Easy Modbus
  1. Home
  2. Modbus register maps
  3. Woodward
  4. easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)

Generator controller · Modbus register map

Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500) Modbus register map

Updated 17 November 2026

Short answer

The easYgen-2000 series (2200/2300/2500) is Woodward's genset controller for single and paralleled sets. It is a Modbus RTU slave: data protocol 5100 is block-read from Modicon 450001, and parameters 503-510 take remote start/stop, acknowledge and interface setpoints. This map covers voltages, currents, frequencies, energy and hours, the operating state, control and alarm bit words, J1939 speed/pressure/hours and the remote-control parameters.

This page lists 71 Modbus registers for the Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Woodward’s own free documentation (linked below) and checked against it.

Manufacturer
Woodward
Model
easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)
Equipment type
Generator controller
Registers
71 (5 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
easYgen-2200, easYgen-2300, easYgen-2500, easYgen-2000 Series
Source document
easYgen-2200/2300/2500 Genset Control - Manual · 37535D · rev. 2016-08-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)

Integration in brief

Block-read up to 128 holding registers from wire address 50000. Start or stop by writing 0 and then bit 0 (start) or bit 1 (stop) to parameter 503; acknowledge with two rising edges of bit 4.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 50002Control modeUINT16Control mode AUTO/STOP/MANUALRead
HR 50018Operation mode / statusUINT16Operating stateRead
HR 50045Alarm classes latchedBITMAP16Latched alarm classesRead
HR 50006Gen. frequencyUINT16Generator frequencyRead
HR 50052Gen. voltage L1-L2UINT32 ABCDGenerator voltage L1-L2Read
HR 50034Gen. current 1UINT32 ABCDGenerator current 1Read
HR 50021Battery voltageUINT16Battery voltageRead
HR 503Remote control word 1BITMAP16Remote start / stop / acknowledgeRead/write

Enable Modbus control & writes

Enable Modbus on the serial interface and set its slave ID and baud in the controller's interface parameters. Include 04.13 Remote request in the LogicsManager start condition for remote starts.

Byte order & addressing

Network setup

Watch out for

Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

71 of 71 shown
Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR503doc 503 (40504)Remote control word 1Rising edges start, stop and acknowledge.BITMAP16Read/writebit 0 = Start (rising edge); bit 1 = Stop (rising edge); bit 4 = Acknowledge (rising edge, twice)
HR507doc 507 (40508)Remote active power setpointINTEGER 32 in 1/10 kW; used with data source 05.06.INT32ABCD× 0.1kWRead/write
HR508doc 508 (40509)Remote power factor setpointINTEGER 16, -710 to 1000 to 710; used with data source 05.12.INT16× 0.001Read/write
HR509doc 509 (40510)Remote frequency setpoint0-7000; used when AnalogManager source 05.03 is selected.UINT16× 0.01HzRead/write
HR510doc 510 (40511)Remote voltage setpoint50-650000 V; used with data source 05.09.UINT32ABCDVRead/write
HR50000doc 450001Protocol IDReads 5100.UINT16Read
HR50001doc 450002Pickup speedUINT16rpmRead
HR50002doc 450003Control modeMask the low 4 bits (000Fh).UINT16Read1 = AUTO; 2 = STOP; 4 = MANUAL
HR50004doc 450005Av. Gen. Wye-VoltageUINT32ABCD× 0.1VRead
HR50006doc 450007Gen. frequencyUINT16× 0.01HzRead
HR50007doc 450008Av. Gen. Delta-VoltageUINT32ABCD× 0.1VRead
HR50009doc 450010Mains / Busbar frequencyUINT16× 0.01HzRead
HR50010doc 450011Av. Mains / Busbar Wye-VoltageUINT32ABCD× 0.1VRead
HR50013doc 450014Av. Mains / Busbar Delta-VoltageUINT32ABCD× 0.1VRead
HR50015doc 450016Engine, number of start requestsUINT16Read
HR50018doc 450019Operation mode / statusCurrent operating state code.UINT16Read13200 = Auxiliary services postrun; 13201 = Aux. services prerun; 13202 = Critical mode; 13203 = Motor Stop; 13204 = Cool down; 13205 = Mains settling; 13206 = Engine Start; 13207 = Start – Pause; 13208 = Preglow; 13209 = GCB dead bus close; 13210 = MCB dead bus close; 13211 = Emergency run; 13212 = Turning; 13213 = Ignition; 13214 = Crank protect; 13215 = Emergency/Critical; 13216 = Idle run active; 13250 = Gen. stable time; 13251 = In operation; 13252 = Power limited prerun; 13253 = AUTO mode ready; 13254 = Ramp to rated; 13255 = GCB open; 13256 = Unloading generator; 13257 = MCB open; 13258 = Loading generator; 13259 = Synchronization GCB; 13260 = Synchronization MCB; 13261 = GCB -> MCB Delay; 13262 = MCB -> GCB Delay; 13263 = Start w/o Load; 13264 = Unloading mains; 13265 = Synchronization permissive; 13266 = Synchronization check; 13267 = Synchronization off; 13281 = Derating active
HR50021doc 450022Battery voltageUINT16× 0.1VRead
HR50022doc 450023Av. Mains CurrentUINT32ABCD× 0.001ARead
HR50025doc 450026Av. Gen. CurrentUINT32ABCD× 0.001ARead
HR50028doc 450029Meas. ground currentUINT32ABCD× 0.001ARead
HR50031doc 450032Calculated ground currentUINT32ABCD× 0.001ARead
HR50033doc 450034Control bits 1BITMAP16Readbit 1 = Auxiliary services postrun is active; bit 2 = Auxiliary services prerun is active; bit 3 = Engine is released (speed governor is enabled); bit 4 = Critical mode is active in automatic mode; bit 5 = Engine start is requested; bit 6 = Breaker delay timer has expired; bit 7 = Engine Monitoring delay timer has expired; bit 8 = Auxiliary services generally active; bit 9 = Cooldown is active; bit 13 = Start without closing GCB; bit 14 = Idle mode active; bit 15 = Idle mode active (suppresses undervoltage/underfrequency monitoring)
HR50034doc 450035Gen. current 1UINT32ABCD× 0.001ARead
HR50036doc 450037Control bits 2BITMAP16Readbit 0 = Increment Engine Start Counter; bit 3 = The genset runs mains parallel; bit 5 = Stopping Magnet is active; bit 11 = Emergency mode is currently active; bit 12 = Mains settling timer is running; bit 13 = Preglow / Ignition is active; bit 14 = Operating Magnet / Gasrelay is active; bit 15 = Crank (Starter) is active
HR50037doc 450038Gen. current 2UINT32ABCD× 0.001ARead
HR50039doc 450040Control bits 3BITMAP16Readbit 0 = Power limited prerun; bit 1 = Unloading mains is active; bit 2 = Unloading generator is active; bit 3 = Closing MCB is active; bit 4 = Opening MCB is active; bit 5 = Synchronization MCB is active; bit 6 = Closing GCB is active; bit 7 = Opening GCB is active; bit 8 = Synchronization GCB is active; bit 10 = MCB is closed; bit 11 = GCB is closed; bit 12 = 3-Position Controller Volt./ReactPow lower; bit 13 = 3-Position Controller Volt./ReactPow raise; bit 14 = 3-Position Controller Freq./Power lower; bit 15 = 3-Position Controller Freq./Power raise
HR50040doc 450041Gen. current 3UINT32ABCD× 0.001ARead
HR50042doc 450043Control bits 4BITMAP16Readbit 1 = The Critical Mode Postrun is active; bit 2 = LDSS: The LDSS function is active; bit 3 = LDSS: Minimum Running Time is active; bit 4 = LDSS: The Engine is stopped, if possible; bit 5 = LDSS: The Engine is stopped; bit 6 = LDSS: The Engine is started; bit 7 = Generator with a closed GCB is requested; bit 8 = Reactive power load share is acitve; bit 9 = Active power load share is acitve; bit 10 = Dead busbar closure request for GCB or MCB
HR50043doc 450044Mains current L1UINT32ABCD× 0.001ARead
HR50045doc 450046Alarm classes latchedBITMAP16Readbit 0 = Alarm class A latched; bit 1 = Alarm class B latched; bit 2 = Alarm class C latched; bit 3 = Alarm class D latched; bit 4 = Alarm class E latched; bit 5 = Alarm class F latched
HR50052doc 450053Gen. voltage L1-L2UINT32ABCD× 0.1VRead
HR50055doc 450056Gen. voltage L1-NUINT32ABCD× 0.1VRead
HR50058doc 450059Gen. voltage L2-L3UINT32ABCD× 0.1VRead
HR50061doc 450062Gen. voltage L2-NUINT32ABCD× 0.1VRead
HR50063doc 450064Alarms 1 latched (engine)BITMAP16Readbit 0 = CANopen error at CAN Interface 1; bit 1 = Mainten. hours exceeded latched; bit 2 = Mainten. days exceeded latched; bit 3 = Start fail latched; bit 4 = CAN-Fault J1939 latched; bit 5 = MCB fail to open latched; bit 6 = MCB fail to close latched; bit 7 = GCB fail to open latched; bit 8 = GCB fail to close latched; bit 9 = Shutdwn malfunct. latched; bit 10 = Speed/freq.mism. Latched; bit 11 = Unintended stop latched; bit 12 = Underspeed 2 latched; bit 13 = Underspeed 1 latched; bit 14 = Overspeed 2 latched; bit 15 = Overspeed 1 latched
HR50064doc 450065Gen. voltage L3-L1UINT32ABCD× 0.1VRead
HR50066doc 450067Alarms 2 latchedBITMAP16Readbit 0 = Amber warning lamp latched; bit 1 = Red stop lamp latched; bit 2 = EEPROM failure latched; bit 3 = Missing members on CAN; bit 4 = Parameter Alignment; bit 5 = CANopen error at CAN Interface 2; bit 11 = Ph.rotation mismatch latched; bit 12 = Charge alt. low voltage (D+) latched; bit 14 = MCB syn. timeout latched; bit 15 = GCB syn. timeout latched
HR50067doc 450068Gen. voltage L3-NUINT32ABCD× 0.1VRead
HR50070doc 450071Mains / Busbar voltage L1-L2UINT32ABCD× 0.1VRead
HR50072doc 450073Generator alarms latchedBITMAP16Readbit 1 = Gen. Overload IOP 2 latched; bit 2 = Gen. Overload IOP 1 latched; bit 3 = Gen. Rv/Rd pow.2 latched; bit 4 = Gen. Rv/Rd pow.1 latched; bit 5 = Gen. overcurr. 3 latched; bit 6 = Gen. overcurr. 2 latched; bit 7 = Gen. overcurr. 1 latched; bit 8 = Gen.undervolt. 2 latched; bit 9 = Gen.undervolt. 1 latched; bit 10 = Gen.overvolt. 2 latched; bit 11 = Gen.overvolt. 1 latched; bit 12 = Gen.underfreq. 2 latched; bit 13 = Gen.underfreq. 1 latched; bit 14 = Gen.overfreq. 2 latched; bit 15 = Gen.overfreq. 1 latched
HR50073doc 450074Mains / Busbar voltage L1-NUINT32ABCD× 0.1VRead
HR50075doc 450076Generator alarms 1 latchedBITMAP16Readbit 0 = Gen. underexcited 2 latched; bit 1 = Gen. underexcited 1 latched; bit 2 = Gen. overexcited 2 latched; bit 3 = Gen. overexcited 1 latched; bit 4 = Gen. Overload MOP 2 latched; bit 5 = Gen. Overload MOP 1 latched; bit 6 = Operating range failed, latched; bit 7 = Inv.time ov.curr. Latched; bit 8 = Gen. unloading fault Latched; bit 9 = Gen act.pwr mismatch Latched; bit 10 = Gen. phase rot. misw. Latched; bit 11 = Ground fault 2 latched; bit 12 = Ground fault 1 latched; bit 13 = Gen. Asymmetry latched; bit 14 = Unbal. load 2 latched; bit 15 = Unbal. load 1 latched
HR50076doc 450077Mains / Busbar voltage L2-L3UINT32ABCD× 0.1VRead
HR50078doc 450079Mains / busbar alarms latchedBITMAP16Readbit 2 = Mains phase rot. Miswired latched; bit 6 = Mains / Busbar decoupling latched; bit 7 = Mains / Busbar phaseshift latched; bit 8 = Mains / Busbar un.volt. 2 latched; bit 9 = Mains / Busbar un.volt. 1 latched; bit 10 = Mains / Busbar ov.volt. 2 latched; bit 11 = Mains / Busbar ov.volt. 1 latched; bit 12 = Mains / Busbar un.freq. 2 latched; bit 13 = Mains / Busbar un.freq. 1 latched; bit 14 = Mains / Busbar ov.freq. 2 latched; bit 15 = Mains / Busbar ov.freq. 1 latched
HR50079doc 450080Mains / Busbar voltage L2-NUINT32ABCD× 0.1VRead
HR50081doc 450082Mains alarms 2 latchedBITMAP16Readbit 0 = QV monitoring 2; bit 1 = QV monitoring 1; bit 3 = Mns. Volt increase; bit 5 = Mns. Time-dep. Volt.; bit 6 = Mns act.pwr mismatch latched; bit 7 = Mains df/dt
HR50082doc 450083Mains / Busbar voltage L3-L1UINT32ABCD× 0.1VRead
HR50084doc 450085Digital inputs 1-8 alarms latchedBITMAP16Readbit 8 = State Digital Input 1 latched; bit 9 = State Digital Input 2 latched; bit 10 = State Digital Input 3 latched; bit 11 = State Digital Input 4 latched; bit 12 = State Digital Input 5 latched; bit 13 = State Digital Input 6 latched; bit 14 = State Digital Input 7 latched; bit 15 = State Digital Input 8 latched
HR50085doc 450086Mains / Busbar voltage L3-NUINT32ABCD× 0.1VRead
HR50087doc 450088Digital inputs 9-10 alarms latchedBITMAP16Readbit 14 = State Digital Input 9 latched; bit 15 = State Digital Input 10 latched
HR50088doc 450089Gen. real energyUINT32ABCD× 0.01MWhRead
HR50090doc 450091External digital inputs alarms latchedBITMAP16Readbit 0 = State external Digital Input 1 latched; bit 1 = State external Digital Input 2 latched; bit 2 = State external Digital Input 3 latched; bit 3 = State external Digital Input 4 latched; bit 4 = State external Digital Input 5 latched; bit 5 = State external Digital Input 6 latched; bit 6 = State external Digital Input 7 latched; bit 7 = State external Digital Input 8 latched; bit 8 = State external Digital Input 9 latched; bit 9 = State external Digital Input 10 latched; bit 10 = State external Digital Input 11 latched; bit 11 = State external Digital Input 12 latched; bit 12 = State external Digital Input 13 latched; bit 13 = State external Digital Input 14 latched; bit 14 = State external Digital Input 15 latched; bit 15 = State external Digital Input 16 latched
HR50091doc 450092Gen. hours of operationUINT32ABCD× 0.01hRead
HR50093doc 450094Flexible limits 1-16 latchedBITMAP16Readbit 0 = Alarm flexible limit 1 latched; bit 1 = Alarm flexible limit 2 latched; bit 2 = Alarm flexible limit 3 latched; bit 3 = Alarm flexible limit 4 latched; bit 4 = Alarm flexible limit 5 latched; bit 5 = Alarm flexible limit 6 latched; bit 6 = Alarm flexible limit 7 latched; bit 7 = Alarm flexible limit 8 latched; bit 8 = Alarm flexible limit 9 latched; bit 9 = Alarm flexible limit 10 latched; bit 10 = Alarm flexible limit 11 latched; bit 11 = Alarm flexible limit 12 latched; bit 12 = Alarm flexible limit 13 latched; bit 13 = Alarm flexible limit 14 latched; bit 14 = Alarm flexible limit 15 latched; bit 15 = Alarm flexible limit 16 latched
HR50096doc 450097Battery alarms latchedBITMAP16Readbit 0 = Batt.undervolt.1 latched; bit 1 = Batt.overvolt.1 latched; bit 2 = Batt.undervolt.2 latched; bit 3 = Batt.overvolt.2 latched
HR50097doc 450098Analog input wire break latchedBITMAP16Readbit 1 = Analog inp. 1, wire break or shortcut latched; bit 2 = Analog inp. 2, wire break or shortcut latched; bit 3 = Analog inp. 3, wire break or shortcut latched; bit 4 = Analog inp. 4, wire break or shortcut latched
HR50098doc 450099Relay outputs 1-6BITMAP16Readbit 10 = Relay-Output 6; bit 11 = Relay-Output 5; bit 12 = Relay-Output 4; bit 13 = Relay-Output 3; bit 14 = Relay-Output 2; bit 15 = Relay-Output 1 (inverted)
HR50099doc 450100Relay outputs 7-11BITMAP16Readbit 11 = Relay-Output 11; bit 12 = Relay-Output 10; bit 13 = Relay-Output 9; bit 14 = Relay-Output 8; bit 15 = Relay-Output 7
HR50100doc 450101External CAN-I/O relays 1-16BITMAP16Readbit 0 = Output to external CAN-I/O Relay 1; bit 1 = Output to external CAN-I/O Relay 2; bit 2 = Output to external CAN-I/O Relay 3; bit 3 = Output to external CAN-I/O Relay 4; bit 4 = Output to external CAN-I/O Relay 5; bit 5 = Output to external CAN-I/O Relay 6; bit 6 = Output to external CAN-I/O Relay 7; bit 7 = Output to external CAN-I/O Relay 8; bit 8 = Output to external CAN-I/O Relay 9; bit 9 = Output to external CAN-I/O Relay 10; bit 10 = Output to external CAN-I/O Relay 11; bit 11 = Output to external CAN-I/O Relay 12; bit 12 = Output to external CAN-I/O Relay 13; bit 13 = Output to external CAN-I/O Relay 14; bit 14 = Output to external CAN-I/O Relay 15; bit 15 = Output to external CAN-I/O Relay 16
HR50102doc 450103Setpoint frequencyUINT16× 0.01HzRead
HR50106doc 450107Setpoint voltageUINT32ABCDVRead
HR50183doc 450184Engine Speed (j1939-EEC1)UINT16rpmRead
HR50185doc 450186Engine Oil Pressure (j1939-EFL/P1)UINT16kPaRead
HR50187doc 450188Total engine hours (j1939-HOURS)UINT32ABCDhRead
HR50190doc 450191Fuel Rate (j1939-LFE)UINT16× 0.1L/hRead
HR50191doc 450192Coolant Level (j1939-EFL/P1)UINT16× 0.1%Read
HR50192doc 450193Throttle position (j1939-EEC2)UINT16× 0.1%Read
HR50193doc 450194Load at current Speed (j1939-EEC2)UINT16%Read
HR50194doc 450195Engine oil level (j1939-EFL/P1)UINT16× 0.1%Read
HR50195doc 450196Boost pressure (j1939-IC1)UINT16kPaRead
HR50197doc 450198Barometric Pressure (j1939-AMB)UINT16× 0.1kPaRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)

What Modbus registers does the Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500) have?

This map lists 71 registers: 71 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The 5100 table prints the Modicon address (450001) and a start address one lower (450000); the manual says 450001 may become bus address 50000, so the wire address is the Modicon number minus 400001. Parameters use Modicon 40000 + (parameter ID + 1): parameter 503 is 40504 = wire address 503. The manual says some PC tools need a shift of one (504).

What byte order does the Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)?

Start with HR 50002 Control mode (Control mode AUTO/STOP/MANUAL); HR 50018 Operation mode / status (Operating state); HR 50045 Alarm classes latched (Latched alarm classes); HR 50006 Gen. frequency (Generator frequency); HR 50052 Gen. voltage L1-L2 (Generator voltage L1-L2); HR 50034 Gen. current 1 (Generator current 1); HR 50021 Battery voltage (Battery voltage); HR 503 Remote control word 1 (Remote start / stop / acknowledge).

How do I enable Modbus control of the Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)?

Enable Modbus on the serial interface and set its slave ID and baud in the controller's interface parameters. Include 04.13 Remote request in the LogicsManager start condition for remote starts.

Where is the official Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500) Modbus documentation?

The source is easYgen-2200/2300/2500 Genset Control - Manual (37535D), revision 2016-08-02, published free by Woodward at https://www.woodward.com/products/wp-content/uploads/sites/3/2024/08/37535_D.pdf.

More Woodward Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: easYgen-2200/2300/2500 Genset Control - Manual · 37535D · rev. 2016-08-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.