Motor protection relay (overload relay) · Modbus register map
Eaton C440 electronic overload relay (via C441 Ethernet module) Modbus register map
Updated 19 November 2026
The C440 is Eaton's electronic overload relay. With a C441 Ethernet module it reports motor state, phase currents, thermal memory and latched faults over Modbus TCP (and the module's RS-485 port), and accepts remote trip and reset. This map covers the adapter I/O registers, the overload data (300-315), trip/reset control (332) and scaling and identity registers (396-399).
This page lists 37 Modbus registers for the Eaton C440 electronic overload relay (via C441 Ethernet module) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eaton
- Model
- C440 electronic overload relay (via C441 Ethernet module)
- Equipment type
- Motor protection relay (overload relay)
- Registers
- 37 (11 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- C440, C440 overload relay, C441U, C441V
Integration notes: Eaton C440 electronic overload relay (via C441 Ethernet module)
Read 398 once for the current multiplier, then poll 300 (state), 301-304 (currents), 305 (thermal memory) and 306 (latched faults). Write 332 bit 1 to reset or bit 0 to trip.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 299 | Motor control state | UINT16 | Motor state | Read |
| HR 303 | Average current | UINT16 | Average current (scale by 398) | Read |
| HR 397 | Current scale value | UINT16 | Current scale value | Read |
| HR 304 | Thermal memory | UINT16 | Thermal memory | Read |
| HR 305 | Latched faults | BITMAP16 | Latched fault bits | Read |
| HR 331 | Trip/reset control | BITMAP16 | Remote trip / reset | Read/write |
Enable Modbus control & writes
Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.
Communication loss & watchdog
Register 110 sets the Modbus TCP com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.
Byte order & addressing
- Register numbers are 1-based; subtract 1 on the wire.
- Coil numbers in the manual are bit views of registers (coil = 16 x (register - 1) + bit + 1), not separate data.
Network setup
- IP address mode is set by the DIP switch on the module: 0 = restore 192.168.1.254, 1-253 = last octet with the rest from NV memory, 254 = NV memory (factory 192.168.1.254), 255 = DHCP.
- The C440 table has no serial-port registers: the C441U/C441V serial port is the link to the C440, so use Modbus TCP.
Watch out for
- Several values change scale with hardware or a scale register; check the notes before trusting raw numbers.
Eaton C440 electronic overload relay (via C441 Ethernet module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Field inputs | Adapter input points. | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4 | |||
| HR | 1doc 2 | Control voltage | Adapter supply voltage. | UINT16 | mV | Read | |||
| HR | 4doc 5 | DIP switch value | Present DIP switch state. | BITMAP16 | Read | ||||
| HR | 100doc 101 | Field relay outputs | Adapter output relays. | BITMAP16 | Read/write | bit 0 = Output 1; bit 1 = Output 2 | |||
| HR | 109doc 110 | Modbus TCP com timeout | 0 = disabled. | UINT16 | ms | Read/write | |||
| HR | 110doc 111 | Field relay fault action | Per relay: 0 = apply fault value, 1 = no change. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 111doc 112 | Field relay fault state | Per relay value on comm fault: 0 off, 1 on. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 112doc 113 | Field relay idle action | Per relay: 0 = apply idle value, 1 = no change. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 113doc 114 | Field relay idle state | Per relay value on comm idle: 0 off, 1 on. | BITMAP16 | Read/write | bit 0 = Relay / output 1; bit 1 = Relay / output 2 | |||
| HR | 142doc 143 | IP allocation method | UINT16 | Read | 0 = DHCP; 1 = Upper 3 octets from NV, last octet from DIP switches; 2 = Full address from NV memory; 3 = Restore 192.168.1.254 | ||||
| HR | 200doc 201 | Intercom status | Link between adapter and host device. | BITMAP16 | Read | bit 0 = Connected fully, no errors; bit 1 = Message fault occurred; bit 2 = Devices married, target identified; bit 3 = Basic connection established | |||
| HR | 250doc 251 | Motor ctrl idle loss act disable | 1 = keep motor state on comm idle; 0 = apply idle value (252). | UINT16 | Read/write | ||||
| HR | 251doc 252 | Motor ctrl com idle action value | UINT16 | Read/write | 0 = Ignore (no change); 1 = Stop | ||||
| HR | 252doc 253 | Motor ctrl com loss act disable | 1 = keep motor state on comm loss; 0 = apply loss value (254). | UINT16 | Read/write | ||||
| HR | 253doc 254 | Motor ctrl com loss action value | UINT16 | Read/write | 0 = Ignore (no change); 1 = Stop | ||||
| HR | 299doc 300 | Motor control state | UINT16 | Read | 0 = Stopped; 1 = Running; 2 = Tripped; 3 = Tripped; 4 = Resetting | ||||
| HR | 300doc 301 | Phase A RMS current | Scaled by register 398. | UINT16 | Read | ||||
| HR | 301doc 302 | Phase B RMS current | Scaled by register 398. | UINT16 | Read | ||||
| HR | 302doc 303 | Phase C RMS current | Scaled by register 398. | UINT16 | Read | ||||
| HR | 303doc 304 | Average current | Scaled by register 398. | UINT16 | Read | ||||
| HR | 304doc 305 | Thermal memory | 100% = trip. | UINT16 | % | Read | |||
| HR | 305doc 306 | Latched faults | Cleared by network reset or when current flows. | BITMAP16 | Read | bit 0 = Overload fault; bit 1 = Phase imbalance; bit 2 = Phase loss fault; bit 3 = Ground fault; bit 4 = Network trip command; bit 5 = NV memory failure | |||
| HR | 306doc 307 | Current as percent of FLA | UINT16 | % | Read | ||||
| HR | 307doc 308 | Phase imbalance | UINT16 | % | Read | ||||
| HR | 308doc 309 | Ground fault percent | GF% = ground current / (0.5 x FLA). | UINT16 | % | Read | |||
| HR | 309doc 310 | Ground current | Scaled by register 398. | UINT16 | Read | ||||
| HR | 310doc 311 | FLA setting | From the potentiometer; scaled by 398. | UINT16 | Read | ||||
| HR | 311doc 312 | Overload class | Device dependent. | UINT16 | Read | ||||
| HR | 312doc 313 | Line frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 313doc 314 | Feature states | Bits 0-1 trip class: 00=10, 01=15, 10=20, 11=30. | BITMAP16 | Read | bit 2 = Phase loss/imbalance enabled; bit 3 = Ground fault enabled; bit 4 = Auto reset enabled; bit 5 = Remote reset active; bit 6 = DIP switch position 0; bit 7 = DIP switch position 1; bit 8 = DIP switch position 2; bit 9 = DIP switch position 3 | |||
| HR | 314doc 315 | Device temperature | Accuracy about 10%. | UINT16 | °C | Read | |||
| HR | 331doc 332 | Trip/reset control | Auto-clearing command bits. | BITMAP16 | Read/write | bit 0 = Cause a trip (overrides reset); bit 1 = Cause a reset | |||
| HR | 395doc 396 | Min FLA | Lowest FLA setting; scaled by 398. | UINT16 | Read | ||||
| HR | 396doc 397 | Max FLA | Highest FLA setting; scaled by 398. | UINT16 | Read | ||||
| HR | 397doc 398 | Current scale value | Multiplier for currents: 10 means values are in 0.1 A. | UINT16 | Read | ||||
| HR | 398doc 399 | Product code | Odd number = ground-fault capable. | UINT16 | Read | ||||
| HR | 428doc 429 | Firmware build | UINT16 | Read |
Notes on this map
- Source is a distributor copy (precision-elec.com) of Eaton manual MN04200002E dated August 2012. Eaton lists a later edition (January 2016) at eaton.com, which could not be downloaded from this machine; check it for changes.
- The tables print 1-based Modbus register numbers: the production/consumption-list note says field inputs register 1 is register address 0 (address = register number - 1).
- All registers listed are single 16-bit words. Multi-word items (32-bit adapter serial number at 7, firmware/hardware revision at 9/11, IP addresses 144-154, MAC address 156) have no stated word order or layout and are left out. Signedness is not stated; values are typed unsigned.
- The C440 is used with the stand-alone C441U/C441V module, whose serial port is the link to the C440 and is not available as a monitoring port, so this map is reached over Modbus TCP. Functions 01/02/03/04/05/06/15/16/23 and 43/14 are supported. Coil numbers in the manual are bit views of the same registers and are not listed here.
- Registers 1000-4000 are a user-configurable production/consumption list (custom register block); not expanded here.
- Current registers (301-304, 310, 311, 396, 397) are divided by the multiplier in register 398; e.g. 398 = 10 means 0.1 A units. They are left unscaled here.
- Line frequency 313 is printed in deciHz (0.1 Hz).
- Left out: 400 serial number and 428/430 firmware revision/checksum (32-bit, word order not stated) and 402 hardware revision (packed bytes).
- The C440 table does not list the serial-port setup registers 159-163 that the C441 and S611 tables have.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eaton C440 electronic overload relay (via C441 Ethernet module)
What Modbus registers does the Eaton C440 electronic overload relay (via C441 Ethernet module) have?
This map lists 37 registers: 37 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eaton C440 electronic overload relay (via C441 Ethernet module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0).
What are the minimum Modbus registers to integrate the Eaton C440 electronic overload relay (via C441 Ethernet module)?
Start with HR 299 Motor control state (Motor state); HR 303 Average current (Average current (scale by 398)); HR 397 Current scale value (Current scale value); HR 304 Thermal memory (Thermal memory); HR 305 Latched faults (Latched fault bits); HR 331 Trip/reset control (Remote trip / reset).
How do I enable Modbus control of the Eaton C440 electronic overload relay (via C441 Ethernet module)?
Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.
What happens when the Eaton C440 electronic overload relay (via C441 Ethernet module) loses Modbus communication?
Register 110 sets the Modbus TCP com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.
Where is the official Eaton C440 electronic overload relay (via C441 Ethernet module) Modbus documentation?
The source is C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) (MN04200002E), revision 2012-08. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf. It may be an older revision, so check it against the live unit.
More Eaton Modbus register maps
- Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Power meter
Eaton IQ 250 / IQ 260 Electronic Power Meter
Eaton IQ 250 and IQ 260 meters (including the L logging versions), Modbus map Appendix B of IB02601006E.
Also known as: IQ 250, IQ 260, IQ 250L, IQ 260L, IQ250, IQ260 - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2 - Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34 - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V
Other soft starters & protection relays register maps
- Protection relay
Siemens Reyrolle 7SR10 Argus overcurrent and earth-fault relay (Modbus RTU)
Reyrolle 7SR10 overcurrent / earth-fault relays, default Modbus RTU point list per Communication Protocols manual C53000-L7040-C002-7 (edition 11.2025, V01.00).
Also known as: 7SR10 Argus, Reyrolle 7SR10, 7SR1003, 7SR1004 - Motor management and protection relay
Siemens SIMOCODE pro V Modbus RTU basic unit
SIMOCODE pro V Modbus RTU basic units, per Configuration Manual 04/2015 (A5E33498234002A/RS-AA/001).
Also known as: SIMOCODE pro V Modbus, SIMOCODE pro V Modbus RTU - Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40 - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120
All soft starters & protection relays Modbus register maps →
Source: C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) · MN04200002E · rev. 2012-08 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.