Generator controller · Modbus register map

Kohler Decision-Maker 550 generator set controller (application code 2.10+) Modbus register map

Updated 17 November 2026

Short answer

The Decision-Maker 550 is a Kohler generator set controller. It answers Modbus RTU directly with a holding-register map of generator electrical output, engine status from the ECM or local senders, run-time and maintenance counters, system setpoints, remote timed-run commands and a 16-word system event stack. This map covers the electrical and engine blocks, master switch and mode status, run-time counters, key system settings and the remote functions.

This page lists 63 Modbus registers for the Kohler Decision-Maker 550 generator set controller (application code 2.10+) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.

Manufacturer
Kohler
Model
Decision-Maker 550 generator set controller (application code 2.10+)
Equipment type
Generator controller
Registers
63 (8 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Application code 2.10 or higher
Also known as
Decision-Maker 550, DEC 550, Kohler 550 controller
Source document
Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Kohler Decision-Maker 550 generator set controller (application code 2.10+)

Integration in brief

Read 400001-400028 for generator output and 400033-400047 for engine data in one or two FC 03 requests, check 400079/400080 for switch position and programming mode, and use 401306/401307 for remote timed starts once the controller is in remote programming mode.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0L1-L2 VoltageUINT16L1-L2 voltageRead
HR 6L1 CurrentUINT16L1 currentRead
HR 9FrequencyUINT16FrequencyRead
HR 10Total kWUINT16Total kWRead
HR 34Engine SpeedUINT16Engine speedRead
HR 35Local Battery VoltageUINT16Battery voltageRead
HR 78Master Switch PositionUINT16Master switch positionRead
HR 1499System Events word 1 (events 0-15)BITMAP16System event stack word 1Read

Enable Modbus control & writes

On the controller set the network address (unique per unit) and the baud rate (9600 or 19200) in the communications menu. Writes require the controller's programming mode to be Remote; otherwise writes are rejected with exception 01.

Byte order & addressing

Network setup

Watch out for

Kohler Decision-Maker 550 generator set controller (application code 2.10+) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

63 of 63 shown
Kohler Decision-Maker 550 generator set controller (application code 2.10+) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 400001L1-L2 VoltageUINT16VRead
HR1doc 400002L2-L3 VoltageUINT16VRead
HR2doc 400003L3-L1 VoltageUINT16VRead
HR3doc 400004L1-L0 VoltageUINT16VRead
HR4doc 400005L2-L0 VoltageUINT16VRead
HR5doc 400006L3-L0 VoltageUINT16VRead
HR6doc 400007L1 CurrentUINT16ARead
HR7doc 400008L2 CurrentUINT16ARead
HR8doc 400009L3 CurrentUINT16ARead
HR9doc 400010FrequencyUINT16× 0.01HzRead
HR10doc 400011Total kWUINT16kWRead
HR11doc 400012Percent of Rated kWUINT16%Read
HR12doc 400013Total Power FactorSigned, x100.INT16× 0.01Read
HR13doc 400014L1 kWUINT16kWRead
HR14doc 400015L1 Power FactorSigned, x100.INT16× 0.01Read
HR15doc 400016L2 kWUINT16kWRead
HR16doc 400017L2 Power FactorSigned, x100.INT16× 0.01Read
HR17doc 400018L3 kWUINT16kWRead
HR18doc 400019L3 Power FactorSigned, x100.INT16× 0.01Read
HR19doc 400020Total kVARSigned.INT16kvarRead
HR20doc 400021L1 kVARSigned.INT16kvarRead
HR21doc 400022L2 kVARSigned.INT16kvarRead
HR22doc 400023L3 kVARSigned.INT16kvarRead
HR23doc 400024Total kVAUINT16kVARead
HR24doc 400025L1 kVAUINT16kVARead
HR25doc 400026L2 kVAUINT16kVARead
HR26doc 400027L3 kVAUINT16kVARead
HR27doc 400028Current Lead/LagTwo bits per item: 10 = leading, 01 = lagging.BITMAP16Readbit 0 = Total current lagging (bits 0-1 = 01); bit 1 = Total current leading (bits 0-1 = 10); bit 2 = L1 lagging (bits 2-3 = 01); bit 3 = L1 leading (bits 2-3 = 10); bit 4 = L2 lagging (bits 4-5 = 01); bit 5 = L2 leading (bits 4-5 = 10); bit 6 = L3 lagging (bits 6-7 = 01); bit 7 = L3 leading (bits 6-7 = 10)
HR32doc 400033Oil PressurekPa or psi per 400139. ECM: 0x7FD6 = unavailable, 0x7FFF = out of range.UINT16kPaRead
HR33doc 400034Coolant Temperature°C or °F per 400139. ECM: 0x7FD6 = unavailable, 0x7FFF = out of range.INT16°CRead
HR34doc 400035Engine SpeedECM data: 0x7FD6 = unavailable, 0x7FFF = out of range.UINT16rpmRead
HR35doc 400036Local Battery Voltagex10. ECM data: 0x7FD6 = unavailable, 0x7FFF = out of range.UINT16× 0.1VRead
HR36doc 400037Fuel PressureDDEC/MDEC/ADEC engines only. kPa or psi.UINT16kPaRead
HR37doc 400038Fuel TemperatureDDEC/MDEC/ADEC engines only.INT16°CRead
HR42doc 400043Lube Oil TemperatureDDEC/MDEC/ADEC/Waukesha only.INT16°CRead
HR46doc 400047ECM Battery Voltagex10. DDEC/MDEC/ADEC only.UINT16× 0.1VRead
HR47doc 40048ECM StatusPrinted as 40048 in the table.UINT16Read0 = DDEC-equipped; 1 = Non-ECM; 2 = MDEC/ADEC-equipped
HR50doc 400051MDEC/ADEC Fault CodeNumeric fault code, MDEC/ADEC only.UINT16Read
HR60doc 400061Analog Input 00 (Battery Voltage)UINT16VRead
HR76doc 400077Digital Input Status word 1Inputs 0-15.BITMAP16Readbit 0 = Remote start contacts; bit 1 = Emergency stop; bit 2 = Low coolant level; bit 3 = Digital input 1; bit 4 = Digital input 2; bit 5 = Digital input 3; bit 6 = Digital input 4; bit 7 = Digital input 5; bit 8 = Digital input 6; bit 9 = Digital input 7; bit 10 = Digital input 8; bit 11 = Digital input 9; bit 12 = Digital input 10; bit 13 = Digital input 11; bit 14 = Digital input 12; bit 15 = Digital input 13
HR77doc 400078Digital Input Status word 2 / option flagsBITMAP16Readbit 0 = Digital input 14; bit 1 = Digital input 15; bit 2 = Digital input 16; bit 3 = Digital input 17; bit 4 = Digital input 18; bit 5 = Digital input 19; bit 6 = Digital input 20; bit 7 = Digital input 21; bit 8 = DDEC flag; bit 9 = MDEC/ADEC flag; bit 10 = Tier 1 flag; bit 11 = Waukesha flag
HR78doc 400079Master Switch PositionUINT16Read0 = Error; 1 = Auto; 2 = Off; 3 = Run
HR79doc 400080Programming Mode StatusUINT16Read1 = Off; 2 = Local; 3 = Remote
HR83doc 400084Total Number of StartsUINT16Read
HR84doc 400085Total Run Timex100, low word first.UINT32CDAB× 0.01hRead
HR86doc 400087Total Run Time Loadedx100, low word first.UINT32CDAB× 0.01hRead
HR88doc 400089Total Run Time Unloadedx100, low word first.UINT32CDAB× 0.01hRead
HR90doc 400091Total Run Time kW HrsLow word first.UINT32CDABkWhRead
HR92doc 400093RTSM Total HrsRun time since maintenance, x100, low word first.UINT32CDAB× 0.01hRead
HR98doc 400099RTSM kW HrsSince maintenance, low word first.UINT32CDABkWhRead
HR107doc 400108Last Run Lengthx100.UINT16× 0.01hRead
HR111doc 400112Is Timed Run ActiveUINT16Read0 = False; 1 = True
HR125doc 400126System VoltageSetpoint.UINT16VRead/write
HR126doc 400127System FrequencySetpoint.UINT16HzRead/write
HR127doc 400128System PhaseUINT16Read/write1 = 3 phase delta; 2 = 3 phase wye; 3 = Single phase
HR128doc 400129kW RatingUINT16kWRead/write
HR138doc 400139Metric UnitsSets metric or English units for engine values.UINT16Read/write0 = False; 1 = True
HR140doc 400141Rated CurrentUINT16ARead
HR1305doc 401306Start Timed RunWrite 1 to start a timed run.UINT16Write0 = No start; 1 = Start
HR1306doc 401307Stop Timed RunWrite 1 to stop a timed run.UINT16Write0 = No stop; 1 = Stop
HR1308doc 401309Remote Fault ResetUINT16Write0 = No reset; 1 = Reset
HR1499doc 401500System Events word 1 (events 0-15)Read the whole 16-word stack 401500-401515 in one request.BITMAP16Read
HR9998doc 409999Device ID20 = Decision-Maker 550.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Kohler Decision-Maker 550 generator set controller (application code 2.10+)

What Modbus registers does the Kohler Decision-Maker 550 generator set controller (application code 2.10+) have?

This map lists 63 registers: 63 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Kohler Decision-Maker 550 generator set controller (application code 2.10+) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 6-digit holding-register references (400001 = first holding register, 409999 = register 49999 in 5-digit form), so 400001 is wire address 0 and 401306 is wire address 1305.

What byte order does the Kohler Decision-Maker 550 generator set controller (application code 2.10+) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Kohler Decision-Maker 550 generator set controller (application code 2.10+)?

Start with HR 0 L1-L2 Voltage (L1-L2 voltage); HR 6 L1 Current (L1 current); HR 9 Frequency (Frequency); HR 10 Total kW (Total kW); HR 34 Engine Speed (Engine speed); HR 35 Local Battery Voltage (Battery voltage); HR 78 Master Switch Position (Master switch position); HR 1499 System Events word 1 (events 0-15) (System event stack word 1).

How do I enable Modbus control of the Kohler Decision-Maker 550 generator set controller (application code 2.10+)?

On the controller set the network address (unique per unit) and the baud rate (9600 or 19200) in the communications menu. Writes require the controller's programming mode to be Remote; otherwise writes are rejected with exception 01.

Where is the official Kohler Decision-Maker 550 generator set controller (application code 2.10+) Modbus documentation?

The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.

More Kohler Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.