Generator controller (synchronizer and load sharing control) · Modbus register map
Woodward DSLC-2 Digital Synchronizer and Load Control Modbus register map
Updated 17 November 2026
The DSLC-2 synchronises a generator to a bus and shares or controls its real and reactive load alongside the engine and voltage regulators. It is a Modbus RTU slave on RS-485 and a Modbus/TCP slave on Ethernet network B. Measurements and status come from data protocol 5200 at Modicon 450001; interface setpoints and remote discrete-input commands are written to parameters. This map covers frequencies, phase angle, 32-bit generator and bus values, energy, control modes, condition flags, alarms, relays and discrete inputs, and the interface setpoints.
This page lists 69 Modbus registers for the Woodward DSLC-2 Digital Synchronizer and Load Control — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Woodward’s own free documentation (linked below) and checked against it.
- Manufacturer
- Woodward
- Model
- DSLC-2 Digital Synchronizer and Load Control
- Registers
- 69 (6 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- DSLC2, DSLC-2 synchronizer
Integration notes: Woodward DSLC-2 Digital Synchronizer and Load Control
Block-read up to 128 holding registers from wire address 50000 for frequencies, modes, flags and alarms, and from 50100 for the 32-bit generator values and energy. To command the unit, release functions to the interface in 7645, then switch them in 7644; write setpoints to 7640-7642 and 7780.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 50010 | Generator frequency | INT16 | Generator frequency | Read |
| HR 50023 | Busbar frequency | INT16 | Busbar frequency | Read |
| HR 50032 | Phase Angle Generator / Busbar | INT16 | Phase angle generator / bus | Read |
| HR 50056 | Sync Control State | INT16 | Synchronizer state | Read |
| HR 50057 | Load Control Mode | INT16 | Load control mode | Read |
| HR 50075 | Alarms 1 | BITMAP16 | Alarms 1 | Read |
| HR 50100 | Total generator power | INT32 ABCD | Total generator power (32-bit) | Read |
| HR 50114 | Generator current 1 | INT32 ABCD | Generator current 1 (32-bit) | Read |
Enable Modbus control & writes
RS-485 (serial interface 2): set Modbus slave ID 3188 (default 1; 0 disables Modbus), baud 3170 (default 19.2 kBd), parity 3171 (default none), stop bits 3172 (default one). Network B Modbus/TCP slave ID is parameter 5451 (default 255). Release remote functions in 7645.
Communication loss & watchdog
No timeout parameter is given. On an interface connection loss the discrete-input states stay as they were; energising DI 22 'Modbus reset' returns all functions to hardware control and clears the control bits.
Byte order & addressing
- Some PLCs need the address shifted by one; the manual notes 450001 may become bus address 50000.
- 32-bit parameters such as 7642 and 7780 are written as two registers in one request, high word first.
- Bits of 7644/7645 are numbered 01-16 in the manual without saying whether 01 is the least significant bit, so no bit map is given here; check on a test unit before relying on a bit position.
Network setup
- Network B default IP address is 192.168.1.1 (parameters 5430-5433).
- Reply delay for RS-485 is parameter 3189 (0.00-2.55 s).
Watch out for
- Releasing Run/Permissive to the interface lets the PLC close the generator breaker via synchronisation; test carefully.
- After a connection loss you must de-energise DI 22 before 7645 can be set back to interface control.
Woodward DSLC-2 Digital Synchronizer and Load Control Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 7640doc 7640 (47641) | Interface power factor setpoint | -500 (capacitive) to 1000 to 500 (inductive); used when 7635 = Interface. | INT16 | × 0.001 | Read/write | |||
| HR | 7641doc 7641 (47642) | Interface frequency setpoint | 0-7000; used when parameter 7783 = Interface. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 7642doc 7642 (47643) | Interface active power setpoint (base load) | Positive only; used when 7634 = Interface. Manual example: 1000 kW = 1000. | INT32 | ABCD | kW | Read/write | ||
| HR | 7644doc 7644 (47645) | Discrete inputs over interface | Bit field (bits 01-16, see notes) switching functions released by 7645. | UINT16 | Read/write | ||||
| HR | 7645doc 7645 (47646) | Release discrete inputs to interface | Same bit list as 7644; 1 = interface controlled, 0 = hardware input. | UINT16 | Read/write | ||||
| HR | 7780doc 7780 (47781) | Interface voltage setpoint | 50-650000 V; used when 7784 = Interface. | UINT32 | ABCD | V | Read/write | ||
| HR | 50000 | Protocol ID | Reads 5200. | INT16 | Read | ||||
| HR | 50010 | Generator frequency | INT16 | × 0.01 | Hz | Read | |||
| HR | 50013 | Generator power factor | INT16 | × 0.001 | Read | ||||
| HR | 50023 | Busbar frequency | INT16 | × 0.01 | Hz | Read | |||
| HR | 50025 | Auxiliary busbar frequency | INT16 | × 0.01 | Hz | Read | |||
| HR | 50032 | Phase Angle Generator / Busbar | INT16 | × 0.1 | ° | Read | |||
| HR | 50033 | Active Setpoint generator frequency | INT16 | × 0.01 | Hz | Read | |||
| HR | 50034 | Active Setpoint generator voltage | INT16 | × 0.01 | % | Read | |||
| HR | 50035 | Active Setpoint generator load level | INT16 | × 0.01 | % | Read | |||
| HR | 50036 | Active Setpoint generator reactive power | INT16 | × 0.01 | % | Read | |||
| HR | 50044 | Battery voltage | INT16 | × 0.1 | V | Read | |||
| HR | 50048 | Speed Biasing (AO1) | INT16 | × 0.01 | % | Read | |||
| HR | 50049 | AVR Biasing (AO2) | INT16 | × 0.01 | % | Read | |||
| HR | 50056 | Sync Control State | INT16 | Read | 0 = Off; 1 = Check mode active; 2 = Permissive mode active; 3 = Run mode active; 4 = Close Timer runs; 5 = Sync Timer runs; 6 = Breaker synchronized; 7 = Auto-Off position; 8 = Manual | ||||
| HR | 50057 | Load Control Mode | INT16 | Read | 0 = Inactive; 1 = Droop; 2 = At Unload Trip; 3 = Load sharing; 4 = Base load control; 5 = reserved; 6 = Process control; 7 = reserved; 8 = Peak load control (reserved); 9 = Zero power control (reserved); 10 = Load share (reserved); 11 = Process slave (reserved) | ||||
| HR | 50058 | Reactive Load Control Mode | INT16 | Read | 0 = Inactive; 1 = Off; 2 = Droop; 3 = VAR sharing; 4 = Reactive load control; 5 = reserved; 6 = reserved; 7 = Remote process control (reserved); 8 = (reserved); 9 = Zero power control (reserved); 10 = Reactive load share (reserved); 11 = Process slave (reserved) | ||||
| HR | 50059 | Condition Flags 1 | BITMAP16 | Read | bit 1 = Generator clock wise system is recognized; bit 2 = Generator counter clock wise system is recognized; bit 4 = Busbar is dead (in same segment); bit 5 = Aux. Busbar clock wise system is recognized; bit 6 = Aux. Busbar anti clock wise system is recognized; bit 10 = Busbar is ok (in same segment); bit 12 = Generator breaker is closed; bit 13 = Generator is OK; bit 15 = Generator is Dead | ||||
| HR | 50060 | Condition Flags 2 | BITMAP16 | Read | bit 8 = Reactive power load share is active; bit 9 = Active power load share is active; bit 10 = Dead busbar closure request active | ||||
| HR | 50061 | Condition Flags 3 | BITMAP16 | Read | bit 2 = Unloading generator is active; bit 6 = Closing GCB is active; bit 7 = Opening GCB is active; bit 8 = Synchronization GCB is active; bit 11 = GCB is closed; bit 12 = 3-Position Controller Volt./ReactPow lower; bit 13 = 3-Position Controller Volt./ReactPow raise | ||||
| HR | 50067 | Interface Control Switch | BITMAP16 | Read | bit 0 = Source: Synchronization GCB check switch; bit 1 = Source: Synchronization GCB permissive switch; bit 2 = Source: Synchronization GCB run switch; bit 3 = Source: CB Aux contact switch; bit 4 = Source: Raise voltage switch; bit 5 = Source: Lower voltage switch; bit 6 = Source: Base load switch; bit 7 = Source: Load/ Unload switch; bit 8 = Source: Ramp pause switch; bit 9 = Source: Raise load switch; bit 10 = Source: Lower load switch; bit 11 = Source: Process switch; bit 12 = Source: Droop switch; bit 13 = Source: Modbus reset switch; bit 14 = Source: System update switch | ||||
| HR | 50071 | Relay Outputs 1 | BITMAP16 | Read | bit 0 = Alarm Relay (R1); bit 1 = Load Switch Relay (R2); bit 2 = High Limit Relay (R3); bit 3 = Low Limit Relay (R4); bit 4 = Breaker Open Relay (R5); bit 5 = Breaker Close Relay (R6); bit 6 = Centralized Alarm (R7); bit 7 = Alarm 1 (R8)/3 pos.Controller f/act. Pwr raise; bit 8 = Alarm 2 (R9)/3 pos.Controller f/act. Pwr lower; bit 9 = Alarm 3 (R10); bit 10 = Voltage Raise Relay (R11); bit 11 = Voltage Lower Relay (R12) | ||||
| HR | 50075 | Alarms 1 | BITMAP16 | Read | bit 0 = Synchronizer Timeout; bit 1 = GCB Close Failure; bit 2 = High Load Limit; bit 3 = Low Load Limit; bit 4 = High Process Limit; bit 5 = Low Process Limit; bit 6 = Low Voltage Limit; bit 7 = High Voltage Limit; bit 8 = Voltage Range Limit; bit 9 = Communication Error NW A; bit 10 = Low Frequency Limit; bit 11 = Missing member; bit 12 = Centralized Alarms; bit 13 = GCB Open Failure; bit 14 = Deadbus closure mismatch; bit 15 = High Frequency Limit | ||||
| HR | 50081 | Discrete Inputs 1 | BITMAP16 | Read | bit 0 = Synchronization Check switch is active (DI1); bit 1 = Synchronization Permissive switch is active (DI2); bit 2 = Synchronization Run switch is active (DI3); bit 3 = Circuit Breaker Aux. is closed (DI4); bit 4 = Voltage Raise Switch (DI5); bit 5 = Voltage Lower Switch (DI6); bit 6 = Base Load Control Switch (DI7); bit 7 = Load/Unload Switch (DI8) (Energized=Load); bit 8 = Ramp Pause Switch (DI9); bit 9 = Load Raise Switch (DI10); bit 10 = Load Lower Switch (DI11); bit 11 = Process Control Switch (DI12) | ||||
| HR | 50082 | Digital Inputs 2 | BITMAP16 | Read | bit 0 = Segment connection 12 is closed (DI13); bit 1 = Segment connection 23 is closed (DI14); bit 2 = Segment connection 34 is closed (DI15); bit 3 = Segment connection 45 is closed (DI16); bit 4 = Segment connection 56 is closed (DI17); bit 5 = Segment connection 67 is closed (DI18); bit 6 = Segment connection 78 is closed (DI19); bit 7 = Segment connection 81 is closed (DI20); bit 8 = Droop (DI21); bit 9 = Modbus reset (DI22); bit 10 = System update (DI23) | ||||
| HR | 50083 | Alarms 5 | BITMAP16 | Read | bit 0 = Busbar mismatch; bit 1 = Phase rotation mismatch; bit 2 = Communication Error NW B; bit 3 = Network A Error; bit 4 = Network B Error; bit 5 = Devices not matched | ||||
| HR | 50100 | Total generator power | INT32 | ABCD | W | Read | |||
| HR | 50102 | Total generator reactive power | INT32 | ABCD | var | Read | |||
| HR | 50104 | Total generator apparent power | INT32 | ABCD | VA | Read | |||
| HR | 50106 | Average generator Wye-Voltage | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50108 | Average generator Delta-Voltage | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50110 | Average Busbar 1 Delta-Voltage | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50112 | Average generator Current | INT32 | ABCD | × 0.001 | A | Read | ||
| HR | 50114 | Generator current 1 | INT32 | ABCD | × 0.001 | A | Read | ||
| HR | 50116 | Generator current 2 | INT32 | ABCD | × 0.001 | A | Read | ||
| HR | 50118 | Generator current 3 | INT32 | ABCD | × 0.001 | A | Read | ||
| HR | 50120 | Generator voltage L1-L2 | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50122 | Generator voltage L2-L3 | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50124 | Generator voltage L3-L1 | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50126 | Generator voltage L1-N | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50128 | Generator voltage L2-N | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50130 | Generator voltage L3-N | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50132 | Generator active power 1-N | INT32 | ABCD | W | Read | |||
| HR | 50134 | Generator active power 2-N | INT32 | ABCD | W | Read | |||
| HR | 50136 | Generator active power 3-N | INT32 | ABCD | W | Read | |||
| HR | 50138 | Busbar voltage (L1-N) L1-L2 | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50140 | Average Aux.busbar Wye-Voltage | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50142 | Average Aux.busbar Delta-Voltage | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50144 | Aux.busbar voltage L1-L2 | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50146 | Aux.busbar voltage L2-L3 | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50148 | Aux.busbar voltage L3-L1 | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50150 | Aux.busbar voltage L1-N | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50152 | Aux.busbar voltage L2-N | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50154 | Aux.busbar voltage L3-N | INT32 | ABCD | × 0.1 | V | Read | ||
| HR | 50160 | Load reference | INT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 50162 | Reactive load reference | INT32 | ABCD | × 0.1 | kvar | Read | ||
| HR | 50164 | Process reference input | INT32 | ABCD | × 0.1 | Read | |||
| HR | 50166 | Process signal input | INT32 | ABCD | × 0.1 | Read | |||
| HR | 50168 | Process reference toolkit | INT32 | ABCD | × 0.1 | Read | |||
| HR | 50170 | Remote load reference input | INT32 | ABCD | × 0.1 | kW | Read | ||
| HR | 50174 | Gen.pos.act.energy | INT32 | ABCD | × 0.01 | MWh | Read | ||
| HR | 50178 | Gen.pos.react.energy | INT32 | ABCD | × 0.01 | Mvarh | Read | ||
| HR | 50180 | Gen.neg.react.energy | INT32 | ABCD | × 0.01 | Mvarh | Read | ||
| HR | 50182 | Hours of operation | INT32 | ABCD | × 0.01 | h | Read |
Notes on this map
- The 5200 table states size (16/32 bit) and format (signed / bit array) for each value. The manual says 32-bit values are sent high word at the lower address (interface setpoint example), so 32-bit values are ABCD.
- Left out: the 16-bit power, reactive power, voltage and current values at 50011-50031, which are scaled by exponent registers 50001-50003; use the 32-bit values from 50100 instead. Also left out: values with only a range instead of a multiplier (remote load/process input AI4, process signal input AI5 and 50065/50066, power factor input and reference, ASA/CBS numbers) and unnamed bits.
- Load and reactive load control mode enums are shared with the MSLC-2 in the manual; only the DSLC-2 meanings are listed here.
- Interface setpoints need no password but only take effect when their setpoint-source parameter (7634, 7635, 7783, 7784) is set to Interface.
- The CB Aux and Modbus reset functions always stay hardware controlled even if released in 7645.
- Bits of 7644/7645 in manual order 01-16: Check, Permissive, Run, CB Aux, Voltage raise, Voltage lower, Base load, Load/Unload, Ramp pause, Load raise, Load lower, Process, Droop mode, Modbus reset, System update, N/A.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Woodward DSLC-2 Digital Synchronizer and Load Control
What Modbus registers does the Woodward DSLC-2 Digital Synchronizer and Load Control have?
This map lists 69 registers: 69 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Woodward DSLC-2 Digital Synchronizer and Load Control Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The 5200 table prints both the bus address (50000) and the Modicon address (450001); this map records and sends the bus address. Parameters use Modicon 40000 + (parameter ID + 1), so parameter 7642 is Modicon 47643 = wire address 7642; the manual's ModScan32 screenshots for 7642 (address 7643, 1-based) and 7640 (7641) confirm this. The worked examples print '407642' and '40509', which are typos that do not follow the manual's own rule.
What byte order does the Woodward DSLC-2 Digital Synchronizer and Load Control use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Woodward DSLC-2 Digital Synchronizer and Load Control?
Start with HR 50010 Generator frequency (Generator frequency); HR 50023 Busbar frequency (Busbar frequency); HR 50032 Phase Angle Generator / Busbar (Phase angle generator / bus); HR 50056 Sync Control State (Synchronizer state); HR 50057 Load Control Mode (Load control mode); HR 50075 Alarms 1 (Alarms 1); HR 50100 Total generator power (Total generator power (32-bit)); HR 50114 Generator current 1 (Generator current 1 (32-bit)).
How do I enable Modbus control of the Woodward DSLC-2 Digital Synchronizer and Load Control?
RS-485 (serial interface 2): set Modbus slave ID 3188 (default 1; 0 disables Modbus), baud 3170 (default 19.2 kBd), parity 3171 (default none), stop bits 3172 (default one). Network B Modbus/TCP slave ID is parameter 5451 (default 255). Release remote functions in 7645.
What happens when the Woodward DSLC-2 Digital Synchronizer and Load Control loses Modbus communication?
No timeout parameter is given. On an interface connection loss the discrete-input states stay as they were; energising DI 22 'Modbus reset' returns all functions to hardware control and clears the control bits.
Where is the official Woodward DSLC-2 Digital Synchronizer and Load Control Modbus documentation?
The source is DSLC-2 Digital Synchronizer and Load Control - Manual (37443J), revision 2022-02-08, published free by Woodward at https://www.woodward.com/products/wp-content/uploads/sites/3/2024/08/37443_J.pdf.
More Woodward Modbus register maps
- Generator controller
Woodward easYgen-1000 Series genset controller (Modbus RTU)
easYgen-1000 series software version 2.1xxx, transmission telegram protocol 4003, per interface manual 37393B.
Also known as: easYgen-1000, easYgen1000, easYgen-1000 Series - Generator controller
Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)
easYgen-2200/2300/2500, data protocol 5100 (basic visualization), per manual 37535D.
Also known as: easYgen-2200, easYgen-2300, easYgen-2500, easYgen-2000 Series - Generator controller
Woodward easYgen-3000XT Series
easYgen-3100XT-P1 / 3200XT-P1 / 3200XT-P1-LT, release 2.17-0, default Modbus data protocol 5010 (Basic Visualization).
Also known as: easYgen-3100XT-P1, easYgen-3200XT-P1, easYgen-3200XT-P1-LT, easYgen-3100XT, easYgen-3200XT - Generator controller (utility-tie master synchronizer)
Woodward MSLC-2 Master Synchronizer and Load Control
MSLC-2, data protocol 5200, per manual 37444G.
Also known as: MSLC2, MSLC-2 master synchronizer
Other generator controllers register maps
- Transfer switch controller
BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)
BTicino M7000CBNCU03 (Legrand cat. no. 4 226 82) automatic changeover controller, Modbus RTU/ASCII via the M7000CBNRS485 expansion module or the IR-USB / IR-WiFi front interfaces, per document LE09509AA-01/17-01.
Also known as: M7000CBNCU03, 4 226 82, 422682, Legrand 4 226 82 - Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2 - Transfer switch
Lovato Electric ATL610 automatic transfer switch controller
ATL610 ATS controller via the optical port or an EXP1010/1011/1012/1013 communication module, per protocol document I428 GB I 09 22.
Also known as: ATL610, ATL 610, EXP1012, EXP1013 - Generator controller
Lovato Electric RGK800SA stand-alone genset controller
RGK800SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800SA, RGK800 SA - Generator controller
SmartGen HGM9510N / HGM9520N / HGM9530N
HGM9510N, HGM9520N and HGM9530N paralleling genset controllers, protocol document v1.5.
Also known as: HGM9520N, HGM9530N
All generator controllers Modbus register maps →
Source: DSLC-2 Digital Synchronizer and Load Control - Manual · 37443J · rev. 2022-02-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.