- Home
- Modbus register maps
- DEIF
- SGC 420 Mk II Single Genset Controller
Generator controller · Modbus register map
DEIF SGC 420 Mk II Single Genset Controller Modbus register map
Updated 19 November 2026
The SGC 420 Mk II is DEIF's second-generation single genset controller with RS-485 Modbus RTU. Values can be read as holding registers (function 03) or input registers (function 04) at the same addresses. This map covers the 16-bit generator, mains, load and engine readings, run-time counters, the packed I/O and genset-status words and the mode-change command.
This page lists 55 Modbus registers for the DEIF SGC 420 Mk II Single Genset Controller — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.
- Manufacturer
- DEIF
- Model
- SGC 420 Mk II Single Genset Controller
- Equipment type
- Generator controller
- Registers
- 55 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Firmware
- R19.0
- Also known as
- SGC 420 MkII, SGC 420 Mk2
- Source document
- SGC 420 Mk II Modbus tables · 4189341402 rev. C
Integration notes: DEIF SGC 420 Mk II Single Genset Controller
Poll holding registers 1-64 with function 03 (or 04) for live values and the DG status word for running/fault state. Write 2 (START), 1 (STOP) or 4 (AUTO) to register 0 with function 16.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Generator L1-N voltage | UINT16 | Generator L1-N voltage | Read |
| HR 7 | Generator R frequency | UINT16 | Generator frequency | Read |
| HR 23 | Load L1 current | UINT16 | Load L1 current | Read |
| HR 29 | Load total power | INT16 | Total kW | Read |
| HR 56 | Battery voltage | UINT16 | Battery voltage | Read |
| HR 91 | DG status word | UINT16 | Genset status flags | Read |
| HR 0 | Protocol revision (read) / DG mode command (write) | UINT16 | Mode-change command | Read/write |
Enable Modbus control & writes
Set the RS-485 communication mode to Modbus in the controller's communication menu and give it a server ID; see the user manual.
Byte order & addressing
- Function 16 uses its own small write map: register 0 takes one mode key code at a time, 1 sets the DTC parent specifier and 2-6 (Modbus digital and analog input values). Reading those same numbers returns measurements instead.
- Functions 03 and 04 return the same data.
Network setup
- RS-485 server ID, baud rate and parity are set in the controller menu (see the user manual).
Watch out for
- Phase frequencies are labelled R, Y, B (L1, L2, L3).
DEIF SGC 420 Mk II Single Genset Controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Protocol revision (read) / DG mode command (write) | FC03/04 return the protocol revision; FC16 writes one key code. | UINT16 | Read/write | 1 = STOP; 2 = START; 4 = AUTO; 64 = ACK | |||
| HR | 1 | Generator L1-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 2 | Generator L2-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 3 | Generator L3-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 4 | Generator L1-L2 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 5 | Generator L2-L3 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 6 | Generator L3-L1 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 7 | Generator R frequency | Phase R (L1) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 8 | Generator Y frequency | Phase Y (L2) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 9 | Generator B frequency | Phase B (L3) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 10 | Generator power factor L1 | INT16 | × 0.01 | Read | ||||
| HR | 11 | Generator power factor L2 | INT16 | × 0.01 | Read | ||||
| HR | 12 | Generator power factor L3 | INT16 | × 0.01 | Read | ||||
| HR | 13 | Generator average power factor | INT16 | × 0.01 | Read | ||||
| HR | 14 | Mains L1-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 15 | Mains L2-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 16 | Mains L3-N voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 17 | Mains L1-L2 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 18 | Mains L2-L3 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 19 | Mains L3-L1 voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 20 | Mains R frequency | Phase R (L1) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 21 | Mains Y frequency | Phase Y (L2) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 22 | Mains B frequency | Phase B (L3) frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 23 | Load L1 current | UINT16 | × 0.1 | A | Read | |||
| HR | 24 | Load L2 current | UINT16 | × 0.1 | A | Read | |||
| HR | 25 | Load L3 current | UINT16 | × 0.1 | A | Read | |||
| HR | 26 | Load L1 power | INT16 | × 0.1 | kW | Read | |||
| HR | 27 | Load L2 power | INT16 | × 0.1 | kW | Read | |||
| HR | 28 | Load L3 power | INT16 | × 0.1 | kW | Read | |||
| HR | 29 | Load total power | INT16 | × 0.1 | kW | Read | |||
| HR | 31 | Load L1 apparent power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 32 | Load L2 apparent power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 33 | Load L3 apparent power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 34 | Load total apparent power | UINT16 | × 0.1 | kVA | Read | |||
| HR | 35 | Load L1 reactive power | UINT16 | × 0.1 | kvar | Read | |||
| HR | 36 | Load L2 reactive power | UINT16 | × 0.1 | kvar | Read | |||
| HR | 37 | Load L3 reactive power | UINT16 | × 0.1 | kvar | Read | |||
| HR | 38 | Load total reactive power | UINT16 | × 0.1 | kvar | Read | |||
| HR | 51 | Oil pressure | From the sensor or the ECU, depending on configuration. | UINT16 | × 0.1 | bar | Read | ||
| HR | 52 | Coolant temperature | From the sensor or the ECU, depending on configuration. | INT16 | × 0.1 | °C | Read | ||
| HR | 53 | Fuel level | UINT16 | % | Read | ||||
| HR | 54 | Fuel Level in litres | UINT16 | × 0.1 | L | Read | |||
| HR | 55 | Charge alternator voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 56 | Battery voltage | Measured or ECU value. | UINT16 | × 0.1 | V | Read | ||
| HR | 57 | Engine speed | Measured or ECU value. | UINT16 | rpm | Read | |||
| HR | 58 | No of starts | UINT16 | Read | |||||
| HR | 59 | No of trips | UINT16 | Read | |||||
| HR | 61 | Engine run hours from ECU | Register 60 (not listed) is used above 65535 h. | UINT16 | h | Read | |||
| HR | 62 | Engine run minutes from ECU | UINT16 | min | Read | ||||
| HR | 63 | Mains run hours | UINT16 | h | Read | ||||
| HR | 64 | Mains run minutes | UINT16 | min | Read | ||||
| HR | 89 | Digital input status word | Inputs A-P, one per bit; see notes. | UINT16 | Read | ||||
| HR | 90 | Digital output status word | Outputs A-G, one per bit; see notes. | UINT16 | Read | ||||
| HR | 91 | DG status word | Mode, mains healthy, load position, running and common alarm flags; see notes. | UINT16 | Read | ||||
| HR | 95 | Current time stamp: year | UINT16 | Read |
Notes on this map
- Scaling values in the table (0.1, 0.01) are used as multipliers here even though the column header reads 10^-x; the values only make sense as multipliers, and the first-generation SGC tables use the same numbers as plain multipliers.
- Left out: the energy counters 39-50 (listed as FLOAT32 CDAB but also with a 0.1 scaling, which leaves it unclear whether the float is already in kWh) and the run-hours overflow word at 60. Percentage load (30) is left out because its unit is printed as kW.
- Left out: the alarm-state words 72-88 (four 4-bit alarm states per word, values 0 disabled, 1 not active, 2 warning, 3 shutdown, 4 electrical trip, 5 notification). They share the bit-numbering caveat below and are not split here.
- Word 89 packs inputs P (table bit 1) up to A (bit 16); word 90 packs outputs G (bit 10) up to A (bit 16). Word 91 packs, from table bit 1 up: common notification, common warning, common electric trip, common shutdown, gen available, fail to start, stopped with fault, stopped normally, DG running, load on DG, load on mains, operation mode (bits 12-14: 100 manual, 101 auto, 110 scheduler), mains healthy, SGC mode (bit 16). The table numbers bits 1-16 without saying whether bit 1 is the least significant bit, so the words are listed whole.
- Also not listed: the packed time-stamp bytes, the CPCB IV+, EGR and DTC blocks and the J1939 values passed through from the engine ECU.
- See the user manual 4189341360 for wiring and the RS485 menu: https://deif-cdn-umbraco.azureedge.net/media/uvtnn0df/sgc-420-mk-ii-user-manual-4189341360-uk.pdf
- Also not listed: auxiliary inputs S1-S4 (65-68) and the site battery values (69-71), which have no unit printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DEIF SGC 420 Mk II Single Genset Controller
What Modbus registers does the DEIF SGC 420 Mk II Single Genset Controller have?
This map lists 55 registers: 55 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DEIF SGC 420 Mk II Single Genset Controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print plain register numbers starting at 0 (register 0 is the protocol revision / mode command), with no 4xxxx prefix, so the printed number is the request address. The same numbers work with function 03 and function 04.
What are the minimum Modbus registers to integrate the DEIF SGC 420 Mk II Single Genset Controller?
Start with HR 1 Generator L1-N voltage (Generator L1-N voltage); HR 7 Generator R frequency (Generator frequency); HR 23 Load L1 current (Load L1 current); HR 29 Load total power (Total kW); HR 56 Battery voltage (Battery voltage); HR 91 DG status word (Genset status flags); HR 0 Protocol revision (read) / DG mode command (write) (Mode-change command).
How do I enable Modbus control of the DEIF SGC 420 Mk II Single Genset Controller?
Set the RS-485 communication mode to Modbus in the controller's communication menu and give it a server ID; see the user manual.
Where is the official DEIF SGC 420 Mk II Single Genset Controller Modbus documentation?
The source is SGC 420 Mk II Modbus tables (4189341402 rev. C), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/bxrpobcf/sgc-420-mk-ii-modbus-tables-4189341402-uk.xlsx.
More DEIF Modbus register maps
- Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF AGC 150 Generator Marine controller
AGC 150 Marine software 1.39.0 (marine Modbus server tables revision E), GEN-M (marine genset) controller type. The iE 150 Marine tables 4189341431 rev. H match these tables.
Also known as: AGC 150 GEN-M, AGC 150 Generator Marine, iE 150 Marine - Generator controller
DEIF AGC 200 Advanced Genset Controller
AGC 200 series software 4.68.2.x, genset (DG) application only.
Also known as: AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200 - Generator controller
DEIF AGC-4 Automatic Genset Controller
AGC-4 software 4.83.0 (Modbus tables revision I), genset (DG) application; mains and BTB variants share many addresses but are not covered.
Also known as: AGC-4 DG, AGC 4, Multi-line 2 AGC-4 - Generator controller
DEIF AGC-4 Mk II Automatic Genset Controller
AGC-4 Mk II software 6.31.0 (Modbus tables revision N), genset (GEN) application only.
Also known as: AGC-4 Mk2, AGC-4 MkII - Generator controller
DEIF SGC 120 / SGC 121 Single Genset Controller
SGC 120 and SGC 121 (first generation, not Mk II); the SGC 120 user manual 4189341340B covers application software 9.04.
Also known as: SGC 120, SGC 121, SGC120, SGC121 - Generator controller
DEIF SGC 120 Mk II Single Genset Controller
SGC 120 Mk II software R18.0 (Modbus tables revision C).
Also known as: SGC 120 MkII, SGC 120 Mk2
Other generator controllers register maps
- Transfer switch
Lovato Electric ATL610 automatic transfer switch controller
ATL610 ATS controller via the optical port or an EXP1010/1011/1012/1013 communication module, per protocol document I428 GB I 09 22.
Also known as: ATL610, ATL 610, EXP1012, EXP1013 - Generator controller
Lovato Electric RGK800SA stand-alone genset controller
RGK800SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800SA, RGK800 SA - Generator controller
SmartGen HGM9510N / HGM9520N / HGM9530N
HGM9510N, HGM9520N and HGM9530N paralleling genset controllers, protocol document v1.5.
Also known as: HGM9520N, HGM9530N - Power meter (transfer switch metering)
ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)
ASCO Power Manager Xp, firmware FS611842-006 (some registers AS629262-004); document 381339-221 revision I.
Also known as: ASCO Power Manager Xp, Power Manager Xp, 381339-221 - Generator controller
Datakom DKG-705
Datakom DKG-705 AMF, parallel-to-mains and dual genset synchronization unit with J1939, Modbus application manual V-02-07 (14.04.2008).
Also known as: DKG 705, DKG705 - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
All generator controllers Modbus register maps →
Source: SGC 420 Mk II Modbus tables · 4189341402 rev. C. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.