Generator controller · Modbus register map

Lovato Electric RGK900MC mains/master controller Modbus register map

Updated 19 November 2026

Short answer

The RGK900MC is one of Lovato's RGK genset controllers. It answers Modbus RTU and ASCII on its serial ports and Modbus TCP through the EXP1013 Ethernet module, and all measurements are 32-bit values read with function 04 (or 03). This map lists the electrical measurements, engine speed, battery voltage and energy totals that the protocol document marks for this model.

This page lists 89 Modbus registers for the Lovato Electric RGK900MC mains/master controller — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Lovato Electric
Model
RGK900MC mains/master controller
Equipment type
Generator controller
Registers
89 (0 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
RGK 900MC, RGK900 MC
Source document
RGK series generating set controller - Modbus communication protocol · I375 I GB 08 22 · rev. 2022-08-26
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lovato Electric RGK900MC mains/master controller

Integration in brief

Read the 32-bit measures with function 04 (or 03), two registers each, high word first, at the table address minus one. Mode bits are in the 0F98H status copy.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 27L1-L2 Voltage - GeneratorUINT32 ABCDGenerator L1-L2 voltageRead
IR 91Frequency - GeneratorUINT32 ABCDGenerator frequencyRead
IR 13L1 CurrentUINT32 ABCDPhase L1 currentRead
IR 111Eqv. Active Power - GeneratorINT32 ABCDGenerator total active powerRead
IR 4007Battery voltageUINT32 ABCDBattery voltageRead
IR 3991Modbus Function 0x07 cloneUINT32 ABCDOperating mode (status copy)Read
IR 21L1-L2 Voltage - Mains (Bus)UINT32 ABCDMains L1-L2 voltageRead

Enable Modbus control & writes

Set the communication port (built-in serial or optical port, or an EXP expansion module) in the device setup menu; see the RGK instruction manual for the menu.

Byte order & addressing

Network setup

Watch out for

Lovato Electric RGK900MC mains/master controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

89 of 89 shown
Lovato Electric RGK900MC mains/master controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR1doc 0002HL1 Phase Voltage - Mains (Bus)UINT32ABCD× 0.01VRead
IR3doc 0004HL2 Phase Voltage - Mains (Bus)UINT32ABCD× 0.01VRead
IR5doc 0006HL3 Phase Voltage - Mains (Bus)UINT32ABCD× 0.01VRead
IR7doc 0008HL1 Phase Voltage - GeneratorUINT32ABCD× 0.01VRead
IR9doc 000AHL2 Phase Voltage - GeneratorUINT32ABCD× 0.01VRead
IR11doc 000CHL3 Phase Voltage - GeneratorUINT32ABCD× 0.01VRead
IR13doc 000EHL1 CurrentUINT32ABCD× 0.0001ARead
IR15doc 0010HL2 CurrentUINT32ABCD× 0.0001ARead
IR17doc 0012HL3 CurrentUINT32ABCD× 0.0001ARead
IR21doc 0016HL1-L2 Voltage - Mains (Bus)UINT32ABCD× 0.01VRead
IR23doc 0018HL2-L3 Voltage - Mains (Bus)UINT32ABCD× 0.01VRead
IR25doc 001AHL3-L1 Voltage - Mains (Bus)UINT32ABCD× 0.01VRead
IR27doc 001CHL1-L2 Voltage - GeneratorUINT32ABCD× 0.01VRead
IR29doc 001EHL2-L3 Voltage - GeneratorUINT32ABCD× 0.01VRead
IR31doc 0020HL3-L1 Voltage - GeneratorUINT32ABCD× 0.01VRead
IR33doc 0022HL1 Active Power - Mains (Bus)INT32ABCD× 0.01WRead
IR35doc 0024HL2 Active Power - Mains (Bus)INT32ABCD× 0.01WRead
IR37doc 0026HL3 Active Power - Mains (Bus)INT32ABCD× 0.01WRead
IR45doc 002EHL1 Reactive Power - Mains (Bus)INT32ABCD× 0.01varRead
IR47doc 0030HL2 Reactive Power - Mains (Bus)INT32ABCD× 0.01varRead
IR49doc 0032HL3 Reactive Power - Mains (Bus)INT32ABCD× 0.01varRead
IR57doc 003AHL1 Apparent Power - Mains (Bus)UINT32ABCD× 0.01VARead
IR59doc 003CHL2 Apparent Power - Mains (Bus)UINT32ABCD× 0.01VARead
IR61doc 003EHL3 Apparent Power - Mains (Bus)UINT32ABCD× 0.01VARead
IR69doc 0046HL1 Power Factor - Mains (Bus)INT32ABCD× 0.0001Read
IR71doc 0048HL2 Power Factor - Mains (Bus)INT32ABCD× 0.0001Read
IR73doc 004AHL3 Power Factor - Mains (Bus)INT32ABCD× 0.0001Read
IR81doc 0052HEqv. Phase Voltage - Mains (Bus)UINT32ABCD× 0.01VRead
IR83doc 0054HEqv. Phase-To-Phase Voltage Mains (Bus)UINT32ABCD× 0.01VRead
IR85doc 0056HFrequency - Mains (Bus)UINT32ABCD× 0.001HzRead
IR87doc 0058HEqv. Phase Voltage - GeneratorUINT32ABCD× 0.01VRead
IR89doc 005AHEqv. Phase-To-Phase Voltage - GeneratorUINT32ABCD× 0.01VRead
IR91doc 005CHFrequency - GeneratorUINT32ABCD× 0.001HzRead
IR93doc 005EHEqv Power Factor - Mains (Bus)INT32ABCD× 0.0001Read
IR99doc 0064HEqv Power Factor - GeneratorINT32ABCD× 0.0001Read
IR105doc 006AHEqv. Active Power - Mains (Bus)INT32ABCD× 0.01WRead
IR107doc 006CHEqv. Reactive Power - Mains (Bus)INT32ABCD× 0.01varRead
IR109doc 006EHEqv. Apparent Power - Mains (Bus)UINT32ABCD× 0.01VARead
IR111doc 0070HEqv. Active Power - GeneratorINT32ABCD× 0.01WRead
IR113doc 0072HEqv. Reactive Power - GeneratorINT32ABCD× 0.01varRead
IR115doc 0074HEqv. Apparent Power - GeneratorUINT32ABCD× 0.01VARead
IR135doc 0088HPhase-Phase Voltage asymmetry - GeneratorUINT32ABCD× 0.01%Read
IR137doc 008AHPhase-neutral Voltage asymmetry - GeneratorUINT32ABCD× 0.01%Read
IR139doc 008CHCurrent Asymmetry - GeneratorUINT32ABCD× 0.01%Read
IR141doc 008EHEngine speedUINT32ABCD× 0.1rpmRead
IR143doc 0090HL1-2 Voltage Thd - GeneratorUINT32ABCD× 0.01%Read
IR145doc 0092HL2-3 Voltage Thd - GeneratorUINT32ABCD× 0.01%Read
IR147doc 0094HL3-1 Voltage Thd - GeneratorUINT32ABCD× 0.01%Read
IR149doc 0096HL1 Voltage Thd - GeneratorUINT32ABCD× 0.01%Read
IR151doc 0098HL2 Voltage Thd - GeneratorUINT32ABCD× 0.01%Read
IR153doc 009AHL3 Voltage Thd - GeneratorUINT32ABCD× 0.01%Read
IR155doc 009CHL1 Current Thd - GeneratorUINT32ABCD× 0.01%Read
IR157doc 009EHL2 Current Thd - GeneratorUINT32ABCD× 0.01%Read
IR159doc 00A0HL3 Current Thd - GeneratorUINT32ABCD× 0.01%Read
IR169doc 00AAHL1 Current - view -UINT32ABCD× 0.0001ARead
IR171doc 00ACHL2 Current - view -UINT32ABCD× 0.0001ARead
IR173doc 00AEHL3 Current - view -UINT32ABCD× 0.0001ARead
IR175doc 00B0HNeutral Current - view -UINT32ABCD× 0.0001ARead
IR179doc 00B4HDelta frequencyINT32ABCD× 0.001HzRead
IR181doc 00B6HActive Power - LoadINT32ABCD× 0.01WRead
IR183doc 00B8HReactive Power - LoadINT32ABCD× 0.01varRead
IR185doc 00BAHApparent Power - LoadINT32ABCD× 0.01VARead
IR187doc 00BCHPower factor - loadINT32ABCD× 0.0001Read
IR195doc 00C4HNominal power of devices connected to busUINT32ABCD× 0.01Read
IR197doc 00C6HLoad powerUINT32ABCD× 0.01Read
IR199doc 00C8HPower reserveUINT32ABCD× 0.01Read
IR3989doc 0F96HGenerator contactor closing counterUINT32ABCDRead
IR3991doc 0F98HModbus Function 0x07 cloneCopy of the function 07 status byte; bits in notes.UINT32ABCDRead
IR4007doc 0FA8HBattery voltageUINT32ABCD× 0.01VRead
IR6687doc 1A20HTotal imp. Active Energy - Mains (Bus)UINT32ABCD× 0.1kWhRead
IR6689doc 1A22HTotal exported Active Energy - Mains (Bus)UINT32ABCD× 0.1kWhRead
IR6691doc 1A24HTotal imp. Reactive Energy - Mains (Bus)UINT32ABCD× 0.1kvarhRead
IR6693doc 1A26HTotal exp. Reactive Energy - Mains (Bus)UINT32ABCD× 0.1kvarhRead
IR6695doc 1A28HTotal Apparent Energy - Mains (Bus)UINT32ABCD× 0.1kVAhRead
IR6697doc 1A2AHTotal imp. Active Energy - GeneratorUINT32ABCD× 0.1kWhRead
IR6699doc 1A2CHTotal exported Active Energy - GeneratorUINT32ABCD× 0.1kWhRead
IR6701doc 1A2EHTotal imp. Reactive Energy - GeneratorUINT32ABCD× 0.1kvarhRead
IR6703doc 1A30HTotal exp. Reactive Energy - GeneratorUINT32ABCD× 0.1kvarhRead
IR6705doc 1A32HTotal Apparent Energy - GeneratorUINT32ABCD× 0.1kVAhRead
IR6943doc 1B20HPartial imp. Active Energy - Mains (Bus)UINT32ABCD× 0.1kWhRead
IR6945doc 1B22HPartial exported Active Energy - Mains (Bus)UINT32ABCD× 0.1kWhRead
IR6947doc 1B24HPartial imp. Reactive Energy - Mains (Bus)UINT32ABCD× 0.1kvarhRead
IR6949doc 1B26HPartial exp. Reactive Energy - Mains (Bus)UINT32ABCD× 0.1kvarhRead
IR6951doc 1B28HPartial Apparent Energy - Mains (Bus)UINT32ABCD× 0.1kVAhRead
IR6953doc 1B2AHPartial imp. Active Energy - GeneratorUINT32ABCD× 0.1kWhRead
IR6955doc 1B2CHPartial exported Active Energy - GeneratorUINT32ABCD× 0.1kWhRead
IR6957doc 1B2EHPartial imp. Reactive Energy - GeneratorUINT32ABCD× 0.1kvarhRead
IR6959doc 1B30HPartial exp. Reactive Energy - GeneratorUINT32ABCD× 0.1kvarhRead
IR6961doc 1B32HPartial Apparent Energy - GeneratorUINT32ABCD× 0.1kVAhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lovato Electric RGK900MC mains/master controller

What Modbus registers does the Lovato Electric RGK900MC mains/master controller have?

This map lists 89 registers: 89 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lovato Electric RGK900MC mains/master controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print hex addresses (for example 0024H) and the document says the address in the query must be one lower than the table value. Its example reads mains L2 active power, listed at 0024H, with start address 00 23. 'address' here is already reduced by one.

What byte order does the Lovato Electric RGK900MC mains/master controller use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lovato Electric RGK900MC mains/master controller?

Start with IR 27 L1-L2 Voltage - Generator (Generator L1-L2 voltage); IR 91 Frequency - Generator (Generator frequency); IR 13 L1 Current (Phase L1 current); IR 111 Eqv. Active Power - Generator (Generator total active power); IR 4007 Battery voltage (Battery voltage); IR 3991 Modbus Function 0x07 clone (Operating mode (status copy)); IR 21 L1-L2 Voltage - Mains (Bus) (Mains L1-L2 voltage).

How do I enable Modbus control of the Lovato Electric RGK900MC mains/master controller?

Set the communication port (built-in serial or optical port, or an EXP expansion module) in the device setup menu; see the RGK instruction manual for the menu.

Where is the official Lovato Electric RGK900MC mains/master controller Modbus documentation?

The source is RGK series generating set controller - Modbus communication protocol (I375 I GB 08 22), revision 2022-08-26, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/32.%20CONTROLLORI%20GRUPPI%20ELETTROGENI%20E%20PROTEZIONE%20MOTORE/I375IGB08_22.pdf.

More Lovato Electric Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: RGK series generating set controller - Modbus communication protocol · I375 I GB 08 22 · rev. 2022-08-26. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.