Generator controller · Modbus register map

DEIF AGC 150 Generator controller Modbus register map

Updated 19 November 2026

Short answer

The AGC 150 is DEIF's single and paralleling genset controller. It is a Modbus server on Ethernet (Modbus TCP) and on its RS-485 ports (Modbus RTU). This map lists the GEN-type AC measurements, energy and hour counters, DC supply, mode and status flags, and the control command words used for remote start, stop, breaker and mode commands.

This page lists 197 Modbus registers for the DEIF AGC 150 Generator controller — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.

Manufacturer
DEIF
Model
AGC 150 Generator controller
Equipment type
Generator controller
Registers
197 (19 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
3
Default serial
9600 baud
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
1.39.0
Also known as
AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN
Source document
AGC 150 Modbus server tables · 4189341212 rev. Z
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: DEIF AGC 150 Generator controller

Integration in brief

Read input registers 501-538 with function 04 for generator values and 1019 for the active mode. Write holding register 5 or 6 with bit 0 set plus the command bit to start, stop, open/close breakers or change mode.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 501Generator voltage L1-L2INT16Generator voltage L1-L2Read
IR 507Generator frequency L1INT16Generator frequencyRead
IR 513Generator current L1INT16Generator current L1Read
IR 519Generator powerINT16Generator active powerRead
IR 554Absolute running hoursINT32 ABCDRunning hoursRead
IR 1019Mode flags word 1019BITMAP16Active modeRead
HR 5Control command word 5BITMAP16Remote start/stop and breaker commandsWrite

Enable Modbus control & writes

RS-485: set ID (7511/7521) and speed (7512/7522) under Communication > RS485. Ethernet: set the IP under Settings > Communication > Ethernet setup or in the utility software.

Communication loss & watchdog

RS-485 communication error: enable with 7516/7526, timer 7513/7523 (1-100 s, default 10 s), fail class 7517/7527 (default Warning).

Byte order & addressing

Network setup

Watch out for

DEIF AGC 150 Generator controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

197 of 197 shown
DEIF AGC 150 Generator controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
DI0GB position ONBITRead
DI1MB position ONBITRead
DI3RunningBITRead
DI4Generator voltage/frequency OKBITRead
DI5Mains failure (Single DG)BITRead
DI6BLOCK modeBITRead
DI7No Regulation modeBITRead
DI8MANUAL modeBITRead
DI9AUTO modeBITRead
DI10TEST modeBITRead
DI11GB position OFFBITRead
DI12MB position OFFBITRead
DI13IslandBITRead
DI14Automatic mains failure (AMF)BITRead
DI15Peak shavingBITRead
DI16Fixed powerBITRead
DI17Mains power export (MPE)BITRead
DI18Load takeover (LTO)BITRead
DI19Power managementBITRead
DI20Any alarm on PMS ID1BITRead
DI21Any alarm on PMS ID2BITRead
DI22Any alarm on PMS ID3BITRead
DI23Any alarm on PMS ID4BITRead
DI24Any alarm on PMS ID5BITRead
DI25Any alarm on PMS ID6BITRead
DI26Any alarm on PMS ID7BITRead
DI27Any alarm on PMS ID8BITRead
DI28Any alarm mains (Mains Command Unit)BITRead
DI29Battery testBITRead
DI31Ready AUTO-start GEN1BITRead
DI32Ready AUTO-start GEN2BITRead
DI33Ready AUTO-start GEN3BITRead
DI34Ready AUTO-start GEN4BITRead
DI35Ready AUTO-start GEN5BITRead
DI36Ready AUTO-start GEN6BITRead
DI37Ready AUTO-start GEN7BITRead
DI38Ready AUTO-start GEN8BITRead
DI53Mains sync. inhibitBITRead
DI54Any mains sync. inhibitBITRead
DI7713rd party loadshare statusBITRead
DI7723rd party digital loadshare protocolBITRead
DI7733rd party loadshare active power setpointBITRead
DI7743rd party loadshare reactive power setpointBITRead
DI7753rd party loadshare number of unitsBITRead
DI7763rd party loadshare number of active unitsBITRead
IR500Application versionINT16Read
IR501Generator voltage L1-L2INT16VRead
IR502Generator voltage L2-L3INT16VRead
IR503Generator voltage L3-L1INT16VRead
IR504Generator voltage L1-NINT16VRead
IR505Generator voltage L2-NINT16VRead
IR506Generator voltage L3-NINT16VRead
IR507Generator frequency L1INT16× 0.01HzRead
IR508Generator frequency L2INT16× 0.01HzRead
IR509Generator frequency L3INT16× 0.01HzRead
IR510Generator voltage phase angle L1-L2INT16× 0.1°Read
IR511Generator voltage phase angle L2-L3INT16× 0.1°Read
IR512Generator voltage phase angle L3-L1INT16× 0.1°Read
IR513Generator current L1INT16ARead
IR514Generator current L2INT16ARead
IR515Generator current L3INT16ARead
IR516Generator power L1INT16kWRead
IR517Generator power L2INT16kWRead
IR518Generator power L3INT16kWRead
IR519Generator powerINT16kWRead
IR520Generator reactive power L1INT16kvarRead
IR521Generator reactive power L2INT16kvarRead
IR522Generator reactive power L3INT16kvarRead
IR523Generator reactive powerINT16kvarRead
IR524Generator apparent power L1INT16kVARead
IR525Generator apparent power L2INT16kVARead
IR526Generator apparent power L3INT16kVARead
IR527Generator apparent powerINT16kVARead
IR528Generator Export reactive energy counter, totalINT32ABCDkvarhRead
IR530Generator Export, active energy counter, dayINT32ABCDkWhRead
IR532Generator Export, active energy counter, weekINT32ABCDkWhRead
IR534Generator Export, active energy counter, monthINT32ABCDkWhRead
IR536Generator Export, active energy counter, totalINT32ABCDkWhRead
IR538Generator PFINT16× 0.01Read
IR539Bus B voltage L1-L2INT16VRead
IR540Bus B voltage L2-L3INT16VRead
IR541Bus B voltage L3-L1INT16VRead
IR542Bus B voltage L1-NINT16VRead
IR543Bus B voltage L2-NINT16VRead
IR544Bus B voltage L3-NINT16VRead
IR545Bus B frequency L1INT16× 0.01HzRead
IR546Bus B frequency L2INT16× 0.01HzRead
IR547Bus B frequency L3INT16× 0.01HzRead
IR548Bus B voltage phase angle L1-L2INT16× 0.1°Read
IR549Bus B voltage phase angle L2-L3INT16× 0.1°Read
IR550Bus B voltage phase angle L3-L1INT16× 0.1°Read
IR551U BB L1 - U GEN L1 phase angleINT16× 0.1°Read
IR552U BB L2 - U GEN L2 phase angleINT16× 0.1°Read
IR553U BB L3 - U GEN L3 phase angleINT16× 0.1°Read
IR554Absolute running hoursINT32ABCDRead
IR556Relative running hoursINT32ABCDRead
IR558No. of alarmsINT16Read
IR559No. of unacknowledged alarmsINT16Read
IR560No. of active acknowledged alarmsINT16Read
IR561Running minute counter, shutdown overrideINT16Read
IR562Running hour counter, shutdown overrideINT16Read
IR563No. of GB operationsINT16Read
IR564No. of MB operationsINT16Read
IR566Start attemptsINT16Read
IR567DC supply term. 1-2INT16× 0.1VRead
IR569Service timer 1 running hoursINT16Read
IR570Service timer 1 running daysINT16Read
IR571Service timer 2 running hoursINT16Read
IR572Service timer 2 running daysINT16Read
IR573Cos-phiINT16× 0.01Read
IR574cos phi inductive/capacitiveINT16Read0 = Inductive; 1 = Capacitive
IR576RPM (revolutions per minute)INT16rpmRead
IR577Running hours load profileINT32ABCDRead
IR689Power derate valueINT16× 0.1%Read
IR700Actual nominal power (Includes derate etc.)INT16Read
IR747Generator power (% of nominal)INT16%Read
IR748Generator reactive power (% of nominal)INT16%Read
IR7504th current input: I neutral (true RMS)INT16ARead
IR7514th current input: I ground (3rd harmonic filter)INT16ARead
IR7524th current input: Apparent powerINT16kVARead
IR7534th current input: Active powerINT16kWRead
IR7544th current input: Reactive powerINT16kvarRead
IR7554th current input: Cos-phiINT16× 0.01Read
IR756cos phi inductive/capacitiveINT16Read0 = Inductive; 1 = Capacitive
IR7574th current input: Power factorINT16× 0.01Read
IR760Absolute running minutesINT16minRead
IR7644th current input: I busbar (true RMS)INT16ARead
IR765Active Power LoadINT32ABCDkWRead
IR790Generator Export reactive energy counter, monthINT32ABCDkvarhRead
IR792Generator Export reactive energy counter, weekINT32ABCDkvarhRead
IR794Generator Export reactive energy counter, dayINT32ABCDkvarhRead
IR796Generator Import active energy counter, totalINT32ABCDkWhRead
IR798Generator Import active energy counter, monthINT32ABCDkWhRead
IR800Generator Import active energy counter, weekINT32ABCDkWhRead
IR802Generator Import active energy counter, dayINT32ABCDkWhRead
IR804Generator Import reactive energy counter, totalINT32ABCDkvarhRead
IR806Generator Import reactive energy counter, monthINT32ABCDkvarhRead
IR808Generator Import reactive energy counter, weekINT32ABCDkvarhRead
IR810Generator Import reactive energy counter, dayINT32ABCDkvarhRead
IR816Demand of peak current 1INT16Read
IR817Demand of peak current 2INT16Read
IR818Demand of peak current 3INT16Read
IR819Demand of avg. peak current 1INT16Read
IR820Demand of avg. peak current 2INT16Read
IR821Demand of avg. peak current 3INT16Read
IR822Start attempts standardINT16Read
IR823Start attempts double starterINT16Read
IR833P ref actualINT16Read
IR1018Status flags word 1018One flag per bit.BITMAP16Readbit 0 = Mains failure (Single DG); bit 1 = MB position ON (Single DG); bit 2 = DG ramp down; bit 3 = Start GOV/AVR regulation; bit 4 = GB position ON; bit 5 = GB synchronising; bit 6 = Engine running; bit 7 = Running detected, timer expired; bit 8 = DG Hz/V OK, timer expired; bit 9 = Battery test ongoing; bit 10 = Shutdown override active; bit 11 = GB position OFF; bit 12 = MB position OFF; bit 13 = BB Hz/V OK; bit 14 = Single DG, MB synchronising; bit 15 = Dry mode
IR1019Mode flags word 1019Active running mode and plant mode, one bit each.BITMAP16Readbit 0 = BLOCK mode; bit 1 = No Regulation mode; bit 2 = MANUAL mode; bit 3 = AUTO mode; bit 4 = TEST; bit 5 = Island; bit 6 = AMF; bit 7 = Peak shaving; bit 8 = Fixed power; bit 9 = Mains power export; bit 10 = Load takeover; bit 11 = Power management; bit 15 = AMF active
IR1278Mlogic event counter 1INT16Read
IR1279Mlogic event counter 2INT16Read
IR1280Mlogic event counter 3INT16Read
IR1281Mlogic event counter 4INT16Read
IR1282Mlogic event counter 5INT16Read
IR1283Mlogic event counter 6INT16Read
IR1284Mlogic event counter 7INT16Read
IR1285Mlogic event counter 8INT16Read
IR1842BB Export, active energy counter, totalINT32ABCDkWhRead
IR1844BB Export, active energy counter, monthINT32ABCDkWhRead
IR1846BB Export, active energy counter, weekINT32ABCDkWhRead
IR1848BB Export, active energy counter, dayINT32ABCDkWhRead
IR1850BB Export, reactive energy counter, totalINT32ABCDkvarhRead
IR1852BB Export, reactive energy counter, monthINT32ABCDkvarhRead
IR1854BB Export, reactive energy counter, weekINT32ABCDkvarhRead
IR1856BB Export, reactive energy counter, dayINT32ABCDkvarhRead
IR1858BB Import, active energy counter, totalINT32ABCDkWhRead
IR1860BB Import, active energy counter, monthINT32ABCDkWhRead
IR1862BB Import, active energy counter, weekINT32ABCDkWhRead
IR1864BB Import, active energy counter, dayINT32ABCDkWhRead
IR1866BB Import, reactive energy counter, totalINT32ABCDkvarhRead
IR1868BB Import, reactive energy counter, monthINT32ABCDkvarhRead
IR1870BB Import, reactive energy counter, weekINT32ABCDkvarhRead
IR1872BB Import, reactive energy counter, dayINT32ABCDkvarhRead
IR1900General purpose PID 1 prioritized inputINT16Read
IR1901General purpose PID 2 prioritized inputINT16Read
IR1902General purpose PID 3 prioritized inputINT16Read
IR1903General purpose PID 4 prioritized inputINT16Read
HR0Power regulator setpoint0 to 100 % of nominal power; activated in menu 7501.INT16Read/write
HR1cosPhi regulator setpoint60-100 means cos phi x 100 (100 = 1.00). Menu 7504.INT16Read/write
HR2Reactive power regulator setpoint-100 to +100 % of nominal; negative = capacitive. Menu 7505.INT16Read/write
HR3Frequency regulator setpoint-100 to +100 % = -10.0 to +10.0 % of nominal frequency. Menu 7502.INT16Read/write
HR4Voltage regulator setpoint-100 to +100 % = -10.0 to +10.0 % of nominal voltage. Menu 7503.INT16Read/write
HR5Control command word 5Write-only command bits; reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Remote start; bit 2 = Remote GB ON; bit 3 = Remote GB OFF; bit 4 = Remote stop; bit 5 = Reset GOV/AVR regulation output to offset; bit 6 = Start + sync. (MAN); bit 7 = Alarm inhibit 1; bit 8 = Alarm inhibit 2; bit 9 = Alarm inhibit 3; bit 10 = Alarm ack.; bit 11 = Nominal setting 1; bit 12 = Nominal setting 2; bit 13 = Nominal setting 3; bit 14 = Nominal setting 4; bit 15 = Deload and stop (MAN)
HR6Control command word 6Write-only command bits; reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Island; bit 2 = Automatic mains failure (AMF); bit 3 = Peak shaving; bit 4 = Fixed power; bit 5 = Mains power export (MPE); bit 6 = Load takeover (LTO); bit 9 = MB ON (Single DG); bit 10 = MB OFF (Single DG); bit 11 = Auto start/stop; bit 12 = NO REGULATION mode; bit 13 = AUTO mode; bit 14 = MANUAL mode; bit 15 = TEST mode
HR7Control command word 7Write-only command bits; reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = External frequency control; bit 2 = External voltage control; bit 3 = External power control; bit 4 = External reactive power control; bit 5 = External power factor control; bit 6 = Capacitive PF; bit 7 = Base load; bit 8 = 1. priority; bit 9 = Application 1; bit 10 = Application 2; bit 11 = Application 3; bit 12 = Application 4; bit 13 = Battery test; bit 15 = Synchronise clock to 4:00 a.m.
HR8Control command word 8Write-only command bits; reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual toggle event 1; bit 2 = Virtual toggle event 2; bit 3 = Virtual toggle event 3; bit 4 = Virtual toggle event 4; bit 5 = Virtual toggle event 5; bit 6 = Virtual toggle event 6; bit 7 = Virtual toggle event 7; bit 8 = Virtual toggle event 8; bit 9 = Virtual toggle event 9; bit 10 = Virtual toggle event 10; bit 11 = Virtual toggle event 11; bit 12 = Virtual toggle event 12; bit 13 = Virtual toggle event 13; bit 14 = Virtual toggle event 14; bit 15 = Virtual toggle event 15
HR9Control command word 9Write-only command bits; reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual toggle event 16; bit 2 = Virtual toggle event 17; bit 3 = Virtual toggle event 18; bit 4 = Virtual toggle event 19; bit 5 = Virtual toggle event 20; bit 6 = Virtual toggle event 21; bit 7 = Virtual toggle event 22; bit 8 = Virtual toggle event 23; bit 9 = Virtual toggle event 24; bit 10 = Virtual toggle event 25; bit 11 = Virtual toggle event 26; bit 12 = Virtual toggle event 27; bit 13 = Virtual toggle event 28; bit 14 = Virtual toggle event 29; bit 15 = Virtual toggle event 30
HR10Control command word 10Write-only command bits; reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 31; bit 2 = Virtual event 32; bit 4 = Clear log; bit 5 = Clear Parameter edits; bit 8 = Nominal setting 5; bit 9 = Nominal setting 6
HR13Control command word 13Write-only command bits; reads back 0.BITMAP16Writebit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Enable external frequency control; bit 2 = Disable external frequency control; bit 3 = Enable external voltage control; bit 4 = Disable external voltage control; bit 5 = Enable external power control; bit 6 = Disable external power control; bit 7 = Enable external VAr control; bit 8 = Disable external VAr control; bit 9 = Enable external CosPhi control; bit 10 = Disable external CosPhi control; bit 11 = Enable PM base load; bit 12 = Disable PM base load; bit 13 = Reset horn
HR58000Year (2003-2099)Controller clock; write to set.INT16Read/write
HR58001Month (1-12)Controller clock; write to set.INT16Read/write
HR58002Date (1-31)Controller clock; write to set.INT16Read/write
HR58003Day (1-7, Monday - Sunday)Controller clock; write to set.INT16Read/write
HR58004Hour (0-23)Controller clock; write to set.INT16Read/write
HR58005Min (0-59)Controller clock; write to set.INT16Read/write
HR58006Sec (0-59)Controller clock; write to set.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the DEIF AGC 150 Generator controller

What Modbus registers does the DEIF AGC 150 Generator controller have?

This map lists 197 registers: 45 discrete inputs, 133 input registers, 19 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the DEIF AGC 150 Generator controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The 'Modbus address' column is the address in the request. The tables also print a 6-digit PLC address one higher (input 501 = PLC 300502).

What byte order does the DEIF AGC 150 Generator controller use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the DEIF AGC 150 Generator controller?

Start with IR 501 Generator voltage L1-L2 (Generator voltage L1-L2); IR 507 Generator frequency L1 (Generator frequency); IR 513 Generator current L1 (Generator current L1); IR 519 Generator power (Generator active power); IR 554 Absolute running hours (Running hours); IR 1019 Mode flags word 1019 (Active mode); HR 5 Control command word 5 (Remote start/stop and breaker commands).

How do I enable Modbus control of the DEIF AGC 150 Generator controller?

RS-485: set ID (7511/7521) and speed (7512/7522) under Communication > RS485. Ethernet: set the IP under Settings > Communication > Ethernet setup or in the utility software.

What happens when the DEIF AGC 150 Generator controller loses Modbus communication?

RS-485 communication error: enable with 7516/7526, timer 7513/7523 (1-100 s, default 10 s), fail class 7517/7527 (default Warning).

Where is the official DEIF AGC 150 Generator controller Modbus documentation?

The source is AGC 150 Modbus server tables (4189341212 rev. Z), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/f2hiadel/agc-150-modbus-server-tables-4189341212-uk.xlsx.

More DEIF Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: AGC 150 Modbus server tables · 4189341212 rev. Z. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.