Variable frequency drive · Modbus register map
Eaton PowerXL DC1 compact drive (Modbus RTU) Modbus register map
Updated 19 November 2026
The PowerXL DC1 talks Modbus RTU on its RJ45 RS-485 socket. Eaton numbers every value by an ID: a small process-data block (command, speed reference, status/fault word, speed, current) plus parameter IDs. Every value is a single 16-bit register with an implied decimal point. This map covers the process data and the communication settings.
This page lists 19 Modbus registers for the Eaton PowerXL DC1 compact drive (Modbus RTU) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eaton
- Model
- PowerXL DC1 compact drive (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 19 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2
Integration notes: Eaton PowerXL DC1 compact drive (Modbus RTU)
Write the speed reference to ID 2 and the command word to ID 1 (bit 0 = run), then read IDs 6-8 for status, speed and current. The control-source parameter must select Modbus first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Fieldbus command | BITMAP16 | Run/stop/reset command word | Read/write |
| HR 1 | Fieldbus speed reference | UINT16 | Speed reference (0.1 Hz) | Read/write |
| HR 5 | Status and fault word | BITMAP16 | Status bits and fault number | Read |
| HR 6 | Actual speed | UINT16 | Actual frequency | Read |
| HR 7 | Motor current | UINT16 | Motor current | Read |
| HR 139 | Local process data source | UINT16 | Control source must select Modbus | Read/write |
Enable Modbus control & writes
Set P-12 = 3 (Modbus control) or 4 (Modbus control with Modbus ramp times). DI1 must be held high (enable) when running from Modbus. Drive address, baud rate and comms timeout are sub-settings of P-36; parity is P-56.
Communication loss & watchdog
P-36 sub-setting 'Modbus RTU0 COM Timeout': 0 = no action, 1-4 = trip after 30 ms / 100 ms / 1 s / 3 s, 5-8 = ramp to stop after 30 ms / 100 ms / 1 s / 3 s. A Modbus timeout shows fault 50 (Sc-FO1).
Byte order & addressing
- Register = ID - 1 on the wire; tools with a +1 offset take the ID directly.
- Function codes 03, 06, 16 and 23 only; at most 11 registers per read.
- The high byte of ID 6 is a fault number, not flags.
Network setup
- P-36 holds the drive address (1-63, default 1), baud rate (9.6-115.2 kbit/s) and the comms timeout.
- P-56 sets parity/stop bits; section 2.3.2 gives the default as no parity, 1 stop bit, 8 data bits.
- The RS-485 link is on the RJ45 socket.
Watch out for
- Without the DI1/STO enable the drive reports 'Stop' and will not run from Modbus.
- Set bit 2 of the command word to reset a fault.
Eaton PowerXL DC1 compact drive (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc ID 1 | Fieldbus command | Control word: run, direction, reset, coast, quick stop. | BITMAP16 | Read/write | bit 0 = 0 = stop, 1 = run (operational); bit 1 = 0 = forward (clockwise), 1 = reverse; bit 2 = 1 = reset fault; bit 3 = 1 = coast to stop; bit 5 = 1 = quick stop (ramp 2); bit 6 = 1 = run at fixed frequency FF1; bit 7 = 1 = force the setpoint to 0 | |||
| HR | 1doc ID 2 | Fieldbus speed reference | Setpoint frequency, limited to the min/max frequency parameters. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 3doc ID 4 | Modbus ramp time | Ramp time sent over Modbus, 0-60000. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 5doc ID 6 | Status and fault word | Low byte = status bits, high byte = fault number. | BITMAP16 | Read | bit 0 = 1 = ready (READY); bit 1 = 1 = running (RUN); bit 2 = 0 = forward, 1 = reverse; bit 3 = 1 = fault (FAULT); bit 4 = 1 = actual frequency equals setpoint (0 = ramping); bit 5 = 1 = zero speed; bit 6 = 1 = speed control active; bit 7 = Hardware enable: 0 = no, 1 = yes; bit 8-15 = Fault word: the fault number (see notes), 0 = no fault | |||
| HR | 6doc ID 7 | Actual speed | Output frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 7doc ID 8 | Motor current | UINT16 | × 0.1 | A | Read | |||
| HR | 8doc ID 9 | Torque | Motor torque, 1000 = 100 %. | UINT16 | × 0.1 | % | Read | ||
| HR | 10doc ID 11 | Digital inputs | Input states; the lowest bit is DI1. | BITMAP16 | Read | bit 0 = DI1; bit 1 = DI2 | |||
| HR | 11doc ID 12 | Drive type code | Part-number code: frame size, voltage class, phases and power index as hex digits. | UINT16 | Read | ||||
| HR | 14doc ID 15 | Control section software version | Two implied decimals. | UINT16 | × 0.01 | Read | |||
| HR | 15doc ID 16 | Power section software version | Two implied decimals. | UINT16 | × 0.01 | Read | |||
| HR | 16doc ID 17 | Drive recognition | Fixed family code; DC1 reads 10. | UINT16 | Read | ||||
| HR | 22doc 23 (P0-08) | DC-link voltage | UINT16 | V | Read | ||||
| HR | 130doc 131 (P-03) | Acceleration time t-acc | 300 = 3.00 s. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 131doc 132 (P-04) | Deceleration time t-dec | 300 = 3.00 s. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 134doc 135 (P-07) | Motor rated voltage | UINT16 | V | Read/write | ||||
| HR | 135doc 136 (P-08) | Motor rated current | 100 = 10.0 A. | UINT16 | × 0.1 | A | Read/write | ||
| HR | 139doc 140 (P-12) | Local process data source | Selects where run commands and the speed reference come from. | UINT16 | Read/write | 0 = Terminal control; 1 = Keypad, forward only; 2 = Keypad, forward and reverse; 3 = Modbus RTU control; 4 = Modbus control with Modbus ramp times; 5 = PI controller, external feedback; 6 = PI controller, external feedback plus AI1; 7 = CANopen, internal ramps; 8 = CANopen, CANopen ramps; 9 = SmartWire-DT control and speed reference; 10 = SmartWire-DT control, terminal speed reference; 11 = Terminal control, SmartWire-DT speed reference; 13 = SmartWire-DT control and reference, digital input enables | |||
| HR | 183doc 184 (P-56) | Modbus parity type | UINT16 | Read/write | 0 = No parity, 1 stop bit; 1 = No parity, 2 stop bits; 2 = Odd parity, 1 stop bit; 3 = Even parity, 1 stop bit |
Notes on this map
- Every value is one 16-bit register; the decimal point is implied (a displayed 0.3 A is sent as 3).
- The manual does not state signedness for the process data; they are typed UINT16 because their ranges are non-negative (direction is a status bit).
- Output power (ID 10) is left out: the summary table gives scale 1 but the detailed text says one decimal (53 = 5.3 kW). The power (ID 13) and voltage range (ID 14) words are left out because their meaning depends on the drive's kW/HP setting.
- Fault numbers in the high byte of ID 6 for the DC1 (decimal, as printed in table 11): 0 no-Flt (no fault), 1 OI-b brake overcurrent, 2 OL-br brake resistor overload, 3 O-I output overcurrent, 4 I.t-trP motor overload, 5 PS-trp hardware overcurrent, 6 O.Volt DC overvoltage, 7 U.Volt DC undervoltage, 8 O-t heatsink overtemperature, 9 U-t undertemperature, 10 P-dEf defaults loaded, 11 E-trip external fault, 12 SC-ObS keypad/PC comms error, 13 FlT-dc DC ripple too high, 14 P-LOss input phase loss, 16 Th-flt heatsink thermistor fault, 17 dAtA-F memory error, 18 4-20 F analog input out of range, 19 dAtA-E memory error, 21 F-Ptc motor PTC, 22 FAn-F fan fault, 23 O-hEAt ambient too hot, 26 OUt-F output fault, 40-44 AtF-01..05 motor identification failed, 49 Out-Ph motor phase lost, 50 Sc-FO1 Modbus timeout, 51 Sc-FO2 CANopen timeout. The 'Stop' display (enable signal missing) is listed without a number and is not a fault.
- Left out: f-max/f-min and the fixed frequencies (the table scales them as 3000 = 50.0 Hz, i.e. 60 counts per Hz); register 164 (P-36), which packs the address in the low byte, baud in bits 8-11 and timeout in bits 12-15; the analog-input registers 20/21 (scale 4096 = 100 % but range printed 0-1000); serial number words 29-32; run-hour words 25-28.
- Left out: heatsink temperature (24); its range starts at -10 °C but the data-format cell is blank, so signedness is not stated.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eaton PowerXL DC1 compact drive (Modbus RTU)
What Modbus registers does the Eaton PowerXL DC1 compact drive (Modbus RTU) have?
This map lists 19 registers: 19 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eaton PowerXL DC1 compact drive (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual numbers registers from ID 1. Its frame examples read status ID 6 with start address 0005h and write command ID 1 to address 0000h, so ID n is wire address n-1.
What are the minimum Modbus registers to integrate the Eaton PowerXL DC1 compact drive (Modbus RTU)?
Start with HR 0 Fieldbus command (Run/stop/reset command word); HR 1 Fieldbus speed reference (Speed reference (0.1 Hz)); HR 5 Status and fault word (Status bits and fault number); HR 6 Actual speed (Actual frequency); HR 7 Motor current (Motor current); HR 139 Local process data source (Control source must select Modbus).
How do I enable Modbus control of the Eaton PowerXL DC1 compact drive (Modbus RTU)?
Set P-12 = 3 (Modbus control) or 4 (Modbus control with Modbus ramp times). DI1 must be held high (enable) when running from Modbus. Drive address, baud rate and comms timeout are sub-settings of P-36; parity is P-56.
What happens when the Eaton PowerXL DC1 compact drive (Modbus RTU) loses Modbus communication?
P-36 sub-setting 'Modbus RTU0 COM Timeout': 0 = no action, 1-4 = trip after 30 ms / 100 ms / 1 s / 3 s, 5-8 = ramp to stop after 30 ms / 100 ms / 1 s / 3 s. A Modbus timeout shows fault 50 (Sc-FO1).
Where is the official Eaton PowerXL DC1 compact drive (Modbus RTU) Modbus documentation?
The source is PowerXL Modbus RTU Communication manual for Variable Frequency Drives / Variable Speed Starters DA1, DB1, DC1, DE1 (MN040018EN), revision 2022-12, published free by Eaton at https://es-assets.eaton.com/DOCUMENTATION/AWB_MANUALS/MN040018_EN.pdf.
More Eaton Modbus register maps
- Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V - Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Power meter
Eaton IQ 250 / IQ 260 Electronic Power Meter
Eaton IQ 250 and IQ 260 meters (including the L logging versions), Modbus map Appendix B of IB02601006E.
Also known as: IQ 250, IQ 260, IQ 250L, IQ 260L, IQ250, IQ260 - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34 - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V
Other variable frequency drives register maps
- Variable frequency drive
Hitachi WJ-C1 series inverter (Modbus RTU)
Hitachi WJ-C1 inverters using the built-in RS485 port in Modbus-RTU mode; User's Guide NT361X, chapters 11 and 18.
Also known as: WJ-C1, WJ-C1 series - Variable frequency drive
Invertek Drives Optidrive P2 (built-in Modbus RTU)
Invertek Optidrive P2 drives (0.75-250 kW) using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-P2MAN-IN V3.10.
Also known as: ODP-2, Optidrive P2 IP20, Optidrive P2 IP55, Optidrive P2 IP66 - Variable frequency drive
INVT Goodrive350 (GD350) high-performance multifunction VFD
INVT Goodrive350 drives (not GD350A) using the built-in RS-485 Modbus RTU port, per the GD350 manual V1.1 (communication chapter).
Also known as: GD350, Goodrive350, GD350 series - Variable frequency drive
Lenze SMVector drive with ESVZAR0 RS-485 Modbus module
Lenze AC Tech SMVector drives up to 10 HP with the ESVZAR0 RS-485 Modbus module, module software 1.01 / 1.10 / 1.30 (guide CMVMB401C).
Also known as: SMVector, SMV, ESVZAR0, Lenze AC Tech SMV, CMVMB401C - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D
All variable frequency drives Modbus register maps →
Source: PowerXL Modbus RTU Communication manual for Variable Frequency Drives / Variable Speed Starters DA1, DB1, DC1, DE1 · MN040018EN · rev. 2022-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.