Variable frequency drive · Modbus register map

Lenze SCF Series drive with Modbus module (basic network control) Modbus register map

Updated 17 November 2026

Short answer

The SCF is a Lenze AC Tech drive. With its Modbus option it can be started, stopped, reversed and speed-controlled over Modbus RTU at 9600 baud. This map holds the basic control registers from Lenze's quick-start note plus the rule that maps every SCF parameter to a Modbus register.

This page lists 6 Modbus registers for the Lenze SCF Series drive with Modbus module (basic network control) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lenze’s own free documentation (linked below) and checked against it.

Manufacturer
Lenze
Model
SCF Series drive with Modbus module (basic network control)
Equipment type
Variable frequency drive
Registers
6 (4 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
SCF, Lenze AC Tech SCF, AN0028
Source document
Application Note: Basic Network Control of the SCF Drive using ModBus Communications · AN0028/A1 · rev. 2008-01 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lenze SCF Series drive with Modbus module (basic network control)

Integration in brief

Set P14 = 01 and P43 = address, write 0 (or the password) to 40049 once after power-up, then write 0008h to 40002 to start and the speed in 0.1 Hz to 40041 (with P05 = 01). Read 40027 for the run status.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 48Unlock (AC Tech register 48)UINT16UnlockWrite
HR 1Drive control (AC Tech register 1)BITMAP16Start / stop / directionWrite
HR 40Keypad speed command (AC Tech register 40)UINT16Speed commandRead/write
HR 26Run status (AC Tech register 26, low byte)UINT16Run statusRead

Enable Modbus control & writes

P14 = 01 enables serial communication; P43 sets the address (1-247); P15 sets data format and watchdog.

Communication loss & watchdog

Fixed 10 s: if enabled via P15 and the master stops communicating while the drive is under network control, the drive stops.

Byte order & addressing

Network setup

Watch out for

Lenze SCF Series drive with Modbus module (basic network control) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

6 of 6 shown
Lenze SCF Series drive with Modbus module (basic network control) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 40002Drive control (AC Tech register 1)One command per write: 0004h stop, 0008h start, 0040h reverse, 0080h forward, 0200h manual.BITMAP16Writebit 2 = Stop (per P04); bit 3 = Start; bit 6 = Set reverse (needs P17 = 2); bit 7 = Set forward; bit 9 = Manual mode (use keypad speed register)
HR24doc 40025Status block start (AC Tech register 24)First of a 6-register status block; read 6 registers from here.UINT16Read
HR26doc 40027Run status (AC Tech register 26, low byte)Low byte = operational status code; see values.UINT16Read0 = Fault lockout; 1 = Fault; 2 = Start pending; 3 = Stop; 4 = DC brake; 5 = Run at 0 Hz; 6 = Run; 7 = Accel; 8 = Decel; 9 = Current limit; 10 = Decel override; 11 = Lower transistors switching on
HR40doc 40041Keypad speed command (AC Tech register 40)Network speed when P05 = 01 (keypad); 412 = 41.2 Hz.UINT16× 0.1HzRead/write
HR48doc 40049Unlock (AC Tech register 48)0 unlocks control only; password (default 225) also unlocks parameters.UINT16Write
HR69doc 40070P19 acceleration timeExample of the parameter rule: register = parameter + 51.UINT16× 0.1sRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lenze SCF Series drive with Modbus module (basic network control)

What Modbus registers does the Lenze SCF Series drive with Modbus module (basic network control) have?

This map lists 6 registers: 6 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lenze SCF Series drive with Modbus module (basic network control) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The note gives 4xxxx Modbus register numbers, which are AC Tech register + 1 (control register 1 = 40002). Wire address = Modbus register - 40001, so the control register is address 1. SCF parameter Pn is Modbus register n + 51 (P19 -> 40070).

What are the minimum Modbus registers to integrate the Lenze SCF Series drive with Modbus module (basic network control)?

Start with HR 48 Unlock (AC Tech register 48) (Unlock); HR 1 Drive control (AC Tech register 1) (Start / stop / direction); HR 40 Keypad speed command (AC Tech register 40) (Speed command); HR 26 Run status (AC Tech register 26, low byte) (Run status).

How do I enable Modbus control of the Lenze SCF Series drive with Modbus module (basic network control)?

P14 = 01 enables serial communication; P43 sets the address (1-247); P15 sets data format and watchdog.

What happens when the Lenze SCF Series drive with Modbus module (basic network control) loses Modbus communication?

Fixed 10 s: if enabled via P15 and the master stops communicating while the drive is under network control, the drive stops.

Where is the official Lenze SCF Series drive with Modbus module (basic network control) Modbus documentation?

The source is Application Note: Basic Network Control of the SCF Drive using ModBus Communications (AN0028/A1), revision 2008-01. Lenze doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2014/08/basic-network-control-of-scf-drive-using-modbus-communications.pdf. It may be an older revision, so check it against the live unit.

More Lenze Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Application Note: Basic Network Control of the SCF Drive using ModBus Communications · AN0028/A1 · rev. 2008-01 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.