Soft starter · Modbus register map
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP) Modbus register map
Updated 19 November 2026
The Lovato ADXL is a soft starter for three-phase motors. With the optional EXC1042 RS-485 board it answers Modbus RTU or ASCII (the addendum also lists Modbus TCP as a protocol choice). This map covers voltage, currents, powers, power factor, frequency, torque, thermal status, thyristor temperature, I/O bits, the start/stop commands, the command register and the parameter-access selectors.
This page lists 32 Modbus registers for the Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lovato Electric
- Model
- ADXL soft starters (Modbus RTU / ASCII / TCP)
- Equipment type
- Soft starter
- Registers
- 32 (8 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042
Integration notes: Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
Fit the EXC1042 RS-485 board, set P08 serial parameters, then read currents (08h-0Dh), total power (3Ah), thermal status (FB0h) and thyristor temperature (FB2h) as big-endian 32-bit values. Start and stop with a 1 written to 1002h and 1003h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 7 | L1 current | UINT32 ABCD | L1 current | Read |
| IR 57 | Total active power | INT32 ABCD | Total active power | Read |
| IR 4015 | Motor thermal status | UINT32 ABCD | Motor thermal status | Read |
| IR 4017 | Thyristor temperature | UINT32 ABCD | Thyristor temperature | Read |
| IR 3967 | Motor hour meter | UINT32 ABCD | Motor hours (seconds) | Read |
| HR 4097 | Motor start command | UINT16 | Start command | Write |
| HR 4098 | Motor stop command | UINT16 | Stop command | Write |
Enable Modbus control & writes
Install the EXC1042 RS-485 communication board, then in menu 01-SETUP > P08 COMMUNICATION set node address (08.01), baud rate (08.02), data format (08.03), stop bits (08.04) and protocol (08.05).
Byte order & addressing
- Table addresses are one above the wire address.
- 32-bit values are high word first.
- Phase active powers are kW/100000 but total active power is kW/10000.
Network setup
- Defaults: node 1, 9600 baud, 8 data bits, no parity, 1 stop bit, Modbus RTU.
- Data format choices: 8 bit none/odd/even and 7 bit odd/even.
Watch out for
- Without the EXC1042 board the soft starter has no Modbus port.
- Only function 06 is listed for writes; function 16 is not among the supported functions.
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 5doc 06h | L3-L1 voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 7doc 08h | L1 current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 9doc 0Ah | L2 current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 11doc 0Ch | L3 current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 19doc 14h | L1 active power | INT32 | ABCD | × 0.00001 | kW | Read | ||
| IR | 21doc 16h | L2 active power | INT32 | ABCD | × 0.00001 | kW | Read | ||
| IR | 23doc 18h | L3 active power | INT32 | ABCD | × 0.00001 | kW | Read | ||
| IR | 37doc 26h | L1 power factor | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 39doc 28h | L2 power factor | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 41doc 2Ah | L3 power factor | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 49doc 32h | Frequency | UINT32 | ABCD | × 0.001 | Hz | Read | ||
| IR | 57doc 3Ah | Total active power | Printed as kW/10000 (phase powers are kW/100000). | INT32 | ABCD | × 0.0001 | kW | Read | |
| IR | 63doc 40h | Total power factor | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 117doc 76h | Max current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 119doc 78h | Torque | UINT32 | ABCD | × 0.1 | % | Read | ||
| IR | 121doc 7Ah | Maximum instantaneous current | UINT32 | ABCD | × 0.1 | % | Read | ||
| IR | 3967doc F80h | Motor hour meter | Printed as h/3600, i.e. the count is in seconds. | UINT32 | ABCD | s | Read | ||
| IR | 3969doc F82h | Start counter | UINT32 | ABCD | Read | ||||
| IR | 4015doc FB0h | Motor thermal status | UINT32 | ABCD | % | Read | |||
| IR | 4017doc FB2h | Thyristor temperature | UINT32 | ABCD | × 0.1 | °C | Read | ||
| IR | 8447doc 2100h | Inputs 1-3 | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3 | ||||
| IR | 8512doc 2141h | Outputs 1-3 | BITMAP16 | Read | bit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3 | ||||
| IR | 8575doc 2180h | Remote variables 1-4 | BITMAP16 | Read | bit 0 = Remote 1; bit 1 = Remote 2; bit 2 = Remote 3; bit 3 = Remote 4 | ||||
| IR | 8639doc 21C0h | Limit thresholds 1-4 | BITMAP16 | Read | bit 0 = Limit 1; bit 1 = Limit 2; bit 2 = Limit 3; bit 3 = Limit 4 | ||||
| HR | 4097doc 1002h | Motor start command | Write 1 to start the motor. | UINT16 | Write | ||||
| HR | 4098doc 1003h | Motor stop command | Write 1 to stop the motor. | UINT16 | Write | ||||
| HR | 12034doc 2F03h | Save to flash / reboot | Write 5 to save parameters to flash (also given as the reboot command). | UINT16 | Write | ||||
| HR | 12271doc 2FF0h | Command register | Write a command code (function 06). | UINT16 | Write | 0 = C01 Reset maintenance interval; 1 = C02 Thermal status reset; 2 = C03 Reset start counter; 3 = C04 Reset motor hour meter; 4 = C05 Reset energy counters; 5 = C06 Reset LIM variables with memory; 10 = C11 Repeat AUTOSET wizard; 11 = C12 Restore factory defaults; 12 = C13 Save copy of setup; 13 = C14 Restore copy of setup; 14 = C15 Test with low power motor; 15 = C16 Reset event list | |||
| HR | 20479doc 5000h | Parameter menu number | Step 1 of parameter access. | UINT16 | Read/write | ||||
| HR | 20480doc 5001h | Parameter sub-menu number | Step 2, if the menu has sub-menus. | UINT16 | Read/write | ||||
| HR | 20481doc 5002h | Parameter number | Step 3: parameter within the menu. | UINT16 | Read/write | ||||
| HR | 20527doc 5030h | Event pointer / counter | High byte = events stored, low byte = last index. Write to select an event. | UINT16 | Read/write |
Notes on this map
- Measurements are read with function 03 or 04 (same data); they are listed as input registers. Commands and parameters are written with function 06 only (no function 16 is listed).
- Word order: the read example returns 00 00 01 10 for a thyristor temperature of 27.2 °C (272 x 0.1), so the high word comes first (ABCD).
- Scales are the divisors printed in the unit column: V/100, A/10000, kW/100000 for phase powers but kW/10000 for total power, PF/10000, Hz/1000, %/10, °C/10.
- Left out: the status register F84h (printed as 2 words but 'Unsigned integer', so its width is unclear) and the total active energy at 1B20h (4 words labelled 'Unsigned long'). Function 07 (read exception status) returns a status byte with start/stop input, block, alarm, motor running and bypass bits.
- Left out: the 28-register event description text at 5032h (read via the pointer at 5030h).
- Parameter access: write the menu (5000h), sub-menu (5001h) and parameter number (5002h), then read or write the value at table address 5004h (wire 5003h); write 5 to 2F03h to save and reboot. 5004h is not listed as a register because the document prints no data format for it. The document recommends a reboot (5 to 2F03h) after commands C11-C14.
- Only one communication port can be configured (menu P08).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
What Modbus registers does the Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP) have?
This map lists 32 registers: 24 input registers, 8 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print hex addresses one higher than the address sent on the wire; the document says to subtract one, and its example reads thyristor temperature (table 0FB2h) by sending 0F B1. Write example: parameter menu 5000h is sent as 4F FF. Addresses here are already reduced by one.
What byte order does the Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)?
Start with IR 7 L1 current (L1 current); IR 57 Total active power (Total active power); IR 4015 Motor thermal status (Motor thermal status); IR 4017 Thyristor temperature (Thyristor temperature); IR 3967 Motor hour meter (Motor hours (seconds)); HR 4097 Motor start command (Start command); HR 4098 Motor stop command (Stop command).
How do I enable Modbus control of the Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)?
Install the EXC1042 RS-485 communication board, then in menu 01-SETUP > P08 COMMUNICATION set node address (08.01), baud rate (08.02), data format (08.03), stop bits (08.04) and protocol (08.05).
Where is the official Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP) Modbus documentation?
The source is ADXL soft starter Modbus communication protocol (addendum) (I454IGB03_22), revision 2022-03-28, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/05.%20SOFT%20STARTER/I454IGB03_22.pdf.
More Lovato Electric Modbus register maps
- Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Transfer switch
Lovato Electric ATL610 automatic transfer switch controller
ATL610 ATS controller via the optical port or an EXP1010/1011/1012/1013 communication module, per protocol document I428 GB I 09 22.
Also known as: ATL610, ATL 610, EXP1012, EXP1013 - Transfer switch
Lovato Electric ATL800 / ATL900 automatic transfer switch controllers
ATL800 and ATL900 ATS controllers (document I463 GB I 11 21); LINE3, BRK3 and TB2 items are ATL900 only.
Also known as: ATL800, ATL900, ATL 800, ATL 900 - Power meter (power factor controller)
Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers
DCRL3, DCRL5 and DCRL8 automatic power factor controllers with optical port or EXP10xx modules (Modbus TCP on DCRL8 only), per protocol document I427 GB 05 20.
Also known as: DCRL3, DCRL5, DCRL8, DCRL 3, DCRL 5, DCRL 8 - Power meter (power analyzer)
Lovato Electric DMG7000 / DMG7500 / DMG8000 / DMG9000 power analyzers
Lovato DMG7000, DMG7500, DMG8000 and DMG9000 panel power analyzers on any Modbus port (RTU, ASCII or TCP); DMG9000-only rows are marked.
Also known as: DMG7000, DMG7500, DMG8000, DMG9000, DMG 7000, DMG 8000, DMG 9000, Lovato DMG - Pump (diesel fire pump controller)
Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers
FFL700DP and FFL800DP diesel engine fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800DP), per protocol document I557 GB I 11 17.
Also known as: FFL700DP, FFL800DP, FFL 700 DP, FFL 800 DP - Pump (electric fire pump controller)
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
FFL700EP and FFL800EP electric fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800EP), per protocol document I589 GB I 08 22.
Also known as: FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP - Generator controller
Lovato Electric RGK610 genset controller
RGK610, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 610 - Generator controller
Lovato Electric RGK700 AMF genset controller
RGK700, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700, RGK700 AMF - Generator controller
Lovato Electric RGK700SA stand-alone genset controller
RGK700SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700SA, RGK700 SA - Generator controller
Lovato Electric RGK750 genset controller
RGK750, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 750 - Generator controller
Lovato Electric RGK800 AMF genset controller
RGK800, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800, RGK800 AMF - Generator controller
Lovato Electric RGK800SA stand-alone genset controller
RGK800SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800SA, RGK800 SA - Generator controller
Lovato Electric RGK900 genset paralleling controller
RGK900, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900 - Generator controller
Lovato Electric RGK900MC mains/master controller
RGK900MC, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900MC, RGK900 MC - Generator controller
Lovato Electric RGK900SA genset paralleling controller (stand-alone)
RGK900SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900SA, RGK900 SA - Variable frequency drive
Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)
Lovato VT1 series drives on the built-in RS-485 port, per communication manual I646 GB I 02 21 (Modbus part).
Also known as: VT1, Lovato VT1, VT1 series
Other soft starters & protection relays register maps
- Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40 - Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370
All soft starters & protection relays Modbus register maps →
Source: ADXL soft starter Modbus communication protocol (addendum) · I454IGB03_22 · rev. 2022-03-28. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.