Generator controller · Modbus register map
Kohler Decision-Maker 3500 generator set controller Modbus register map
Updated 17 November 2026
The Decision-Maker 3500 is a Kohler generator set controller whose map also carries bus, synchronizing and generator management data. Its Modbus RTU map reports generator and bus electrical values as percentages of the set's ratings, engine data, run-time counters, genset state and master switch position, plus event logs and configuration. This map covers the electrical, engine, run-time, rating and status registers.
This page lists 67 Modbus registers for the Kohler Decision-Maker 3500 generator set controller — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.
- Manufacturer
- Kohler
- Model
- Decision-Maker 3500 generator set controller
- Equipment type
- Generator controller
- Registers
- 67 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Map version 2; firmware 1.4 or later for some registers
- Also known as
- Decision-Maker 3500, DEC3500, DEC 3500
Integration notes: Kohler Decision-Maker 3500 generator set controller
Read 400001-400039 for generator electrical values and 400059-400076 for engine data, then multiply the percentages by the ratings at 400105-400109 to get volts, amps and kW. Watch 400652 for genset state and 400653 for the master switch position.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3 | Generator Voltage L-L Average | UINT16 | Generator L-L average voltage, % of rated | Read |
| HR 11 | Generator Current Average | UINT16 | Generator average current, % of rated | Read |
| HR 12 | Generator Frequency | UINT16 | Generator frequency | Read |
| HR 16 | Generator Total Real Power | INT16 | Total real power, % of rated kW | Read |
| HR 60 | Engine Speed | UINT16 | Engine speed | Read |
| HR 61 | Battery Voltage | UINT16 | Battery voltage | Read |
| HR 651 | Status | UINT16 | Genset state | Read |
| HR 652 | Master Switch Position | UINT16 | Master switch position | Read |
Enable Modbus control & writes
Use Kohler SiteTech to set the Modbus address (1-247, unique per unit) and baud rate (9600, 19200, 38400 or 57600) on the controller.
Byte order & addressing
- Electrical values are percent of rating, not engineering units.
- Counters use LW/HW register pairs (low word first).
- 0xFFC0 in any register means unsupported in this application.
Network setup
- Serial format is 8 data bits, no parity, 1 stop bit.
- Read 409999 = 49 to confirm the controller type.
Watch out for
- Maximum 50 registers per read and 16 per write; do not start a block read on an undefined register.
Kohler Decision-Maker 3500 generator set controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 400001 | Generator Voltage L1-L2 | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 1doc 400002 | Generator Voltage L2-L3 | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 2doc 400003 | Generator Voltage L3-L1 | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 3doc 400004 | Generator Voltage L-L Average | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 4doc 400005 | Generator Voltage L1-N | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 5doc 400006 | Generator Voltage L2-N | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 6doc 400007 | Generator Voltage L3-N | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 7doc 400008 | Generator Voltage L-N Average | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 8doc 400009 | Generator Current L1 | Percent of rated current, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 9doc 400010 | Generator Current L2 | Percent of rated current, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 10doc 400011 | Generator Current L3 | Percent of rated current, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 11doc 400012 | Generator Current Average | Percent of rated current, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 12doc 400013 | Generator Frequency | x100. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 13doc 400014 | Generator Real Power L1 | Percent of rated kW, x100. Full load per phase = 33.3%. | INT16 | × 0.01 | % | Read | ||
| HR | 14doc 400015 | Generator Real Power L2 | Percent of rated kW, x100. | INT16 | × 0.01 | % | Read | ||
| HR | 15doc 400016 | Generator Real Power L3 | Percent of rated kW, x100. | INT16 | × 0.01 | % | Read | ||
| HR | 16doc 400017 | Generator Total Real Power | Percent of rated kW, x100. | INT16 | × 0.01 | % | Read | ||
| HR | 20doc 400021 | Generator Reactive Power | Percent of rated kW, x100. Full reactive load = 75%. | INT16 | × 0.01 | % | Read | ||
| HR | 24doc 400025 | Generator Apparent Power | Percent of rated kW, x100. Full alternator load = 125%. | UINT16 | × 0.01 | % | Read | ||
| HR | 25doc 400026 | Generator Power Factor L1 | x100; negative = reverse power. | INT16 | × 0.01 | Read | |||
| HR | 26doc 400027 | Generator Power Factor L2 | x100; negative = reverse power. | INT16 | × 0.01 | Read | |||
| HR | 27doc 400028 | Generator Power Factor L3 | x100; negative = reverse power. | INT16 | × 0.01 | Read | |||
| HR | 28doc 400029 | Generator Power Factor | x100; negative = reverse power. | INT16 | × 0.01 | Read | |||
| HR | 34doc 400035 | Phase Rotation | UINT16 | Read | 0 = Unknown; 1 = ABC; 2 = CBA; 3 = Single-phase | ||||
| HR | 38doc 400039 | Generator Avg Current Lead/Lag | UINT16 | Read | 0 = Invalid; 1 = Leading; 2 = Lagging | ||||
| HR | 43doc 400044 | Bus Voltage L1-L2 | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 46doc 400047 | Bus Voltage L-L Average | Percent of rated voltage, x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 47doc 400048 | Total Bus Real Power | Percent of rated kW, x100. | INT16 | × 0.01 | % | Read | ||
| HR | 49doc 400050 | Bus Frequency | x100. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 50doc 400051 | Bus Phase Rotation | UINT16 | Read | 0 = Unknown; 1 = ABC; 2 = CBA; 3 = Single-phase | ||||
| HR | 58doc 400059 | Engine Oil Pressure | x10. | UINT16 | × 0.1 | kPa | Read | ||
| HR | 59doc 400060 | Engine Coolant Temperature | x10. | INT16 | × 0.1 | °C | Read | ||
| HR | 60doc 400061 | Engine Speed | UINT16 | rpm | Read | ||||
| HR | 61doc 400062 | Battery Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 62doc 400063 | Controller Temperature | INT16 | °C | Read | ||||
| HR | 63doc 400064 | Engine Fuel Pressure | UINT16 | kPa | Read | ||||
| HR | 64doc 400065 | Engine Fuel Temperature | INT16 | °C | Read | ||||
| HR | 65doc 400066 | Engine Fuel Rate | UINT16 | l/h | Read | ||||
| HR | 66doc 400067 | Fuel Used During Last Run | UINT16 | l | Read | ||||
| HR | 67doc 400068 | Engine Coolant Pressure | x10. | UINT16 | × 0.1 | kPa | Read | ||
| HR | 68doc 400069 | Engine Coolant Level | x100. | UINT16 | × 0.01 | % | Read | ||
| HR | 69doc 400070 | Engine Oil Temperature | INT16 | °C | Read | ||||
| HR | 70doc 400071 | Engine Oil Level | UINT16 | % | Read | ||||
| HR | 71doc 400072 | Engine Crankcase Pressure | UINT16 | kPa | Read | ||||
| HR | 72doc 400073 | Intake Air Temperature | INT16 | °C | Read | ||||
| HR | 73doc 400074 | Intake Air Pressure | UINT16 | kPa | Read | ||||
| HR | 75doc 400076 | ECM Battery Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 82doc 400083-400084 | Total Runtime Hours | x10; LW at 400083, HW at 400084. | UINT32 | CDAB | × 0.1 | h | Read | |
| HR | 84doc 400085-400086 | Total Runtime Loaded Hours | x10; LW first. | UINT32 | CDAB | × 0.1 | h | Read | |
| HR | 88doc 400089-400090 | Total Runtime kW Hours | LW first. | UINT32 | CDAB | kWh | Read | ||
| HR | 104doc 400105 | System Voltage | UINT16 | V | Read/write | ||||
| HR | 105doc 400106 | System Frequency | UINT16 | Hz | Read/write | ||||
| HR | 106doc 400107 | System Phase Connection | UINT16 | Read/write | 0 = Single-phase; 1 = Dog leg; 2 = Wye; 3 = Delta | ||||
| HR | 107doc 400108 | Rated Current | Reference for the current percentages. | UINT16 | A | Read | |||
| HR | 108doc 400109 | Genset kW Rating | x10. Reference for the power percentages. | UINT16 | × 0.1 | kW | Read | ||
| HR | 109doc 400110 | System Battery Voltage | UINT16 | V | Read/write | ||||
| HR | 110doc 400111 | Engine Run Speed | UINT16 | rpm | Read/write | ||||
| HR | 512doc 400513 | Total Number of Starts | UINT16 | Read | |||||
| HR | 513doc 400514-400515 | Runtime Hours Since Maintenance | x10; LW first. | UINT32 | CDAB | × 0.1 | h | Read | |
| HR | 523doc 400524 | Operating Days Since Last Maintenance | UINT16 | days | Read | ||||
| HR | 524doc 400525 | Starts Since Last Maintenance | UINT16 | Read | |||||
| HR | 651doc 400652 | Status | Generator set state. | UINT16 | Read | 0 = Off; 1 = Crank on; 2 = Crank pause; 3 = Idle; 4 = Running; 5 = Cool down; 6 = Stopping; 7 = Shutdown; 8 = Performing loaded test; 9 = Performing unloaded test; 10 = Performing variable speed exercise; 11 = Performing loaded exercise; 12 = Fuel priming; 13 = ECM powered; 14 = Fault cool down; 15 = Standby; 16 = Preheat; 17 = Performing unloaded full speed exercise; 18 = Performing full speed diagnostics; 19 = Stopped by generator management; 20 = Synchronizing; 21 = Protective relay tripped contactor; 22 = Start delay; 23 = Stationary regen; 24 = Choke | |||
| HR | 652doc 400653 | Master Switch Position | UINT16 | Read | 0 = Error; 1 = Auto; 2 = Off; 3 = Run | ||||
| HR | 894doc 400895 | Number of Active Events | UINT16 | Read | |||||
| HR | 9996doc 409997 | Vendor | 7728 = Kohler Co. | UINT16 | Read | ||||
| HR | 9997doc 409998 | Modbus Map Version | 2 for this map. | UINT16 | Read | ||||
| HR | 9998doc 409999 | Controller Type | 49 = Decision-Maker 3500. | UINT16 | Read |
Notes on this map
- Generator and bus voltages, currents and powers are reported as percent of the set's rated values (x100), not volts, amps or kW. Rated current is at 400108 and the kW rating at 400109; the rated voltage is the system voltage at 400105.
- 32-bit UDINT counters are split into an LW register followed by an HW register, so they are listed CDAB.
- Left out: 400087-400088 (the low word is labelled controller total operation time while the high word is labelled unloaded hours), per-phase reactive and apparent power, phase angles, speed/voltage bias, the voltage/resistance/digital channel configuration blocks, time delays, protective relay and synchronizer settings, load management, generator management, event logs and the ID strings.
- Invalid-data flags: 0xFFC0 = register not supported in this application; 0x7FE0-0x7FFF = supported but the value is unknown (for example ECM sensors with the ECM unpowered).
- Registers marked in the manual as needing firmware 1.4 or later return errors on older firmware.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Kohler Decision-Maker 3500 generator set controller
What Modbus registers does the Kohler Decision-Maker 3500 generator set controller have?
This map lists 67 registers: 67 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Kohler Decision-Maker 3500 generator set controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 6-digit holding-register references (400001 = first holding register; 409999 is register 49999 in 5-digit form), so 400001 is wire address 0 and 400652 is wire address 651.
What byte order does the Kohler Decision-Maker 3500 generator set controller use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Kohler Decision-Maker 3500 generator set controller?
Start with HR 3 Generator Voltage L-L Average (Generator L-L average voltage, % of rated); HR 11 Generator Current Average (Generator average current, % of rated); HR 12 Generator Frequency (Generator frequency); HR 16 Generator Total Real Power (Total real power, % of rated kW); HR 60 Engine Speed (Engine speed); HR 61 Battery Voltage (Battery voltage); HR 651 Status (Genset state); HR 652 Master Switch Position (Master switch position).
How do I enable Modbus control of the Kohler Decision-Maker 3500 generator set controller?
Use Kohler SiteTech to set the Modbus address (1-247, unique per unit) and baud rate (9600, 19200, 38400 or 57600) on the controller.
Where is the official Kohler Decision-Maker 3500 generator set controller Modbus documentation?
The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.
More Kohler Modbus register maps
- Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller - Generator controller
Kohler Decision-Maker 6000 generator set controller
Kohler Decision-Maker 6000 generator set controllers, Modbus RTU on the controller's RS-485/RS-232 port, per section 8 of TP-6113.
Also known as: Decision-Maker 6000, DEC 6000, Kohler 6000 controller - Transfer switch
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
Kohler Decision-Maker MPAC 750, 1200 and 1500 ATS controllers, Modbus RTU on the logic board RS-485 port or Modbus TCP, per section 14 of TP-6113.
Also known as: Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC - Transfer switch
Kohler MPAC 1000 automatic transfer switch controller
Kohler MPAC 1000 ATS controllers, Modbus RTU on RS-485, per section 12 of TP-6113.
Also known as: MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
Other generator controllers register maps
- Transfer switch
Lovato Electric ATL800 / ATL900 automatic transfer switch controllers
ATL800 and ATL900 ATS controllers (document I463 GB I 11 21); LINE3, BRK3 and TB2 items are ATL900 only.
Also known as: ATL800, ATL900, ATL 800, ATL 900 - Generator controller
Lovato Electric RGK900 genset paralleling controller
RGK900, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900 - Generator controller (synchronizer and load sharing control)
Woodward DSLC-2 Digital Synchronizer and Load Control
DSLC-2, data protocol 5200, per manual 37443J.
Also known as: DSLC2, DSLC-2 synchronizer - Transfer switch controller
BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)
BTicino M7000CBNCU03 (Legrand cat. no. 4 226 82) automatic changeover controller, Modbus RTU/ASCII via the M7000CBNRS485 expansion module or the IR-USB / IR-WiFi front interfaces, per document LE09509AA-01/17-01.
Also known as: M7000CBNCU03, 4 226 82, 422682, Legrand 4 226 82 - Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2
All generator controllers Modbus register maps →
Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.