Generator controller · Modbus register map
Datakom DKG-705 Modbus register map
Updated 17 November 2026
The DKG-705 is a Datakom genset controller for automatic mains failure, mains paralleling and dual-genset synchronization. Its Modbus RTU slave runs on the RS232 port (or RS422/485 via an external converter) and exposes mains and genset voltages, currents, frequencies, engine values, alarm and relay bit fields, J1939 engine data and a register for changing the operating mode. All data is read with function 03 and written one register at a time with function 06.
This page lists 49 Modbus registers for the Datakom DKG-705 — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Datakom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Datakom
- Model
- DKG-705
- Equipment type
- Generator controller
- Registers
- 49 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- DKG 705, DKG705
Integration notes: Datakom DKG-705
Read up to 16 holding registers per request with function 03 from 0000h (electrical values) and 002Ah (engine values, alarms, status). Change operating mode by writing a mode bit to 0040h with function 06.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3 | Phase U voltage | UINT16 | Phase U voltage | Read |
| HR 6 | Phase U current | UINT16 | Phase U current | Read |
| HR 19 | Genset frequency | UINT16 | Genset frequency | Read |
| HR 42 | Engine speed | UINT16 | Engine speed | Read |
| HR 50 | Shutdown alarm bits 1 | BITMAP16 | Shutdown alarms | Read |
| HR 63 | Genset operating status | UINT16 | Genset operating status | Read |
| HR 64 | Last pressed key / mode command | BITMAP16 | Operating mode command | Read/write |
Enable Modbus control & writes
Set a controller address (1-250) in parameter P_650 to turn Modbus on; address 0 disables Modbus and returns the port to the Rainbow protocol.
Byte order & addressing
- Only functions 03 and 06 are supported; write one register at a time.
- A read of more than 16 registers returns only the first 16.
- Writing a read-only register returns exception code 10 (write protection).
Network setup
- Serial format is fixed at 9600 bps, 8 data bits, no parity, 1 stop bit.
- The Modbus port is RS232; use an external RS422/485 converter or modem for multi-drop or remote links.
Watch out for
- The unit replies at least 4.3 ms after the request; allow for it in master timing.
Datakom DKG-705 Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000 | Phase R voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 1doc 0001 | Phase S voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 2doc 0002 | Phase T voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 3doc 0003 | Phase U voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 4doc 0004 | Phase V voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 5doc 0005 | Phase W voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 6doc 0006 | Phase U current | UINT16 | × 0.1 | A | Read | |||
| HR | 7doc 0007 | Phase V current | UINT16 | × 0.1 | A | Read | |||
| HR | 8doc 0008 | Phase W current | UINT16 | × 0.1 | A | Read | |||
| HR | 9doc 0009 | Phase R current | UINT16 | × 0.1 | A | Read | |||
| HR | 10doc 000A | Phase S current | UINT16 | × 0.1 | A | Read | |||
| HR | 11doc 000B | Phase T current | UINT16 | × 0.1 | A | Read | |||
| HR | 12doc 000C | Phase RS voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 13doc 000D | Phase ST voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 14doc 000E | Phase TR voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 15doc 000F | Phase UV voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 16doc 0010 | Phase VW voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 17doc 0011 | Phase WU voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 18doc 0012 | Mains frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 19doc 0013 | Genset frequency | UINT16 | × 0.1 | Hz | Read | |||
| HR | 20doc 0014 | Genset phase order | Low byte valid. | BITMAP16 | Read | bit 7 = 0 = phase order correct | |||
| HR | 21doc 0015 | Mains phase order | Low byte valid. | BITMAP16 | Read | bit 7 = 0 = phase order correct | |||
| HR | 42doc 002A | Engine speed | UINT16 | rpm | Read | ||||
| HR | 43doc 002B | Oil pressure | UINT16 | × 0.1 | bar | Read | |||
| HR | 44doc 002C | Coolant temperature | UINT16 | °C | Read | ||||
| HR | 45doc 002D | Fuel level | UINT16 | % | Read | ||||
| HR | 46doc 002E | Oil temperature | UINT16 | °C | Read | ||||
| HR | 47doc 002F | Battery voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 49doc 0031 | External DC voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 50doc 0032 | Shutdown alarm bits 1 | 1 = active. | BITMAP16 | Read | bit 0 = external input_0 shutdown alarm; bit 1 = external input_1 shutdown alarm; bit 2 = external input_2 shutdown alarm; bit 3 = external input_3 shutdown alarm; bit 4 = external input_4 shutdown alarm; bit 5 = external input_5 shutdown alarm; bit 6 = external input_6 shutdown alarm; bit 7 = external input_7 shutdown alarm; bit 9 = genset under frequency shutdown alarm; bit 10 = genset over frequency shutdown alarm; bit 11 = high battery voltage shutdown alarm; bit 12 = low fuel level (measured) shutdown alarm; bit 13 = high oil temperature (measured) shutdown alarm; bit 14 = high coolant temp. (measured) shutdown alarm; bit 15 = low oil pressure (measured) shutdown alarm | |||
| HR | 51doc 0033 | Shutdown alarm bits 2 | 1 = active. | BITMAP16 | Read | bit 0 = fail to stop shutdown alarm; bit 1 = fail to start shutdown alarm; bit 2 = genset low voltage fail shutdown alarm; bit 3 = genset high voltage fail shutdown alarm; bit 4 = slave unavailable shutdown alarm; bit 5 = genset phase sequence fail shutdown alarm; bit 6 = genset low rpm shutdown alarm; bit 7 = genset high rpm shutdown alarm; bit 11 = J1939 ECU communication fail shutdown alarm; bit 14 = communication lost shutdown alarm | |||
| HR | 52doc 0034 | Loaddump alarm bits | 1 = active. | BITMAP16 | Read | bit 0 = external input_0 loaddump alarm; bit 1 = external input_1 loaddump alarm; bit 2 = external input_2 loaddump alarm; bit 3 = external input_3 loaddump alarm; bit 4 = external input_4 loaddump alarm; bit 5 = external input_5 loaddump alarm; bit 6 = external input_6 loaddump alarm; bit 7 = external input_7 loaddump alarm; bit 13 = genset reverse power loaddump alarm; bit 14 = genset excess power loaddump alarm; bit 15 = alternator overcurrent loaddump alarm | |||
| HR | 53doc 0035 | Warning bits 1 | 1 = active. | BITMAP16 | Read | bit 11 = J1939 ECU warning; bit 12 = genset on load warning; bit 13 = mains on load warning; bit 14 = service request warning | |||
| HR | 54doc 0036 | Warning bits 2 | 1 = active. | BITMAP16 | Read | bit 0 = external input_0 warning; bit 1 = external input_1 warning; bit 2 = external input_2 warning; bit 3 = external input_3 warning; bit 4 = external input_4 warning; bit 5 = external input_5 warning; bit 6 = external input_6 warning; bit 7 = external input_7 warning; bit 8 = synchronization fail warning; bit 9 = genset under frequency warning; bit 10 = genset over frequency warning; bit 11 = high battery voltage warning; bit 12 = low fuel level (measured) warning; bit 13 = high oil temperature (measured) warning; bit 14 = high coolant temperature (measured) warning; bit 15 = low oil pressure (measured) warning | |||
| HR | 55doc 0037 | Warning bits 3 | 1 = active. | BITMAP16 | Read | bit 0 = mains phase sequence fail warning; bit 2 = charge fail warning; bit 3 = low battery voltage warning; bit 4 = AVR control fail warning; bit 5 = GOV control fail warning; bit 6 = genset low rpm warning; bit 7 = genset high rpm warning; bit 8 = mains failure at parallel warning; bit 9 = mains recerse power at parallel warning; bit 10 = mains frequency fail at parallel warning; bit 11 = no mains frequency at parallel warning; bit 12 = ROCOF (df/dt) failure at parallel warning; bit 13 = vectorshift (df/dt) failure at parallel warning; bit 14 = communication lost warning | |||
| HR | 57doc 0039 | On-board relay output status | BITMAP16 | Read | bit 1 = relay_1 status (terminal_36); bit 2 = relay_2 status ( terminal_33), start relay; bit 3 = relay_3 status (terminal_37); bit 4 = relay_4 status (terminal_1), genset contactor; bit 5 = relay_5 status (terminal_10), mains contactor; bit 6 = relay_6 status (terminal_32), fuel relay; bit 7 = relay_7 status (terminal_35) | ||||
| HR | 58doc 003A | Relay extension module status | BITMAP16 | Read | bit 0 = module_1, relay_1 status; bit 1 = module_1, relay_2 status; bit 2 = module_1, relay_3 status; bit 3 = module_1, relay_4 status; bit 4 = module_1, relay_5 status; bit 5 = module_1, relay_6 status; bit 6 = module_1, relay_7 status; bit 7 = module_1, relay_8 status; bit 8 = module_2, relay_1 status; bit 9 = module_2, relay_2 status; bit 10 = module_2, relay_3 status; bit 11 = module_2, relay_4 status; bit 12 = module_2, relay_5 status; bit 13 = module_2, relay_6 status; bit 14 = module_2, relay_7 status; bit 15 = module_2, relay_8 status | ||||
| HR | 59doc 003B | Relay function status 1 | BITMAP16 | Read | bit 0 = choke; bit 1 = preheat; bit 2 = crank; bit 3 = alarm (timed); bit 4 = genset contactor; bit 5 = mains contactor; bit 6 = fuel; bit 7 = stop; bit 8 = load shedding; bit 9 = alarm (not timed); bit 10 = load contactor; bit 11 = auto ready; bit 12 = master relay; bit 13 = exerciser on; bit 14 = fuel pump | ||||
| HR | 60doc 003C | Relay function status 2 | BITMAP16 | Read | bit 0 = external DC fail; bit 1 = idle speed operation; bit 2 = gas engine gas solenoid; bit 5 = flashing relay | ||||
| HR | 61doc 003D | Operating mode | BITMAP16 | Read | bit 4 = auto mode; bit 5 = off mode; bit 6 = test mode; bit 7 = load test mode | ||||
| HR | 63doc 003F | Genset operating status | UINT16 | Read | 0 = load on mains; 1 = waiting before fuel (preheat); 2 = waiting before/between cranks; 3 = cranking; 4 = engine heating; 5 = synchronization for load transfer to genset; 6 = genset contactor timer (synch mode); 7 = genset contactor timer (non synch mode); 8 = load on genset; 9 = synchronization for load transfer to mains; 10 = mains contactor timer (synch mode); 11 = mains conntactor timer (non synch mode); 12 = cooldown operation; 13 = stopping; 14 = soft transfer from gen to mains; 15 = soft transfer from mains to gen | ||||
| HR | 64doc 0040 | Last pressed key / mode command | Write a mode bit to change operating mode over Modbus. | BITMAP16 | Read/write | bit 4 = Auto mode; bit 5 = Off mode; bit 6 = Test mode; bit 7 = Load test mode | |||
| HR | 96doc 0060 | J1939 engine speed | UINT16 | × 0.125 | rpm | Read | |||
| HR | 98doc 0062 | J1939 oil pressure | UINT16 | × 0.1 | bar | Read | |||
| HR | 99doc 0063-0064 | J1939 total engine hours | Raw value is hours x20. | UINT32 | CDAB | × 0.05 | h | Read | |
| HR | 103doc 0067 | J1939 fuel pressure | UINT16 | × 0.1 | bar | Read | |||
| HR | 105doc 0069 | J1939 fuel rate | UINT16 | × 0.1 | l/h | Read | |||
| HR | 112doc 0070 | J1939 warning 1 FMI | UINT16 | Read | |||||
| HR | 113doc 0071 | J1939 warning 1 SPN | UINT16 | Read |
Notes on this map
- Word order: the manual states that for data longer than 16 bits the least significant register comes first, so the 32-bit engine-hours value is CDAB.
- Coefficients: the 'coefficient' column is the factor the value was multiplied by before storing (e.g. x10 oil pressure in bars), so scale here is 1/coefficient.
- Registers marked '8bit' carry their value in the low byte only; the high byte must be ignored.
- Left out: genset and mains active, reactive and apparent power and power factor. Active and reactive power use a sign-magnitude format (high 8 bits sign, low 24 bits value), PF is a signed byte, and the manual gives no power unit.
- Left out: the clock registers (BCD), charge input ratio and GOV/AVR output percentages (fractional encodings), synchroscope angle (sign-magnitude), J1939 temperatures (offset), the parameter block from 1000h and most J1939 warning slots.
- The source names phase sets R/S/T and U/V/W but does not say which is mains and which is genset.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Datakom DKG-705
What Modbus registers does the Datakom DKG-705 have?
This map lists 49 registers: 49 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Datakom DKG-705 Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register addresses are printed in hex and go straight into the request; the manual's example 01 03 00 20 00 10 reads 16 registers starting at 20h (32 decimal).
What byte order does the Datakom DKG-705 use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Datakom DKG-705?
Start with HR 3 Phase U voltage (Phase U voltage); HR 6 Phase U current (Phase U current); HR 19 Genset frequency (Genset frequency); HR 42 Engine speed (Engine speed); HR 50 Shutdown alarm bits 1 (Shutdown alarms); HR 63 Genset operating status (Genset operating status); HR 64 Last pressed key / mode command (Operating mode command).
How do I enable Modbus control of the Datakom DKG-705?
Set a controller address (1-250) in parameter P_650 to turn Modbus on; address 0 disables Modbus and returns the port to the Rainbow protocol.
Where is the official Datakom DKG-705 Modbus documentation?
The source is DKG-705 Modbus Application Manual (V-02-07), revision 2008-04-14, published free by Datakom at https://www.datakom.com.tr/upload/Files/705_MODBUS.pdf.
More Datakom Modbus register maps
Other generator controllers register maps
- Generator controller
DEIF SGC 120 Mk II Single Genset Controller
SGC 120 Mk II software R18.0 (Modbus tables revision C).
Also known as: SGC 120 MkII, SGC 120 Mk2 - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS - Generator controller
Lovato Electric RGK800 AMF genset controller
RGK800, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800, RGK800 AMF - Generator controller
SmartGen HGM7100N Series
HGM7110N (auto start) and HGM7120N (AMF) genset controllers, protocol document v1.3.
Also known as: HGM7110N, HGM7120N - Transfer switch controller
ASCO 7000 Series Group 5 transfer switch controller (Modbus RTU)
ASCO 7000 Series Group 5 controller, firmware 607540-023 (some bits 607540-033); document 381339-221 revision I. Power Manager Xp registers in the same document are not included.
Also known as: ASCO 7000 Group 5, Group 5 Controller, 381339-221 - Generator controller
DEIF SGC 120 / SGC 121 Single Genset Controller
SGC 120 and SGC 121 (first generation, not Mk II); the SGC 120 user manual 4189341340B covers application software 9.04.
Also known as: SGC 120, SGC 121, SGC120, SGC121
All generator controllers Modbus register maps →
Source: DKG-705 Modbus Application Manual · V-02-07 · rev. 2008-04-14. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.