  4. i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)

Variable frequency drive · Modbus register map

Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Lenze's i510 is a compact cabinet frequency inverter whose Modbus/CANopen control unit acts as a Modbus RTU slave. Besides 24 freely mappable registers, it has fixed blocks: status data from 42001 and control data from 42101. This map covers those predefined registers: AC drive control and status words, frequency setpoint and actual frequency, drive status, error code, motor voltage and current, apparent power, temperatures, DC bus and torque.

This page lists 17 Modbus registers for the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lenze’s own free documentation (linked below) and checked against it.

Manufacturer
Lenze
Model
i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Equipment type
Variable frequency drive
Registers
17 (6 writable)
Transport
Modbus RTU
Default unit ID
1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
01.01.01.00
Also known as
i500 series, i510 Cabinet, I51AE
Source document
Inverter i510 Cabinet 0.25 ... 2.2 kW - Configuration | Commissioning | Service · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)

Integration in brief

Set the front selector to Modbus, activate the network (0x2631:037 = TRUE) and make the network the setpoint source (0x2860:001 = 5). Write 0x0061 to 42101 (run forward + control and reference from network) and the frequency to 42102 in 0.01 Hz; read 42001-42011 for status and measurements.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2100AC Drive control word (0x400B:001)BITMAP16AC Drive control word (start/stop/reset)Read/write
HR 2101Network setpoint frequency (0x400B:005)UINT16Frequency setpoint, 0.01 HzRead/write
HR 2000AC Drive status word (0x400C:001)BITMAP16AC Drive status wordRead
HR 2001Actual frequency (0x400C:006)UINT16Actual frequency, 0.01 HzRead
HR 2002Error code (0x603F)UINT16Error codeRead
HR 2005Actual motor current (0x2D88)INT16Motor current, 0.1 ARead
HR 2010DC-bus voltage (0x2D87)UINT16DC-bus voltageRead

Enable Modbus control & writes

Set the Modbus/CANopen selector on the inverter front to Modbus. Set 0x2631:037 (PAR 400/037) Activate network = TRUE and 0x2860:001 (PAR 201/001) = 5 Network. Set node address 0x2321:001 (1-247, default 1), baud 0x2321:002 and data format 0x2321:003 (both default Automatic), then restart Modbus communication (0x2320 = 1) or power-cycle.

Communication loss & watchdog

0x2858:002 Time-out (0.0-300.0 s, default 2.0 s) with 0x2858:001 Response to time-out (default Error).

Byte order & addressing

Network setup

Watch out for

Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

17 of 17 shown
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2000doc 42001AC Drive status word (0x400C:001)EtherNet/IP AC drive profile bits.BITMAP16Readbit 0 = Fault/trip; bit 1 = Reserved; bit 2 = Running forward; bit 3 = Running reverse; bit 4 = Ready; bit 5 = Control from network; bit 6 = Reference from network; bit 7 = At reference; bit 8 = Reserved; bit 9 = Reserved; bit 10 = Reserved; bit 11 = Reserved; bit 12 = Process controller active; bit 13 = Torque mode active; bit 14 = Current limit reached; bit 15 = DC braking active
HR2001doc 42002Actual frequency (0x400C:006)Unsigned; direction is in the status word.UINT16× 0.01HzRead
HR2002doc 42003Error code (0x603F)Active error code.UINT16Read
HR2003doc 42004Drive status (0x400C:005)UINT16Read0 = Error (non-resettable); 1 = Error; 2 = Waiting for start; 3 = Identification not executed; 4 = Controller inhibit; 5 = Stop; 7 = Identification; 8 = Running; 9 = Acceleration; 10 = Deceleration; 11 = Deceleration override; 12 = DC braking; 13 = Flying start; 14 = Current limit reached; 16 = Process controller idle state
HR2004doc 42005Actual motor voltage (0x2D89)UINT16VRead
HR2005doc 42006Actual motor current (0x2D88)INT16× 0.1ARead
HR2006doc 42007Current actual value (0x6078)Motor current in percent.INT16× 0.1%Read
HR2007doc 42008Apparent power (0x2DA2:002)42008 = high word, 42009 = low word.INT32ABCD× 0.001kWRead
HR2009doc 42010Heatsink temperature (0x2D84:001)INT16× 0.1°CRead
HR2010doc 42011DC-bus voltage (0x2D87)UINT16VRead
HR2012doc 42013Torque actual value (0x6077)Percent of rated motor torque.INT16× 0.1%Read
HR2100doc 42101AC Drive control word (0x400B:001)EtherNet/IP AC drive profile bits.BITMAP16Read/writebit 0 = Run forward; bit 1 = Run reverse; bit 2 = Reset error (0-1 edge); bit 3 = Reserved; bit 4 = Reserved; bit 5 = Control from network; bit 6 = Reference from network; bit 7 = Reserved; bit 8 = Reserved; bit 9 = Reserved; bit 10 = Reserved; bit 11 = Reserved; bit 12 = Controller inhibit; bit 13 = Quick stop; bit 14 = Process controller off; bit 15 = DC braking
HR2101doc 42102Network setpoint frequency (0x400B:005)Unsigned, 0.00-599.00 Hz; direction via control word.UINT16× 0.01HzRead/write
HR2104doc 42105Network process controller setpoint (0x400B:007)-300.00 to 300.00 process units.INT16× 0.01PUnitRead/write
HR2105doc 42106Target torque (0x6071)100 % = motor rated torque (0x6076).INT16× 0.1%Read/write
HR2106doc 42107NETWordIN1 (0x4008:001)Freely assignable bit functions (0x400E).BITMAP16Read/write
HR2107doc 42108NETWordIN4 (0x4008:004)0.0-100.0 %.UINT16× 0.1%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)

What Modbus registers does the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) have?

This map lists 17 registers: 17 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states all data are 4X registers numbered from 1 but addressed from 0, so register 40001 is address 0; its example writes register 42101 to address 2100 (0x0834). So 42001 = wire 2000 and 42101 = wire 2100.

What byte order does the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)?

Start with HR 2100 AC Drive control word (0x400B:001) (AC Drive control word (start/stop/reset)); HR 2101 Network setpoint frequency (0x400B:005) (Frequency setpoint, 0.01 Hz); HR 2000 AC Drive status word (0x400C:001) (AC Drive status word); HR 2001 Actual frequency (0x400C:006) (Actual frequency, 0.01 Hz); HR 2002 Error code (0x603F) (Error code); HR 2005 Actual motor current (0x2D88) (Motor current, 0.1 A); HR 2010 DC-bus voltage (0x2D87) (DC-bus voltage).

How do I enable Modbus control of the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)?

Set the Modbus/CANopen selector on the inverter front to Modbus. Set 0x2631:037 (PAR 400/037) Activate network = TRUE and 0x2860:001 (PAR 201/001) = 5 Network. Set node address 0x2321:001 (1-247, default 1), baud 0x2321:002 and data format 0x2321:003 (both default Automatic), then restart Modbus communication (0x2320 = 1) or power-cycle.

What happens when the Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) loses Modbus communication?

0x2858:002 Time-out (0.0-300.0 s, default 2.0 s) with 0x2858:001 Response to time-out (default Error).

Where is the official Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU) Modbus documentation?

The source is Inverter i510 Cabinet 0.25 ... 2.2 kW - Configuration | Commissioning | Service. Lenze doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2017/02/Lenze-AC-Tech-i500-i510-VFD-Users-Manual-For-Commissioning.pdf. It may be an older revision, so check it against the live unit.

More Lenze Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Inverter i510 Cabinet 0.25 ... 2.2 kW - Configuration | Commissioning | Service · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.