Kohler MPAC 1500 automatic transfer switch controller Modbus register map

Updated 17 November 2026

Short answer

The MPAC 1500 is a Kohler automatic transfer switch controller. Its Modbus map gives normal (N) and emergency (E) source voltages and frequencies, load current, contactor position and source availability, transition mode, time-delay status, accessory and I/O states, transfer statistics and write-only test and manual-operation commands. This map covers the monitoring block, nominal ratings, transition mode, I/O and accessory status, maintenance counters and the command registers.

This page lists 48 Modbus registers for the Kohler MPAC 1500 automatic transfer switch controller — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.

Manufacturer
Kohler
Model
MPAC 1500 automatic transfer switch controller
Equipment type
Transfer switch
Registers
48 (10 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
Source document
Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Kohler MPAC 1500 automatic transfer switch controller

Integration in brief

Poll 40001-40019 in one FC 03 read for contactor position, source availability, both sources' voltages and frequencies and load current. Use 41350 bit commands for remote tests and peak shave, and 41312-41319 for transfer statistics.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0System OverviewBITMAP16Contactor position and source availabilityRead
HR 7Source N L1-L2 VoltageUINT16Normal source L1-L2 voltageRead
HR 10Source E L1-L2 VoltageUINT16Emergency source L1-L2 voltageRead
HR 13Source N FrequencyUINT16Normal source frequencyRead
HR 14Source E FrequencyUINT16Emergency source frequencyRead
HR 15Current L1UINT16Load current L1Read
HR 741Accessory StatusBITMAP16Accessory status (tests, peak shave)Read

Enable Modbus control & writes

On the controller's communications setup enable Modbus Server Port 1/Port 2 (serial) or Modbus Server TCP (Ethernet), set each port's address (1-247) and baud rate (9600, 19200 or 57600), and for TCP the unit ID, IP address and subnet mask.

Byte order & addressing

Network setup

Watch out for

Kohler MPAC 1500 automatic transfer switch controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

48 of 48 shown
Kohler MPAC 1500 automatic transfer switch controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001System OverviewContactor position, preferred source and source availability.BITMAP16Readbit 0 = Contactor position bit 0 (bits 0-1: 00 = off, 01 = normal, 10 = emergency, 11 = fault); bit 1 = Contactor position bit 1; bit 2 = Preferred source: 0 = source 1, 1 = source 2; bit 3 = Bits 3-12: top event on the warning stack; bit 13 = Preferred source available; bit 14 = Standby source available
HR1doc 40002Source N L1-L0 Voltagex10.UINT16× 0.1VRead
HR2doc 40003Source N L2-L0 Voltagex10.UINT16× 0.1VRead
HR3doc 40004Source N L3-L0 Voltagex10.UINT16× 0.1VRead
HR4doc 40005Source E L1-L0 Voltagex10.UINT16× 0.1VRead
HR5doc 40006Source E L2-L0 Voltagex10.UINT16× 0.1VRead
HR6doc 40007Source E L3-L0 Voltagex10.UINT16× 0.1VRead
HR7doc 40008Source N L1-L2 Voltagex10.UINT16× 0.1VRead
HR8doc 40009Source N L2-L3 Voltagex10.UINT16× 0.1VRead
HR9doc 40010Source N L3-L1 Voltagex10.UINT16× 0.1VRead
HR10doc 40011Source E L1-L2 Voltagex10.UINT16× 0.1VRead
HR11doc 40012Source E L2-L3 Voltagex10.UINT16× 0.1VRead
HR12doc 40013Source E L3-L1 Voltagex10.UINT16× 0.1VRead
HR13doc 40014Source N Frequencyx10.UINT16× 0.1HzRead
HR14doc 40015Source E Frequencyx10.UINT16× 0.1HzRead
HR15doc 40016Current L1x10.UINT16× 0.1ARead
HR16doc 40017Current L2x10.UINT16× 0.1ARead
HR17doc 40018Current L3x10.UINT16× 0.1ARead
HR18doc 40019Closed Transition In-Phase Degree DeltaUINT16°Read
HR44doc 40045Phase Rotation ActualHigh byte normal, low byte emergency: 0 = disabled, 1 = ABC, 2 = CBA.UINT16Read
HR46doc 40047Nominal Normal Voltagex10.UINT16× 0.1VRead/write
HR47doc 40048Nominal Emergency Voltagex10.UINT16× 0.1VRead/write
HR48doc 40049Nominal Normal Frequencyx10.UINT16× 0.1HzRead/write
HR49doc 40050Nominal Emergency Frequencyx10.UINT16× 0.1HzRead/write
HR50doc 40051Normal Number of Phases1 or 3.UINT16Read/write
HR51doc 40052Emergency Number of Phases1 or 3.UINT16Read/write
HR52doc 40053Rated Amperage0-4000.UINT16ARead/write
HR56doc 40057Transition ModeDistributor-level password needed: send it in 40058 in the same write.BITMAP16Read/writebit 0 = Transition bit 0 (bits 0-1: 00 = open, 01 = programmed, 10 = closed); bit 1 = Transition bit 1; bit 2 = Mode bit 0 (bits 2-3: 01 = genset-util, 10 = util-util, 00 = genset-genset, 11 = util-gen-gen); bit 3 = Mode bit 1; bit 4 = Supervised transfer control switch: 0 = auto, 1 = manual
HR74doc 40075Active Time Delay NumberUINT16Read
HR75doc 40076Active Time Delay Remainingx10.UINT16× 0.1sRead
HR76doc 40077Active Time Delay Presetx10.UINT16× 0.1sRead
HR193doc 40194MLB Output StateOne bit per main logic board output.BITMAP16Read
HR194doc 40195MLB Input StateOne bit per main logic board input.BITMAP16Read
HR741doc 40742Accessory StatusBITMAP16Readbit 0 = Exercise in progress; bit 1 = In-phase monitor active; bit 2 = Load control in progress; bit 3 = Peak shaving in progress; bit 4 = Loaded test occurring; bit 5 = Unloaded test occurring; bit 6 = Auto-loaded test occurring
HR742doc 40743DIP Switch PositionBITMAP16Readbit 0 = Maintenance mode; bit 1 = Password disabled; bit 2 = Spare 3 on; bit 3 = Spare 4 on
HR1009doc 41010Last Outage TimeMinutes since midnight.UINT16minRead
HR1199doc 412001500 Code RevisionHigh byte = major, low byte = minor version.UINT16Read
HR1299doc 41300-41301Minutes Not in Preferred TotalMost significant word first.UINT32ABCDminRead
HR1303doc 41304-41305Minutes in Standby TotalMost significant word first.UINT32ABCDminRead
HR1307doc 41308-41309Minutes of Operation TotalMost significant word first.UINT32ABCDminRead
HR1311doc 41312Switch Transfers TotalUINT16Read
HR1313doc 41314Failures to Transfer TotalUINT16Read
HR1315doc 41316Loss of Preferred Transfers TotalUINT16Read
HR1317doc 41318Transfer Time N->EUINT16msRead
HR1318doc 41319Transfer Time E->NUINT16msRead
HR1349doc 41350Maintenance/Test and Manual OperationsWrite-only command bits.BITMAP16Writebit 0 = Reset maintenance records; bit 1 = Start peak shave; bit 2 = End peak shave; bit 3 = Start remote loaded test; bit 4 = Start remote unloaded test; bit 6 = End remote test; bit 7 = Force transfer to OFF; bit 8 = Resume programmed transition operation; bit 9 = End current time delay
HR1350doc 41351Auto-Load Run TimeAny non-zero value starts the test.UINT16minWrite
HR9998doc 49999Device IDMPAC 1500 = 0x17 (23).UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Kohler MPAC 1500 automatic transfer switch controller

What Modbus registers does the Kohler MPAC 1500 automatic transfer switch controller have?

This map lists 48 registers: 48 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Kohler MPAC 1500 automatic transfer switch controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. This section prints 5-digit holding-register references starting at 40001, so 40001 is wire address 0 and 41350 is wire address 1349.

What byte order does the Kohler MPAC 1500 automatic transfer switch controller use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Kohler MPAC 1500 automatic transfer switch controller?

Start with HR 0 System Overview (Contactor position and source availability); HR 7 Source N L1-L2 Voltage (Normal source L1-L2 voltage); HR 10 Source E L1-L2 Voltage (Emergency source L1-L2 voltage); HR 13 Source N Frequency (Normal source frequency); HR 14 Source E Frequency (Emergency source frequency); HR 15 Current L1 (Load current L1); HR 741 Accessory Status (Accessory status (tests, peak shave)).

How do I enable Modbus control of the Kohler MPAC 1500 automatic transfer switch controller?

On the controller's communications setup enable Modbus Server Port 1/Port 2 (serial) or Modbus Server TCP (Ethernet), set each port's address (1-247) and baud rate (9600, 19200 or 57600), and for TCP the unit ID, IP address and subnet mask.

Where is the official Kohler MPAC 1500 automatic transfer switch controller Modbus documentation?

The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.

More Kohler Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.