- Home
- Modbus register maps
- Kohler
- MPAC 1500 automatic transfer switch controller
Transfer switch · Modbus register map
Kohler MPAC 1500 automatic transfer switch controller Modbus register map
Updated 17 November 2026
The MPAC 1500 is a Kohler automatic transfer switch controller. Its Modbus map gives normal (N) and emergency (E) source voltages and frequencies, load current, contactor position and source availability, transition mode, time-delay status, accessory and I/O states, transfer statistics and write-only test and manual-operation commands. This map covers the monitoring block, nominal ratings, transition mode, I/O and accessory status, maintenance counters and the command registers.
This page lists 48 Modbus registers for the Kohler MPAC 1500 automatic transfer switch controller — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.
- Manufacturer
- Kohler
- Model
- MPAC 1500 automatic transfer switch controller
- Equipment type
- Transfer switch
- Registers
- 48 (10 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
Integration notes: Kohler MPAC 1500 automatic transfer switch controller
Poll 40001-40019 in one FC 03 read for contactor position, source availability, both sources' voltages and frequencies and load current. Use 41350 bit commands for remote tests and peak shave, and 41312-41319 for transfer statistics.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | System Overview | BITMAP16 | Contactor position and source availability | Read |
| HR 7 | Source N L1-L2 Voltage | UINT16 | Normal source L1-L2 voltage | Read |
| HR 10 | Source E L1-L2 Voltage | UINT16 | Emergency source L1-L2 voltage | Read |
| HR 13 | Source N Frequency | UINT16 | Normal source frequency | Read |
| HR 14 | Source E Frequency | UINT16 | Emergency source frequency | Read |
| HR 15 | Current L1 | UINT16 | Load current L1 | Read |
| HR 741 | Accessory Status | BITMAP16 | Accessory status (tests, peak shave) | Read |
Enable Modbus control & writes
On the controller's communications setup enable Modbus Server Port 1/Port 2 (serial) or Modbus Server TCP (Ethernet), set each port's address (1-247) and baud rate (9600, 19200 or 57600), and for TCP the unit ID, IP address and subnet mask.
Byte order & addressing
- Each serial port needs its own Modbus address.
- Counters in 41300-41311 are high word first, unlike the LSW-first LONG type used by Kohler generator controllers.
- 40045 packs the normal-source rotation in the high byte and the emergency-source rotation in the low byte.
Network setup
- Serial format is 8 data bits, no parity, 1 stop bit.
- Register 49999 returns 23 (0x17) for the MPAC 1500.
Watch out for
- The general exception table caps reads at 50 registers and writes at 16.
- Bit 7 of 41350 forces the switch to OFF; use with care on a live load.
Kohler MPAC 1500 automatic transfer switch controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | System Overview | Contactor position, preferred source and source availability. | BITMAP16 | Read | bit 0 = Contactor position bit 0 (bits 0-1: 00 = off, 01 = normal, 10 = emergency, 11 = fault); bit 1 = Contactor position bit 1; bit 2 = Preferred source: 0 = source 1, 1 = source 2; bit 3 = Bits 3-12: top event on the warning stack; bit 13 = Preferred source available; bit 14 = Standby source available | |||
| HR | 1doc 40002 | Source N L1-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 2doc 40003 | Source N L2-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 3doc 40004 | Source N L3-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 4doc 40005 | Source E L1-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 5doc 40006 | Source E L2-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 6doc 40007 | Source E L3-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 7doc 40008 | Source N L1-L2 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 8doc 40009 | Source N L2-L3 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 9doc 40010 | Source N L3-L1 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 10doc 40011 | Source E L1-L2 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 11doc 40012 | Source E L2-L3 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 12doc 40013 | Source E L3-L1 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 13doc 40014 | Source N Frequency | x10. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 14doc 40015 | Source E Frequency | x10. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 15doc 40016 | Current L1 | x10. | UINT16 | × 0.1 | A | Read | ||
| HR | 16doc 40017 | Current L2 | x10. | UINT16 | × 0.1 | A | Read | ||
| HR | 17doc 40018 | Current L3 | x10. | UINT16 | × 0.1 | A | Read | ||
| HR | 18doc 40019 | Closed Transition In-Phase Degree Delta | UINT16 | ° | Read | ||||
| HR | 44doc 40045 | Phase Rotation Actual | High byte normal, low byte emergency: 0 = disabled, 1 = ABC, 2 = CBA. | UINT16 | Read | ||||
| HR | 46doc 40047 | Nominal Normal Voltage | x10. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 47doc 40048 | Nominal Emergency Voltage | x10. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 48doc 40049 | Nominal Normal Frequency | x10. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 49doc 40050 | Nominal Emergency Frequency | x10. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 50doc 40051 | Normal Number of Phases | 1 or 3. | UINT16 | Read/write | ||||
| HR | 51doc 40052 | Emergency Number of Phases | 1 or 3. | UINT16 | Read/write | ||||
| HR | 52doc 40053 | Rated Amperage | 0-4000. | UINT16 | A | Read/write | |||
| HR | 56doc 40057 | Transition Mode | Distributor-level password needed: send it in 40058 in the same write. | BITMAP16 | Read/write | bit 0 = Transition bit 0 (bits 0-1: 00 = open, 01 = programmed, 10 = closed); bit 1 = Transition bit 1; bit 2 = Mode bit 0 (bits 2-3: 01 = genset-util, 10 = util-util, 00 = genset-genset, 11 = util-gen-gen); bit 3 = Mode bit 1; bit 4 = Supervised transfer control switch: 0 = auto, 1 = manual | |||
| HR | 74doc 40075 | Active Time Delay Number | UINT16 | Read | |||||
| HR | 75doc 40076 | Active Time Delay Remaining | x10. | UINT16 | × 0.1 | s | Read | ||
| HR | 76doc 40077 | Active Time Delay Preset | x10. | UINT16 | × 0.1 | s | Read | ||
| HR | 193doc 40194 | MLB Output State | One bit per main logic board output. | BITMAP16 | Read | ||||
| HR | 194doc 40195 | MLB Input State | One bit per main logic board input. | BITMAP16 | Read | ||||
| HR | 741doc 40742 | Accessory Status | BITMAP16 | Read | bit 0 = Exercise in progress; bit 1 = In-phase monitor active; bit 2 = Load control in progress; bit 3 = Peak shaving in progress; bit 4 = Loaded test occurring; bit 5 = Unloaded test occurring; bit 6 = Auto-loaded test occurring | ||||
| HR | 742doc 40743 | DIP Switch Position | BITMAP16 | Read | bit 0 = Maintenance mode; bit 1 = Password disabled; bit 2 = Spare 3 on; bit 3 = Spare 4 on | ||||
| HR | 1009doc 41010 | Last Outage Time | Minutes since midnight. | UINT16 | min | Read | |||
| HR | 1199doc 41200 | 1500 Code Revision | High byte = major, low byte = minor version. | UINT16 | Read | ||||
| HR | 1299doc 41300-41301 | Minutes Not in Preferred Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1303doc 41304-41305 | Minutes in Standby Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1307doc 41308-41309 | Minutes of Operation Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1311doc 41312 | Switch Transfers Total | UINT16 | Read | |||||
| HR | 1313doc 41314 | Failures to Transfer Total | UINT16 | Read | |||||
| HR | 1315doc 41316 | Loss of Preferred Transfers Total | UINT16 | Read | |||||
| HR | 1317doc 41318 | Transfer Time N->E | UINT16 | ms | Read | ||||
| HR | 1318doc 41319 | Transfer Time E->N | UINT16 | ms | Read | ||||
| HR | 1349doc 41350 | Maintenance/Test and Manual Operations | Write-only command bits. | BITMAP16 | Write | bit 0 = Reset maintenance records; bit 1 = Start peak shave; bit 2 = End peak shave; bit 3 = Start remote loaded test; bit 4 = Start remote unloaded test; bit 6 = End remote test; bit 7 = Force transfer to OFF; bit 8 = Resume programmed transition operation; bit 9 = End current time delay | |||
| HR | 1350doc 41351 | Auto-Load Run Time | Any non-zero value starts the test. | UINT16 | min | Write | |||
| HR | 9998doc 49999 | Device ID | MPAC 1500 = 0x17 (23). | UINT16 | Read |
Notes on this map
- Serial port 1 defaults to Modbus address 1 and port 2 to address 2; Modbus TCP uses unit ID 3 from the factory.
- The 2-register maintenance counters (41300-41311) are stated as most significant word first, so they are ABCD. 41012-41013 (duration of last outage) is a 2-word value without a stated word order and is left out.
- 40057 (transition mode) is in the guide's distributor-password group: the guide says to send the data register and the password (40058) in the same request. 40042 has its own password register at 40040. Calibration and factory settings also need the distributor-level password and are not listed.
- Left out: synchronizing settings, time delays and trip points (40059-40107), programmable I/O event-code assignments, expansion board states, accessory setup, exerciser, common alarms, customer strings, clock/DST registers, packed date fields and the event history.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Kohler MPAC 1500 automatic transfer switch controller
What Modbus registers does the Kohler MPAC 1500 automatic transfer switch controller have?
This map lists 48 registers: 48 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Kohler MPAC 1500 automatic transfer switch controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. This section prints 5-digit holding-register references starting at 40001, so 40001 is wire address 0 and 41350 is wire address 1349.
What byte order does the Kohler MPAC 1500 automatic transfer switch controller use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Kohler MPAC 1500 automatic transfer switch controller?
Start with HR 0 System Overview (Contactor position and source availability); HR 7 Source N L1-L2 Voltage (Normal source L1-L2 voltage); HR 10 Source E L1-L2 Voltage (Emergency source L1-L2 voltage); HR 13 Source N Frequency (Normal source frequency); HR 14 Source E Frequency (Emergency source frequency); HR 15 Current L1 (Load current L1); HR 741 Accessory Status (Accessory status (tests, peak shave)).
How do I enable Modbus control of the Kohler MPAC 1500 automatic transfer switch controller?
On the controller's communications setup enable Modbus Server Port 1/Port 2 (serial) or Modbus Server TCP (Ethernet), set each port's address (1-247) and baud rate (9600, 19200 or 57600), and for TCP the unit ID, IP address and subnet mask.
Where is the official Kohler MPAC 1500 automatic transfer switch controller Modbus documentation?
The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.
More Kohler Modbus register maps
- Generator controller
Kohler Decision-Maker 3500 generator set controller
Kohler Decision-Maker 3500 generator set controllers (Modbus map version 2; some registers need firmware 1.4 or later), Modbus RTU on RS-485.
Also known as: Decision-Maker 3500, DEC3500, DEC 3500 - Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller - Generator controller
Kohler Decision-Maker 6000 generator set controller
Kohler Decision-Maker 6000 generator set controllers, Modbus RTU on the controller's RS-485/RS-232 port, per section 8 of TP-6113.
Also known as: Decision-Maker 6000, DEC 6000, Kohler 6000 controller - Transfer switch
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
Kohler Decision-Maker MPAC 750, 1200 and 1500 ATS controllers, Modbus RTU on the logic board RS-485 port or Modbus TCP, per section 14 of TP-6113.
Also known as: Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC - Transfer switch
Kohler MPAC 1000 automatic transfer switch controller
Kohler MPAC 1000 ATS controllers, Modbus RTU on RS-485, per section 12 of TP-6113.
Also known as: MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS
Other generator controllers register maps
- Generator controller
Lovato Electric RGK800 AMF genset controller
RGK800, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800, RGK800 AMF - Generator controller
SmartGen HGM7100N Series
HGM7110N (auto start) and HGM7120N (AMF) genset controllers, protocol document v1.3.
Also known as: HGM7110N, HGM7120N - Transfer switch controller
ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)
ASCO 7000 Series Group 5 controller, firmware 607540-023 (some bits 607540-033); document 381339-221 revision I. Power Manager Xp registers in the same document are not included.
Also known as: ASCO 7000 Group 5, Group 5 Controller, 381339-221 - Generator controller
Datakom D-300 / D-500 / D-700 genset controllers
Datakom D-300, D-500 and D-700 controllers, Modbus application manual V5.6 (firmware 5.6 era).
Also known as: D-300, D-500, D-700, D300, D500, D700 - Generator controller
DEIF SGC 120 / SGC 121 Single Genset Controller
SGC 120 and SGC 121 (first generation, not Mk II); the SGC 120 user manual 4189341340B covers application software 9.04.
Also known as: SGC 120, SGC 121, SGC120, SGC121 - Generator controller
Lovato Electric RGK750 genset controller
RGK750, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 750
All generator controllers Modbus register maps →
Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.