- i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Variable frequency drive · Modbus register map
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus register map
Updated 17 November 2026
Lenze's i510 is a compact cabinet frequency inverter whose Modbus/CANopen control unit acts as a Modbus RTU slave. Besides 24 freely mappable registers, it has fixed blocks: status data from 42001 and control data from 42101. This map covers those predefined registers: AC drive control and status words, frequency setpoint and actual frequency, drive status, error code, motor voltage and current, apparent power, temperatures, DC bus and torque.
This page lists 17 Modbus registers for the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lenze’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lenze
- Model
- i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 17 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 01.01.01.00
- Also known as
- i500 series, i510 Cabinet, I51AE
Integration notes: Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Set the front selector to Modbus, activate the network (0x2631:037 = TRUE) and make the network the setpoint source (0x2860:001 = 5). Write 0x0061 to 42101 (run forward + control and reference from network) and the frequency to 42102 in 0.01 Hz; read 42001-42011 for status and measurements.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2100 | AC Drive control word (0x400B:001) | BITMAP16 | AC Drive control word (start/stop/reset) | Read/write |
| HR 2101 | Network setpoint frequency (0x400B:005) | UINT16 | Frequency setpoint, 0.01 Hz | Read/write |
| HR 2000 | AC Drive status word (0x400C:001) | BITMAP16 | AC Drive status word | Read |
| HR 2001 | Actual frequency (0x400C:006) | UINT16 | Actual frequency, 0.01 Hz | Read |
| HR 2002 | Error code (0x603F) | UINT16 | Error code | Read |
| HR 2005 | Actual motor current (0x2D88) | INT16 | Motor current, 0.1 A | Read |
| HR 2010 | DC-bus voltage (0x2D87) | UINT16 | DC-bus voltage | Read |
Enable Modbus control & writes
Set the Modbus/CANopen selector on the inverter front to Modbus. Set 0x2631:037 (PAR 400/037) Activate network = TRUE and 0x2860:001 (PAR 201/001) = 5 Network. Set node address 0x2321:001 (1-247, default 1), baud 0x2321:002 and data format 0x2321:003 (both default Automatic), then restart Modbus communication (0x2320 = 1) or power-cycle.
Communication loss & watchdog
0x2858:002 Time-out (0.0-300.0 s, default 2.0 s) with 0x2858:001 Response to time-out (default Error).
Byte order & addressing
- Register 42101 is sent as address 2100 (0x0834).
- The frequency setpoint and actual frequency are unsigned; direction comes from control word bits 0/1 and status bits 2/3.
- With automatic baud rate or data format detection the first 5-10 messages after power-up are lost.
- Digital input DI1 is 'Start enable' by default and must be high for the drive to start.
Network setup
- Baud 2400-115200 or automatic; data format 8E1, 8O1, 8N2 or automatic.
- A minimum response delay can be set in 0x2321:004 (0-1000 ms).
Watch out for
- The manual's example: writing 0x0061 to 42101 on node 1 starts the drive if DI1 is high.
- MOD-ERR LED blinking = communication error; MOD-RUN and MOD-ERR flickering = automatic baud detection still running.
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2000doc 42001 | AC Drive status word (0x400C:001) | EtherNet/IP AC drive profile bits. | BITMAP16 | Read | bit 0 = Fault/trip; bit 1 = Reserved; bit 2 = Running forward; bit 3 = Running reverse; bit 4 = Ready; bit 5 = Control from network; bit 6 = Reference from network; bit 7 = At reference; bit 8 = Reserved; bit 9 = Reserved; bit 10 = Reserved; bit 11 = Reserved; bit 12 = Process controller active; bit 13 = Torque mode active; bit 14 = Current limit reached; bit 15 = DC braking active | |||
| HR | 2001doc 42002 | Actual frequency (0x400C:006) | Unsigned; direction is in the status word. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 2002doc 42003 | Error code (0x603F) | Active error code. | UINT16 | Read | ||||
| HR | 2003doc 42004 | Drive status (0x400C:005) | UINT16 | Read | 0 = Error (non-resettable); 1 = Error; 2 = Waiting for start; 3 = Identification not executed; 4 = Controller inhibit; 5 = Stop; 7 = Identification; 8 = Running; 9 = Acceleration; 10 = Deceleration; 11 = Deceleration override; 12 = DC braking; 13 = Flying start; 14 = Current limit reached; 16 = Process controller idle state | ||||
| HR | 2004doc 42005 | Actual motor voltage (0x2D89) | UINT16 | V | Read | ||||
| HR | 2005doc 42006 | Actual motor current (0x2D88) | INT16 | × 0.1 | A | Read | |||
| HR | 2006doc 42007 | Current actual value (0x6078) | Motor current in percent. | INT16 | × 0.1 | % | Read | ||
| HR | 2007doc 42008 | Apparent power (0x2DA2:002) | 42008 = high word, 42009 = low word. | INT32 | ABCD | × 0.001 | kW | Read | |
| HR | 2009doc 42010 | Heatsink temperature (0x2D84:001) | INT16 | × 0.1 | °C | Read | |||
| HR | 2010doc 42011 | DC-bus voltage (0x2D87) | UINT16 | V | Read | ||||
| HR | 2012doc 42013 | Torque actual value (0x6077) | Percent of rated motor torque. | INT16 | × 0.1 | % | Read | ||
| HR | 2100doc 42101 | AC Drive control word (0x400B:001) | EtherNet/IP AC drive profile bits. | BITMAP16 | Read/write | bit 0 = Run forward; bit 1 = Run reverse; bit 2 = Reset error (0-1 edge); bit 3 = Reserved; bit 4 = Reserved; bit 5 = Control from network; bit 6 = Reference from network; bit 7 = Reserved; bit 8 = Reserved; bit 9 = Reserved; bit 10 = Reserved; bit 11 = Reserved; bit 12 = Controller inhibit; bit 13 = Quick stop; bit 14 = Process controller off; bit 15 = DC braking | |||
| HR | 2101doc 42102 | Network setpoint frequency (0x400B:005) | Unsigned, 0.00-599.00 Hz; direction via control word. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 2104doc 42105 | Network process controller setpoint (0x400B:007) | -300.00 to 300.00 process units. | INT16 | × 0.01 | PUnit | Read/write | ||
| HR | 2105doc 42106 | Target torque (0x6071) | 100 % = motor rated torque (0x6076). | INT16 | × 0.1 | % | Read/write | ||
| HR | 2106doc 42107 | NETWordIN1 (0x4008:001) | Freely assignable bit functions (0x400E). | BITMAP16 | Read/write | ||||
| HR | 2107doc 42108 | NETWordIN4 (0x4008:004) | 0.0-100.0 %. | UINT16 | × 0.1 | % | Read/write |
Notes on this map
- This copy is hosted by the US distributor Precision Electric and is the unaltered Lenze commissioning manual; Lenze's own copy sits in its download portal and was not found as a direct public link.
- Data types and scaling come from the parameter attribute list (data type and network factor: the integer read is divided by the factor, e.g. factor 10 -> scale 0.1).
- Apparent power 42008/42009 is a 32-bit signed value; the register table states 42008 = high word and 42009 = low word (ABCD), factor 1000 (kW as printed).
- Left out: 42012 digital inputs (0x60FD is a 32-bit parameter but only one register is assigned, so which half is sent is unclear); 42103 and 42104, because the register table gives 42103 as NETWordIN2 with address 0x4008:003 (which the attribute list calls NETWordIN3) and repeats 0x400B:001 for 42104.
- The 24 freely mappable registers (0x232B:1-24, internal register numbers from 2500 shown in 0x232C) are not listed; their content depends on configuration.
- Only function codes 3, 6, 16 and 23 are supported; all data are holding registers. Data are big-endian (most significant byte first).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
What Modbus registers does the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) have?
This map lists 17 registers: 17 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states all data are 4X registers numbered from 1 but addressed from 0, so register 40001 is address 0; its example writes register 42101 to address 2100 (0x0834). So 42001 = wire 2000 and 42101 = wire 2100.
What byte order does the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)?
Start with HR 2100 AC Drive control word (0x400B:001) (AC Drive control word (start/stop/reset)); HR 2101 Network setpoint frequency (0x400B:005) (Frequency setpoint, 0.01 Hz); HR 2000 AC Drive status word (0x400C:001) (AC Drive status word); HR 2001 Actual frequency (0x400C:006) (Actual frequency, 0.01 Hz); HR 2002 Error code (0x603F) (Error code); HR 2005 Actual motor current (0x2D88) (Motor current, 0.1 A); HR 2010 DC-bus voltage (0x2D87) (DC-bus voltage).
How do I enable Modbus control of the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)?
Set the Modbus/CANopen selector on the inverter front to Modbus. Set 0x2631:037 (PAR 400/037) Activate network = TRUE and 0x2860:001 (PAR 201/001) = 5 Network. Set node address 0x2321:001 (1-247, default 1), baud 0x2321:002 and data format 0x2321:003 (both default Automatic), then restart Modbus communication (0x2320 = 1) or power-cycle.
What happens when the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) loses Modbus communication?
0x2858:002 Time-out (0.0-300.0 s, default 2.0 s) with 0x2858:001 Response to time-out (default Error).
Where is the official Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus documentation?
The source is Inverter i510 Cabinet 0.25 ... 2.2 kW - Configuration | Commissioning | Service. Lenze doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2017/02/Lenze-AC-Tech-i500-i510-VFD-Users-Manual-For-Commissioning.pdf. It may be an older revision, so check it against the live unit.
More Lenze Modbus register maps
- Variable frequency drive
Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)
Lenze AC Tech MC1000 and MC3000 Series drives, software 213-083 rev 13 (parameter configurations 188-190); reference guide RG-MCMOD.
Also known as: MC1000, MC3000, MC Series, Lenze AC Tech MC, RG-MCMOD - Variable frequency drive
Lenze MCH Series HVAC drive (Modbus RTU)
Lenze AC Tech MCH Series drives, software 213-070 rev 00 (parameter configuration 148); reference guide RG-MHMOD.
Also known as: MCH, Lenze AC Tech MCH, RG-MHMOD - Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028 - Variable frequency drive
Lenze SMVector drive with ESVZAR0 RS-485 Modbus module
Lenze AC Tech SMVector drives up to 10 HP with the ESVZAR0 RS-485 Modbus module, module software 1.01 / 1.10 / 1.30 (guide CMVMB401C).
Also known as: SMVector, SMV, ESVZAR0, Lenze AC Tech SMV, CMVMB401C
Other variable frequency drives register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
SEW-EURODRIVE MOVITRAC LTP-B standard inverter (built-in Modbus RTU)
SEW-EURODRIVE MOVITRAC LTP-B inverters on the RJ45 Modbus RTU port (no communication or encoder option card fitted), per product manual 31554814/EN edition 10/2023.
Also known as: MOVITRAC LTP-B, LTP-B, MC LTP B - Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series - Variable frequency drive
WEG CFW500 frequency inverter (Modbus RTU)
WEG CFW500 drives as a Modbus RTU slave on the RS-485 port of the plug-in module (Modbus RTU User's Guide 10002253377 rev 04); parameter scaling from the V2.2X programming manual.
Also known as: CFW500 VFD, CFW500-IOS, CFW500-CRS485, CFW500-CUSB, CFW500-CRS232 - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact
All variable frequency drives Modbus register maps →
Source: Inverter i510 Cabinet 0.25 ... 2.2 kW - Configuration | Commissioning | Service · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.