  4. C441 Motor Insight motor protection relay (via C441 Ethernet module)

Motor protection relay · Modbus register map

Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus register map

Updated 19 November 2026

Short answer

Motor Insight is Eaton's voltage and current monitoring motor protection relay. The C441 Ethernet module serves its data over Modbus TCP and RS-485 Modbus RTU together with its own I/O and network settings. This map covers the adapter I/O and comms registers, the motor measurements and trip/warning words (300-336), the command register and the protection settings (400-446).

This page lists 89 Modbus registers for the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) — 57 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.

Manufacturer
Eaton
Model
C441 Motor Insight motor protection relay (via C441 Ethernet module)
Equipment type
Motor protection relay
Registers
89 (57 writable)
Transport
Modbus TCP, Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T
Source document
C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) · MN04200002E · rev. 2012-08 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)

Integration in brief

Read 300-315 for currents, voltages, power and thermal pile, and 330-332 for trip and warning bits. Write command codes to 400 (e.g. 0xAA reset relay) and settings to 403-446. Comm-loss behaviour is set with 440/441 and 251-254.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 299Current I1UINT16Phase A currentRead
HR 302Current averageUINT16Average currentRead
HR 306Voltage averageUINT16Average voltageRead
HR 307Motor powerUINT16Motor powerRead
HR 313Thermal pileUINT16Thermal pileRead
HR 329Trip reasonBITMAP16Trip reason bitsRead
HR 331Warning / alarm indicationsBITMAP16Warning bitsRead
HR 399Command registerUINT16Command register (reset relay etc.)Read/write

Enable Modbus control & writes

Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.

Communication loss & watchdog

Register 110 (Modbus TCP) and 159 (serial) set a com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.

Byte order & addressing

Network setup

Watch out for

Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

89 of 89 shown
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Field inputsAdapter input points.BITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4
HR1doc 2Control voltageAdapter supply voltage.UINT16mVRead
HR4doc 5DIP switch valuePresent DIP switch state.BITMAP16Read
HR100doc 101Field relay outputsAdapter output relays.BITMAP16Read/writebit 0 = Output 1; bit 1 = Output 2
HR109doc 110Modbus TCP com timeout0 = disabled.UINT16msRead/write
HR110doc 111Field relay fault actionPer relay: 0 = apply fault value, 1 = no change.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR111doc 112Field relay fault statePer relay value on comm fault: 0 off, 1 on.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR112doc 113Field relay idle actionPer relay: 0 = apply idle value, 1 = no change.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR113doc 114Field relay idle statePer relay value on comm idle: 0 off, 1 on.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR142doc 143IP allocation methodUINT16Read0 = DHCP; 1 = Upper 3 octets from NV, last octet from DIP switches; 2 = Full address from NV memory; 3 = Restore 192.168.1.254
HR158doc 159Modbus serial com timeout0 = disabled.UINT16msRead/write
HR159doc 160Modbus TX modeUINT16Read/write0 = RTU; 1 = ASCII
HR160doc 161Modbus baud rateUINT16Read/write0 = 19200; 1 = 9600; 2 = 57600; 3 = 115200
HR161doc 162Modbus addressSerial slave address loaded at start-up.UINT16Read/write
HR162doc 163Modbus parity and stop bitsUINT16Read/write0 = Even, 1 stop; 1 = Odd, 1 stop; 2 = None, 2 stop; 3 = Even, 2 stop; 4 = Odd, 2 stop; 5 = None, 1 stop
HR200doc 201Intercom statusLink between adapter and host device.BITMAP16Readbit 0 = Connected fully, no errors; bit 1 = Message fault occurred; bit 2 = Devices married, target identified; bit 3 = Basic connection established
HR250doc 251Motor ctrl idle loss act disable1 = keep motor state on comm idle; 0 = apply idle value (252).UINT16Read/write
HR251doc 252Motor ctrl com idle action valueUINT16Read/write0 = Ignore (no change); 1 = Stop
HR252doc 253Motor ctrl com loss act disable1 = keep motor state on comm loss; 0 = apply loss value (254).UINT16Read/write
HR253doc 254Motor ctrl com loss action valueUINT16Read/write0 = Ignore (no change); 1 = Stop
HR299doc 300Current I1Phase A RMS; scale depends on model (see notes).UINT16Read
HR300doc 301Current I2Phase B RMS; scale depends on model.UINT16Read
HR301doc 302Current I3Phase C RMS; scale depends on model.UINT16Read
HR302doc 303Current averageAverage RMS; scale depends on model.UINT16Read
HR303doc 304Voltage L1-L2UINT16VRead
HR304doc 305Voltage L2-L3UINT16VRead
HR305doc 306Voltage L3-L1UINT16VRead
HR306doc 307Voltage averageUINT16VRead
HR307doc 308Motor power0.1 kW with external CTs, else 0.01 kW (see notes).UINT16Read
HR308doc 309Voltage unbalanceUINT16%Read
HR309doc 310Current unbalanceUINT16%Read
HR310doc 311Apparent power factorReal over apparent power.UINT16%Read
HR311doc 312Residual ground currentUINT16× 0.01ARead
HR312doc 313Line frequencyUINT16× 0.01HzRead
HR313doc 314Thermal pile100% causes an overload trip.UINT16%Read
HR314doc 315Fault codeMost recent fault when read as one register.UINT16Read
HR324doc 325Rapid cycling restart delay remainingSupply fault time to restart.UINT16sRead
HR325doc 326Normal restart delay remainingMotor fault time to restart.UINT16sRead
HR326doc 327Underload restart delay remainingLoad fault time to restart.UINT16sRead
HR327doc 328Run time hoursResettable.UINT16hRead/write
HR328doc 329Start countResettable.UINT16Read
HR329doc 330Trip reasonBITMAP16Readbit 0 = Restart attempts exceeded; bit 1 = Relay turned off (network/UI); bit 2 = Contactor failure; bit 3 = Under current trip; bit 4 = Overload trip; bit 5 = Ground fault trip; bit 6 = Current unbalance trip; bit 7 = Current single phase; bit 9 = High power trip; bit 10 = Over voltage trip; bit 11 = Under voltage trip; bit 12 = Voltage unbalance trip; bit 13 = Over current trip; bit 14 = Low power trip; bit 15 = Phase reversal trip
HR330doc 331Overload statusBITMAP16Readbit 0 = Overload trip; bit 1 = Ground fault trip; bit 2 = High power trip; bit 7 = Relay closed
HR331doc 332Warning / alarm indicationsBITMAP16Readbit 0 = Low voltage warning; bit 1 = High voltage warning; bit 2 = Voltage unbalance warning; bit 3 = Low power warning; bit 4 = Reverse phase warning; bit 5 = Current unbalance warning; bit 6 = Voltage single phase warning; bit 7 = Current single phase warning; bit 8 = Ground fault warning
HR332doc 333C441 DSP firmware versionUINT16Read
HR333doc 334UI firmware versionUINT16Read
HR334doc 335C441 unit IDModel identifier.UINT16Read/write186 = C441BA; 187 = C441BB; 202 = C441CA; 203 = C441CB; 218 = C441DA; 219 = C441DB; 234 = C4410109(x); 235 = C4410590(x)
HR335doc 336Aux relay trip reason120 V control power models.BITMAP16Readbit 1 = Relay turned off (network/UI); bit 2 = Contactor failure; bit 3 = Under current trip; bit 4 = Overload trip; bit 5 = Ground fault trip; bit 6 = Current unbalance trip; bit 7 = Current single phase; bit 8 = Mains frequency fault; bit 9 = High power trip; bit 10 = Over voltage trip; bit 11 = Under voltage trip; bit 12 = Voltage unbalance trip; bit 13 = Over current trip; bit 14 = Low power trip; bit 15 = Phase reversal trip
HR399doc 400Command registerWrite a command code.UINT16Read/write102 = Clear motor run hours (0x66); 119 = Clear fault queue 1 (0x77); 120 = Clear fault queue (0x78); 136 = Network watchdog enable (0x88); 153 = Network watchdog disable (0x99); 170 = Reset relay (0xAA); 187 = Clear motor start count (0xBB); 204 = Force ground fault (0xCC); 221 = Fault relay off (0xDD); 238 = Reset auxiliary relay (0xEE)
HR401doc 402Configuration resetUINT16Read/write1 = Soft reset (like power cycle); 2 = Factory reset
HR402doc 403CT multiplierConductor passes or CT ratio code (see notes).UINT16Read/write
HR403doc 404Ground fault pick-up levelUINT16× 0.01ARead/write
HR404doc 405Under current pick-up levelUINT16%Read/write
HR405doc 406Low power pick-up levelUINT16× 0.01kWRead/write
HR406doc 407Overload FLAMotor full load current.UINT16× 0.01ARead/write
HR407doc 408Current unbalance pick-up levelUINT16%Read/write
HR408doc 409Overload trip classUINT16Read/write
HR409doc 410Under voltage pick-up levelUINT16VRead/write
HR410doc 411Over voltage pick-up levelUINT16VRead/write
HR411doc 412Voltage unbalance pick-up levelUINT16%Read/write
HR412doc 413Jam pick-up levelUINT16%Read/write
HR413doc 414High kW trip limitUINT16× 0.01kWRead/write
HR414doc 415Phase orderUINT16Read/write0 = Trip disabled; 1 = ACB; 2 = ABC
HR415doc 416Supply fault hold-off timeRestart delay.UINT16sRead/write
HR416doc 417Motor fault hold-off timeUINT16minRead/write
HR417doc 418Load fault hold-off timeUINT16minRead/write
HR418doc 419Load fault number of restarts0 manual, 1-4 attempts, 5 automatic.UINT16Read/write
HR419doc 420Motor fault number of restarts0 manual, 1-4 attempts, 5 automatic.UINT16Read/write
HR420doc 421Ground fault trip delayUINT16sRead/write
HR421doc 422Under current trip delayUINT16sRead/write
HR422doc 423Low power trip delayUINT16sRead/write
HR423doc 424Jam trip delayUINT16sRead/write
HR424doc 425Current unbalance trip delayUINT16sRead/write
HR425doc 426Under voltage trip delayUINT16sRead/write
HR426doc 427Over voltage trip delayUINT16sRead/write
HR427doc 428Voltage unbalance trip delayUINT16sRead/write
HR428doc 429High kW trip timeUINT16sRead/write
HR429doc 430Current phase loss trip delayUINT16sRead/write
HR432doc 433Trip enable bitsBITMAP16Read/writebit 0 = Ground fault; bit 1 = Voltage unbalance; bit 2 = Current unbalance; bit 3 = Under current; bit 4 = Phase loss; bit 5 = Jam; bit 6 = Low power; bit 7 = High power; bit 8 = Over voltage; bit 9 = Under voltage; bit 10 = Phase order
HR433doc 434Overload reset modeUINT16Read/write0 = Manual reset; 1 = Use motor fault reset delay and attempts
HR434doc 435Voltage faults trip modeUINT16Read/write0 = Trip on supply fault; 1 = Alarm, no trip (inhibit start)
HR435doc 436Ground fault trip modeUINT16Read/write0 = Trip on ground fault; 1 = Alarm, no trip
HR436doc 437Run transition percentPercent of FLA.UINT16%Read/write
HR437doc 438Run transition timeUINT16sRead/write
HR438doc 439Network statusBITMAP16Readbit 0 = Watchdog enabled; bit 2 = Front panel locked
HR439doc 440C441 comm loss timeoutUINT16msRead/write
HR440doc 441C441 comm loss behaviorUINT16Read/write1 = Fault (default); 2 = Hold last state
HR442doc 443Load fault reset delay calcUINT16Read/write0 = Disabled (default); 1 = Enabled
HR445doc 446Aux relay reset delay120 V models; 0 = no auto reset, 1-500 min.UINT16minRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)

What Modbus registers does the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) have?

This map lists 89 registers: 89 holding registers. 57 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0).

What are the minimum Modbus registers to integrate the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)?

Start with HR 299 Current I1 (Phase A current); HR 302 Current average (Average current); HR 306 Voltage average (Average voltage); HR 307 Motor power (Motor power); HR 313 Thermal pile (Thermal pile); HR 329 Trip reason (Trip reason bits); HR 331 Warning / alarm indications (Warning bits); HR 399 Command register (Command register (reset relay etc.)).

How do I enable Modbus control of the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)?

Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.

What happens when the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) loses Modbus communication?

Register 110 (Modbus TCP) and 159 (serial) set a com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.

Where is the official Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus documentation?

The source is C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) (MN04200002E), revision 2012-08. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf. It may be an older revision, so check it against the live unit.