Soft starter · Modbus register map

Eaton S811+ soft starter (via C441 Ethernet module) Modbus register map

Updated 19 November 2026

Short answer

The S811+ is Eaton's larger soft starter with full motor protection, metering and a configurable I/O block. Through the C441 Ethernet module it is reachable over Modbus TCP and RS-485 Modbus RTU. This map covers the adapter I/O registers, status, fault and warning words, single-word current, power and frequency monitors, the network control words (500/501) and the main protection and comm-loss settings.

This page lists 88 Modbus registers for the Eaton S811+ soft starter (via C441 Ethernet module) — 61 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.

Manufacturer
Eaton
Model
S811+ soft starter (via C441 Ethernet module)
Equipment type
Soft starter
Registers
88 (61 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
S811+, S811 Plus, S811+ soft starter, C441U, C441V
Source document
C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) · MN04200002E · rev. 2012-08 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eaton S811+ soft starter (via C441 Ethernet module)

Integration in brief

Poll 300 for running/faulted/bypass state, 304/305 for fault and warning bits, 340 for average line current (0.1 A) and 361 for kW. Control the motor with register 500 (permissive bit 2 plus run bit 0) or 501 in two-wire mode, and set 684 for comm-loss behaviour.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 299Motor control statusBITMAP16Status wordRead
HR 303Motor control faultsBITMAP16Fault bitsRead
HR 304Motor control warningsBITMAP16Warning bitsRead
HR 339Average line current (0.1 A)UINT16Average line currentRead
HR 360Average 3-phase real powerUINT16Real powerRead
HR 306Thermal pile usedUINT16Thermal pileRead
HR 499Modbus motor control wordBITMAP16Network control wordRead/write

Enable Modbus control & writes

Network control needs 623 = 0 (local-only off); 687 selects three-wire (500, which also needs permissive bit 2 set) or two-wire (501) control. Modbus TCP is served by the C441 module (IP via DHCP, NV memory or DIP switches).

Communication loss & watchdog

684 sets the motor's comm-loss action (auto stop, run, hold or all-stop fault); 686 is the comm idle timeout that raises a device-missing fault; 110/159 set adapter-level Modbus timeouts.

Byte order & addressing

Network setup

Watch out for

Eaton S811+ soft starter (via C441 Ethernet module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

88 of 88 shown
Eaton S811+ soft starter (via C441 Ethernet module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Field inputsAdapter input points.BITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4
HR1doc 2Control voltageAdapter supply voltage.UINT16mVRead
HR4doc 5DIP switch valuePresent DIP switch state.BITMAP16Read
HR100doc 101Field relay outputsAdapter output relays.BITMAP16Read/writebit 0 = Output 1; bit 1 = Output 2
HR109doc 110Modbus TCP com timeout0 = disabled.UINT16msRead/write
HR110doc 111Field relay fault actionPer relay: 0 = apply fault value, 1 = no change.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR111doc 112Field relay fault statePer relay value on comm fault: 0 off, 1 on.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR112doc 113Field relay idle actionPer relay: 0 = apply idle value, 1 = no change.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR113doc 114Field relay idle statePer relay value on comm idle: 0 off, 1 on.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR142doc 143IP allocation methodUINT16Read0 = DHCP; 1 = Upper 3 octets from NV, last octet from DIP switches; 2 = Full address from NV memory; 3 = Restore 192.168.1.254
HR158doc 159Modbus serial com timeout0 = disabled.UINT16msRead/write
HR159doc 160Modbus TX modeUINT16Read/write0 = RTU; 1 = ASCII
HR160doc 161Modbus baud rateUINT16Read/write0 = 19200; 1 = 9600; 2 = 57600; 3 = 115200
HR161doc 162Modbus addressSerial slave address loaded at start-up.UINT16Read/write
HR162doc 163Modbus parity and stop bitsUINT16Read/write0 = Even, 1 stop; 1 = Odd, 1 stop; 2 = None, 2 stop; 3 = Even, 2 stop; 4 = Odd, 2 stop; 5 = None, 1 stop
HR200doc 201Intercom statusLink between adapter and host device.BITMAP16Readbit 0 = Connected fully, no errors; bit 1 = Message fault occurred; bit 2 = Devices married, target identified; bit 3 = Basic connection established
HR252doc 253Motor ctrl com idle act disable1 = keep motor state on comm idle; 0 = apply idle value (254).UINT16Read/write
HR253doc 254Motor ctrl com idle action valueUINT16Read/write0 = Ignore (no change); 1 = Stop
HR299doc 300Motor control statusBITMAP16Readbit 0 = Running1 (RUN1 active); bit 1 = Running2 (jog active); bit 2 = Permissive (start allowed); bit 3 = Ramp2 settings active; bit 4 = Local control (0 = network); bit 5 = Faulted; bit 6 = Warning (self-clearing); bit 7 = In bypass
HR303doc 304Motor control faultsBITMAP16Readbit 0 = Phase loss; bit 1 = Phase imbalance; bit 2 = Thermal pile; bit 3 = Overcurrent; bit 4 = Breaker fault; bit 5 = Ground fault; bit 6 = Motor stall; bit 7 = Motor jam; bit 8 = Over-temperature; bit 9 = Underload; bit 11 = E-stop; bit 15 = Other
HR304doc 305Motor control warningsBITMAP16Readbit 0 = Phase loss; bit 1 = Phase imbalance; bit 2 = Thermal pile; bit 3 = Overcurrent; bit 4 = Breaker fault; bit 5 = Ground fault; bit 6 = Motor stall; bit 7 = Motor jam; bit 8 = Over-temperature; bit 9 = Underload; bit 15 = Other
HR305doc 306Average current % FLAAverage phase current as percent of nameplate FLA.UINT16%Read
HR306doc 307Thermal pile usedTrips at 100%.UINT16%Read
HR312doc 313Analog input valuePercent of the selected range.UINT16%Read
HR313doc 314Analog input statusUINT16Read0 = Not active; 1 = Under range; 2 = Over range; 3 = In overdrive; 4 = In range
HR314doc 315Discrete input statusBITMAP16Readbit 0 = Terminal input 1; bit 1 = Terminal input 2; bit 2 = Terminal input 3; bit 3 = Terminal input 4; bit 4 = Network input 1 (C441 input 1); bit 5 = Network input 2 (C441 input 2); bit 6 = Network input 3 (C441 input 3); bit 7 = Network input 4 (C441 input 4)
HR315doc 316Discrete output statusBITMAP16Readbit 0 = Form A relay; bit 1 = Form C relay; bit 2 = Network output 1 (C441 output 1); bit 3 = Network output 2 (C441 output 2)
HR335doc 336Average line current (A)Motor line current, 1 A units.UINT16ARead
HR339doc 340Average line current (0.1 A)UINT16× 0.1ARead
HR351doc 352Average pole current (A)Current through the power poles, 1 A units.UINT16ARead
HR355doc 356Average pole current (0.1 A)UINT16× 0.1ARead
HR359doc 360Power factor0 to 1.0000.UINT16× 0.0001Read
HR360doc 361Average 3-phase real powerUINT16kWRead
HR364doc 365DC control voltageUINT16× 0.001VRead
HR365doc 366Device temperatureUINT16× 0.1°CRead
HR366doc 367Auto reset countAuto reset attempts so far.UINT16Read
HR367doc 368Line frequencyUINT16× 0.01HzRead
HR368doc 369Incoming phase sequenceUINT16Read0 = ABC; 1 = ACB
HR379doc 380Application statusLast active fault.UINT16Read
HR499doc 500Modbus motor control wordThree-wire control (687 = 0).BITMAP16Read/writebit 0 = Run1 start (edge); bit 1 = Jog (level); bit 2 = Permissive (level, must be 1 to start); bit 3 = Fault reset; bit 7 = Ramp2 profile
HR500doc 501Modbus two-wire motor control wordTwo-wire control (687 = 1).BITMAP16Read/writebit 0 = Run1 (level); bit 1 = Jog (level); bit 3 = Fault reset; bit 7 = Ramp2 profile
HR502doc 503Modbus baud rateS811+ port; applied at power-up.UINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200 (default); 5 = 38400; 6 = 57600; 7 = 115200
HR503doc 504Modbus node addressFrom the DIP switches; read at power-up.UINT16Read
HR504doc 505Modbus parityApplied at power-up.UINT16Read/write0 = Even, 1 stop; 1 = Odd, 1 stop; 2 = None, 2 stop
HR506doc 507Modbus modeUINT16Read/write0 = RTU (default); 1 = ASCII
HR601doc 602Motor nameplate FLAUINT16× 0.1ARead/write
HR602doc 603Overload trip class5-30, default 20.UINT16Read/write
HR605doc 606Motor wiring configurationUINT16Read/write0 = Inline (default); 1 = Inside the delta
HR606doc 607Expected incoming phase sequenceUINT16Read/write0 = ABC; 1 = ACB
HR607doc 608Motor start methodUINT16Read/write0 = Ramp start (voltage ramp); 1 = Current limit; 3 = Pump start
HR613doc 614Kickstart duration0.0-2.0 s.UINT16× 0.1sRead/write
HR622doc 623Local control only enableUINT16Read/write0 = Disabled (network control possible); 1 = Enabled (terminal block only)
HR639doc 640Fault reset modeUINT16Read/write0 = Manual; 1 = Auto; 2 = Power-on reset
HR642doc 643Overload trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR643doc 644Overload during startUINT16Read/write0 = Disabled during start ramp; 1 = Enabled during start ramp
HR644doc 645Phase reversal trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR645doc 646Undercurrent trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR646doc 647Undercurrent trip levelPercent of nameplate FLA.UINT16%Read/write
HR647doc 648Undercurrent trip duration0.0-60.0 s.UINT16× 0.1sRead/write
HR648doc 649Motor jam trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR649doc 650Motor stall trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR650doc 651Phase loss trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR652doc 653Phase loss duration0.0-60.0 s.UINT16× 0.1sRead/write
HR653doc 654Phase imbalance trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR655doc 656Phase imbalance trip duration0.0-60.0 s.UINT16× 0.1sRead/write
HR657doc 658Voltage imbalance trip duration0.0-60.0 s.UINT16× 0.1sRead/write
HR658doc 659Under voltage trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR659doc 660Under voltage trip thresholdPercent of rated motor voltage.UINT16%Read/write
HR660doc 661Under voltage trip duration0.0-60.0 s.UINT16× 0.1sRead/write
HR661doc 662Over voltage trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR662doc 663Over voltage trip thresholdPercent of rated motor voltage.UINT16%Read/write
HR663doc 664Over voltage trip duration0.0-60.0 s.UINT16× 0.1sRead/write
HR664doc 665Line frequency trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR665doc 666Frequency deviation trip thresholdPercent of rated line frequency.UINT16%Read/write
HR666doc 667Frequency trip duration0.0-60.0 s.UINT16× 0.1sRead/write
HR667doc 668Average power trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR668doc 669Low power trip thresholdPercent of rated W (sqrt3 x 0.8 x FLA x rated V).UINT16%Read/write
HR669doc 670High power trip thresholdPercent of rated W.UINT16%Read/write
HR670doc 671Power trip duration0.0-60.0 s.UINT16× 0.1sRead/write
HR671doc 672Analog input trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR674doc 675Analog input trip duration0.0-60.0 s.UINT16× 0.1sRead/write
HR675doc 676Temperature sensor trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR676doc 677SCR not firing trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR677doc 678SCR shorted trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR683doc 684Motor comm loss actionUINT16Read/write0 = Auto stop; 1 = Auto run1; 3 = Hold last state; 7 = All-stop fault (trips)
HR686doc 687Network two-wire control enableUINT16Read/write0 = 3-wire control (register 500); 1 = 2-wire control (register 501)
HR687doc 688Ground fault trip enableUINT16Read/write0 = Disable; 1 = Fault enable; 2 = Warning enable
HR688doc 689Ground fault inhibit from start delay0.0-20.0 s after the start ramp.UINT16× 0.1sRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eaton S811+ soft starter (via C441 Ethernet module)

What Modbus registers does the Eaton S811+ soft starter (via C441 Ethernet module) have?

This map lists 88 registers: 88 holding registers. 61 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eaton S811+ soft starter (via C441 Ethernet module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0). The manual itself calls the control words 'Modbus reg #500' and '#501'.

What are the minimum Modbus registers to integrate the Eaton S811+ soft starter (via C441 Ethernet module)?

Start with HR 299 Motor control status (Status word); HR 303 Motor control faults (Fault bits); HR 304 Motor control warnings (Warning bits); HR 339 Average line current (0.1 A) (Average line current); HR 360 Average 3-phase real power (Real power); HR 306 Thermal pile used (Thermal pile); HR 499 Modbus motor control word (Network control word).

How do I enable Modbus control of the Eaton S811+ soft starter (via C441 Ethernet module)?

Network control needs 623 = 0 (local-only off); 687 selects three-wire (500, which also needs permissive bit 2 set) or two-wire (501) control. Modbus TCP is served by the C441 module (IP via DHCP, NV memory or DIP switches).

What happens when the Eaton S811+ soft starter (via C441 Ethernet module) loses Modbus communication?

684 sets the motor's comm-loss action (auto stop, run, hold or all-stop fault); 686 is the comm idle timeout that raises a device-missing fault; 110/159 set adapter-level Modbus timeouts.

Where is the official Eaton S811+ soft starter (via C441 Ethernet module) Modbus documentation?

The source is C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) (MN04200002E), revision 2012-08. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf. It may be an older revision, so check it against the live unit.

More Eaton Modbus register maps

Other soft starters & protection relays register maps

All soft starters & protection relays Modbus register maps →

Source: C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) · MN04200002E · rev. 2012-08 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.