Variable frequency drive · Modbus register map
Lenze SMVector drive with ESVZAR0 RS-485 Modbus module Modbus register map
Updated 17 November 2026
The SMVector is a Lenze AC Tech inverter (models up to 10 HP in this guide). The ESVZAR0 option module adds Modbus RTU on RS-485. Registers 1-99 are network control and status (control word, status word, frequencies, load, fault, run-hour counters, network speed/PID/torque commands); every drive parameter Pxxx is also readable as register xxx.
This page lists 33 Modbus registers for the Lenze SMVector drive with ESVZAR0 RS-485 Modbus module — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lenze’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lenze
- Model
- SMVector drive with ESVZAR0 RS-485 Modbus module
- Equipment type
- Variable frequency drive
- Registers
- 33 (15 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- derived from parameter numbers
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- ESVZAR0 module software 1.01, 1.10 or 1.30 (check P494 before writing)
- Also known as
- SMVector, SMV, ESVZAR0, Lenze AC Tech SMV, CMVMB401C
Integration notes: Lenze SMVector drive with ESVZAR0 RS-485 Modbus module
Set P400 = 2, address/baud/format in P410-P412, then read #23-#29 for status, frequencies, load and fault. To run from the network: assert a terminal set to NET ENABLE, write 0 to #48 to unlock #1 (or the P194 password to also unlock #44), then write control bits to #1 and the speed to #44.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Drive control | BITMAP16 | Control word: start/stop/direction | Write |
| HR 48 | Unlock controls | UINT16 | Unlock controls | Write |
| HR 44 | Network speed command | UINT16 | Network speed command | Read/write |
| HR 23 | Drive status | BITMAP16 | Status word | Read |
| HR 25 | Actual frequency | UINT16 | Actual frequency | Read |
| HR 29 | Present fault (high byte) / commanded direction (low byte) | UINT16 | Present fault | Read |
Enable Modbus control & writes
P400 = 2 (Modbus RTU); P410 address, P411 baud, P412 format. For control set one of P121-P123 to 09 (NET ENABLE) and close that TB-13 input, and P100 to 00, 01, 03 or 04. Use P101 = 06 or bits 12-15 of #1 to make the network the speed reference.
Communication loss & watchdog
Once controls are unlocked via #48, P425 (0-300 s, default 10.0 s) sets the message time-out and P426 the action (default trip fault). Any read keeps it alive.
Byte order & addressing
- Function codes 03 and 04 are identical; FC16 only writes one register.
- Only one action bit per write to #1, except stop/quick stop/inhibit; otherwise exception 04.
- Writing #1 with bit 1 (lock security) ends network control and stops the drive if P100 = 3.
- Broadcast is not supported.
Network setup
- RS-485 on the ESVZAR0 terminal block; terminate the end of the network.
- Default 9600 baud, 8 data bits, no parity, 2 stop bits, address 1.
Watch out for
- If P494 does not show 1.01, 1.10 or 1.30, Lenze warns not to write any register with this map.
- Writes are ignored unless the NET ENABLE terminal is configured and closed.
Lenze SMVector drive with ESVZAR0 RS-485 Modbus module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc #1 (4X 40002) | Drive control | Set one bit per write (0x0008 start, 0x0004 stop). Unlock via #48 first. | BITMAP16 | Write | bit 0 = Quick stop; bit 1 = Lock security (ends network control); bit 2 = Stop (per P111); bit 3 = Start; bit 4 = Inhibit; bit 5 = Network reference off; bit 6 = Set reverse; bit 7 = Set forward; bit 8 = Stop forcing manual reference; bit 9 = Force manual reference (P101); bit 10 = DC braking on; bit 11 = DC braking off; bit 12 = Network reference select (bits 12-15 enumeration) | |||
| HR | 19doc #19 (4X 40020) | Drive family | Reads 72 for SMVector. | UINT16 | Read | ||||
| HR | 21doc #21 (4X 40022) | Drive size index | Voltage / power rating code (table 7 of the guide). | UINT16 | Read | ||||
| HR | 23doc #23 (4X 40024) | Drive status | BITMAP16 | Read | bit 0 = Running (0 = stopped); bit 1 = Quick stop active; bit 2 = Commanded direction reverse; bit 3 = Actual direction reverse; bit 4 = Network reference sets active source; bit 5 = Network enable active; bit 6 = Closed loop (PID on); bit 7 = AUTO source; bit 8 = Set point source code bit 0; bit 9 = Set point source code bit 1; bit 10 = Set point source code bit 2; bit 11 = Set point source code bit 3; bit 12 = Control source code bit 0; bit 13 = Control source code bit 1; bit 14 = Network control enabled; bit 15 = DC braking active | ||||
| HR | 24doc #24 (4X 40025) | Command frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 25doc #25 (4X 40026) | Actual frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 26doc #26 (4X 40027) | Load (high byte) / run status (low byte) | High byte = load % of rated current; low byte = operational status code. | UINT16 | Read | ||||
| HR | 27doc #27 (4X 40028) | Actual direction (high byte) / control mode (low byte) | High: 0 fwd, 1 rev. Low: 0 local, 1 terminal, 2 remote keypad, 3 net only, 4 net control. | UINT16 | Read | ||||
| HR | 28doc #28 (4X 40029) | Speed source (high byte) / auto-manual (low byte) | High: 0 keypad ... 11 network, 12 jog. Low: 0 manual, 1 auto. | UINT16 | Read | ||||
| HR | 29doc #29 (4X 40030) | Present fault (high byte) / commanded direction (low byte) | High byte = fault code (see notes). Low: 0 fwd, 1 rev. | UINT16 | Read | ||||
| HR | 37doc #37 (4X 40038) | Actual PID setpoint | Signed, one decimal. | INT16 | × 0.1 | Read | |||
| HR | 38doc #38 (4X 40039) | PID setpoint command | INT16 | × 0.1 | Read | ||||
| HR | 39doc #39 (4X 40040) | PID feedback | INT16 | × 0.1 | Read | ||||
| HR | 40doc #40 (4X 40041) | Keypad speed command | UINT16 | × 0.1 | Hz | Read/write | |||
| HR | 41doc #41 (4X 40042) | Keypad PID setpoint command | INT16 | × 0.1 | Read | ||||
| HR | 42doc #42 (4X 40043) | Keypad torque command | UINT16 | × 0.1 | % | Read/write | |||
| HR | 44doc #44 (4X 40045) | Network speed command | P102 to P103. Used when the network is the speed reference. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 46doc #46 (4X 40047) | Network torque command | 0.0-400.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 48doc #48 (4X 40049) | Unlock controls | 0 unlocks register #1; the password (P194, default 225) unlocks all. | UINT16 | Write | ||||
| HR | 49doc #49 (4X 40050) | Unlock parameters | Password (P194) unlocks all writable registers except #1. | UINT16 | Write | ||||
| HR | 50doc #50 (4X 40051) | Parameter version | UINT16 | Read | |||||
| HR | 60doc #60 (4X 40061) | Total run time hours | Low word at #60, high word at #61. | UINT32 | CDAB | h | Read | ||
| HR | 64doc #64 (4X 40065) | Total power-on hours | Low word at #64, high word at #65. | UINT32 | CDAB | h | Read | ||
| HR | 70doc #70 (4X 40071) | Network controlled digital output + relay | Needs P140/P142 = 25 (network controlled). | BITMAP16 | Read/write | bit 9 = TB-14 output energized; bit 10 = Relay energized | |||
| HR | 71doc #71 (4X 40072) | Network controlled analog output | Needs P150 = 09 (network controlled). | UINT16 | × 0.1 | % | Read/write | ||
| HR | 400doc #400 (4X 40401) | P400 network protocol | UINT16 | Read/write | 0 = Not active; 1 = Remote keypad; 2 = Modbus RTU | ||||
| HR | 402doc #402 (4X 40403) | P402 module status | UINT16 | Read | 0 = Not initialized; 1 = Init: module to EPM; 2 = Init: EPM to module; 3 = Online; 4 = Failed initialization; 5 = Time-out error; 6 = Initialization failed; 7 = Initialization error | ||||
| HR | 410doc #410 (4X 40411) | P410 network address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 411doc #411 (4X 40412) | P411 baud rate | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600 (default); 3 = 19200; 4 = 38400; 5 = 57600; 6 = 115200 | ||||
| HR | 412doc #412 (4X 40413) | P412 data format | UINT16 | Read/write | 0 = 8N2 (default); 1 = 8N1; 2 = 8E1; 3 = 8O1 | ||||
| HR | 425doc #425 (4X 40426) | P425 network message time-out | 0.0-300.0 s, default 10.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 426doc #426 (4X 40427) | P426 time-out action | UINT16 | Read/write | 0 = Not active; 1 = Stop (P111); 2 = Quick stop; 3 = Inhibit; 4 = Trip fault (default) | ||||
| HR | 530doc #530 (4X 40531) | P530 terminal and protection status | BITMAP16 | Read | bit 2 = Protection status; bit 3 = Fast current limit; bit 4 = Input TB-1; bit 6 = Input TB-13A; bit 7 = Input TB-13B; bit 8 = Input TB-13C; bit 9 = Output TB-14; bit 10 = Relay output; bit 11 = Charge relay; bit 12 = Assertion level switch |
Notes on this map
- Host: copy hosted by Precision Electric (a Lenze AC Tech distributor); a search did not find this guide as a direct download on lenze.com.
- Scaling: values are sent in internal units, value x 10^DP; e.g. 34.3 Hz is sent as 343. Frequencies, torque, PID and analog output are one-decimal values (scale 0.1). PID values (37-39, 41, 45) are signed.
- Word order: registers #60/#61 and #64/#65 are low word first; the guide's example shows run-time hours 0x12345678 read as 5678h then 1234h (CDAB).
- Left out: motor voltage #30 and total kWh #32/#33 (scaling defers to the drive manual), and the 32-bit registers #511/#540/#541 (high word first per the guide, but its #540 example frame uses the address of #511). Parameters #100-399 and #500-599 follow the SMV operating instructions (SV01) and are not listed.
- Present fault codes (high byte of #29): 0 no fault, 1 TMP output, 2 output transistor, 3 ground, 4 high drive temperature, 5 flying start, 6 high DC bus, 7 low DC bus, 8 thermal overload, 9 OEM, 10 illegal setup, 11 dynamic brake over-temperature, 12 single phase, 13 external, 14 control, 15 start error, 16 incompatibility, 17 internal 1 (EPM), 18 internal 2, 19 internal 3, 20/21 internal 5, 22 internal 6, 23 internal 7, 24 internal 8, 25 internal 9, 26 personality, 27 AD offset, 28 remote keypad lost, 29 assertion level, 30 internal 4, 31 internal 0, 32 follower lost, 33 ISO comm, 34 SPI time-out, 35 invalid message received, 36 network time-out.
- Run status codes (low byte of #26): 0 fault lockout, 1 fault, 2 start pending, 3 IDE not done, 4 inhibit, 5 stop, 6 lower transistors on, 7 run IDE, 8 run, 9 accel, 10 decel, 11 decel override, 12 DC brake, 13 flying restart, 14 slow current limit, 15 fast current limit, 16 sleep.
- Usually only one register per read; exceptions are #24 (6 registers #24-29) and the 2-register counters. FC16 writes only one register.
- Left out: network PID setpoint command #45. Table 5 marks it read-only, but section 8.3 says to write it; the access is unclear.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lenze SMVector drive with ESVZAR0 RS-485 Modbus module
What Modbus registers does the Lenze SMVector drive with ESVZAR0 RS-485 Modbus module have?
This map lists 33 registers: 33 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lenze SMVector drive with ESVZAR0 RS-485 Modbus module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Lenze numbers registers by drive register #, and Modbus 4X/3X register = drive register + 1. The drive register # is the wire address: the guide's example reads #60 with start address 0x003C. Drive parameter Pxxx is register #xxx (P103 = #103).
What byte order does the Lenze SMVector drive with ESVZAR0 RS-485 Modbus module use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lenze SMVector drive with ESVZAR0 RS-485 Modbus module?
Start with HR 1 Drive control (Control word: start/stop/direction); HR 48 Unlock controls (Unlock controls); HR 44 Network speed command (Network speed command); HR 23 Drive status (Status word); HR 25 Actual frequency (Actual frequency); HR 29 Present fault (high byte) / commanded direction (low byte) (Present fault).
How do I enable Modbus control of the Lenze SMVector drive with ESVZAR0 RS-485 Modbus module?
P400 = 2 (Modbus RTU); P410 address, P411 baud, P412 format. For control set one of P121-P123 to 09 (NET ENABLE) and close that TB-13 input, and P100 to 00, 01, 03 or 04. Use P101 = 06 or bits 12-15 of #1 to make the network the speed reference.
What happens when the Lenze SMVector drive with ESVZAR0 RS-485 Modbus module loses Modbus communication?
Once controls are unlocked via #48, P425 (0-300 s, default 10.0 s) sets the message time-out and P426 the action (default trip fault). Any read keeps it alive.
Where is the official Lenze SMVector drive with ESVZAR0 RS-485 Modbus module Modbus documentation?
The source is SMVector ESVZAR0 RS-485 Modbus Communication Module - Communications Interface Reference Guide (CMVMB401C). Lenze doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2014/08/lenze-ac-tech-rs485-modbus-communications-reference.pdf. It may be an older revision, so check it against the live unit.
More Lenze Modbus register maps
- Variable frequency drive
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Lenze i510 cabinet inverters 0.25-2.2 kW with the Modbus/CANopen control unit, selector set to Modbus, firmware 01.01.01.00 as documented in the commissioning manual.
Also known as: i500 series, i510 Cabinet, I51AE - Variable frequency drive
Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)
Lenze AC Tech MC1000 and MC3000 Series drives, software 213-083 rev 13 (parameter configurations 188-190); reference guide RG-MCMOD.
Also known as: MC1000, MC3000, MC Series, Lenze AC Tech MC, RG-MCMOD - Variable frequency drive
Lenze MCH Series HVAC drive (Modbus RTU)
Lenze AC Tech MCH Series drives, software 213-070 rev 00 (parameter configuration 148); reference guide RG-MHMOD.
Also known as: MCH, Lenze AC Tech MCH, RG-MHMOD - Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028
Other variable frequency drives register maps
- Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D - Variable frequency drive
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse A510 inverters using the built-in RS-485 port (CN6), per communication addendum DOCUMENT-TECO-A510-AC001 Ver01 (2015-04).
Also known as: TECO A510, A510s - Variable frequency drive
Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)
Toshiba TOSVERT VF-nC3 series inverters using the built-in RS-485 port with f829 = 1 (Modbus RTU), per manual E6581657.
Also known as: VF-nC3, VF-nC3M, TOSVERT VF-nC3, VFNC3 - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass
All variable frequency drives Modbus register maps →
Source: SMVector ESVZAR0 RS-485 Modbus Communication Module - Communications Interface Reference Guide · CMVMB401C · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.