- Home
- Modbus register maps
- DEIF
- AGC 150 Generator controller
Generator controller · Modbus register map
DEIF AGC 150 Generator controller Modbus register map
Updated 19 November 2026
The AGC 150 is DEIF's single and paralleling genset controller. It is a Modbus server on Ethernet (Modbus TCP) and on its RS-485 ports (Modbus RTU). This map lists the GEN-type AC measurements, energy and hour counters, DC supply, mode and status flags, and the control command words used for remote start, stop, breaker and mode commands.
This page lists 197 Modbus registers for the DEIF AGC 150 Generator controller — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.
- Manufacturer
- DEIF
- Model
- AGC 150 Generator controller
- Equipment type
- Generator controller
- Registers
- 197 (19 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 3
- Default serial
- 9600 baud
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 1.39.0
- Also known as
- AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN
- Source document
- AGC 150 Modbus server tables · 4189341212 rev. Z
Integration notes: DEIF AGC 150 Generator controller
Read input registers 501-538 with function 04 for generator values and 1019 for the active mode. Write holding register 5 or 6 with bit 0 set plus the command bit to start, stop, open/close breakers or change mode.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 501 | Generator voltage L1-L2 | INT16 | Generator voltage L1-L2 | Read |
| IR 507 | Generator frequency L1 | INT16 | Generator frequency | Read |
| IR 513 | Generator current L1 | INT16 | Generator current L1 | Read |
| IR 519 | Generator power | INT16 | Generator active power | Read |
| IR 554 | Absolute running hours | INT32 ABCD | Running hours | Read |
| IR 1019 | Mode flags word 1019 | BITMAP16 | Active mode | Read |
| HR 5 | Control command word 5 | BITMAP16 | Remote start/stop and breaker commands | Write |
Enable Modbus control & writes
RS-485: set ID (7511/7521) and speed (7512/7522) under Communication > RS485. Ethernet: set the IP under Settings > Communication > Ethernet setup or in the utility software.
Communication loss & watchdog
RS-485 communication error: enable with 7516/7526, timer 7513/7523 (1-100 s, default 10 s), fail class 7517/7527 (default Warning).
Byte order & addressing
- A command word is ignored unless bit 0 is 1 in the same write.
- Function 04 addresses 0-499 are a user-configurable copy area.
Network setup
- RS-485 default ID 3 and 9600 baud; 9600, 19200, 38400 or 115200 baud selectable.
Watch out for
- AC voltages, currents and powers are whole units (scale 1); frequency and power factor use 0.01, and DC supply voltage uses 0.1.
DEIF AGC 150 Generator controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0 | GB position ON | BIT | Read | |||||
| DI | 1 | MB position ON | BIT | Read | |||||
| DI | 3 | Running | BIT | Read | |||||
| DI | 4 | Generator voltage/frequency OK | BIT | Read | |||||
| DI | 5 | Mains failure (Single DG) | BIT | Read | |||||
| DI | 6 | BLOCK mode | BIT | Read | |||||
| DI | 7 | No Regulation mode | BIT | Read | |||||
| DI | 8 | MANUAL mode | BIT | Read | |||||
| DI | 9 | AUTO mode | BIT | Read | |||||
| DI | 10 | TEST mode | BIT | Read | |||||
| DI | 11 | GB position OFF | BIT | Read | |||||
| DI | 12 | MB position OFF | BIT | Read | |||||
| DI | 13 | Island | BIT | Read | |||||
| DI | 14 | Automatic mains failure (AMF) | BIT | Read | |||||
| DI | 15 | Peak shaving | BIT | Read | |||||
| DI | 16 | Fixed power | BIT | Read | |||||
| DI | 17 | Mains power export (MPE) | BIT | Read | |||||
| DI | 18 | Load takeover (LTO) | BIT | Read | |||||
| DI | 19 | Power management | BIT | Read | |||||
| DI | 20 | Any alarm on PMS ID1 | BIT | Read | |||||
| DI | 21 | Any alarm on PMS ID2 | BIT | Read | |||||
| DI | 22 | Any alarm on PMS ID3 | BIT | Read | |||||
| DI | 23 | Any alarm on PMS ID4 | BIT | Read | |||||
| DI | 24 | Any alarm on PMS ID5 | BIT | Read | |||||
| DI | 25 | Any alarm on PMS ID6 | BIT | Read | |||||
| DI | 26 | Any alarm on PMS ID7 | BIT | Read | |||||
| DI | 27 | Any alarm on PMS ID8 | BIT | Read | |||||
| DI | 28 | Any alarm mains (Mains Command Unit) | BIT | Read | |||||
| DI | 29 | Battery test | BIT | Read | |||||
| DI | 31 | Ready AUTO-start GEN1 | BIT | Read | |||||
| DI | 32 | Ready AUTO-start GEN2 | BIT | Read | |||||
| DI | 33 | Ready AUTO-start GEN3 | BIT | Read | |||||
| DI | 34 | Ready AUTO-start GEN4 | BIT | Read | |||||
| DI | 35 | Ready AUTO-start GEN5 | BIT | Read | |||||
| DI | 36 | Ready AUTO-start GEN6 | BIT | Read | |||||
| DI | 37 | Ready AUTO-start GEN7 | BIT | Read | |||||
| DI | 38 | Ready AUTO-start GEN8 | BIT | Read | |||||
| DI | 53 | Mains sync. inhibit | BIT | Read | |||||
| DI | 54 | Any mains sync. inhibit | BIT | Read | |||||
| DI | 771 | 3rd party loadshare status | BIT | Read | |||||
| DI | 772 | 3rd party digital loadshare protocol | BIT | Read | |||||
| DI | 773 | 3rd party loadshare active power setpoint | BIT | Read | |||||
| DI | 774 | 3rd party loadshare reactive power setpoint | BIT | Read | |||||
| DI | 775 | 3rd party loadshare number of units | BIT | Read | |||||
| DI | 776 | 3rd party loadshare number of active units | BIT | Read | |||||
| IR | 500 | Application version | INT16 | Read | |||||
| IR | 501 | Generator voltage L1-L2 | INT16 | V | Read | ||||
| IR | 502 | Generator voltage L2-L3 | INT16 | V | Read | ||||
| IR | 503 | Generator voltage L3-L1 | INT16 | V | Read | ||||
| IR | 504 | Generator voltage L1-N | INT16 | V | Read | ||||
| IR | 505 | Generator voltage L2-N | INT16 | V | Read | ||||
| IR | 506 | Generator voltage L3-N | INT16 | V | Read | ||||
| IR | 507 | Generator frequency L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 508 | Generator frequency L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 509 | Generator frequency L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 510 | Generator voltage phase angle L1-L2 | INT16 | × 0.1 | ° | Read | |||
| IR | 511 | Generator voltage phase angle L2-L3 | INT16 | × 0.1 | ° | Read | |||
| IR | 512 | Generator voltage phase angle L3-L1 | INT16 | × 0.1 | ° | Read | |||
| IR | 513 | Generator current L1 | INT16 | A | Read | ||||
| IR | 514 | Generator current L2 | INT16 | A | Read | ||||
| IR | 515 | Generator current L3 | INT16 | A | Read | ||||
| IR | 516 | Generator power L1 | INT16 | kW | Read | ||||
| IR | 517 | Generator power L2 | INT16 | kW | Read | ||||
| IR | 518 | Generator power L3 | INT16 | kW | Read | ||||
| IR | 519 | Generator power | INT16 | kW | Read | ||||
| IR | 520 | Generator reactive power L1 | INT16 | kvar | Read | ||||
| IR | 521 | Generator reactive power L2 | INT16 | kvar | Read | ||||
| IR | 522 | Generator reactive power L3 | INT16 | kvar | Read | ||||
| IR | 523 | Generator reactive power | INT16 | kvar | Read | ||||
| IR | 524 | Generator apparent power L1 | INT16 | kVA | Read | ||||
| IR | 525 | Generator apparent power L2 | INT16 | kVA | Read | ||||
| IR | 526 | Generator apparent power L3 | INT16 | kVA | Read | ||||
| IR | 527 | Generator apparent power | INT16 | kVA | Read | ||||
| IR | 528 | Generator Export reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 530 | Generator Export, active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 532 | Generator Export, active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 534 | Generator Export, active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 536 | Generator Export, active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 538 | Generator PF | INT16 | × 0.01 | Read | ||||
| IR | 539 | Bus B voltage L1-L2 | INT16 | V | Read | ||||
| IR | 540 | Bus B voltage L2-L3 | INT16 | V | Read | ||||
| IR | 541 | Bus B voltage L3-L1 | INT16 | V | Read | ||||
| IR | 542 | Bus B voltage L1-N | INT16 | V | Read | ||||
| IR | 543 | Bus B voltage L2-N | INT16 | V | Read | ||||
| IR | 544 | Bus B voltage L3-N | INT16 | V | Read | ||||
| IR | 545 | Bus B frequency L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 546 | Bus B frequency L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 547 | Bus B frequency L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 548 | Bus B voltage phase angle L1-L2 | INT16 | × 0.1 | ° | Read | |||
| IR | 549 | Bus B voltage phase angle L2-L3 | INT16 | × 0.1 | ° | Read | |||
| IR | 550 | Bus B voltage phase angle L3-L1 | INT16 | × 0.1 | ° | Read | |||
| IR | 551 | U BB L1 - U GEN L1 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 552 | U BB L2 - U GEN L2 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 553 | U BB L3 - U GEN L3 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 554 | Absolute running hours | INT32 | ABCD | Read | ||||
| IR | 556 | Relative running hours | INT32 | ABCD | Read | ||||
| IR | 558 | No. of alarms | INT16 | Read | |||||
| IR | 559 | No. of unacknowledged alarms | INT16 | Read | |||||
| IR | 560 | No. of active acknowledged alarms | INT16 | Read | |||||
| IR | 561 | Running minute counter, shutdown override | INT16 | Read | |||||
| IR | 562 | Running hour counter, shutdown override | INT16 | Read | |||||
| IR | 563 | No. of GB operations | INT16 | Read | |||||
| IR | 564 | No. of MB operations | INT16 | Read | |||||
| IR | 566 | Start attempts | INT16 | Read | |||||
| IR | 567 | DC supply term. 1-2 | INT16 | × 0.1 | V | Read | |||
| IR | 569 | Service timer 1 running hours | INT16 | Read | |||||
| IR | 570 | Service timer 1 running days | INT16 | Read | |||||
| IR | 571 | Service timer 2 running hours | INT16 | Read | |||||
| IR | 572 | Service timer 2 running days | INT16 | Read | |||||
| IR | 573 | Cos-phi | INT16 | × 0.01 | Read | ||||
| IR | 574 | cos phi inductive/capacitive | INT16 | Read | 0 = Inductive; 1 = Capacitive | ||||
| IR | 576 | RPM (revolutions per minute) | INT16 | rpm | Read | ||||
| IR | 577 | Running hours load profile | INT32 | ABCD | Read | ||||
| IR | 689 | Power derate value | INT16 | × 0.1 | % | Read | |||
| IR | 700 | Actual nominal power (Includes derate etc.) | INT16 | Read | |||||
| IR | 747 | Generator power (% of nominal) | INT16 | % | Read | ||||
| IR | 748 | Generator reactive power (% of nominal) | INT16 | % | Read | ||||
| IR | 750 | 4th current input: I neutral (true RMS) | INT16 | A | Read | ||||
| IR | 751 | 4th current input: I ground (3rd harmonic filter) | INT16 | A | Read | ||||
| IR | 752 | 4th current input: Apparent power | INT16 | kVA | Read | ||||
| IR | 753 | 4th current input: Active power | INT16 | kW | Read | ||||
| IR | 754 | 4th current input: Reactive power | INT16 | kvar | Read | ||||
| IR | 755 | 4th current input: Cos-phi | INT16 | × 0.01 | Read | ||||
| IR | 756 | cos phi inductive/capacitive | INT16 | Read | 0 = Inductive; 1 = Capacitive | ||||
| IR | 757 | 4th current input: Power factor | INT16 | × 0.01 | Read | ||||
| IR | 760 | Absolute running minutes | INT16 | min | Read | ||||
| IR | 764 | 4th current input: I busbar (true RMS) | INT16 | A | Read | ||||
| IR | 765 | Active Power Load | INT32 | ABCD | kW | Read | |||
| IR | 790 | Generator Export reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 792 | Generator Export reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 794 | Generator Export reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 796 | Generator Import active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 798 | Generator Import active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 800 | Generator Import active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 802 | Generator Import active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 804 | Generator Import reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 806 | Generator Import reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 808 | Generator Import reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 810 | Generator Import reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 816 | Demand of peak current 1 | INT16 | Read | |||||
| IR | 817 | Demand of peak current 2 | INT16 | Read | |||||
| IR | 818 | Demand of peak current 3 | INT16 | Read | |||||
| IR | 819 | Demand of avg. peak current 1 | INT16 | Read | |||||
| IR | 820 | Demand of avg. peak current 2 | INT16 | Read | |||||
| IR | 821 | Demand of avg. peak current 3 | INT16 | Read | |||||
| IR | 822 | Start attempts standard | INT16 | Read | |||||
| IR | 823 | Start attempts double starter | INT16 | Read | |||||
| IR | 833 | P ref actual | INT16 | Read | |||||
| IR | 1018 | Status flags word 1018 | One flag per bit. | BITMAP16 | Read | bit 0 = Mains failure (Single DG); bit 1 = MB position ON (Single DG); bit 2 = DG ramp down; bit 3 = Start GOV/AVR regulation; bit 4 = GB position ON; bit 5 = GB synchronising; bit 6 = Engine running; bit 7 = Running detected, timer expired; bit 8 = DG Hz/V OK, timer expired; bit 9 = Battery test ongoing; bit 10 = Shutdown override active; bit 11 = GB position OFF; bit 12 = MB position OFF; bit 13 = BB Hz/V OK; bit 14 = Single DG, MB synchronising; bit 15 = Dry mode | |||
| IR | 1019 | Mode flags word 1019 | Active running mode and plant mode, one bit each. | BITMAP16 | Read | bit 0 = BLOCK mode; bit 1 = No Regulation mode; bit 2 = MANUAL mode; bit 3 = AUTO mode; bit 4 = TEST; bit 5 = Island; bit 6 = AMF; bit 7 = Peak shaving; bit 8 = Fixed power; bit 9 = Mains power export; bit 10 = Load takeover; bit 11 = Power management; bit 15 = AMF active | |||
| IR | 1278 | Mlogic event counter 1 | INT16 | Read | |||||
| IR | 1279 | Mlogic event counter 2 | INT16 | Read | |||||
| IR | 1280 | Mlogic event counter 3 | INT16 | Read | |||||
| IR | 1281 | Mlogic event counter 4 | INT16 | Read | |||||
| IR | 1282 | Mlogic event counter 5 | INT16 | Read | |||||
| IR | 1283 | Mlogic event counter 6 | INT16 | Read | |||||
| IR | 1284 | Mlogic event counter 7 | INT16 | Read | |||||
| IR | 1285 | Mlogic event counter 8 | INT16 | Read | |||||
| IR | 1842 | BB Export, active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 1844 | BB Export, active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 1846 | BB Export, active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 1848 | BB Export, active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 1850 | BB Export, reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 1852 | BB Export, reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 1854 | BB Export, reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 1856 | BB Export, reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 1858 | BB Import, active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 1860 | BB Import, active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 1862 | BB Import, active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 1864 | BB Import, active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 1866 | BB Import, reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 1868 | BB Import, reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 1870 | BB Import, reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 1872 | BB Import, reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 1900 | General purpose PID 1 prioritized input | INT16 | Read | |||||
| IR | 1901 | General purpose PID 2 prioritized input | INT16 | Read | |||||
| IR | 1902 | General purpose PID 3 prioritized input | INT16 | Read | |||||
| IR | 1903 | General purpose PID 4 prioritized input | INT16 | Read | |||||
| HR | 0 | Power regulator setpoint | 0 to 100 % of nominal power; activated in menu 7501. | INT16 | Read/write | ||||
| HR | 1 | cosPhi regulator setpoint | 60-100 means cos phi x 100 (100 = 1.00). Menu 7504. | INT16 | Read/write | ||||
| HR | 2 | Reactive power regulator setpoint | -100 to +100 % of nominal; negative = capacitive. Menu 7505. | INT16 | Read/write | ||||
| HR | 3 | Frequency regulator setpoint | -100 to +100 % = -10.0 to +10.0 % of nominal frequency. Menu 7502. | INT16 | Read/write | ||||
| HR | 4 | Voltage regulator setpoint | -100 to +100 % = -10.0 to +10.0 % of nominal voltage. Menu 7503. | INT16 | Read/write | ||||
| HR | 5 | Control command word 5 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Remote start; bit 2 = Remote GB ON; bit 3 = Remote GB OFF; bit 4 = Remote stop; bit 5 = Reset GOV/AVR regulation output to offset; bit 6 = Start + sync. (MAN); bit 7 = Alarm inhibit 1; bit 8 = Alarm inhibit 2; bit 9 = Alarm inhibit 3; bit 10 = Alarm ack.; bit 11 = Nominal setting 1; bit 12 = Nominal setting 2; bit 13 = Nominal setting 3; bit 14 = Nominal setting 4; bit 15 = Deload and stop (MAN) | |||
| HR | 6 | Control command word 6 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Island; bit 2 = Automatic mains failure (AMF); bit 3 = Peak shaving; bit 4 = Fixed power; bit 5 = Mains power export (MPE); bit 6 = Load takeover (LTO); bit 9 = MB ON (Single DG); bit 10 = MB OFF (Single DG); bit 11 = Auto start/stop; bit 12 = NO REGULATION mode; bit 13 = AUTO mode; bit 14 = MANUAL mode; bit 15 = TEST mode | |||
| HR | 7 | Control command word 7 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = External frequency control; bit 2 = External voltage control; bit 3 = External power control; bit 4 = External reactive power control; bit 5 = External power factor control; bit 6 = Capacitive PF; bit 7 = Base load; bit 8 = 1. priority; bit 9 = Application 1; bit 10 = Application 2; bit 11 = Application 3; bit 12 = Application 4; bit 13 = Battery test; bit 15 = Synchronise clock to 4:00 a.m. | |||
| HR | 8 | Control command word 8 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual toggle event 1; bit 2 = Virtual toggle event 2; bit 3 = Virtual toggle event 3; bit 4 = Virtual toggle event 4; bit 5 = Virtual toggle event 5; bit 6 = Virtual toggle event 6; bit 7 = Virtual toggle event 7; bit 8 = Virtual toggle event 8; bit 9 = Virtual toggle event 9; bit 10 = Virtual toggle event 10; bit 11 = Virtual toggle event 11; bit 12 = Virtual toggle event 12; bit 13 = Virtual toggle event 13; bit 14 = Virtual toggle event 14; bit 15 = Virtual toggle event 15 | |||
| HR | 9 | Control command word 9 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual toggle event 16; bit 2 = Virtual toggle event 17; bit 3 = Virtual toggle event 18; bit 4 = Virtual toggle event 19; bit 5 = Virtual toggle event 20; bit 6 = Virtual toggle event 21; bit 7 = Virtual toggle event 22; bit 8 = Virtual toggle event 23; bit 9 = Virtual toggle event 24; bit 10 = Virtual toggle event 25; bit 11 = Virtual toggle event 26; bit 12 = Virtual toggle event 27; bit 13 = Virtual toggle event 28; bit 14 = Virtual toggle event 29; bit 15 = Virtual toggle event 30 | |||
| HR | 10 | Control command word 10 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 31; bit 2 = Virtual event 32; bit 4 = Clear log; bit 5 = Clear Parameter edits; bit 8 = Nominal setting 5; bit 9 = Nominal setting 6 | |||
| HR | 13 | Control command word 13 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Enable external frequency control; bit 2 = Disable external frequency control; bit 3 = Enable external voltage control; bit 4 = Disable external voltage control; bit 5 = Enable external power control; bit 6 = Disable external power control; bit 7 = Enable external VAr control; bit 8 = Disable external VAr control; bit 9 = Enable external CosPhi control; bit 10 = Disable external CosPhi control; bit 11 = Enable PM base load; bit 12 = Disable PM base load; bit 13 = Reset horn | |||
| HR | 58000 | Year (2003-2099) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58001 | Month (1-12) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58002 | Date (1-31) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58003 | Day (1-7, Monday - Sunday) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58004 | Hour (0-23) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58005 | Min (0-59) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58006 | Sec (0-59) | Controller clock; write to set. | INT16 | Read/write |
Notes on this map
- The source is an Excel workbook. Each row has a scaling exponent x; the value is raw x 10^-x, so x=2 means scale 0.01. Units are as printed.
- 32-bit values are ABCD: the manual (section 3.4) puts the high 16 bits at the lower address.
- Data formats, RS-485 settings and the communication-error timer come from the AGC 150 Modbus server user manual 4189341435-B (https://deif-cdn-umbraco.azureedge.net/media/w25puznj/agc-150-modbus-server-user-manual-4189341435-uk.pdf).
- Only rows marked for the GEN controller type are listed; BTB, MAINS, GEN-H, ENG and ATS types reuse addresses.
- Left out: configurable area 0-499, analogue/multi-inputs and CIO values, alarm bits, EIC engine data (including 26000 upward), DAVR, power-management, PMS lite, PV monitoring, the ASCII controller-name words 770-775, the command-flag coils, and input 767 (reactive power load printed with unit kW).
- Parameters are read and written at an address-area start plus the parameter's USW address (for example 12 + 6000 = 6012 for alarm acknowledge of over-voltage 1).
- The active-alarm list is at input registers 28000-28099 (each holds the USW address of an active alarm); not listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DEIF AGC 150 Generator controller
What Modbus registers does the DEIF AGC 150 Generator controller have?
This map lists 197 registers: 45 discrete inputs, 133 input registers, 19 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DEIF AGC 150 Generator controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The 'Modbus address' column is the address in the request. The tables also print a 6-digit PLC address one higher (input 501 = PLC 300502).
What byte order does the DEIF AGC 150 Generator controller use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the DEIF AGC 150 Generator controller?
Start with IR 501 Generator voltage L1-L2 (Generator voltage L1-L2); IR 507 Generator frequency L1 (Generator frequency); IR 513 Generator current L1 (Generator current L1); IR 519 Generator power (Generator active power); IR 554 Absolute running hours (Running hours); IR 1019 Mode flags word 1019 (Active mode); HR 5 Control command word 5 (Remote start/stop and breaker commands).
How do I enable Modbus control of the DEIF AGC 150 Generator controller?
RS-485: set ID (7511/7521) and speed (7512/7522) under Communication > RS485. Ethernet: set the IP under Settings > Communication > Ethernet setup or in the utility software.
What happens when the DEIF AGC 150 Generator controller loses Modbus communication?
RS-485 communication error: enable with 7516/7526, timer 7513/7523 (1-100 s, default 10 s), fail class 7517/7527 (default Warning).
Where is the official DEIF AGC 150 Generator controller Modbus documentation?
The source is AGC 150 Modbus server tables (4189341212 rev. Z), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/f2hiadel/agc-150-modbus-server-tables-4189341212-uk.xlsx.
More DEIF Modbus register maps
- Generator controller
DEIF AGC 150 Generator Marine controller
AGC 150 Marine software 1.39.0 (marine Modbus server tables revision E), GEN-M (marine genset) controller type. The iE 150 Marine tables 4189341431 rev. H match these tables.
Also known as: AGC 150 GEN-M, AGC 150 Generator Marine, iE 150 Marine - Generator controller
DEIF AGC 200 Advanced Genset Controller
AGC 200 series software 4.68.2.x, genset (DG) application only.
Also known as: AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200 - Generator controller
DEIF AGC-4 Automatic Genset Controller
AGC-4 software 4.83.0 (Modbus tables revision I), genset (DG) application; mains and BTB variants share many addresses but are not covered.
Also known as: AGC-4 DG, AGC 4, Multi-line 2 AGC-4 - Generator controller
DEIF AGC-4 Mk II Automatic Genset Controller
AGC-4 Mk II software 6.31.0 (Modbus tables revision N), genset (GEN) application only.
Also known as: AGC-4 Mk2, AGC-4 MkII - Generator controller
DEIF SGC 120 / SGC 121 Single Genset Controller
SGC 120 and SGC 121 (first generation, not Mk II); the SGC 120 user manual 4189341340B covers application software 9.04.
Also known as: SGC 120, SGC 121, SGC120, SGC121 - Generator controller
DEIF SGC 120 Mk II Single Genset Controller
SGC 120 Mk II software R18.0 (Modbus tables revision C).
Also known as: SGC 120 MkII, SGC 120 Mk2 - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2
Other generator controllers register maps
- Transfer switch
Lovato Electric ATL610 automatic transfer switch controller
ATL610 ATS controller via the optical port or an EXP1010/1011/1012/1013 communication module, per protocol document I428 GB I 09 22.
Also known as: ATL610, ATL 610, EXP1012, EXP1013 - Generator controller
Lovato Electric RGK800SA stand-alone genset controller
RGK800SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800SA, RGK800 SA - Generator controller
SmartGen HGM9510N / HGM9520N / HGM9530N
HGM9510N, HGM9520N and HGM9530N paralleling genset controllers, protocol document v1.5.
Also known as: HGM9520N, HGM9530N - Power meter (transfer switch metering)
ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)
ASCO Power Manager Xp, firmware FS611842-006 (some registers AS629262-004); document 381339-221 revision I.
Also known as: ASCO Power Manager Xp, Power Manager Xp, 381339-221 - Generator controller
Datakom DKG-705
Datakom DKG-705 AMF, parallel-to-mains and dual genset synchronization unit with J1939, Modbus application manual V-02-07 (14.04.2008).
Also known as: DKG 705, DKG705 - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
All generator controllers Modbus register maps →
Source: AGC 150 Modbus server tables · 4189341212 rev. Z. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.