Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus register map
Updated 19 November 2026
Motor Insight is Eaton's voltage and current monitoring motor protection relay. The C441 Ethernet module serves its data over Modbus TCP and RS-485 Modbus RTU together with its own I/O and network settings. This map covers the adapter I/O and comms registers, the motor measurements and trip/warning words (300-336), the command register and the protection settings (400-446).
This page lists 89 Modbus registers for the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) — 57 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eaton
- Model
- C441 Motor Insight motor protection relay (via C441 Ethernet module)
- Equipment type
- Motor protection relay
- Registers
- 89 (57 writable)
- Transport
- Modbus TCP, Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T
Integration notes: Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Read 300-315 for currents, voltages, power and thermal pile, and 330-332 for trip and warning bits. Write command codes to 400 (e.g. 0xAA reset relay) and settings to 403-446. Comm-loss behaviour is set with 440/441 and 251-254.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 299 | Current I1 | UINT16 | Phase A current | Read |
| HR 302 | Current average | UINT16 | Average current | Read |
| HR 306 | Voltage average | UINT16 | Average voltage | Read |
| HR 307 | Motor power | UINT16 | Motor power | Read |
| HR 313 | Thermal pile | UINT16 | Thermal pile | Read |
| HR 329 | Trip reason | BITMAP16 | Trip reason bits | Read |
| HR 331 | Warning / alarm indications | BITMAP16 | Warning bits | Read |
| HR 399 | Command register | UINT16 | Command register (reset relay etc.) | Read/write |
Enable Modbus control & writes
Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.
Communication loss & watchdog
Register 110 (Modbus TCP) and 159 (serial) set a com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.
Byte order & addressing
- Register numbers are 1-based; subtract 1 on the wire.
- Coil numbers in the manual are bit views of registers (coil = 16 x (register - 1) + bit + 1), not separate data.
Network setup
- Serial port settings live in 160-163 (mode, baud, address, parity/stop) where the table lists them.
- On a C441R/C441T the RS-485 port is an extra Modbus RTU/ASCII monitoring port that serves the same register map.
Watch out for
- Several values change scale with hardware or a scale register; check the notes before trusting raw numbers.
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Field inputs | Adapter input points. | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4 | |||
| HR | 1doc 2 | Control voltage | Adapter supply voltage. | UINT16 | mV | Read | |||
| HR | 4doc 5 | DIP switch value | Present DIP switch state. | BITMAP16 | Read | ||||
| HR | 100doc 101 | Field relay outputs | Adapter output relays. | BITMAP16 | Read/write | bit 0 = Output 1; bit 1 = Output 2 | |||
| HR | 109doc 110 | Modbus TCP com timeout | 0 = disabled. | UINT16 | ms | Read/write | |||
| HR | 110doc 111 | Field relay fault action | Per relay: 0 = apply fault value, 1 = no change. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 111doc 112 | Field relay fault state | Per relay value on comm fault: 0 off, 1 on. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 112doc 113 | Field relay idle action | Per relay: 0 = apply idle value, 1 = no change. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 113doc 114 | Field relay idle state | Per relay value on comm idle: 0 off, 1 on. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 142doc 143 | IP allocation method | UINT16 | Read | 0 = DHCP; 1 = Upper 3 octets from NV, last octet from DIP switches; 2 = Full address from NV memory; 3 = Restore 192.168.1.254 | ||||
| HR | 158doc 159 | Modbus serial com timeout | 0 = disabled. | UINT16 | ms | Read/write | |||
| HR | 159doc 160 | Modbus TX mode | UINT16 | Read/write | 0 = RTU; 1 = ASCII | ||||
| HR | 160doc 161 | Modbus baud rate | UINT16 | Read/write | 0 = 19200; 1 = 9600; 2 = 57600; 3 = 115200 | ||||
| HR | 161doc 162 | Modbus address | Serial slave address loaded at start-up. | UINT16 | Read/write | ||||
| HR | 162doc 163 | Modbus parity and stop bits | UINT16 | Read/write | 0 = Even, 1 stop; 1 = Odd, 1 stop; 2 = None, 2 stop; 3 = Even, 2 stop; 4 = Odd, 2 stop; 5 = None, 1 stop | ||||
| HR | 200doc 201 | Intercom status | Link between adapter and host device. | BITMAP16 | Read | bit 0 = Connected fully, no errors; bit 1 = Message fault occurred; bit 2 = Devices married, target identified; bit 3 = Basic connection established | |||
| HR | 250doc 251 | Motor ctrl idle loss act disable | 1 = keep motor state on comm idle; 0 = apply idle value (252). | UINT16 | Read/write | ||||
| HR | 251doc 252 | Motor ctrl com idle action value | UINT16 | Read/write | 0 = Ignore (no change); 1 = Stop | ||||
| HR | 252doc 253 | Motor ctrl com loss act disable | 1 = keep motor state on comm loss; 0 = apply loss value (254). | UINT16 | Read/write | ||||
| HR | 253doc 254 | Motor ctrl com loss action value | UINT16 | Read/write | 0 = Ignore (no change); 1 = Stop | ||||
| HR | 299doc 300 | Current I1 | Phase A RMS; scale depends on model (see notes). | UINT16 | Read | ||||
| HR | 300doc 301 | Current I2 | Phase B RMS; scale depends on model. | UINT16 | Read | ||||
| HR | 301doc 302 | Current I3 | Phase C RMS; scale depends on model. | UINT16 | Read | ||||
| HR | 302doc 303 | Current average | Average RMS; scale depends on model. | UINT16 | Read | ||||
| HR | 303doc 304 | Voltage L1-L2 | UINT16 | V | Read | ||||
| HR | 304doc 305 | Voltage L2-L3 | UINT16 | V | Read | ||||
| HR | 305doc 306 | Voltage L3-L1 | UINT16 | V | Read | ||||
| HR | 306doc 307 | Voltage average | UINT16 | V | Read | ||||
| HR | 307doc 308 | Motor power | 0.1 kW with external CTs, else 0.01 kW (see notes). | UINT16 | Read | ||||
| HR | 308doc 309 | Voltage unbalance | UINT16 | % | Read | ||||
| HR | 309doc 310 | Current unbalance | UINT16 | % | Read | ||||
| HR | 310doc 311 | Apparent power factor | Real over apparent power. | UINT16 | % | Read | |||
| HR | 311doc 312 | Residual ground current | UINT16 | × 0.01 | A | Read | |||
| HR | 312doc 313 | Line frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 313doc 314 | Thermal pile | 100% causes an overload trip. | UINT16 | % | Read | |||
| HR | 314doc 315 | Fault code | Most recent fault when read as one register. | UINT16 | Read | ||||
| HR | 324doc 325 | Rapid cycling restart delay remaining | Supply fault time to restart. | UINT16 | s | Read | |||
| HR | 325doc 326 | Normal restart delay remaining | Motor fault time to restart. | UINT16 | s | Read | |||
| HR | 326doc 327 | Underload restart delay remaining | Load fault time to restart. | UINT16 | s | Read | |||
| HR | 327doc 328 | Run time hours | Resettable. | UINT16 | h | Read/write | |||
| HR | 328doc 329 | Start count | Resettable. | UINT16 | Read | ||||
| HR | 329doc 330 | Trip reason | BITMAP16 | Read | bit 0 = Restart attempts exceeded; bit 1 = Relay turned off (network/UI); bit 2 = Contactor failure; bit 3 = Under current trip; bit 4 = Overload trip; bit 5 = Ground fault trip; bit 6 = Current unbalance trip; bit 7 = Current single phase; bit 9 = High power trip; bit 10 = Over voltage trip; bit 11 = Under voltage trip; bit 12 = Voltage unbalance trip; bit 13 = Over current trip; bit 14 = Low power trip; bit 15 = Phase reversal trip | ||||
| HR | 330doc 331 | Overload status | BITMAP16 | Read | bit 0 = Overload trip; bit 1 = Ground fault trip; bit 2 = High power trip; bit 7 = Relay closed | ||||
| HR | 331doc 332 | Warning / alarm indications | BITMAP16 | Read | bit 0 = Low voltage warning; bit 1 = High voltage warning; bit 2 = Voltage unbalance warning; bit 3 = Low power warning; bit 4 = Reverse phase warning; bit 5 = Current unbalance warning; bit 6 = Voltage single phase warning; bit 7 = Current single phase warning; bit 8 = Ground fault warning | ||||
| HR | 332doc 333 | C441 DSP firmware version | UINT16 | Read | |||||
| HR | 333doc 334 | UI firmware version | UINT16 | Read | |||||
| HR | 334doc 335 | C441 unit ID | Model identifier. | UINT16 | Read/write | 186 = C441BA; 187 = C441BB; 202 = C441CA; 203 = C441CB; 218 = C441DA; 219 = C441DB; 234 = C4410109(x); 235 = C4410590(x) | |||
| HR | 335doc 336 | Aux relay trip reason | 120 V control power models. | BITMAP16 | Read | bit 1 = Relay turned off (network/UI); bit 2 = Contactor failure; bit 3 = Under current trip; bit 4 = Overload trip; bit 5 = Ground fault trip; bit 6 = Current unbalance trip; bit 7 = Current single phase; bit 8 = Mains frequency fault; bit 9 = High power trip; bit 10 = Over voltage trip; bit 11 = Under voltage trip; bit 12 = Voltage unbalance trip; bit 13 = Over current trip; bit 14 = Low power trip; bit 15 = Phase reversal trip | |||
| HR | 399doc 400 | Command register | Write a command code. | UINT16 | Read/write | 102 = Clear motor run hours (0x66); 119 = Clear fault queue 1 (0x77); 120 = Clear fault queue (0x78); 136 = Network watchdog enable (0x88); 153 = Network watchdog disable (0x99); 170 = Reset relay (0xAA); 187 = Clear motor start count (0xBB); 204 = Force ground fault (0xCC); 221 = Fault relay off (0xDD); 238 = Reset auxiliary relay (0xEE) | |||
| HR | 401doc 402 | Configuration reset | UINT16 | Read/write | 1 = Soft reset (like power cycle); 2 = Factory reset | ||||
| HR | 402doc 403 | CT multiplier | Conductor passes or CT ratio code (see notes). | UINT16 | Read/write | ||||
| HR | 403doc 404 | Ground fault pick-up level | UINT16 | × 0.01 | A | Read/write | |||
| HR | 404doc 405 | Under current pick-up level | UINT16 | % | Read/write | ||||
| HR | 405doc 406 | Low power pick-up level | UINT16 | × 0.01 | kW | Read/write | |||
| HR | 406doc 407 | Overload FLA | Motor full load current. | UINT16 | × 0.01 | A | Read/write | ||
| HR | 407doc 408 | Current unbalance pick-up level | UINT16 | % | Read/write | ||||
| HR | 408doc 409 | Overload trip class | UINT16 | Read/write | |||||
| HR | 409doc 410 | Under voltage pick-up level | UINT16 | V | Read/write | ||||
| HR | 410doc 411 | Over voltage pick-up level | UINT16 | V | Read/write | ||||
| HR | 411doc 412 | Voltage unbalance pick-up level | UINT16 | % | Read/write | ||||
| HR | 412doc 413 | Jam pick-up level | UINT16 | % | Read/write | ||||
| HR | 413doc 414 | High kW trip limit | UINT16 | × 0.01 | kW | Read/write | |||
| HR | 414doc 415 | Phase order | UINT16 | Read/write | 0 = Trip disabled; 1 = ACB; 2 = ABC | ||||
| HR | 415doc 416 | Supply fault hold-off time | Restart delay. | UINT16 | s | Read/write | |||
| HR | 416doc 417 | Motor fault hold-off time | UINT16 | min | Read/write | ||||
| HR | 417doc 418 | Load fault hold-off time | UINT16 | min | Read/write | ||||
| HR | 418doc 419 | Load fault number of restarts | 0 manual, 1-4 attempts, 5 automatic. | UINT16 | Read/write | ||||
| HR | 419doc 420 | Motor fault number of restarts | 0 manual, 1-4 attempts, 5 automatic. | UINT16 | Read/write | ||||
| HR | 420doc 421 | Ground fault trip delay | UINT16 | s | Read/write | ||||
| HR | 421doc 422 | Under current trip delay | UINT16 | s | Read/write | ||||
| HR | 422doc 423 | Low power trip delay | UINT16 | s | Read/write | ||||
| HR | 423doc 424 | Jam trip delay | UINT16 | s | Read/write | ||||
| HR | 424doc 425 | Current unbalance trip delay | UINT16 | s | Read/write | ||||
| HR | 425doc 426 | Under voltage trip delay | UINT16 | s | Read/write | ||||
| HR | 426doc 427 | Over voltage trip delay | UINT16 | s | Read/write | ||||
| HR | 427doc 428 | Voltage unbalance trip delay | UINT16 | s | Read/write | ||||
| HR | 428doc 429 | High kW trip time | UINT16 | s | Read/write | ||||
| HR | 429doc 430 | Current phase loss trip delay | UINT16 | s | Read/write | ||||
| HR | 432doc 433 | Trip enable bits | BITMAP16 | Read/write | bit 0 = Ground fault; bit 1 = Voltage unbalance; bit 2 = Current unbalance; bit 3 = Under current; bit 4 = Phase loss; bit 5 = Jam; bit 6 = Low power; bit 7 = High power; bit 8 = Over voltage; bit 9 = Under voltage; bit 10 = Phase order | ||||
| HR | 433doc 434 | Overload reset mode | UINT16 | Read/write | 0 = Manual reset; 1 = Use motor fault reset delay and attempts | ||||
| HR | 434doc 435 | Voltage faults trip mode | UINT16 | Read/write | 0 = Trip on supply fault; 1 = Alarm, no trip (inhibit start) | ||||
| HR | 435doc 436 | Ground fault trip mode | UINT16 | Read/write | 0 = Trip on ground fault; 1 = Alarm, no trip | ||||
| HR | 436doc 437 | Run transition percent | Percent of FLA. | UINT16 | % | Read/write | |||
| HR | 437doc 438 | Run transition time | UINT16 | s | Read/write | ||||
| HR | 438doc 439 | Network status | BITMAP16 | Read | bit 0 = Watchdog enabled; bit 2 = Front panel locked | ||||
| HR | 439doc 440 | C441 comm loss timeout | UINT16 | ms | Read/write | ||||
| HR | 440doc 441 | C441 comm loss behavior | UINT16 | Read/write | 1 = Fault (default); 2 = Hold last state | ||||
| HR | 442doc 443 | Load fault reset delay calc | UINT16 | Read/write | 0 = Disabled (default); 1 = Enabled | ||||
| HR | 445doc 446 | Aux relay reset delay | 120 V models; 0 = no auto reset, 1-500 min. | UINT16 | min | Read/write |
Notes on this map
- Source is a distributor copy (precision-elec.com) of Eaton manual MN04200002E dated August 2012. Eaton lists a later edition (January 2016) at eaton.com, which could not be downloaded from this machine; check it for changes.
- The tables print 1-based Modbus register numbers: the production/consumption-list note says field inputs register 1 is register address 0 (address = register number - 1).
- All registers listed are single 16-bit words. Multi-word items (32-bit adapter serial number at 7, firmware/hardware revision at 9/11, IP addresses 144-154, MAC address 156) have no stated word order or layout and are left out. Signedness is not stated; values are typed unsigned.
- The same map is served over Modbus TCP and over the adapter's RS-485 Modbus RTU port; functions 01/02/03/04/05/06/15/16/23 and 43/14 are supported. Coil numbers in the manual are bit views of the same registers and are not listed here.
- Registers 1000-4000 are a user-configurable production/consumption list (custom register block); not expanded here.
- Current registers 300-303 are 0.1 A on 90 A models and on 9 A models with external CTs, and 0.01 A on 9 A models without CTs; motor power 308 is 0.1 kW with external CTs and 0.01 kW otherwise. They are left unscaled here; apply the factor that matches the hardware.
- Fault code 315 heads a fault queue: read as a list, faults run newest first. The table's next entry is 325.
- CT multiplier 403: 90 A units 1-4 conductor passes; 9 A units 1-2 passes or 3 = 150:5, 4 = 300:5, 5 = 600:5 CTs.
- Register 401 (Motor Control) has no description in the manual and is left out.
- Defaults are those printed for the C441R/C441T serial monitoring port (address 1, 19.2k, even parity, 1 stop bit, RTU); data bits and the Modbus TCP port are not stated.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
What Modbus registers does the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) have?
This map lists 89 registers: 89 holding registers. 57 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0).
What are the minimum Modbus registers to integrate the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)?
Start with HR 299 Current I1 (Phase A current); HR 302 Current average (Average current); HR 306 Voltage average (Average voltage); HR 307 Motor power (Motor power); HR 313 Thermal pile (Thermal pile); HR 329 Trip reason (Trip reason bits); HR 331 Warning / alarm indications (Warning bits); HR 399 Command register (Command register (reset relay etc.)).
How do I enable Modbus control of the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)?
Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.
What happens when the Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) loses Modbus communication?
Register 110 (Modbus TCP) and 159 (serial) set a com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.
Where is the official Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module) Modbus documentation?
The source is C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) (MN04200002E), revision 2012-08. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf. It may be an older revision, so check it against the live unit.
More Eaton Modbus register maps
- Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Power meter
Eaton IQ 250 / IQ 260 Electronic Power Meter
Eaton IQ 250 and IQ 260 meters (including the L logging versions), Modbus map Appendix B of IB02601006E.
Also known as: IQ 250, IQ 260, IQ 250L, IQ 260L, IQ250, IQ260 - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2 - Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34 - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V
Other soft starters & protection relays register maps
- Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042
All soft starters & protection relays Modbus register maps →
Source: C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) · MN04200002E · rev. 2012-08 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.