Generator controller (synchronizer and load sharing control) · Modbus register map

Woodward DSLC-2 Digital Synchronizer and Load Control Modbus register map

Updated 17 November 2026

Short answer

The DSLC-2 synchronises a generator to a bus and shares or controls its real and reactive load alongside the engine and voltage regulators. It is a Modbus RTU slave on RS-485 and a Modbus/TCP slave on Ethernet network B. Measurements and status come from data protocol 5200 at Modicon 450001; interface setpoints and remote discrete-input commands are written to parameters. This map covers frequencies, phase angle, 32-bit generator and bus values, energy, control modes, condition flags, alarms, relays and discrete inputs, and the interface setpoints.

This page lists 69 Modbus registers for the Woodward DSLC-2 Digital Synchronizer and Load Control — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Woodward’s own free documentation (linked below) and checked against it.

Manufacturer
Woodward
Model
DSLC-2 Digital Synchronizer and Load Control
Equipment type
Generator controller (synchronizer and load sharing control)
Registers
69 (6 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
DSLC2, DSLC-2 synchronizer
Source document
DSLC-2 Digital Synchronizer and Load Control - Manual · 37443J · rev. 2022-02-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Woodward DSLC-2 Digital Synchronizer and Load Control

Integration in brief

Block-read up to 128 holding registers from wire address 50000 for frequencies, modes, flags and alarms, and from 50100 for the 32-bit generator values and energy. To command the unit, release functions to the interface in 7645, then switch them in 7644; write setpoints to 7640-7642 and 7780.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 50010Generator frequencyINT16Generator frequencyRead
HR 50023Busbar frequencyINT16Busbar frequencyRead
HR 50032Phase Angle Generator / BusbarINT16Phase angle generator / busRead
HR 50056Sync Control StateINT16Synchronizer stateRead
HR 50057Load Control ModeINT16Load control modeRead
HR 50075Alarms 1BITMAP16Alarms 1Read
HR 50100Total generator powerINT32 ABCDTotal generator power (32-bit)Read
HR 50114Generator current 1INT32 ABCDGenerator current 1 (32-bit)Read

Enable Modbus control & writes

RS-485 (serial interface 2): set Modbus slave ID 3188 (default 1; 0 disables Modbus), baud 3170 (default 19.2 kBd), parity 3171 (default none), stop bits 3172 (default one). Network B Modbus/TCP slave ID is parameter 5451 (default 255). Release remote functions in 7645.

Communication loss & watchdog

No timeout parameter is given. On an interface connection loss the discrete-input states stay as they were; energising DI 22 'Modbus reset' returns all functions to hardware control and clears the control bits.

Byte order & addressing

Network setup

Watch out for

Woodward DSLC-2 Digital Synchronizer and Load Control Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

69 of 69 shown
Woodward DSLC-2 Digital Synchronizer and Load Control Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR7640doc 7640 (47641)Interface power factor setpoint-500 (capacitive) to 1000 to 500 (inductive); used when 7635 = Interface.INT16× 0.001Read/write
HR7641doc 7641 (47642)Interface frequency setpoint0-7000; used when parameter 7783 = Interface.UINT16× 0.01HzRead/write
HR7642doc 7642 (47643)Interface active power setpoint (base load)Positive only; used when 7634 = Interface. Manual example: 1000 kW = 1000.INT32ABCDkWRead/write
HR7644doc 7644 (47645)Discrete inputs over interfaceBit field (bits 01-16, see notes) switching functions released by 7645.UINT16Read/write
HR7645doc 7645 (47646)Release discrete inputs to interfaceSame bit list as 7644; 1 = interface controlled, 0 = hardware input.UINT16Read/write
HR7780doc 7780 (47781)Interface voltage setpoint50-650000 V; used when 7784 = Interface.UINT32ABCDVRead/write
HR50000Protocol IDReads 5200.INT16Read
HR50010Generator frequencyINT16× 0.01HzRead
HR50013Generator power factorINT16× 0.001Read
HR50023Busbar frequencyINT16× 0.01HzRead
HR50025Auxiliary busbar frequencyINT16× 0.01HzRead
HR50032Phase Angle Generator / BusbarINT16× 0.1°Read
HR50033Active Setpoint generator frequencyINT16× 0.01HzRead
HR50034Active Setpoint generator voltageINT16× 0.01%Read
HR50035Active Setpoint generator load levelINT16× 0.01%Read
HR50036Active Setpoint generator reactive powerINT16× 0.01%Read
HR50044Battery voltageINT16× 0.1VRead
HR50048Speed Biasing (AO1)INT16× 0.01%Read
HR50049AVR Biasing (AO2)INT16× 0.01%Read
HR50056Sync Control StateINT16Read0 = Off; 1 = Check mode active; 2 = Permissive mode active; 3 = Run mode active; 4 = Close Timer runs; 5 = Sync Timer runs; 6 = Breaker synchronized; 7 = Auto-Off position; 8 = Manual
HR50057Load Control ModeINT16Read0 = Inactive; 1 = Droop; 2 = At Unload Trip; 3 = Load sharing; 4 = Base load control; 5 = reserved; 6 = Process control; 7 = reserved; 8 = Peak load control (reserved); 9 = Zero power control (reserved); 10 = Load share (reserved); 11 = Process slave (reserved)
HR50058Reactive Load Control ModeINT16Read0 = Inactive; 1 = Off; 2 = Droop; 3 = VAR sharing; 4 = Reactive load control; 5 = reserved; 6 = reserved; 7 = Remote process control (reserved); 8 = (reserved); 9 = Zero power control (reserved); 10 = Reactive load share (reserved); 11 = Process slave (reserved)
HR50059Condition Flags 1BITMAP16Readbit 1 = Generator clock wise system is recognized; bit 2 = Generator counter clock wise system is recognized; bit 4 = Busbar is dead (in same segment); bit 5 = Aux. Busbar clock wise system is recognized; bit 6 = Aux. Busbar anti clock wise system is recognized; bit 10 = Busbar is ok (in same segment); bit 12 = Generator breaker is closed; bit 13 = Generator is OK; bit 15 = Generator is Dead
HR50060Condition Flags 2BITMAP16Readbit 8 = Reactive power load share is active; bit 9 = Active power load share is active; bit 10 = Dead busbar closure request active
HR50061Condition Flags 3BITMAP16Readbit 2 = Unloading generator is active; bit 6 = Closing GCB is active; bit 7 = Opening GCB is active; bit 8 = Synchronization GCB is active; bit 11 = GCB is closed; bit 12 = 3-Position Controller Volt./ReactPow lower; bit 13 = 3-Position Controller Volt./ReactPow raise
HR50067Interface Control SwitchBITMAP16Readbit 0 = Source: Synchronization GCB check switch; bit 1 = Source: Synchronization GCB permissive switch; bit 2 = Source: Synchronization GCB run switch; bit 3 = Source: CB Aux contact switch; bit 4 = Source: Raise voltage switch; bit 5 = Source: Lower voltage switch; bit 6 = Source: Base load switch; bit 7 = Source: Load/ Unload switch; bit 8 = Source: Ramp pause switch; bit 9 = Source: Raise load switch; bit 10 = Source: Lower load switch; bit 11 = Source: Process switch; bit 12 = Source: Droop switch; bit 13 = Source: Modbus reset switch; bit 14 = Source: System update switch
HR50071Relay Outputs 1BITMAP16Readbit 0 = Alarm Relay (R1); bit 1 = Load Switch Relay (R2); bit 2 = High Limit Relay (R3); bit 3 = Low Limit Relay (R4); bit 4 = Breaker Open Relay (R5); bit 5 = Breaker Close Relay (R6); bit 6 = Centralized Alarm (R7); bit 7 = Alarm 1 (R8)/3 pos.Controller f/act. Pwr raise; bit 8 = Alarm 2 (R9)/3 pos.Controller f/act. Pwr lower; bit 9 = Alarm 3 (R10); bit 10 = Voltage Raise Relay (R11); bit 11 = Voltage Lower Relay (R12)
HR50075Alarms 1BITMAP16Readbit 0 = Synchronizer Timeout; bit 1 = GCB Close Failure; bit 2 = High Load Limit; bit 3 = Low Load Limit; bit 4 = High Process Limit; bit 5 = Low Process Limit; bit 6 = Low Voltage Limit; bit 7 = High Voltage Limit; bit 8 = Voltage Range Limit; bit 9 = Communication Error NW A; bit 10 = Low Frequency Limit; bit 11 = Missing member; bit 12 = Centralized Alarms; bit 13 = GCB Open Failure; bit 14 = Deadbus closure mismatch; bit 15 = High Frequency Limit
HR50081Discrete Inputs 1BITMAP16Readbit 0 = Synchronization Check switch is active (DI1); bit 1 = Synchronization Permissive switch is active (DI2); bit 2 = Synchronization Run switch is active (DI3); bit 3 = Circuit Breaker Aux. is closed (DI4); bit 4 = Voltage Raise Switch (DI5); bit 5 = Voltage Lower Switch (DI6); bit 6 = Base Load Control Switch (DI7); bit 7 = Load/Unload Switch (DI8) (Energized=Load); bit 8 = Ramp Pause Switch (DI9); bit 9 = Load Raise Switch (DI10); bit 10 = Load Lower Switch (DI11); bit 11 = Process Control Switch (DI12)
HR50082Digital Inputs 2BITMAP16Readbit 0 = Segment connection 12 is closed (DI13); bit 1 = Segment connection 23 is closed (DI14); bit 2 = Segment connection 34 is closed (DI15); bit 3 = Segment connection 45 is closed (DI16); bit 4 = Segment connection 56 is closed (DI17); bit 5 = Segment connection 67 is closed (DI18); bit 6 = Segment connection 78 is closed (DI19); bit 7 = Segment connection 81 is closed (DI20); bit 8 = Droop (DI21); bit 9 = Modbus reset (DI22); bit 10 = System update (DI23)
HR50083Alarms 5BITMAP16Readbit 0 = Busbar mismatch; bit 1 = Phase rotation mismatch; bit 2 = Communication Error NW B; bit 3 = Network A Error; bit 4 = Network B Error; bit 5 = Devices not matched
HR50100Total generator powerINT32ABCDWRead
HR50102Total generator reactive powerINT32ABCDvarRead
HR50104Total generator apparent powerINT32ABCDVARead
HR50106Average generator Wye-VoltageINT32ABCD× 0.1VRead
HR50108Average generator Delta-VoltageINT32ABCD× 0.1VRead
HR50110Average Busbar 1 Delta-VoltageINT32ABCD× 0.1VRead
HR50112Average generator CurrentINT32ABCD× 0.001ARead
HR50114Generator current 1INT32ABCD× 0.001ARead
HR50116Generator current 2INT32ABCD× 0.001ARead
HR50118Generator current 3INT32ABCD× 0.001ARead
HR50120Generator voltage L1-L2INT32ABCD× 0.1VRead
HR50122Generator voltage L2-L3INT32ABCD× 0.1VRead
HR50124Generator voltage L3-L1INT32ABCD× 0.1VRead
HR50126Generator voltage L1-NINT32ABCD× 0.1VRead
HR50128Generator voltage L2-NINT32ABCD× 0.1VRead
HR50130Generator voltage L3-NINT32ABCD× 0.1VRead
HR50132Generator active power 1-NINT32ABCDWRead
HR50134Generator active power 2-NINT32ABCDWRead
HR50136Generator active power 3-NINT32ABCDWRead
HR50138Busbar voltage (L1-N) L1-L2INT32ABCD× 0.1VRead
HR50140Average Aux.busbar Wye-VoltageINT32ABCD× 0.1VRead
HR50142Average Aux.busbar Delta-VoltageINT32ABCD× 0.1VRead
HR50144Aux.busbar voltage L1-L2INT32ABCD× 0.1VRead
HR50146Aux.busbar voltage L2-L3INT32ABCD× 0.1VRead
HR50148Aux.busbar voltage L3-L1INT32ABCD× 0.1VRead
HR50150Aux.busbar voltage L1-NINT32ABCD× 0.1VRead
HR50152Aux.busbar voltage L2-NINT32ABCD× 0.1VRead
HR50154Aux.busbar voltage L3-NINT32ABCD× 0.1VRead
HR50160Load referenceINT32ABCD× 0.1kWRead
HR50162Reactive load referenceINT32ABCD× 0.1kvarRead
HR50164Process reference inputINT32ABCD× 0.1Read
HR50166Process signal inputINT32ABCD× 0.1Read
HR50168Process reference toolkitINT32ABCD× 0.1Read
HR50170Remote load reference inputINT32ABCD× 0.1kWRead
HR50174Gen.pos.act.energyINT32ABCD× 0.01MWhRead
HR50178Gen.pos.react.energyINT32ABCD× 0.01MvarhRead
HR50180Gen.neg.react.energyINT32ABCD× 0.01MvarhRead
HR50182Hours of operationINT32ABCD× 0.01hRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Woodward DSLC-2 Digital Synchronizer and Load Control

What Modbus registers does the Woodward DSLC-2 Digital Synchronizer and Load Control have?

This map lists 69 registers: 69 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Woodward DSLC-2 Digital Synchronizer and Load Control Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The 5200 table prints both the bus address (50000) and the Modicon address (450001); this map records and sends the bus address. Parameters use Modicon 40000 + (parameter ID + 1), so parameter 7642 is Modicon 47643 = wire address 7642; the manual's ModScan32 screenshots for 7642 (address 7643, 1-based) and 7640 (7641) confirm this. The worked examples print '407642' and '40509', which are typos that do not follow the manual's own rule.

What byte order does the Woodward DSLC-2 Digital Synchronizer and Load Control use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Woodward DSLC-2 Digital Synchronizer and Load Control?

Start with HR 50010 Generator frequency (Generator frequency); HR 50023 Busbar frequency (Busbar frequency); HR 50032 Phase Angle Generator / Busbar (Phase angle generator / bus); HR 50056 Sync Control State (Synchronizer state); HR 50057 Load Control Mode (Load control mode); HR 50075 Alarms 1 (Alarms 1); HR 50100 Total generator power (Total generator power (32-bit)); HR 50114 Generator current 1 (Generator current 1 (32-bit)).

How do I enable Modbus control of the Woodward DSLC-2 Digital Synchronizer and Load Control?

RS-485 (serial interface 2): set Modbus slave ID 3188 (default 1; 0 disables Modbus), baud 3170 (default 19.2 kBd), parity 3171 (default none), stop bits 3172 (default one). Network B Modbus/TCP slave ID is parameter 5451 (default 255). Release remote functions in 7645.

What happens when the Woodward DSLC-2 Digital Synchronizer and Load Control loses Modbus communication?

No timeout parameter is given. On an interface connection loss the discrete-input states stay as they were; energising DI 22 'Modbus reset' returns all functions to hardware control and clears the control bits.

Where is the official Woodward DSLC-2 Digital Synchronizer and Load Control Modbus documentation?

The source is DSLC-2 Digital Synchronizer and Load Control - Manual (37443J), revision 2022-02-08, published free by Woodward at https://www.woodward.com/products/wp-content/uploads/sites/3/2024/08/37443_J.pdf.

More Woodward Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: DSLC-2 Digital Synchronizer and Load Control - Manual · 37443J · rev. 2022-02-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.