Soft starter · Modbus register map
Eaton S811+ soft starter (via C441 Ethernet module) Modbus register map
Updated 19 November 2026
The S811+ is Eaton's larger soft starter with full motor protection, metering and a configurable I/O block. Through the C441 Ethernet module it is reachable over Modbus TCP and RS-485 Modbus RTU. This map covers the adapter I/O registers, status, fault and warning words, single-word current, power and frequency monitors, the network control words (500/501) and the main protection and comm-loss settings.
This page lists 88 Modbus registers for the Eaton S811+ soft starter (via C441 Ethernet module) — 61 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eaton
- Model
- S811+ soft starter (via C441 Ethernet module)
- Equipment type
- Soft starter
- Registers
- 88 (61 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- S811+, S811 Plus, S811+ soft starter, C441U, C441V
Integration notes: Eaton S811+ soft starter (via C441 Ethernet module)
Poll 300 for running/faulted/bypass state, 304/305 for fault and warning bits, 340 for average line current (0.1 A) and 361 for kW. Control the motor with register 500 (permissive bit 2 plus run bit 0) or 501 in two-wire mode, and set 684 for comm-loss behaviour.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 299 | Motor control status | BITMAP16 | Status word | Read |
| HR 303 | Motor control faults | BITMAP16 | Fault bits | Read |
| HR 304 | Motor control warnings | BITMAP16 | Warning bits | Read |
| HR 339 | Average line current (0.1 A) | UINT16 | Average line current | Read |
| HR 360 | Average 3-phase real power | UINT16 | Real power | Read |
| HR 306 | Thermal pile used | UINT16 | Thermal pile | Read |
| HR 499 | Modbus motor control word | BITMAP16 | Network control word | Read/write |
Enable Modbus control & writes
Network control needs 623 = 0 (local-only off); 687 selects three-wire (500, which also needs permissive bit 2 set) or two-wire (501) control. Modbus TCP is served by the C441 module (IP via DHCP, NV memory or DIP switches).
Communication loss & watchdog
684 sets the motor's comm-loss action (auto stop, run, hold or all-stop fault); 686 is the comm idle timeout that raises a device-missing fault; 110/159 set adapter-level Modbus timeouts.
Byte order & addressing
- Register numbers are 1-based; subtract 1 on the wire.
- Run1 in register 500 is edge-sensitive, but in 501 it is level-sensitive.
Network setup
- S811+ Modbus settings 503 (baud) and 505 (parity) take effect only after a power cycle; the node address 504 is read from the DIP switches at power-up.
Watch out for
- Writing 101 (adapter relay outputs) can change the relay states.
Eaton S811+ soft starter (via C441 Ethernet module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Field inputs | Adapter input points. | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4 | |||
| HR | 1doc 2 | Control voltage | Adapter supply voltage. | UINT16 | mV | Read | |||
| HR | 4doc 5 | DIP switch value | Present DIP switch state. | BITMAP16 | Read | ||||
| HR | 100doc 101 | Field relay outputs | Adapter output relays. | BITMAP16 | Read/write | bit 0 = Output 1; bit 1 = Output 2 | |||
| HR | 109doc 110 | Modbus TCP com timeout | 0 = disabled. | UINT16 | ms | Read/write | |||
| HR | 110doc 111 | Field relay fault action | Per relay: 0 = apply fault value, 1 = no change. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 111doc 112 | Field relay fault state | Per relay value on comm fault: 0 off, 1 on. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 112doc 113 | Field relay idle action | Per relay: 0 = apply idle value, 1 = no change. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 113doc 114 | Field relay idle state | Per relay value on comm idle: 0 off, 1 on. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 142doc 143 | IP allocation method | UINT16 | Read | 0 = DHCP; 1 = Upper 3 octets from NV, last octet from DIP switches; 2 = Full address from NV memory; 3 = Restore 192.168.1.254 | ||||
| HR | 158doc 159 | Modbus serial com timeout | 0 = disabled. | UINT16 | ms | Read/write | |||
| HR | 159doc 160 | Modbus TX mode | UINT16 | Read/write | 0 = RTU; 1 = ASCII | ||||
| HR | 160doc 161 | Modbus baud rate | UINT16 | Read/write | 0 = 19200; 1 = 9600; 2 = 57600; 3 = 115200 | ||||
| HR | 161doc 162 | Modbus address | Serial slave address loaded at start-up. | UINT16 | Read/write | ||||
| HR | 162doc 163 | Modbus parity and stop bits | UINT16 | Read/write | 0 = Even, 1 stop; 1 = Odd, 1 stop; 2 = None, 2 stop; 3 = Even, 2 stop; 4 = Odd, 2 stop; 5 = None, 1 stop | ||||
| HR | 200doc 201 | Intercom status | Link between adapter and host device. | BITMAP16 | Read | bit 0 = Connected fully, no errors; bit 1 = Message fault occurred; bit 2 = Devices married, target identified; bit 3 = Basic connection established | |||
| HR | 252doc 253 | Motor ctrl com idle act disable | 1 = keep motor state on comm idle; 0 = apply idle value (254). | UINT16 | Read/write | ||||
| HR | 253doc 254 | Motor ctrl com idle action value | UINT16 | Read/write | 0 = Ignore (no change); 1 = Stop | ||||
| HR | 299doc 300 | Motor control status | BITMAP16 | Read | bit 0 = Running1 (RUN1 active); bit 1 = Running2 (jog active); bit 2 = Permissive (start allowed); bit 3 = Ramp2 settings active; bit 4 = Local control (0 = network); bit 5 = Faulted; bit 6 = Warning (self-clearing); bit 7 = In bypass | ||||
| HR | 303doc 304 | Motor control faults | BITMAP16 | Read | bit 0 = Phase loss; bit 1 = Phase imbalance; bit 2 = Thermal pile; bit 3 = Overcurrent; bit 4 = Breaker fault; bit 5 = Ground fault; bit 6 = Motor stall; bit 7 = Motor jam; bit 8 = Over-temperature; bit 9 = Underload; bit 11 = E-stop; bit 15 = Other | ||||
| HR | 304doc 305 | Motor control warnings | BITMAP16 | Read | bit 0 = Phase loss; bit 1 = Phase imbalance; bit 2 = Thermal pile; bit 3 = Overcurrent; bit 4 = Breaker fault; bit 5 = Ground fault; bit 6 = Motor stall; bit 7 = Motor jam; bit 8 = Over-temperature; bit 9 = Underload; bit 15 = Other | ||||
| HR | 305doc 306 | Average current % FLA | Average phase current as percent of nameplate FLA. | UINT16 | % | Read | |||
| HR | 306doc 307 | Thermal pile used | Trips at 100%. | UINT16 | % | Read | |||
| HR | 312doc 313 | Analog input value | Percent of the selected range. | UINT16 | % | Read | |||
| HR | 313doc 314 | Analog input status | UINT16 | Read | 0 = Not active; 1 = Under range; 2 = Over range; 3 = In overdrive; 4 = In range | ||||
| HR | 314doc 315 | Discrete input status | BITMAP16 | Read | bit 0 = Terminal input 1; bit 1 = Terminal input 2; bit 2 = Terminal input 3; bit 3 = Terminal input 4; bit 4 = Network input 1 (C441 input 1); bit 5 = Network input 2 (C441 input 2); bit 6 = Network input 3 (C441 input 3); bit 7 = Network input 4 (C441 input 4) | ||||
| HR | 315doc 316 | Discrete output status | BITMAP16 | Read | bit 0 = Form A relay; bit 1 = Form C relay; bit 2 = Network output 1 (C441 output 1); bit 3 = Network output 2 (C441 output 2) | ||||
| HR | 335doc 336 | Average line current (A) | Motor line current, 1 A units. | UINT16 | A | Read | |||
| HR | 339doc 340 | Average line current (0.1 A) | UINT16 | × 0.1 | A | Read | |||
| HR | 351doc 352 | Average pole current (A) | Current through the power poles, 1 A units. | UINT16 | A | Read | |||
| HR | 355doc 356 | Average pole current (0.1 A) | UINT16 | × 0.1 | A | Read | |||
| HR | 359doc 360 | Power factor | 0 to 1.0000. | UINT16 | × 0.0001 | Read | |||
| HR | 360doc 361 | Average 3-phase real power | UINT16 | kW | Read | ||||
| HR | 364doc 365 | DC control voltage | UINT16 | × 0.001 | V | Read | |||
| HR | 365doc 366 | Device temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 366doc 367 | Auto reset count | Auto reset attempts so far. | UINT16 | Read | ||||
| HR | 367doc 368 | Line frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 368doc 369 | Incoming phase sequence | UINT16 | Read | 0 = ABC; 1 = ACB | ||||
| HR | 379doc 380 | Application status | Last active fault. | UINT16 | Read | ||||
| HR | 499doc 500 | Modbus motor control word | Three-wire control (687 = 0). | BITMAP16 | Read/write | bit 0 = Run1 start (edge); bit 1 = Jog (level); bit 2 = Permissive (level, must be 1 to start); bit 3 = Fault reset; bit 7 = Ramp2 profile | |||
| HR | 500doc 501 | Modbus two-wire motor control word | Two-wire control (687 = 1). | BITMAP16 | Read/write | bit 0 = Run1 (level); bit 1 = Jog (level); bit 3 = Fault reset; bit 7 = Ramp2 profile | |||
| HR | 502doc 503 | Modbus baud rate | S811+ port; applied at power-up. | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200 (default); 5 = 38400; 6 = 57600; 7 = 115200 | |||
| HR | 503doc 504 | Modbus node address | From the DIP switches; read at power-up. | UINT16 | Read | ||||
| HR | 504doc 505 | Modbus parity | Applied at power-up. | UINT16 | Read/write | 0 = Even, 1 stop; 1 = Odd, 1 stop; 2 = None, 2 stop | |||
| HR | 506doc 507 | Modbus mode | UINT16 | Read/write | 0 = RTU (default); 1 = ASCII | ||||
| HR | 601doc 602 | Motor nameplate FLA | UINT16 | × 0.1 | A | Read/write | |||
| HR | 602doc 603 | Overload trip class | 5-30, default 20. | UINT16 | Read/write | ||||
| HR | 605doc 606 | Motor wiring configuration | UINT16 | Read/write | 0 = Inline (default); 1 = Inside the delta | ||||
| HR | 606doc 607 | Expected incoming phase sequence | UINT16 | Read/write | 0 = ABC; 1 = ACB | ||||
| HR | 607doc 608 | Motor start method | UINT16 | Read/write | 0 = Ramp start (voltage ramp); 1 = Current limit; 3 = Pump start | ||||
| HR | 613doc 614 | Kickstart duration | 0.0-2.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 622doc 623 | Local control only enable | UINT16 | Read/write | 0 = Disabled (network control possible); 1 = Enabled (terminal block only) | ||||
| HR | 639doc 640 | Fault reset mode | UINT16 | Read/write | 0 = Manual; 1 = Auto; 2 = Power-on reset | ||||
| HR | 642doc 643 | Overload trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 643doc 644 | Overload during start | UINT16 | Read/write | 0 = Disabled during start ramp; 1 = Enabled during start ramp | ||||
| HR | 644doc 645 | Phase reversal trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 645doc 646 | Undercurrent trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 646doc 647 | Undercurrent trip level | Percent of nameplate FLA. | UINT16 | % | Read/write | |||
| HR | 647doc 648 | Undercurrent trip duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 648doc 649 | Motor jam trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 649doc 650 | Motor stall trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 650doc 651 | Phase loss trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 652doc 653 | Phase loss duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 653doc 654 | Phase imbalance trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 655doc 656 | Phase imbalance trip duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 657doc 658 | Voltage imbalance trip duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 658doc 659 | Under voltage trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 659doc 660 | Under voltage trip threshold | Percent of rated motor voltage. | UINT16 | % | Read/write | |||
| HR | 660doc 661 | Under voltage trip duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 661doc 662 | Over voltage trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 662doc 663 | Over voltage trip threshold | Percent of rated motor voltage. | UINT16 | % | Read/write | |||
| HR | 663doc 664 | Over voltage trip duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 664doc 665 | Line frequency trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 665doc 666 | Frequency deviation trip threshold | Percent of rated line frequency. | UINT16 | % | Read/write | |||
| HR | 666doc 667 | Frequency trip duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 667doc 668 | Average power trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 668doc 669 | Low power trip threshold | Percent of rated W (sqrt3 x 0.8 x FLA x rated V). | UINT16 | % | Read/write | |||
| HR | 669doc 670 | High power trip threshold | Percent of rated W. | UINT16 | % | Read/write | |||
| HR | 670doc 671 | Power trip duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 671doc 672 | Analog input trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 674doc 675 | Analog input trip duration | 0.0-60.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 675doc 676 | Temperature sensor trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 676doc 677 | SCR not firing trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 677doc 678 | SCR shorted trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 683doc 684 | Motor comm loss action | UINT16 | Read/write | 0 = Auto stop; 1 = Auto run1; 3 = Hold last state; 7 = All-stop fault (trips) | ||||
| HR | 686doc 687 | Network two-wire control enable | UINT16 | Read/write | 0 = 3-wire control (register 500); 1 = 2-wire control (register 501) | ||||
| HR | 687doc 688 | Ground fault trip enable | UINT16 | Read/write | 0 = Disable; 1 = Fault enable; 2 = Warning enable | ||||
| HR | 688doc 689 | Ground fault inhibit from start delay | 0.0-20.0 s after the start ramp. | UINT16 | × 0.1 | s | Read/write |
Notes on this map
- Source is a distributor copy (precision-elec.com) of Eaton manual MN04200002E dated August 2012. Eaton lists a later edition (January 2016) at eaton.com, which could not be downloaded from this machine; check it for changes.
- Only registers that are clearly one 16-bit word are listed. Items printed with a gap after them (fault/fault lists 301, 318, 370; mains voltage 308; starts 311; RMS line and pole current blocks 328-357 apart from the averages; pole temperature 362) have no stated length or word order and are left out, as is the float FLA at 600.
- Torque, ramp, stop and start-delay settings without printed units (609-613, 615-622, 641, 681-683) and several trip thresholds without units in the table (652, 655, 657, 673, 674) are left out.
- Registers 503-507 are the S811+'s own Modbus port settings (baud default 19200, RTU default). With a C441U/C441V that port is the link to the adapter, so integrators reach this map over Modbus TCP; the adapter's serial settings are 159-163.
- Signedness is not stated in the manual; values are typed unsigned.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eaton S811+ soft starter (via C441 Ethernet module)
What Modbus registers does the Eaton S811+ soft starter (via C441 Ethernet module) have?
This map lists 88 registers: 88 holding registers. 61 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eaton S811+ soft starter (via C441 Ethernet module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0). The manual itself calls the control words 'Modbus reg #500' and '#501'.
What are the minimum Modbus registers to integrate the Eaton S811+ soft starter (via C441 Ethernet module)?
Start with HR 299 Motor control status (Status word); HR 303 Motor control faults (Fault bits); HR 304 Motor control warnings (Warning bits); HR 339 Average line current (0.1 A) (Average line current); HR 360 Average 3-phase real power (Real power); HR 306 Thermal pile used (Thermal pile); HR 499 Modbus motor control word (Network control word).
How do I enable Modbus control of the Eaton S811+ soft starter (via C441 Ethernet module)?
Network control needs 623 = 0 (local-only off); 687 selects three-wire (500, which also needs permissive bit 2 set) or two-wire (501) control. Modbus TCP is served by the C441 module (IP via DHCP, NV memory or DIP switches).
What happens when the Eaton S811+ soft starter (via C441 Ethernet module) loses Modbus communication?
684 sets the motor's comm-loss action (auto stop, run, hold or all-stop fault); 686 is the comm idle timeout that raises a device-missing fault; 110/159 set adapter-level Modbus timeouts.
Where is the official Eaton S811+ soft starter (via C441 Ethernet module) Modbus documentation?
The source is C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) (MN04200002E), revision 2012-08. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf. It may be an older revision, so check it against the live unit.
More Eaton Modbus register maps
- Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V - Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Power meter
Eaton IQ 250 / IQ 260 Electronic Power Meter
Eaton IQ 250 and IQ 260 meters (including the L logging versions), Modbus map Appendix B of IB02601006E.
Also known as: IQ 250, IQ 260, IQ 250L, IQ 260L, IQ250, IQ260 - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2 - Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34 - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T
Other soft starters & protection relays register maps
- Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250
All soft starters & protection relays Modbus register maps →