DEIF AGC-4 Automatic Genset Controller Modbus register map

Updated 19 November 2026

Short answer

The AGC-4 is DEIF's paralleling and power-management genset controller. Modbus RTU runs on option H2 (RS-485) or H9 (RS-232), and Modbus TCP on the option N Ethernet card. This map covers the genset-variant AC measurements, energy and hour counters, DC supply readings, the running-mode flags, the status flags and the control command words used for remote start, stop, breaker and mode commands.

This page lists 159 Modbus registers for the DEIF AGC-4 Automatic Genset Controller — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.

Manufacturer
DEIF
Model
AGC-4 Automatic Genset Controller
Equipment type
Generator controller
Registers
159 (19 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N1
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
4.83.0
Also known as
AGC-4 DG, AGC 4, Multi-line 2 AGC-4
Source document
AGC-4 Modbus tables · 4189341215 rev. I
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: DEIF AGC-4 Automatic Genset Controller

Integration in brief

Read input registers 501-527 and 538 with function 04 for generator values, 567-568 for DC supply, and 1019 for the active mode. Send commands by writing a word to holding register 5 or 6 with bit 0 set together with the command bit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 501Generator voltage L1-L2INT16Generator voltage L1-L2Read
IR 507Generator frequency L1INT16Generator frequencyRead
IR 513Generator current L1INT16Generator current L1Read
IR 519Generator powerINT16Generator active powerRead
IR 536Generator Export, active energy counter, totalINT32 ABCDExported kWh totalRead
IR 554Absolute running hoursINT32 ABCDAbsolute running hoursRead
IR 1019Mode flags word 1019BITMAP16Active modeRead
HR 5Control command word 5BITMAP16Remote start/stop and breaker commandsWrite

Enable Modbus control & writes

Fit option H2 (RS-485), H9 (RS-232) or option N (Ethernet). Serial settings are in parameters 7500-7520, listed in the AGC-4 parameter list 4189340688.

Byte order & addressing

Network setup

Watch out for

DEIF AGC-4 Automatic Genset Controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

159 of 159 shown
DEIF AGC-4 Automatic Genset Controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
DI0GB position ONBITRead
DI1MB Position ON (Single DG)BITRead
DI3RunningBITRead
DI4Generator voltage/frequency OKBITRead
DI5Mains failure (Single DG)BITRead
DI6Block modeBITRead
DI7Manual modeBITRead
DI8Semi-auto modeBITRead
DI9Auto modeBITRead
DI10Test modeBITRead
DI13IslandBITRead
DI14Automatic mains failure (AMF)BITRead
DI15Peak shavingBITRead
DI16Fixed powerBITRead
DI17Mains power export (MPE)BITRead
DI18Load takeover (LTO)BITRead
DI19Power managementBITRead
DI20Any alarm on PMS ID1BITRead
DI21Any alarm on PMS ID2BITRead
DI22Any alarm on PMS ID3BITRead
DI23Any alarm on PMS ID4BITRead
DI24Any alarm on PMS ID5BITRead
DI25Any alarm on PMS ID6BITRead
DI26Any alarm on PMS ID7BITRead
DI27Any alarm on PMS ID8BITRead
DI28Any alarm mains (Mains Command Unit)BITRead
DI29Battery testBITRead
DI31Ready auto-start DG1BITRead
DI32Ready auto-start DG2BITRead
DI33Ready auto-start DG3BITRead
DI34Ready auto-start DG4BITRead
DI35Ready auto-start DG5BITRead
DI36Ready auto-start DG6BITRead
DI37Ready auto-start DG7BITRead
DI38Ready auto-start DG8BITRead
DI53Mains sync. inhibitBITRead
DI54Any mains sync. inhibitBITRead
IR500Application versionINT16Read
IR501Generator voltage L1-L2INT16VRead
IR502Generator voltage L2-L3INT16VRead
IR503Generator voltage L3-L1INT16VRead
IR504Generator voltage L1-NINT16VRead
IR505Generator voltage L2-NINT16VRead
IR506Generator voltage L3-NINT16VRead
IR507Generator frequency L1INT16× 0.01HzRead
IR508Generator frequency L2INT16× 0.01HzRead
IR509Generator frequency L3INT16× 0.01HzRead
IR510Generator voltage phase angle L1-L2INT16× 0.1°Read
IR511Generator voltage phase angle L2-L3INT16× 0.1°Read
IR512Generator voltage phase angle L3-L1INT16× 0.1°Read
IR513Generator current L1INT16ARead
IR514Generator current L2INT16ARead
IR515Generator current L3INT16ARead
IR516Generator power L1INT16kWRead
IR517Generator power L2INT16kWRead
IR518Generator power L3INT16kWRead
IR519Generator powerINT16kWRead
IR520Generator reactive power L1INT16kvarRead
IR521Generator reactive power L2INT16kvarRead
IR522Generator reactive power L3INT16kvarRead
IR523Generator reactive powerINT16kvarRead
IR524Generator apparent power L1INT16kVARead
IR525Generator apparent power L2INT16kVARead
IR526Generator apparent power L3INT16kVARead
IR527Generator apparent powerINT16kVARead
IR528Generator Export reactive energy counter, totalINT32ABCDkvarhRead
IR530Generator Export, active energy counter, dayINT32ABCDkWhRead
IR532Generator Export, active energy counter, weekINT32ABCDkWhRead
IR534Generator Export, active energy counter, monthINT32ABCDkWhRead
IR536Generator Export, active energy counter, totalINT32ABCDkWhRead
IR538Generator PFINT16× 0.01Read
IR539Bus B voltage L1-L2INT16VRead
IR540Bus B voltage L2-L3INT16VRead
IR541Bus B voltage L3-L1INT16VRead
IR542Bus B voltage L1-NINT16VRead
IR543Bus B voltage L2-NINT16VRead
IR544Bus B voltage L3-NINT16VRead
IR545Bus B frequency L1INT16× 0.01HzRead
IR546Bus B frequency L2INT16× 0.01HzRead
IR547Bus B frequency L3INT16× 0.01HzRead
IR548Bus B voltage phase angle L1-L2INT16× 0.1°Read
IR549Bus B voltage phase angle L2-L3INT16× 0.1°Read
IR550Bus B voltage phase angle L3-L1INT16× 0.1°Read
IR551U BB L1 - U GEN L1 phase angleINT16× 0.1°Read
IR552U BB L2 - U GEN L2 phase angleINT16× 0.1°Read
IR553U BB L3 - U GEN L3 phase angleINT16× 0.1°Read
IR554Absolute running hoursINT32ABCDRead
IR556Relative running hoursINT32ABCDRead
IR558No. of alarmsINT16Read
IR559No. of unacknowledged alarmsINT16Read
IR560No. of active acknowledged alarmsINT16Read
IR561Running minute counter, shutdown overrideINT16Read
IR562Running hour counter, shutdown overrideINT16Read
IR563No. of GB operationsINT16Read
IR564No. of MB operationsINT16Read
IR566Start attemptsINT16Read
IR567DC supply term. 1-2INT16× 0.1VRead
IR568DC supply term. 98-99INT16× 0.1VRead
IR569Service timer 1 running hoursINT16Read
IR570Service timer 1 running daysINT16Read
IR571Service timer 2 running hoursINT16Read
IR572Service timer 2 running daysINT16Read
IR573Cos-phiINT16× 0.01Read
IR574cos phi inductive/capacitiveINT16Read0 = Inductive; 1 = Capacitive
IR576Engine speedINT16rpmRead
IR577Running hours load profileINT32ABCDRead
IR590Internal TemperatureINT16× 0.1°CRead
IR684Service timer 3 running hoursINT16Read
IR685Service timer 3 running daysINT16Read
IR686Service timer 4 running hoursINT16Read
IR687Service timer 4 running daysINT16Read
IR689Power derate valueINT16× 0.1%Read
IR700Actual nominal power (Includes derate etc.)INT16Read
IR750Generator average frequency L1INT16× 0.01HzRead
IR751Generator average frequency L2INT16× 0.01HzRead
IR752Generator average frequency L3INT16× 0.01HzRead
IR753Busbar average frequency L1INT16× 0.01HzRead
IR754Busbar average frequency L2INT16× 0.01HzRead
IR755Busbar average frequency L3INT16× 0.01HzRead
IR790Generator Export reactive energy counter, monthINT32ABCDkvarhRead
IR792Generator Export reactive energy counter, weekINT32ABCDkvarhRead
IR794Generator Export reactive energy counter, dayINT32ABCDkvarhRead
IR796Generator Import active energy counter, totalINT32ABCDkWhRead
IR798Generator Import active energy counter, monthINT32ABCDkWhRead
IR800Generator Import active energy counter, weekINT32ABCDkWhRead
IR802Generator Import active energy counter, dayINT32ABCDkWhRead
IR804Generator Import reactive energy counter, totalINT32ABCDkvarhRead
IR806Generator Import reactive energy counter, monthINT32ABCDkvarhRead
IR808Generator Import reactive energy counter, weekINT32ABCDkvarhRead
IR810Generator Import reactive energy counter, dayINT32ABCDkvarhRead
IR816Demand of peak current 1INT16Read
IR817Demand of peak current 2INT16Read
IR818Demand of peak current 3INT16Read
IR819Demand of avg. peak current 1INT16Read
IR820Demand of avg. peak current 2INT16Read
IR821Demand of avg. peak current 3INT16Read
IR822Start attempts standardINT16Read
IR823Start attempts double starterINT16Read
IR1018Status flags word 1018BITMAP16Readbit 0 = Mains failure (Single DG); bit 1 = MB position ON (Single DG); bit 2 = DG ramp down; bit 3 = Start GOV/AVR regulation; bit 4 = GB position ON; bit 5 = GB synchronising; bit 6 = Engine running; bit 7 = Running detected, timer expired; bit 8 = DG Hz/V OK, timer expired; bit 9 = Battery test ongoing; bit 10 = Shutdown override active; bit 11 = GB position OFF; bit 12 = MB position OFF; bit 13 = BB Hz/V OK; bit 14 = Single DG, MB synchronising; bit 15 = Dry mode
IR1019Mode flags word 1019Active running mode and plant mode, one bit each.BITMAP16Readbit 0 = Block mode; bit 1 = Manual mode; bit 2 = Semi auto mode; bit 3 = Auto mode; bit 4 = Test; bit 5 = Island; bit 6 = AMF; bit 7 = Peak shaving; bit 8 = Fixed power; bit 9 = Mains power export; bit 10 = Load takeover; bit 11 = Power management; bit 15 = AMF active
HR0Power regulator setpoint0 to 100 % of nominal power; used when menu 7501 selects it.INT16Read/write
HR1cos phi regulator setpoint60-100 means cos phi x 100 (100 = 1.00). Menu 7504.INT16Read/write
HR2Reactive power regulator setpoint-100 to +100 % of nominal; negative = capacitive. Menu 7505.INT16Read/write
HR3Frequency regulator setpoint-100 to +100 % = -10.0 to +10.0 % of nominal frequency. Menu 7502.INT16Read/write
HR4Voltage regulator setpoint-100 to +100 % = -10.0 to +10.0 % of nominal voltage. Menu 7503.INT16Read/write
HR5Control command word 5Start/stop, breaker, inhibit and acknowledge commands. Reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Remote start; bit 2 = Remote GB ON; bit 3 = Remote GB OFF; bit 4 = Remote stop; bit 5 = Reset GOV/AVR regulation output to offset; bit 6 = Start+sync. (semi); bit 7 = Alarm inhibit 1; bit 8 = Alarm inhibit 2; bit 9 = Alarm inhibit 3; bit 10 = Alarm ack.; bit 11 = Nominal setting 1; bit 12 = Nominal setting 2; bit 13 = Nominal setting 3; bit 14 = Nominal setting 4; bit 15 = Deload/stop (semi)
HR6Control command word 6Running mode and plant mode selection commands. Reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Island; bit 2 = Automatic mains failure (AMF); bit 3 = Peak shaving; bit 4 = Fixed power; bit 5 = Mains power export (MPE); bit 6 = Load takeover (LTO); bit 9 = MB ON (Single DG); bit 10 = MB OFF (Single DG); bit 11 = Auto start/stop; bit 12 = Manual mode; bit 13 = Auto mode; bit 14 = Semi-Auto mode; bit 15 = Test mode
HR7Control command word 7External control enables, base load, priority and application select.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = External frequency control; bit 2 = External voltage control; bit 3 = External power control; bit 4 = External reactive power control; bit 5 = External power factor control; bit 6 = Capacitive PF; bit 7 = Base load; bit 8 = 1. priority; bit 9 = Application 1; bit 10 = Application 2; bit 11 = Application 3; bit 12 = Application 4; bit 13 = Battery test; bit 15 = Synchronise clock to 4:00 a.m.
HR8Control command word 8M-Logic virtual events 1-15.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 1; bit 2 = Virtual event 2; bit 3 = Virtual event 3; bit 4 = Virtual event 4; bit 5 = Virtual event 5; bit 6 = Virtual event 6; bit 7 = Virtual event 7; bit 8 = Virtual event 8; bit 9 = Virtual event 9; bit 10 = Virtual event 10; bit 11 = Virtual event 11; bit 12 = Virtual event 12; bit 13 = Virtual event 13; bit 14 = Virtual event 14; bit 15 = Virtual event 15
HR9Control command word 9M-Logic virtual events 16-30.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 16; bit 2 = Virtual event 17; bit 3 = Virtual event 18; bit 4 = Virtual event 19; bit 5 = Virtual event 20; bit 6 = Virtual event 21; bit 7 = Virtual event 22; bit 8 = Virtual event 23; bit 9 = Virtual event 24; bit 10 = Virtual event 25; bit 11 = Virtual event 26; bit 12 = Virtual event 27; bit 13 = Virtual event 28; bit 14 = Virtual event 29; bit 15 = Virtual event 30
HR10Control command word 10Virtual events 31-32, clear log, clear parameter edits.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 31; bit 2 = Virtual event 32; bit 4 = Clear log; bit 5 = Clear Parameter edits
HR13Control command word 13Enable/disable external regulation inputs and reset horn.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Enable external frequency control; bit 2 = Disable external frequency control; bit 3 = Enable external voltage control; bit 4 = Disable external voltage control; bit 5 = Enable external power control; bit 6 = Disable external power control; bit 7 = Enable external VAr control; bit 8 = Disable external VAr control; bit 9 = Enable external CosPhi control; bit 10 = Disable external CosPhi control; bit 11 = Enable PM base load; bit 12 = Disable PM base load; bit 13 = Reset horn
HR58000Year (2003-2099)Controller clock; write to set.INT16Read/write
HR58001Month (1-12)Controller clock; write to set.INT16Read/write
HR58002Date (1-31)Controller clock; write to set.INT16Read/write
HR58003Day (1-7, Monday - Sunday)Controller clock; write to set.INT16Read/write
HR58004Hour (0-23)Controller clock; write to set.INT16Read/write
HR58005Min (0-59)Controller clock; write to set.INT16Read/write
HR58006Sec (0-59)Controller clock; write to set.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the DEIF AGC-4 Automatic Genset Controller

What Modbus registers does the DEIF AGC-4 Automatic Genset Controller have?

This map lists 159 registers: 37 discrete inputs, 103 input registers, 19 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the DEIF AGC-4 Automatic Genset Controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables give a 'Modbus address' that goes straight into the request, and also a 6-digit PLC address that is one higher (input register 501 = PLC 300502). Request 501 on the wire for generator voltage L1-L2.

What byte order does the DEIF AGC-4 Automatic Genset Controller use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the DEIF AGC-4 Automatic Genset Controller?

Start with IR 501 Generator voltage L1-L2 (Generator voltage L1-L2); IR 507 Generator frequency L1 (Generator frequency); IR 513 Generator current L1 (Generator current L1); IR 519 Generator power (Generator active power); IR 536 Generator Export, active energy counter, total (Exported kWh total); IR 554 Absolute running hours (Absolute running hours); IR 1019 Mode flags word 1019 (Active mode); HR 5 Control command word 5 (Remote start/stop and breaker commands).

How do I enable Modbus control of the DEIF AGC-4 Automatic Genset Controller?

Fit option H2 (RS-485), H9 (RS-232) or option N (Ethernet). Serial settings are in parameters 7500-7520, listed in the AGC-4 parameter list 4189340688.

Where is the official DEIF AGC-4 Automatic Genset Controller Modbus documentation?

The source is AGC-4 Modbus tables (4189341215 rev. I), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/xywdqum0/agc-4-modbus-tables-4189341215-uk.xlsx.

More DEIF Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: AGC-4 Modbus tables · 4189341215 rev. I. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.