- DCRL3 / DCRL5 / DCRL8 power factor controllers
Power meter (power factor controller) · Modbus register map
Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers Modbus register map
Updated 19 November 2026
The DCRL3, DCRL5 and DCRL8 are Lovato automatic power factor controllers (the register table covers up to 14 steps). They speak Modbus RTU and ASCII, and the DCRL8 also Modbus TCP, on the optical port or EXP10xx expansion modules. This map covers voltage, current, power factor, powers, alarm bits, step timers and counters, harmonics and the mode, step and reset commands.
This page lists 28 Modbus registers for the Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lovato Electric
- Model
- DCRL3 / DCRL5 / DCRL8 power factor controllers
- Equipment type
- Power meter (power factor controller)
- Registers
- 28 (6 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- TCP port
- 1001
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- DCRL3, DCRL5, DCRL8, DCRL 3, DCRL 5, DCRL 8
Integration notes: Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers
Read voltage (04h), current (06h), actual power factor (14h) and the alarm bits (16h) with function 04, subtracting one from each table address. Switch AUT/MAN by writing 1 or 2 to 3000h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 3 | Voltage | UINT32 ABCD | Voltage | Read |
| IR 5 | Current | UINT32 ABCD | Current | Read |
| IR 19 | Actual power factor | INT32 ABCD | Actual power factor | Read |
| IR 21 | Error bits | UINT32 ABCD | Alarm bits | Read |
| IR 51 | Reactive power | INT32 ABCD | Reactive power | Read |
| HR 12287 | Operating mode change | UINT16 | AUT/MAN mode | Write |
Enable Modbus control & writes
Use the optical port or fit an EXP1012 RS-485 (or EXP1013 Ethernet on DCRL8) module, then set node address, speed, data format, stop bits and protocol in the setup menu.
Byte order & addressing
- Table addresses are one above the wire address.
- 32-bit values are high word first.
- Some 'signed' values use a sign bit (bit 31) instead of two's complement.
Network setup
- Defaults: node 01, 9600 baud, 8 data bits, no parity, 1 stop bit, Modbus RTU.
- Ethernet (DCRL8 + EXP1013): default IP 192.168.1.1, port 1001.
- Maximum data field is 80 registers.
Watch out for
- Parameter changes made through 5002h/5004h only take effect after writing 5 to 2F03h (store to EEPROM).
Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 3doc 04h | Voltage | UINT32 | ABCD | V | Read | |||
| IR | 5doc 06h | Current | UINT32 | ABCD | × 0.001 | A | Read | ||
| IR | 9doc 0Ah | Weekly average power factor | UINT32 | ABCD | × 0.01 | Read | |||
| IR | 17doc 12h | Phase angle offset | Printed unit °/4. | UINT32 | ABCD | × 0.25 | ° | Read | |
| IR | 19doc 14h | Actual power factor | Printed as /5000. | INT32 | ABCD | × 0.0002 | Read | ||
| IR | 21doc 16h | Error bits | UINT32 | ABCD | Read | bit 0 = A01 Under compensation; bit 1 = A02 Over compensation; bit 2 = A03 Low current; bit 3 = A04 High current; bit 4 = A05 Low voltage; bit 5 = A06 High voltage; bit 6 = A07 Capacitor overload; bit 7 = A08 Overtemperature; bit 8 = A09 No-voltage release; bit 9 = A10 Voltage THD too high; bit 10 = A11 Current THD too high | |||
| IR | 23doc 18h | Max voltage | UINT32 | ABCD | V | Read | |||
| IR | 25doc 1Ah | Max current | UINT32 | ABCD | × 0.01 | A | Read | ||
| IR | 27doc 1Ch | Max capacitor overload | UINT32 | ABCD | % | Read | |||
| IR | 49doc 32h | Active power | INT32 | ABCD | W | Read | |||
| IR | 51doc 34h | Reactive power | INT32 | ABCD | var | Read | |||
| IR | 53doc 36h | Apparent power | UINT32 | ABCD | VA | Read | |||
| IR | 511doc 200h | Step 1 insertion time | Steps 2-14 follow every 2 registers up to 21Ah. | UINT32 | ABCD | min | Read | ||
| IR | 537doc 21Ah | Step 14 insertion time | UINT32 | ABCD | min | Read | |||
| IR | 8196doc 2005h | Capacitor current overload | UINT16 | % | Read | ||||
| IR | 8198doc 2007h | Hours to maintenance | INT16 | h | Read | ||||
| IR | 8200doc 2009h | THDI | UINT16 | × 0.1 | % | Read | |||
| IR | 8223doc 2020h | Step 1 insertion count | Steps 2-14 at 2021h-202Dh. | UINT16 | Read | ||||
| IR | 8236doc 202Dh | Step 14 insertion count | UINT16 | Read | |||||
| IR | 8255doc 2040h | Step 1 residual power | Steps 2-14 at 2041h-204Dh. | UINT16 | % | Read | |||
| IR | 8319doc 2080h | 2nd voltage harmonic | Up to the 15th at 208Dh. | UINT16 | × 0.1 | % | Read | ||
| IR | 8351doc 20A0h | 2nd current harmonic | Up to the 15th at 20ADh. | UINT16 | × 0.1 | % | Read | ||
| HR | 12034doc 2F03h | Save setup to EEPROM | Write 5 after changing parameters. | UINT16 | Write | ||||
| HR | 12287doc 3000h | Operating mode change | UINT16 | Write | 0 = Toggle AUT/MAN; 1 = MAN mode; 2 = AUT mode | ||||
| HR | 12288doc 3001h | Device reset (warm boot) | Write 1. | UINT16 | Write | ||||
| HR | 12292doc 3005h | Step activation | Write the step number to switch in. | UINT16 | Write | ||||
| HR | 12293doc 3006h | Step de-activation | Write the step number to switch out. | UINT16 | Write | ||||
| HR | 12294doc 3007h | Keyboard lock | UINT16 | Write | 0 = Unlocked; 1 = Locked |
Notes on this map
- Measures are read with function 03 or 04 (same data) and are listed as input registers. Commands use function 06.
- Word order: the RTU example returns 00 00 00 1C for 28 °C and the ASCII example 00 00 01 3D for 317 V, so 32-bit values are high word first (ABCD).
- The RTU example says the panel temperature is at table address 0Eh but sends 00 2D in the frame; the document's written rule (subtract one) and the ASCII example (voltage) are followed here.
- Left out: cos-phi (02h; bit 31 is the sign and bit 30 the inductive/capacitive flag, no scale printed), and delta-kvar, panel temperature and max temperature (marked sign in bit 31, i.e. sign-magnitude, not two's complement).
- Left out: output status (10h; no bit legend), THDV at 2008h (no format printed), apparent energy and parameter values (read via 5002h/5004h with lengths given in the operating manual).
- Intermediate steps follow the printed patterns: insertion times 200h + 2 x (step-1), counts 2020h + (step-1), residual power 2040h + (step-1); only steps 1 and 14 are listed.
- Left out: the command-menu register 2FF0h. The English text says its C01-C09 functions are mapped to single bits and several can run at once, but the table lists plain values 00h-08h, so the write format is unclear.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers
What Modbus registers does the Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers have?
This map lists 28 registers: 22 input registers, 6 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document states that, as in the Modbus standard, the address in a request is the table address minus one; its function 04 example (registers 10h-17h requested with start 00 0F) and ASCII example (table 04h sent as 00 03) agree. Addresses here are already reduced by one.
What byte order does the Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers?
Start with IR 3 Voltage (Voltage); IR 5 Current (Current); IR 19 Actual power factor (Actual power factor); IR 21 Error bits (Alarm bits); IR 51 Reactive power (Reactive power); HR 12287 Operating mode change (AUT/MAN mode).
How do I enable Modbus control of the Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers?
Use the optical port or fit an EXP1012 RS-485 (or EXP1013 Ethernet on DCRL8) module, then set node address, speed, data format, stop bits and protocol in the setup menu.
Where is the official Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers Modbus documentation?
The source is DCRL3 - DCRL5 - DCRL8 digital power factor controller - Modbus communication protocol (I427 GB 05 20), revision 2020-05-20, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/30.%20REGOLATORI%20DI%20RIFASAMENTO%20E%20MODULI%20A%20TIRISTORI/I427IGB05_20.pdf.
More Lovato Electric Modbus register maps
- Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042 - Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Transfer switch
Lovato Electric ATL610 automatic transfer switch controller
ATL610 ATS controller via the optical port or an EXP1010/1011/1012/1013 communication module, per protocol document I428 GB I 09 22.
Also known as: ATL610, ATL 610, EXP1012, EXP1013 - Transfer switch
Lovato Electric ATL800 / ATL900 automatic transfer switch controllers
ATL800 and ATL900 ATS controllers (document I463 GB I 11 21); LINE3, BRK3 and TB2 items are ATL900 only.
Also known as: ATL800, ATL900, ATL 800, ATL 900 - Power meter (power analyzer)
Lovato Electric DMG7000 / DMG7500 / DMG8000 / DMG9000 power analyzers
Lovato DMG7000, DMG7500, DMG8000 and DMG9000 panel power analyzers on any Modbus port (RTU, ASCII or TCP); DMG9000-only rows are marked.
Also known as: DMG7000, DMG7500, DMG8000, DMG9000, DMG 7000, DMG 8000, DMG 9000, Lovato DMG - Pump (diesel fire pump controller)
Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers
FFL700DP and FFL800DP diesel engine fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800DP), per protocol document I557 GB I 11 17.
Also known as: FFL700DP, FFL800DP, FFL 700 DP, FFL 800 DP - Pump (electric fire pump controller)
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
FFL700EP and FFL800EP electric fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800EP), per protocol document I589 GB I 08 22.
Also known as: FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP - Generator controller
Lovato Electric RGK610 genset controller
RGK610, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 610 - Generator controller
Lovato Electric RGK700 AMF genset controller
RGK700, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700, RGK700 AMF - Generator controller
Lovato Electric RGK700SA stand-alone genset controller
RGK700SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700SA, RGK700 SA - Generator controller
Lovato Electric RGK750 genset controller
RGK750, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 750 - Generator controller
Lovato Electric RGK800 AMF genset controller
RGK800, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800, RGK800 AMF - Generator controller
Lovato Electric RGK800SA stand-alone genset controller
RGK800SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800SA, RGK800 SA - Generator controller
Lovato Electric RGK900 genset paralleling controller
RGK900, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900 - Generator controller
Lovato Electric RGK900MC mains/master controller
RGK900MC, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900MC, RGK900 MC - Generator controller
Lovato Electric RGK900SA genset paralleling controller (stand-alone)
RGK900SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900SA, RGK900 SA - Variable frequency drive
Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)
Lovato VT1 series drives on the built-in RS-485 port, per communication manual I646 GB I 02 21 (Modbus part).
Also known as: VT1, Lovato VT1, VT1 series
Other power & energy meters register maps
- Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Power meter (modular multi-circuit energy meter)
Northern Design multicube modular meter, SM352 sub-metering slave (Modbus RTU)
Each SM352 slave meter in a multicube system with the RTU485 Modbus module, per comms manual Rev Beta 1.02 (March 2011).
Also known as: MultiCube, ND multicube, SM352, RTU485 - Sensor / multi-parameter controller
ProMinent DULCOMETER diaLog DACa multi-parameter controller (Modbus RTU)
diaLog DACa controllers with the Modbus RTU interface option, per software manual BA DM 212 12/15.
Also known as: DACa, diaLog DACa, DULCOMETER DACa - Power meter
Rishabh Instruments RISH Delta VAF NX volt/amp/frequency panel meter
Rishabh RISH Delta VAF NX programmable panel meters with RS-485 Modbus RTU, per operating manual AMAN-00IM-0118 Rev. F.
Also known as: RISH Delta VAF NX, Delta VAF NX, RISH Delta VAF - Energy meter
Rishabh Instruments RISH EM 3490 SS single-phase energy meter
Rishabh RISH EM 3490 SS single-phase energy meters with the optional RS-485 Modbus output, per the 1-phase manual Rev D.
Also known as: RISH EM 3490 SS 1P, EM3490SS 1P, EM 3490 SS single-phase - Power meter
Rishabh Instruments RISH LM1360+ RJ12 smart energy meter
Rishabh RISH LM1360 PLUS RJ12 smart energy meters (RJ12 CT inputs) with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. A (01/2026).
Also known as: RISH LM 1360+, LM1360 PLUS RJ12, LM1360+
All power & energy meters Modbus register maps →
Source: DCRL3 - DCRL5 - DCRL8 digital power factor controller - Modbus communication protocol · I427 GB 05 20 · rev. 2020-05-20. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.