Generator controller · Modbus register map

Kohler Decision-Maker 3500 generator set controller Modbus register map

Updated 17 November 2026

Short answer

The Decision-Maker 3500 is a Kohler generator set controller whose map also carries bus, synchronizing and generator management data. Its Modbus RTU map reports generator and bus electrical values as percentages of the set's ratings, engine data, run-time counters, genset state and master switch position, plus event logs and configuration. This map covers the electrical, engine, run-time, rating and status registers.

This page lists 67 Modbus registers for the Kohler Decision-Maker 3500 generator set controller — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.

Manufacturer
Kohler
Model
Decision-Maker 3500 generator set controller
Equipment type
Generator controller
Registers
67 (5 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Map version 2; firmware 1.4 or later for some registers
Also known as
Decision-Maker 3500, DEC3500, DEC 3500
Source document
Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Kohler Decision-Maker 3500 generator set controller

Integration in brief

Read 400001-400039 for generator electrical values and 400059-400076 for engine data, then multiply the percentages by the ratings at 400105-400109 to get volts, amps and kW. Watch 400652 for genset state and 400653 for the master switch position.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3Generator Voltage L-L AverageUINT16Generator L-L average voltage, % of ratedRead
HR 11Generator Current AverageUINT16Generator average current, % of ratedRead
HR 12Generator FrequencyUINT16Generator frequencyRead
HR 16Generator Total Real PowerINT16Total real power, % of rated kWRead
HR 60Engine SpeedUINT16Engine speedRead
HR 61Battery VoltageUINT16Battery voltageRead
HR 651StatusUINT16Genset stateRead
HR 652Master Switch PositionUINT16Master switch positionRead

Enable Modbus control & writes

Use Kohler SiteTech to set the Modbus address (1-247, unique per unit) and baud rate (9600, 19200, 38400 or 57600) on the controller.

Byte order & addressing

Network setup

Watch out for

Kohler Decision-Maker 3500 generator set controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

67 of 67 shown
Kohler Decision-Maker 3500 generator set controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 400001Generator Voltage L1-L2Percent of rated voltage, x100.UINT16× 0.01%Read
HR1doc 400002Generator Voltage L2-L3Percent of rated voltage, x100.UINT16× 0.01%Read
HR2doc 400003Generator Voltage L3-L1Percent of rated voltage, x100.UINT16× 0.01%Read
HR3doc 400004Generator Voltage L-L AveragePercent of rated voltage, x100.UINT16× 0.01%Read
HR4doc 400005Generator Voltage L1-NPercent of rated voltage, x100.UINT16× 0.01%Read
HR5doc 400006Generator Voltage L2-NPercent of rated voltage, x100.UINT16× 0.01%Read
HR6doc 400007Generator Voltage L3-NPercent of rated voltage, x100.UINT16× 0.01%Read
HR7doc 400008Generator Voltage L-N AveragePercent of rated voltage, x100.UINT16× 0.01%Read
HR8doc 400009Generator Current L1Percent of rated current, x100.UINT16× 0.01%Read
HR9doc 400010Generator Current L2Percent of rated current, x100.UINT16× 0.01%Read
HR10doc 400011Generator Current L3Percent of rated current, x100.UINT16× 0.01%Read
HR11doc 400012Generator Current AveragePercent of rated current, x100.UINT16× 0.01%Read
HR12doc 400013Generator Frequencyx100.UINT16× 0.01HzRead
HR13doc 400014Generator Real Power L1Percent of rated kW, x100. Full load per phase = 33.3%.INT16× 0.01%Read
HR14doc 400015Generator Real Power L2Percent of rated kW, x100.INT16× 0.01%Read
HR15doc 400016Generator Real Power L3Percent of rated kW, x100.INT16× 0.01%Read
HR16doc 400017Generator Total Real PowerPercent of rated kW, x100.INT16× 0.01%Read
HR20doc 400021Generator Reactive PowerPercent of rated kW, x100. Full reactive load = 75%.INT16× 0.01%Read
HR24doc 400025Generator Apparent PowerPercent of rated kW, x100. Full alternator load = 125%.UINT16× 0.01%Read
HR25doc 400026Generator Power Factor L1x100; negative = reverse power.INT16× 0.01Read
HR26doc 400027Generator Power Factor L2x100; negative = reverse power.INT16× 0.01Read
HR27doc 400028Generator Power Factor L3x100; negative = reverse power.INT16× 0.01Read
HR28doc 400029Generator Power Factorx100; negative = reverse power.INT16× 0.01Read
HR34doc 400035Phase RotationUINT16Read0 = Unknown; 1 = ABC; 2 = CBA; 3 = Single-phase
HR38doc 400039Generator Avg Current Lead/LagUINT16Read0 = Invalid; 1 = Leading; 2 = Lagging
HR43doc 400044Bus Voltage L1-L2Percent of rated voltage, x100.UINT16× 0.01%Read
HR46doc 400047Bus Voltage L-L AveragePercent of rated voltage, x100.UINT16× 0.01%Read
HR47doc 400048Total Bus Real PowerPercent of rated kW, x100.INT16× 0.01%Read
HR49doc 400050Bus Frequencyx100.UINT16× 0.01HzRead
HR50doc 400051Bus Phase RotationUINT16Read0 = Unknown; 1 = ABC; 2 = CBA; 3 = Single-phase
HR58doc 400059Engine Oil Pressurex10.UINT16× 0.1kPaRead
HR59doc 400060Engine Coolant Temperaturex10.INT16× 0.1°CRead
HR60doc 400061Engine SpeedUINT16rpmRead
HR61doc 400062Battery Voltagex10.UINT16× 0.1VRead
HR62doc 400063Controller TemperatureINT16°CRead
HR63doc 400064Engine Fuel PressureUINT16kPaRead
HR64doc 400065Engine Fuel TemperatureINT16°CRead
HR65doc 400066Engine Fuel RateUINT16l/hRead
HR66doc 400067Fuel Used During Last RunUINT16lRead
HR67doc 400068Engine Coolant Pressurex10.UINT16× 0.1kPaRead
HR68doc 400069Engine Coolant Levelx100.UINT16× 0.01%Read
HR69doc 400070Engine Oil TemperatureINT16°CRead
HR70doc 400071Engine Oil LevelUINT16%Read
HR71doc 400072Engine Crankcase PressureUINT16kPaRead
HR72doc 400073Intake Air TemperatureINT16°CRead
HR73doc 400074Intake Air PressureUINT16kPaRead
HR75doc 400076ECM Battery Voltagex10.UINT16× 0.1VRead
HR82doc 400083-400084Total Runtime Hoursx10; LW at 400083, HW at 400084.UINT32CDAB× 0.1hRead
HR84doc 400085-400086Total Runtime Loaded Hoursx10; LW first.UINT32CDAB× 0.1hRead
HR88doc 400089-400090Total Runtime kW HoursLW first.UINT32CDABkWhRead
HR104doc 400105System VoltageUINT16VRead/write
HR105doc 400106System FrequencyUINT16HzRead/write
HR106doc 400107System Phase ConnectionUINT16Read/write0 = Single-phase; 1 = Dog leg; 2 = Wye; 3 = Delta
HR107doc 400108Rated CurrentReference for the current percentages.UINT16ARead
HR108doc 400109Genset kW Ratingx10. Reference for the power percentages.UINT16× 0.1kWRead
HR109doc 400110System Battery VoltageUINT16VRead/write
HR110doc 400111Engine Run SpeedUINT16rpmRead/write
HR512doc 400513Total Number of StartsUINT16Read
HR513doc 400514-400515Runtime Hours Since Maintenancex10; LW first.UINT32CDAB× 0.1hRead
HR523doc 400524Operating Days Since Last MaintenanceUINT16daysRead
HR524doc 400525Starts Since Last MaintenanceUINT16Read
HR651doc 400652StatusGenerator set state.UINT16Read0 = Off; 1 = Crank on; 2 = Crank pause; 3 = Idle; 4 = Running; 5 = Cool down; 6 = Stopping; 7 = Shutdown; 8 = Performing loaded test; 9 = Performing unloaded test; 10 = Performing variable speed exercise; 11 = Performing loaded exercise; 12 = Fuel priming; 13 = ECM powered; 14 = Fault cool down; 15 = Standby; 16 = Preheat; 17 = Performing unloaded full speed exercise; 18 = Performing full speed diagnostics; 19 = Stopped by generator management; 20 = Synchronizing; 21 = Protective relay tripped contactor; 22 = Start delay; 23 = Stationary regen; 24 = Choke
HR652doc 400653Master Switch PositionUINT16Read0 = Error; 1 = Auto; 2 = Off; 3 = Run
HR894doc 400895Number of Active EventsUINT16Read
HR9996doc 409997Vendor7728 = Kohler Co.UINT16Read
HR9997doc 409998Modbus Map Version2 for this map.UINT16Read
HR9998doc 409999Controller Type49 = Decision-Maker 3500.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Kohler Decision-Maker 3500 generator set controller

What Modbus registers does the Kohler Decision-Maker 3500 generator set controller have?

This map lists 67 registers: 67 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Kohler Decision-Maker 3500 generator set controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 6-digit holding-register references (400001 = first holding register; 409999 is register 49999 in 5-digit form), so 400001 is wire address 0 and 400652 is wire address 651.

What byte order does the Kohler Decision-Maker 3500 generator set controller use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Kohler Decision-Maker 3500 generator set controller?

Start with HR 3 Generator Voltage L-L Average (Generator L-L average voltage, % of rated); HR 11 Generator Current Average (Generator average current, % of rated); HR 12 Generator Frequency (Generator frequency); HR 16 Generator Total Real Power (Total real power, % of rated kW); HR 60 Engine Speed (Engine speed); HR 61 Battery Voltage (Battery voltage); HR 651 Status (Genset state); HR 652 Master Switch Position (Master switch position).

How do I enable Modbus control of the Kohler Decision-Maker 3500 generator set controller?

Use Kohler SiteTech to set the Modbus address (1-247, unique per unit) and baud rate (9600, 19200, 38400 or 57600) on the controller.

Where is the official Kohler Decision-Maker 3500 generator set controller Modbus documentation?

The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.

More Kohler Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.