The SGC 420 Mk II is DEIF's second-generation single genset controller with RS-485 Modbus RTU. Values can be read as holding registers (function 03) or input registers (function 04) at the same addresses. This map covers the 16-bit generator, mains, load and engine readings, run-time counters, the packed I/O and genset-status words and the mode-change command.

This page lists 55 Modbus registers for the DEIF SGC 420 Mk II Single Genset Controller — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.

Manufacturer
DEIF
Model
SGC 420 Mk II Single Genset Controller
Equipment type
Generator controller
Registers
55 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Firmware
R19.0
Also known as
SGC 420 MkII, SGC 420 Mk2
Source document
SGC 420 Mk II Modbus tables · 4189341402 rev. C
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: DEIF SGC 420 Mk II Single Genset Controller

Integration in brief

Poll holding registers 1-64 with function 03 (or 04) for live values and the DG status word for running/fault state. Write 2 (START), 1 (STOP) or 4 (AUTO) to register 0 with function 16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Generator L1-N voltageUINT16Generator L1-N voltageRead
HR 7Generator R frequencyUINT16Generator frequencyRead
HR 23Load L1 currentUINT16Load L1 currentRead
HR 29Load total powerINT16Total kWRead
HR 56Battery voltageUINT16Battery voltageRead
HR 91DG status wordUINT16Genset status flagsRead
HR 0Protocol revision (read) / DG mode command (write)UINT16Mode-change commandRead/write

Enable Modbus control & writes

Set the RS-485 communication mode to Modbus in the controller's communication menu and give it a server ID; see the user manual.

Byte order & addressing

Network setup

Watch out for

DEIF SGC 420 Mk II Single Genset Controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

55 of 55 shown
DEIF SGC 420 Mk II Single Genset Controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Protocol revision (read) / DG mode command (write)FC03/04 return the protocol revision; FC16 writes one key code.UINT16Read/write1 = STOP; 2 = START; 4 = AUTO; 64 = ACK
HR1Generator L1-N voltageUINT16× 0.1VRead
HR2Generator L2-N voltageUINT16× 0.1VRead
HR3Generator L3-N voltageUINT16× 0.1VRead
HR4Generator L1-L2 voltageUINT16× 0.1VRead
HR5Generator L2-L3 voltageUINT16× 0.1VRead
HR6Generator L3-L1 voltageUINT16× 0.1VRead
HR7Generator R frequencyPhase R (L1) frequency.UINT16× 0.1HzRead
HR8Generator Y frequencyPhase Y (L2) frequency.UINT16× 0.1HzRead
HR9Generator B frequencyPhase B (L3) frequency.UINT16× 0.1HzRead
HR10Generator power factor L1INT16× 0.01Read
HR11Generator power factor L2INT16× 0.01Read
HR12Generator power factor L3INT16× 0.01Read
HR13Generator average power factorINT16× 0.01Read
HR14Mains L1-N voltageUINT16× 0.1VRead
HR15Mains L2-N voltageUINT16× 0.1VRead
HR16Mains L3-N voltageUINT16× 0.1VRead
HR17Mains L1-L2 voltageUINT16× 0.1VRead
HR18Mains L2-L3 voltageUINT16× 0.1VRead
HR19Mains L3-L1 voltageUINT16× 0.1VRead
HR20Mains R frequencyPhase R (L1) frequency.UINT16× 0.1HzRead
HR21Mains Y frequencyPhase Y (L2) frequency.UINT16× 0.1HzRead
HR22Mains B frequencyPhase B (L3) frequency.UINT16× 0.1HzRead
HR23Load L1 currentUINT16× 0.1ARead
HR24Load L2 currentUINT16× 0.1ARead
HR25Load L3 currentUINT16× 0.1ARead
HR26Load L1 powerINT16× 0.1kWRead
HR27Load L2 powerINT16× 0.1kWRead
HR28Load L3 powerINT16× 0.1kWRead
HR29Load total powerINT16× 0.1kWRead
HR31Load L1 apparent powerUINT16× 0.1kVARead
HR32Load L2 apparent powerUINT16× 0.1kVARead
HR33Load L3 apparent powerUINT16× 0.1kVARead
HR34Load total apparent powerUINT16× 0.1kVARead
HR35Load L1 reactive powerUINT16× 0.1kvarRead
HR36Load L2 reactive powerUINT16× 0.1kvarRead
HR37Load L3 reactive powerUINT16× 0.1kvarRead
HR38Load total reactive powerUINT16× 0.1kvarRead
HR51Oil pressureFrom the sensor or the ECU, depending on configuration.UINT16× 0.1barRead
HR52Coolant temperatureFrom the sensor or the ECU, depending on configuration.INT16× 0.1°CRead
HR53Fuel levelUINT16%Read
HR54Fuel Level in litresUINT16× 0.1LRead
HR55Charge alternator voltageUINT16× 0.1VRead
HR56Battery voltageMeasured or ECU value.UINT16× 0.1VRead
HR57Engine speedMeasured or ECU value.UINT16rpmRead
HR58No of startsUINT16Read
HR59No of tripsUINT16Read
HR61Engine run hours from ECURegister 60 (not listed) is used above 65535 h.UINT16hRead
HR62Engine run minutes from ECUUINT16minRead
HR63Mains run hoursUINT16hRead
HR64Mains run minutesUINT16minRead
HR89Digital input status wordInputs A-P, one per bit; see notes.UINT16Read
HR90Digital output status wordOutputs A-G, one per bit; see notes.UINT16Read
HR91DG status wordMode, mains healthy, load position, running and common alarm flags; see notes.UINT16Read
HR95Current time stamp: yearUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the DEIF SGC 420 Mk II Single Genset Controller

What Modbus registers does the DEIF SGC 420 Mk II Single Genset Controller have?

This map lists 55 registers: 55 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the DEIF SGC 420 Mk II Single Genset Controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print plain register numbers starting at 0 (register 0 is the protocol revision / mode command), with no 4xxxx prefix, so the printed number is the request address. The same numbers work with function 03 and function 04.

What are the minimum Modbus registers to integrate the DEIF SGC 420 Mk II Single Genset Controller?

Start with HR 1 Generator L1-N voltage (Generator L1-N voltage); HR 7 Generator R frequency (Generator frequency); HR 23 Load L1 current (Load L1 current); HR 29 Load total power (Total kW); HR 56 Battery voltage (Battery voltage); HR 91 DG status word (Genset status flags); HR 0 Protocol revision (read) / DG mode command (write) (Mode-change command).

How do I enable Modbus control of the DEIF SGC 420 Mk II Single Genset Controller?

Set the RS-485 communication mode to Modbus in the controller's communication menu and give it a server ID; see the user manual.

Where is the official DEIF SGC 420 Mk II Single Genset Controller Modbus documentation?

The source is SGC 420 Mk II Modbus tables (4189341402 rev. C), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/bxrpobcf/sgc-420-mk-ii-modbus-tables-4189341402-uk.xlsx.

More DEIF Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →