminals S+/S-/SG with CM.02 = Modbus-RTU, per S100 User Manual V4.3.
Also known as: LSLV-S100, LSIS S100, LS S100, LSLV0075S100-4EOFNS - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)
SEW-EURODRIVE MOVITRAC LTE-B+ inverters on the RJ45 Modbus RTU port, per product manual 31965822/EN edition 03/2024.
Also known as: MOVITRAC LTE-B+, LTE-B+, MC LTE B+, MOVITRAC LTE B plus
All variable frequency drives Modbus register maps →
Source: PowerXL Series VFD Communication Manual · MN040010EN · rev. 2018-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.