Generator controller · Modbus register map
DEIF AGC-4 Automatic Genset Controller Modbus register map
Updated 19 November 2026
The AGC-4 is DEIF's paralleling and power-management genset controller. Modbus RTU runs on option H2 (RS-485) or H9 (RS-232), and Modbus TCP on the option N Ethernet card. This map covers the genset-variant AC measurements, energy and hour counters, DC supply readings, the running-mode flags, the status flags and the control command words used for remote start, stop, breaker and mode commands.
This page lists 159 Modbus registers for the DEIF AGC-4 Automatic Genset Controller — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.
- Manufacturer
- DEIF
- Model
- AGC-4 Automatic Genset Controller
- Equipment type
- Generator controller
- Registers
- 159 (19 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 4.83.0
- Also known as
- AGC-4 DG, AGC 4, Multi-line 2 AGC-4
- Source document
- AGC-4 Modbus tables · 4189341215 rev. I
Integration notes: DEIF AGC-4 Automatic Genset Controller
Read input registers 501-527 and 538 with function 04 for generator values, 567-568 for DC supply, and 1019 for the active mode. Send commands by writing a word to holding register 5 or 6 with bit 0 set together with the command bit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 501 | Generator voltage L1-L2 | INT16 | Generator voltage L1-L2 | Read |
| IR 507 | Generator frequency L1 | INT16 | Generator frequency | Read |
| IR 513 | Generator current L1 | INT16 | Generator current L1 | Read |
| IR 519 | Generator power | INT16 | Generator active power | Read |
| IR 536 | Generator Export, active energy counter, total | INT32 ABCD | Exported kWh total | Read |
| IR 554 | Absolute running hours | INT32 ABCD | Absolute running hours | Read |
| IR 1019 | Mode flags word 1019 | BITMAP16 | Active mode | Read |
| HR 5 | Control command word 5 | BITMAP16 | Remote start/stop and breaker commands | Write |
Enable Modbus control & writes
Fit option H2 (RS-485), H9 (RS-232) or option N (Ethernet). Serial settings are in parameters 7500-7520, listed in the AGC-4 parameter list 4189340688.
Byte order & addressing
- A command word is only accepted when bit 0 is also 1; write e.g. 0x0003 to holding 5 for remote start.
- Addresses 0-499 on function 04 are a user-configurable copy area, not fixed data.
Network setup
- Option H2 RS-485: 9600 or 19200 bit/s, 8 data bits, no parity, 1 stop bit.
- Option N: set the card's IP address with the option N configuration software; Modbus TCP port 502.
Watch out for
- Most AC values are scaled x1 (whole volts, amps, kW); check the scaling column before assuming tenths.
DEIF AGC-4 Automatic Genset Controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0 | GB position ON | BIT | Read | |||||
| DI | 1 | MB Position ON (Single DG) | BIT | Read | |||||
| DI | 3 | Running | BIT | Read | |||||
| DI | 4 | Generator voltage/frequency OK | BIT | Read | |||||
| DI | 5 | Mains failure (Single DG) | BIT | Read | |||||
| DI | 6 | Block mode | BIT | Read | |||||
| DI | 7 | Manual mode | BIT | Read | |||||
| DI | 8 | Semi-auto mode | BIT | Read | |||||
| DI | 9 | Auto mode | BIT | Read | |||||
| DI | 10 | Test mode | BIT | Read | |||||
| DI | 13 | Island | BIT | Read | |||||
| DI | 14 | Automatic mains failure (AMF) | BIT | Read | |||||
| DI | 15 | Peak shaving | BIT | Read | |||||
| DI | 16 | Fixed power | BIT | Read | |||||
| DI | 17 | Mains power export (MPE) | BIT | Read | |||||
| DI | 18 | Load takeover (LTO) | BIT | Read | |||||
| DI | 19 | Power management | BIT | Read | |||||
| DI | 20 | Any alarm on PMS ID1 | BIT | Read | |||||
| DI | 21 | Any alarm on PMS ID2 | BIT | Read | |||||
| DI | 22 | Any alarm on PMS ID3 | BIT | Read | |||||
| DI | 23 | Any alarm on PMS ID4 | BIT | Read | |||||
| DI | 24 | Any alarm on PMS ID5 | BIT | Read | |||||
| DI | 25 | Any alarm on PMS ID6 | BIT | Read | |||||
| DI | 26 | Any alarm on PMS ID7 | BIT | Read | |||||
| DI | 27 | Any alarm on PMS ID8 | BIT | Read | |||||
| DI | 28 | Any alarm mains (Mains Command Unit) | BIT | Read | |||||
| DI | 29 | Battery test | BIT | Read | |||||
| DI | 31 | Ready auto-start DG1 | BIT | Read | |||||
| DI | 32 | Ready auto-start DG2 | BIT | Read | |||||
| DI | 33 | Ready auto-start DG3 | BIT | Read | |||||
| DI | 34 | Ready auto-start DG4 | BIT | Read | |||||
| DI | 35 | Ready auto-start DG5 | BIT | Read | |||||
| DI | 36 | Ready auto-start DG6 | BIT | Read | |||||
| DI | 37 | Ready auto-start DG7 | BIT | Read | |||||
| DI | 38 | Ready auto-start DG8 | BIT | Read | |||||
| DI | 53 | Mains sync. inhibit | BIT | Read | |||||
| DI | 54 | Any mains sync. inhibit | BIT | Read | |||||
| IR | 500 | Application version | INT16 | Read | |||||
| IR | 501 | Generator voltage L1-L2 | INT16 | V | Read | ||||
| IR | 502 | Generator voltage L2-L3 | INT16 | V | Read | ||||
| IR | 503 | Generator voltage L3-L1 | INT16 | V | Read | ||||
| IR | 504 | Generator voltage L1-N | INT16 | V | Read | ||||
| IR | 505 | Generator voltage L2-N | INT16 | V | Read | ||||
| IR | 506 | Generator voltage L3-N | INT16 | V | Read | ||||
| IR | 507 | Generator frequency L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 508 | Generator frequency L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 509 | Generator frequency L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 510 | Generator voltage phase angle L1-L2 | INT16 | × 0.1 | ° | Read | |||
| IR | 511 | Generator voltage phase angle L2-L3 | INT16 | × 0.1 | ° | Read | |||
| IR | 512 | Generator voltage phase angle L3-L1 | INT16 | × 0.1 | ° | Read | |||
| IR | 513 | Generator current L1 | INT16 | A | Read | ||||
| IR | 514 | Generator current L2 | INT16 | A | Read | ||||
| IR | 515 | Generator current L3 | INT16 | A | Read | ||||
| IR | 516 | Generator power L1 | INT16 | kW | Read | ||||
| IR | 517 | Generator power L2 | INT16 | kW | Read | ||||
| IR | 518 | Generator power L3 | INT16 | kW | Read | ||||
| IR | 519 | Generator power | INT16 | kW | Read | ||||
| IR | 520 | Generator reactive power L1 | INT16 | kvar | Read | ||||
| IR | 521 | Generator reactive power L2 | INT16 | kvar | Read | ||||
| IR | 522 | Generator reactive power L3 | INT16 | kvar | Read | ||||
| IR | 523 | Generator reactive power | INT16 | kvar | Read | ||||
| IR | 524 | Generator apparent power L1 | INT16 | kVA | Read | ||||
| IR | 525 | Generator apparent power L2 | INT16 | kVA | Read | ||||
| IR | 526 | Generator apparent power L3 | INT16 | kVA | Read | ||||
| IR | 527 | Generator apparent power | INT16 | kVA | Read | ||||
| IR | 528 | Generator Export reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 530 | Generator Export, active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 532 | Generator Export, active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 534 | Generator Export, active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 536 | Generator Export, active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 538 | Generator PF | INT16 | × 0.01 | Read | ||||
| IR | 539 | Bus B voltage L1-L2 | INT16 | V | Read | ||||
| IR | 540 | Bus B voltage L2-L3 | INT16 | V | Read | ||||
| IR | 541 | Bus B voltage L3-L1 | INT16 | V | Read | ||||
| IR | 542 | Bus B voltage L1-N | INT16 | V | Read | ||||
| IR | 543 | Bus B voltage L2-N | INT16 | V | Read | ||||
| IR | 544 | Bus B voltage L3-N | INT16 | V | Read | ||||
| IR | 545 | Bus B frequency L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 546 | Bus B frequency L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 547 | Bus B frequency L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 548 | Bus B voltage phase angle L1-L2 | INT16 | × 0.1 | ° | Read | |||
| IR | 549 | Bus B voltage phase angle L2-L3 | INT16 | × 0.1 | ° | Read | |||
| IR | 550 | Bus B voltage phase angle L3-L1 | INT16 | × 0.1 | ° | Read | |||
| IR | 551 | U BB L1 - U GEN L1 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 552 | U BB L2 - U GEN L2 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 553 | U BB L3 - U GEN L3 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 554 | Absolute running hours | INT32 | ABCD | Read | ||||
| IR | 556 | Relative running hours | INT32 | ABCD | Read | ||||
| IR | 558 | No. of alarms | INT16 | Read | |||||
| IR | 559 | No. of unacknowledged alarms | INT16 | Read | |||||
| IR | 560 | No. of active acknowledged alarms | INT16 | Read | |||||
| IR | 561 | Running minute counter, shutdown override | INT16 | Read | |||||
| IR | 562 | Running hour counter, shutdown override | INT16 | Read | |||||
| IR | 563 | No. of GB operations | INT16 | Read | |||||
| IR | 564 | No. of MB operations | INT16 | Read | |||||
| IR | 566 | Start attempts | INT16 | Read | |||||
| IR | 567 | DC supply term. 1-2 | INT16 | × 0.1 | V | Read | |||
| IR | 568 | DC supply term. 98-99 | INT16 | × 0.1 | V | Read | |||
| IR | 569 | Service timer 1 running hours | INT16 | Read | |||||
| IR | 570 | Service timer 1 running days | INT16 | Read | |||||
| IR | 571 | Service timer 2 running hours | INT16 | Read | |||||
| IR | 572 | Service timer 2 running days | INT16 | Read | |||||
| IR | 573 | Cos-phi | INT16 | × 0.01 | Read | ||||
| IR | 574 | cos phi inductive/capacitive | INT16 | Read | 0 = Inductive; 1 = Capacitive | ||||
| IR | 576 | Engine speed | INT16 | rpm | Read | ||||
| IR | 577 | Running hours load profile | INT32 | ABCD | Read | ||||
| IR | 590 | Internal Temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 684 | Service timer 3 running hours | INT16 | Read | |||||
| IR | 685 | Service timer 3 running days | INT16 | Read | |||||
| IR | 686 | Service timer 4 running hours | INT16 | Read | |||||
| IR | 687 | Service timer 4 running days | INT16 | Read | |||||
| IR | 689 | Power derate value | INT16 | × 0.1 | % | Read | |||
| IR | 700 | Actual nominal power (Includes derate etc.) | INT16 | Read | |||||
| IR | 750 | Generator average frequency L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 751 | Generator average frequency L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 752 | Generator average frequency L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 753 | Busbar average frequency L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 754 | Busbar average frequency L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 755 | Busbar average frequency L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 790 | Generator Export reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 792 | Generator Export reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 794 | Generator Export reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 796 | Generator Import active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 798 | Generator Import active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 800 | Generator Import active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 802 | Generator Import active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 804 | Generator Import reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 806 | Generator Import reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 808 | Generator Import reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 810 | Generator Import reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 816 | Demand of peak current 1 | INT16 | Read | |||||
| IR | 817 | Demand of peak current 2 | INT16 | Read | |||||
| IR | 818 | Demand of peak current 3 | INT16 | Read | |||||
| IR | 819 | Demand of avg. peak current 1 | INT16 | Read | |||||
| IR | 820 | Demand of avg. peak current 2 | INT16 | Read | |||||
| IR | 821 | Demand of avg. peak current 3 | INT16 | Read | |||||
| IR | 822 | Start attempts standard | INT16 | Read | |||||
| IR | 823 | Start attempts double starter | INT16 | Read | |||||
| IR | 1018 | Status flags word 1018 | BITMAP16 | Read | bit 0 = Mains failure (Single DG); bit 1 = MB position ON (Single DG); bit 2 = DG ramp down; bit 3 = Start GOV/AVR regulation; bit 4 = GB position ON; bit 5 = GB synchronising; bit 6 = Engine running; bit 7 = Running detected, timer expired; bit 8 = DG Hz/V OK, timer expired; bit 9 = Battery test ongoing; bit 10 = Shutdown override active; bit 11 = GB position OFF; bit 12 = MB position OFF; bit 13 = BB Hz/V OK; bit 14 = Single DG, MB synchronising; bit 15 = Dry mode | ||||
| IR | 1019 | Mode flags word 1019 | Active running mode and plant mode, one bit each. | BITMAP16 | Read | bit 0 = Block mode; bit 1 = Manual mode; bit 2 = Semi auto mode; bit 3 = Auto mode; bit 4 = Test; bit 5 = Island; bit 6 = AMF; bit 7 = Peak shaving; bit 8 = Fixed power; bit 9 = Mains power export; bit 10 = Load takeover; bit 11 = Power management; bit 15 = AMF active | |||
| HR | 0 | Power regulator setpoint | 0 to 100 % of nominal power; used when menu 7501 selects it. | INT16 | Read/write | ||||
| HR | 1 | cos phi regulator setpoint | 60-100 means cos phi x 100 (100 = 1.00). Menu 7504. | INT16 | Read/write | ||||
| HR | 2 | Reactive power regulator setpoint | -100 to +100 % of nominal; negative = capacitive. Menu 7505. | INT16 | Read/write | ||||
| HR | 3 | Frequency regulator setpoint | -100 to +100 % = -10.0 to +10.0 % of nominal frequency. Menu 7502. | INT16 | Read/write | ||||
| HR | 4 | Voltage regulator setpoint | -100 to +100 % = -10.0 to +10.0 % of nominal voltage. Menu 7503. | INT16 | Read/write | ||||
| HR | 5 | Control command word 5 | Start/stop, breaker, inhibit and acknowledge commands. Reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Remote start; bit 2 = Remote GB ON; bit 3 = Remote GB OFF; bit 4 = Remote stop; bit 5 = Reset GOV/AVR regulation output to offset; bit 6 = Start+sync. (semi); bit 7 = Alarm inhibit 1; bit 8 = Alarm inhibit 2; bit 9 = Alarm inhibit 3; bit 10 = Alarm ack.; bit 11 = Nominal setting 1; bit 12 = Nominal setting 2; bit 13 = Nominal setting 3; bit 14 = Nominal setting 4; bit 15 = Deload/stop (semi) | |||
| HR | 6 | Control command word 6 | Running mode and plant mode selection commands. Reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Island; bit 2 = Automatic mains failure (AMF); bit 3 = Peak shaving; bit 4 = Fixed power; bit 5 = Mains power export (MPE); bit 6 = Load takeover (LTO); bit 9 = MB ON (Single DG); bit 10 = MB OFF (Single DG); bit 11 = Auto start/stop; bit 12 = Manual mode; bit 13 = Auto mode; bit 14 = Semi-Auto mode; bit 15 = Test mode | |||
| HR | 7 | Control command word 7 | External control enables, base load, priority and application select. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = External frequency control; bit 2 = External voltage control; bit 3 = External power control; bit 4 = External reactive power control; bit 5 = External power factor control; bit 6 = Capacitive PF; bit 7 = Base load; bit 8 = 1. priority; bit 9 = Application 1; bit 10 = Application 2; bit 11 = Application 3; bit 12 = Application 4; bit 13 = Battery test; bit 15 = Synchronise clock to 4:00 a.m. | |||
| HR | 8 | Control command word 8 | M-Logic virtual events 1-15. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 1; bit 2 = Virtual event 2; bit 3 = Virtual event 3; bit 4 = Virtual event 4; bit 5 = Virtual event 5; bit 6 = Virtual event 6; bit 7 = Virtual event 7; bit 8 = Virtual event 8; bit 9 = Virtual event 9; bit 10 = Virtual event 10; bit 11 = Virtual event 11; bit 12 = Virtual event 12; bit 13 = Virtual event 13; bit 14 = Virtual event 14; bit 15 = Virtual event 15 | |||
| HR | 9 | Control command word 9 | M-Logic virtual events 16-30. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 16; bit 2 = Virtual event 17; bit 3 = Virtual event 18; bit 4 = Virtual event 19; bit 5 = Virtual event 20; bit 6 = Virtual event 21; bit 7 = Virtual event 22; bit 8 = Virtual event 23; bit 9 = Virtual event 24; bit 10 = Virtual event 25; bit 11 = Virtual event 26; bit 12 = Virtual event 27; bit 13 = Virtual event 28; bit 14 = Virtual event 29; bit 15 = Virtual event 30 | |||
| HR | 10 | Control command word 10 | Virtual events 31-32, clear log, clear parameter edits. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 31; bit 2 = Virtual event 32; bit 4 = Clear log; bit 5 = Clear Parameter edits | |||
| HR | 13 | Control command word 13 | Enable/disable external regulation inputs and reset horn. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Enable external frequency control; bit 2 = Disable external frequency control; bit 3 = Enable external voltage control; bit 4 = Disable external voltage control; bit 5 = Enable external power control; bit 6 = Disable external power control; bit 7 = Enable external VAr control; bit 8 = Disable external VAr control; bit 9 = Enable external CosPhi control; bit 10 = Disable external CosPhi control; bit 11 = Enable PM base load; bit 12 = Disable PM base load; bit 13 = Reset horn | |||
| HR | 58000 | Year (2003-2099) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58001 | Month (1-12) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58002 | Date (1-31) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58003 | Day (1-7, Monday - Sunday) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58004 | Hour (0-23) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58005 | Min (0-59) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58006 | Sec (0-59) | Controller clock; write to set. | INT16 | Read/write |
Notes on this map
- The source is an Excel workbook. Each row has a scaling exponent x; the value is raw x 10^-x, so x=2 is scale 0.01. Units are as printed.
- 32-bit values: the tables mark every 32-bit register with data format ABCD (high word at the lower address); DEIF's AGC 150 Modbus server manual (4189341435, section 3.4) uses the same notation with that meaning.
- Only rows marked for the DG (genset) application are listed. Mains and BTB controllers reuse the same addresses for mains or bus A values.
- Left out: the configurable area 0-499 (contents set by the Modbus configurator), analogue and multi-input readings (meaning depends on configuration), CIO module inputs, alarm bits, EIC engine data, DAVR data, power-management data and the 208 command-flag coils. They are all in the workbook.
- Parameters are read and written through address areas plus the parameter's USW address (for example holding 4000-5999 'values used'); see the Option H2/H9 document 4189341180.
- Control command bit words read back 0; the live state of the command words can be read on input registers 642-655 (not listed).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DEIF AGC-4 Automatic Genset Controller
What Modbus registers does the DEIF AGC-4 Automatic Genset Controller have?
This map lists 159 registers: 37 discrete inputs, 103 input registers, 19 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DEIF AGC-4 Automatic Genset Controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables give a 'Modbus address' that goes straight into the request, and also a 6-digit PLC address that is one higher (input register 501 = PLC 300502). Request 501 on the wire for generator voltage L1-L2.
What byte order does the DEIF AGC-4 Automatic Genset Controller use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the DEIF AGC-4 Automatic Genset Controller?
Start with IR 501 Generator voltage L1-L2 (Generator voltage L1-L2); IR 507 Generator frequency L1 (Generator frequency); IR 513 Generator current L1 (Generator current L1); IR 519 Generator power (Generator active power); IR 536 Generator Export, active energy counter, total (Exported kWh total); IR 554 Absolute running hours (Absolute running hours); IR 1019 Mode flags word 1019 (Active mode); HR 5 Control command word 5 (Remote start/stop and breaker commands).
How do I enable Modbus control of the DEIF AGC-4 Automatic Genset Controller?
Fit option H2 (RS-485), H9 (RS-232) or option N (Ethernet). Serial settings are in parameters 7500-7520, listed in the AGC-4 parameter list 4189340688.
Where is the official DEIF AGC-4 Automatic Genset Controller Modbus documentation?
The source is AGC-4 Modbus tables (4189341215 rev. I), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/xywdqum0/agc-4-modbus-tables-4189341215-uk.xlsx.
More DEIF Modbus register maps
- Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF AGC 150 Generator Marine controller
AGC 150 Marine software 1.39.0 (marine Modbus server tables revision E), GEN-M (marine genset) controller type. The iE 150 Marine tables 4189341431 rev. H match these tables.
Also known as: AGC 150 GEN-M, AGC 150 Generator Marine, iE 150 Marine - Generator controller
DEIF AGC 200 Advanced Genset Controller
AGC 200 series software 4.68.2.x, genset (DG) application only.
Also known as: AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200 - Generator controller
DEIF AGC-4 Mk II Automatic Genset Controller
AGC-4 Mk II software 6.31.0 (Modbus tables revision N), genset (GEN) application only.
Also known as: AGC-4 Mk2, AGC-4 MkII - Generator controller
DEIF SGC 120 / SGC 121 Single Genset Controller
SGC 120 and SGC 121 (first generation, not Mk II); the SGC 120 user manual 4189341340B covers application software 9.04.
Also known as: SGC 120, SGC 121, SGC120, SGC121 - Generator controller
DEIF SGC 120 Mk II Single Genset Controller
SGC 120 Mk II software R18.0 (Modbus tables revision C).
Also known as: SGC 120 MkII, SGC 120 Mk2 - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2
Other generator controllers register maps
- Generator controller
Kohler Decision-Maker 6000 generator set controller
Kohler Decision-Maker 6000 generator set controllers, Modbus RTU on the controller's RS-485/RS-232 port, per section 8 of TP-6113.
Also known as: Decision-Maker 6000, DEC 6000, Kohler 6000 controller - Generator controller
Lovato Electric RGK700 AMF genset controller
RGK700, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700, RGK700 AMF - Generator controller
Lovato Electric RGK900SA genset paralleling controller (stand-alone)
RGK900SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900SA, RGK900 SA - Generator controller
Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)
easYgen-2200/2300/2500, data protocol 5100 (basic visualization), per manual 37535D.
Also known as: easYgen-2200, easYgen-2300, easYgen-2500, easYgen-2000 Series - Generator controller (paralleling master control)
Cummins MCM3320 master control module (Modbus RTU)
Cummins MCM3320 master control modules on their RS-485 Modbus RTU port, per section 10 of A029X159 Issue 7.
Also known as: MCM3320, MCM 3320, PowerCommand MCM3320 - Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller
All generator controllers Modbus register maps →
Source: AGC-4 Modbus tables · 4189341215 rev. I. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.