Easy Modbus
  1. Home
  2. Modbus register maps
  3. Eaton
  4. S611 soft starter (via C441 Ethernet module)

Soft starter · Modbus register map

Eaton S611 soft starter (via C441 Ethernet module) Modbus register map

Updated 19 November 2026

Short answer

The S611 is an Eaton soft starter with built-in motor protection and metering. Through the C441 Ethernet module its data is served over Modbus TCP and RS-485 Modbus RTU. This map covers adapter I/O and comms registers, motor status and metering (300-338), the run/permissive/reset control word (400) and the start, protection and comm-loss settings (401-445).

This page lists 90 Modbus registers for the Eaton S611 soft starter (via C441 Ethernet module) — 57 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.

Manufacturer
Eaton
Model
S611 soft starter (via C441 Ethernet module)
Equipment type
Soft starter
Registers
90 (57 writable)
Transport
Modbus TCP, Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
S611, S611 soft starter, C441R, C441T
Source document
C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) · MN04200002E · rev. 2012-08 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eaton S611 soft starter (via C441 Ethernet module)

Integration in brief

Poll 300 for run/bypass/fault, 301-305 for current, 306-309 for voltage and 324 for trip bits. Start the motor by setting 400 bit 2 (permissive) and bit 0 (run); bit 3 resets a fault. Set 443-445 so the starter stops or faults when the network drops.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 299Motor statusBITMAP16Motor status bitsRead
HR 304Average currentUINT16Average current (scale by 301)Read
HR 300Current scale factorUINT16Current scale factorRead
HR 308Average voltageUINT16Average voltageRead
HR 313Overload thermal memoryUINT16Thermal memoryRead
HR 323Trip reasonBITMAP16Trip reason bitsRead
HR 399Motor controlBITMAP16Run / permissive / resetRead/write

Enable Modbus control & writes

Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.

Communication loss & watchdog

Register 110 (Modbus TCP) and 159 (serial) set a com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.

Byte order & addressing

Network setup

Watch out for

Eaton S611 soft starter (via C441 Ethernet module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

90 of 90 shown
Eaton S611 soft starter (via C441 Ethernet module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Field inputsAdapter input points.BITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4
HR1doc 2Control voltageAdapter supply voltage.UINT16mVRead
HR4doc 5DIP switch valuePresent DIP switch state.BITMAP16Read
HR100doc 101Field relay outputsAdapter output relays.BITMAP16Read/writebit 0 = Output 1; bit 1 = Output 2
HR109doc 110Modbus TCP com timeout0 = disabled.UINT16msRead/write
HR110doc 111Field relay fault actionPer relay: 0 = apply fault value, 1 = no change.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR111doc 112Field relay fault statePer relay value on comm fault: 0 off, 1 on.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR112doc 113Field relay idle actionPer relay: 0 = apply idle value, 1 = no change.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR113doc 114Field relay idle statePer relay value on comm idle: 0 off, 1 on.BITMAP16Read/writebit 0 = Relay / output 1; bit 1 = Relay / output 2
HR142doc 143IP allocation methodUINT16Read0 = DHCP; 1 = Upper 3 octets from NV, last octet from DIP switches; 2 = Full address from NV memory; 3 = Restore 192.168.1.254
HR158doc 159Modbus serial com timeout0 = disabled.UINT16msRead/write
HR159doc 160Modbus TX modeUINT16Read/write0 = RTU; 1 = ASCII
HR160doc 161Modbus baud rateUINT16Read/write0 = 19200; 1 = 9600; 2 = 57600; 3 = 115200
HR161doc 162Modbus addressSerial slave address loaded at start-up.UINT16Read/write
HR162doc 163Modbus parity and stop bitsUINT16Read/write0 = Even, 1 stop; 1 = Odd, 1 stop; 2 = None, 2 stop; 3 = Even, 2 stop; 4 = Odd, 2 stop; 5 = None, 1 stop
HR200doc 201Intercom statusLink between adapter and host device.BITMAP16Readbit 0 = Connected fully, no errors; bit 1 = Message fault occurred; bit 2 = Devices married, target identified; bit 3 = Basic connection established
HR250doc 251Motor ctrl idle loss act disable1 = keep motor state on comm idle; 0 = apply idle value (252).UINT16Read/write
HR251doc 252Motor ctrl com idle action valueUINT16Read/write0 = Ignore (no change); 1 = Stop
HR252doc 253Motor ctrl com loss act disable1 = keep motor state on comm loss; 0 = apply loss value (254).UINT16Read/write
HR253doc 254Motor ctrl com loss action valueUINT16Read/write0 = Ignore (no change); 1 = Stop
HR299doc 300Motor statusBITMAP16Readbit 0 = Run; bit 2 = In bypass; bit 5 = Fault; bit 11 = Relay 1 state; bit 12 = Relay 2 state; bit 13 = Control from network; bit 14 = Permissive state
HR300doc 301Current scale factorFactor used to scale 302-305.UINT16Read
HR301doc 302Phase A RMS currentScaled by register 301.UINT16Read
HR302doc 303Phase B RMS currentScaled by register 301.UINT16Read
HR303doc 304Phase C RMS currentScaled by register 301.UINT16Read
HR304doc 305Average currentScaled by register 301.UINT16Read
HR305doc 306Vab RMS voltageUINT16VRead
HR306doc 307Vbc RMS voltageUINT16VRead
HR307doc 308Vca RMS voltageUINT16VRead
HR308doc 309Average voltageUINT16VRead
HR309doc 310Total kilowattsPrinted scale factor x10.UINT16× 0.1kWRead
HR310doc 311Apparent power factorPower factor x 100.UINT16× 0.01Read
HR311doc 312Power signTells whether power is positive or negative (generating).UINT16Read
HR312doc 313Line frequencyUINT16× 0.01HzRead
HR313doc 314Overload thermal memory100% causes an overload trip.UINT16%Read
HR314doc 315Current unbalanceUINT16%Read
HR315doc 316Voltage unbalanceUINT16%Read
HR316doc 317Residual ground fault currentScaling x100.UINT16× 0.01Read
HR317doc 318Phase A pole temperatureUINT16× 0.1°CRead
HR318doc 319Phase B pole temperatureUINT16× 0.1°CRead
HR319doc 320Phase C pole temperatureUINT16× 0.1°CRead
HR320doc 321Average pole temperatureUINT16× 0.1°CRead
HR321doc 322Number of startsResettable via 402.UINT16Read
HR322doc 323Total run timeResettable via 402.UINT16hRead
HR323doc 324Trip reasonBITMAP16Readbit 0 = Overload; bit 1 = Jam; bit 2 = Stall; bit 3 = Current imbalance; bit 4 = Load disconnect; bit 5 = Phase loss; bit 6 = Mains fault; bit 7 = Phase reversal; bit 8 = Shorted SCR; bit 9 = SCR not firing; bit 10 = Pole over-temperature; bit 11 = Bypass dropout; bit 12 = SCR overcurrent; bit 13 = Contactor overcurrent; bit 14 = Communication fault; bit 15 = Other device fault
HR324doc 325Fault codeMost recent fault when read as one register.UINT16Read
HR336doc 337UI firmware versionUINT16Read
HR337doc 338Unit IDProduct identifier.UINT16Read
HR399doc 400Motor controlBITMAP16Read/writebit 0 = Run; bit 2 = Permissive; bit 3 = Reset
HR400doc 401Start input behaviorUINT16Read/write0 = Edge; 1 = Level
HR401doc 402Command registerUINT16Read/write1 = Clear motor run hours; 2 = Clear motor start count; 3 = Clear fault queue; 255 = Force overload reset
HR402doc 403Configuration resetUINT16Read/write1 = Soft reset; 2 = Factory defaults
HR403doc 404Overload FLAScaling x10.UINT16× 0.1ARead/write
HR404doc 405Rated voltageMotor rated voltage.UINT16Read/write
HR405doc 406Start methodUINT16Read/write0 = Vramp (voltage ramp); 1 = Limit; 2 = Pump
HR406doc 407Start timeStart ramp time.UINT16× 0.1sRead/write
HR407doc 408Initial torqueStarting torque percent.UINT16%Read/write
HR408doc 409Stop timeStop ramp time.UINT16× 0.1sRead/write
HR409doc 410Pump stop timeUINT16sRead/write
HR410doc 411Kick start timeUINT16× 0.1sRead/write
HR411doc 412Kick start initial torqueUINT16%Read/write
HR412doc 413Reset modeUINT16Read/write0 = Manual; 1 = Auto
HR413doc 414Fault enable bitsBITMAP16Read/writebit 0 = Overload; bit 1 = Jam; bit 2 = Stall; bit 3 = Current imbalance; bit 4 = Load disconnect; bit 5 = Phase loss; bit 6 = Under voltage; bit 7 = Over voltage; bit 8 = Voltage unbalance; bit 9 = Phase reversal; bit 10 = Ground fault; bit 11 = Overload on start; bit 12 = Shorted SCR; bit 13 = SCR not firing; bit 14 = Over temperature
HR414doc 415Overload classUINT16Read/write
HR415doc 416Jam trip levelPercent of FLA.UINT16%Read/write
HR416doc 417Jam trip delayUINT16sRead/write
HR417doc 418Stall trip levelPercent of FLA.UINT16%Read/write
HR418doc 419Residual GF trip levelScaling x100.UINT16× 0.01Read/write
HR419doc 420Residual GF trip delayUINT16sRead/write
HR420doc 421Residual GF start delayUINT16sRead/write
HR421doc 422Current unbalance trip levelUINT16%Read/write
HR422doc 423Current unbalance trip delayUINT16sRead/write
HR423doc 424Load disconnect trip levelPercent of rated FLA.UINT16%Read/write
HR424doc 425Load disconnect trip delayUINT16sRead/write
HR425doc 426Load disconnect sourceUINT16Read/write0 = Under power; 1 = Under current
HR426doc 427Phase loss trip levelUINT16%Read/write
HR427doc 428Phase loss trip delayUINT16sRead/write
HR428doc 429Under voltage levelPercent of set voltage.UINT16%Read/write
HR429doc 430Under voltage trip delayUINT16sRead/write
HR430doc 431Over voltage levelUINT16%Read/write
HR431doc 432Over voltage trip delayUINT16sRead/write
HR432doc 433Voltage unbalance trip levelUINT16%Read/write
HR433doc 434Voltage unbalance trip delayUINT16sRead/write
HR434doc 435Phase sequenceUINT16Read/write1 = ABC; 2 = ACB
HR435doc 436Fault relay configUINT16Read/write0 = Faulted; 1 = Not faulted
HR436doc 437Auxiliary relay configurationUINT16Read/write0 = Faulted; 1 = Not faulted; 2 = Bypass; 3 = Not in bypass; 4 = Motor energized; 5 = Motor not energized
HR437doc 438UI edit lockUINT16Read/write0 = Unlocked; 1 = Locked
HR442doc 443Communication loss timeoutUINT16msRead/write
HR443doc 444Communication loss behaviorUINT16Read/write1 = Fault; 2 = Hold last state; 3 = Stop
HR444doc 445Network timeout enableNetwork watchdog.UINT16Read/write0 = Disable; 1 = Enable

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eaton S611 soft starter (via C441 Ethernet module)

What Modbus registers does the Eaton S611 soft starter (via C441 Ethernet module) have?

This map lists 90 registers: 90 holding registers. 57 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eaton S611 soft starter (via C441 Ethernet module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0).

What are the minimum Modbus registers to integrate the Eaton S611 soft starter (via C441 Ethernet module)?

Start with HR 299 Motor status (Motor status bits); HR 304 Average current (Average current (scale by 301)); HR 300 Current scale factor (Current scale factor); HR 308 Average voltage (Average voltage); HR 313 Overload thermal memory (Thermal memory); HR 323 Trip reason (Trip reason bits); HR 399 Motor control (Run / permissive / reset).

How do I enable Modbus control of the Eaton S611 soft starter (via C441 Ethernet module)?

Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.

What happens when the Eaton S611 soft starter (via C441 Ethernet module) loses Modbus communication?

Register 110 (Modbus TCP) and 159 (serial) set a com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.

Where is the official Eaton S611 soft starter (via C441 Ethernet module) Modbus documentation?

The source is C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) (MN04200002E), revision 2012-08. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf. It may be an older revision, so check it against the live unit.

More Eaton Modbus register maps

Other soft starters & protection relays register maps

All soft starters & protection relays Modbus register maps →

Source: C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V) · MN04200002E · rev. 2012-08 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.