Generator controller · Modbus register map

Datakom DKG-705 Modbus register map

Updated 17 November 2026

Short answer

The DKG-705 is a Datakom genset controller for automatic mains failure, mains paralleling and dual-genset synchronization. Its Modbus RTU slave runs on the RS232 port (or RS422/485 via an external converter) and exposes mains and genset voltages, currents, frequencies, engine values, alarm and relay bit fields, J1939 engine data and a register for changing the operating mode. All data is read with function 03 and written one register at a time with function 06.

This page lists 49 Modbus registers for the Datakom DKG-705 — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Datakom’s own free documentation (linked below) and checked against it.

Manufacturer
Datakom
Model
DKG-705
Equipment type
Generator controller
Registers
49 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
32-bit word order
CDAB low word first (word-swapped)
Also known as
DKG 705, DKG705
Source document
DKG-705 Modbus Application Manual · V-02-07 · rev. 2008-04-14
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Datakom DKG-705

Integration in brief

Read up to 16 holding registers per request with function 03 from 0000h (electrical values) and 002Ah (engine values, alarms, status). Change operating mode by writing a mode bit to 0040h with function 06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3Phase U voltageUINT16Phase U voltageRead
HR 6Phase U currentUINT16Phase U currentRead
HR 19Genset frequencyUINT16Genset frequencyRead
HR 42Engine speedUINT16Engine speedRead
HR 50Shutdown alarm bits 1BITMAP16Shutdown alarmsRead
HR 63Genset operating statusUINT16Genset operating statusRead
HR 64Last pressed key / mode commandBITMAP16Operating mode commandRead/write

Enable Modbus control & writes

Set a controller address (1-250) in parameter P_650 to turn Modbus on; address 0 disables Modbus and returns the port to the Rainbow protocol.

Byte order & addressing

Network setup

Watch out for

Datakom DKG-705 Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

49 of 49 shown
Datakom DKG-705 Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0000Phase R voltageUINT16× 0.1VRead
HR1doc 0001Phase S voltageUINT16× 0.1VRead
HR2doc 0002Phase T voltageUINT16× 0.1VRead
HR3doc 0003Phase U voltageUINT16× 0.1VRead
HR4doc 0004Phase V voltageUINT16× 0.1VRead
HR5doc 0005Phase W voltageUINT16× 0.1VRead
HR6doc 0006Phase U currentUINT16× 0.1ARead
HR7doc 0007Phase V currentUINT16× 0.1ARead
HR8doc 0008Phase W currentUINT16× 0.1ARead
HR9doc 0009Phase R currentUINT16× 0.1ARead
HR10doc 000APhase S currentUINT16× 0.1ARead
HR11doc 000BPhase T currentUINT16× 0.1ARead
HR12doc 000CPhase RS voltageUINT16× 0.1VRead
HR13doc 000DPhase ST voltageUINT16× 0.1VRead
HR14doc 000EPhase TR voltageUINT16× 0.1VRead
HR15doc 000FPhase UV voltageUINT16× 0.1VRead
HR16doc 0010Phase VW voltageUINT16× 0.1VRead
HR17doc 0011Phase WU voltageUINT16× 0.1VRead
HR18doc 0012Mains frequencyUINT16× 0.1HzRead
HR19doc 0013Genset frequencyUINT16× 0.1HzRead
HR20doc 0014Genset phase orderLow byte valid.BITMAP16Readbit 7 = 0 = phase order correct
HR21doc 0015Mains phase orderLow byte valid.BITMAP16Readbit 7 = 0 = phase order correct
HR42doc 002AEngine speedUINT16rpmRead
HR43doc 002BOil pressureUINT16× 0.1barRead
HR44doc 002CCoolant temperatureUINT16°CRead
HR45doc 002DFuel levelUINT16%Read
HR46doc 002EOil temperatureUINT16°CRead
HR47doc 002FBattery voltageUINT16× 0.1VRead
HR49doc 0031External DC voltageUINT16× 0.1VRead
HR50doc 0032Shutdown alarm bits 11 = active.BITMAP16Readbit 0 = external input_0 shutdown alarm; bit 1 = external input_1 shutdown alarm; bit 2 = external input_2 shutdown alarm; bit 3 = external input_3 shutdown alarm; bit 4 = external input_4 shutdown alarm; bit 5 = external input_5 shutdown alarm; bit 6 = external input_6 shutdown alarm; bit 7 = external input_7 shutdown alarm; bit 9 = genset under frequency shutdown alarm; bit 10 = genset over frequency shutdown alarm; bit 11 = high battery voltage shutdown alarm; bit 12 = low fuel level (measured) shutdown alarm; bit 13 = high oil temperature (measured) shutdown alarm; bit 14 = high coolant temp. (measured) shutdown alarm; bit 15 = low oil pressure (measured) shutdown alarm
HR51doc 0033Shutdown alarm bits 21 = active.BITMAP16Readbit 0 = fail to stop shutdown alarm; bit 1 = fail to start shutdown alarm; bit 2 = genset low voltage fail shutdown alarm; bit 3 = genset high voltage fail shutdown alarm; bit 4 = slave unavailable shutdown alarm; bit 5 = genset phase sequence fail shutdown alarm; bit 6 = genset low rpm shutdown alarm; bit 7 = genset high rpm shutdown alarm; bit 11 = J1939 ECU communication fail shutdown alarm; bit 14 = communication lost shutdown alarm
HR52doc 0034Loaddump alarm bits1 = active.BITMAP16Readbit 0 = external input_0 loaddump alarm; bit 1 = external input_1 loaddump alarm; bit 2 = external input_2 loaddump alarm; bit 3 = external input_3 loaddump alarm; bit 4 = external input_4 loaddump alarm; bit 5 = external input_5 loaddump alarm; bit 6 = external input_6 loaddump alarm; bit 7 = external input_7 loaddump alarm; bit 13 = genset reverse power loaddump alarm; bit 14 = genset excess power loaddump alarm; bit 15 = alternator overcurrent loaddump alarm
HR53doc 0035Warning bits 11 = active.BITMAP16Readbit 11 = J1939 ECU warning; bit 12 = genset on load warning; bit 13 = mains on load warning; bit 14 = service request warning
HR54doc 0036Warning bits 21 = active.BITMAP16Readbit 0 = external input_0 warning; bit 1 = external input_1 warning; bit 2 = external input_2 warning; bit 3 = external input_3 warning; bit 4 = external input_4 warning; bit 5 = external input_5 warning; bit 6 = external input_6 warning; bit 7 = external input_7 warning; bit 8 = synchronization fail warning; bit 9 = genset under frequency warning; bit 10 = genset over frequency warning; bit 11 = high battery voltage warning; bit 12 = low fuel level (measured) warning; bit 13 = high oil temperature (measured) warning; bit 14 = high coolant temperature (measured) warning; bit 15 = low oil pressure (measured) warning
HR55doc 0037Warning bits 31 = active.BITMAP16Readbit 0 = mains phase sequence fail warning; bit 2 = charge fail warning; bit 3 = low battery voltage warning; bit 4 = AVR control fail warning; bit 5 = GOV control fail warning; bit 6 = genset low rpm warning; bit 7 = genset high rpm warning; bit 8 = mains failure at parallel warning; bit 9 = mains recerse power at parallel warning; bit 10 = mains frequency fail at parallel warning; bit 11 = no mains frequency at parallel warning; bit 12 = ROCOF (df/dt) failure at parallel warning; bit 13 = vectorshift (df/dt) failure at parallel warning; bit 14 = communication lost warning
HR57doc 0039On-board relay output statusBITMAP16Readbit 1 = relay_1 status (terminal_36); bit 2 = relay_2 status ( terminal_33), start relay; bit 3 = relay_3 status (terminal_37); bit 4 = relay_4 status (terminal_1), genset contactor; bit 5 = relay_5 status (terminal_10), mains contactor; bit 6 = relay_6 status (terminal_32), fuel relay; bit 7 = relay_7 status (terminal_35)
HR58doc 003ARelay extension module statusBITMAP16Readbit 0 = module_1, relay_1 status; bit 1 = module_1, relay_2 status; bit 2 = module_1, relay_3 status; bit 3 = module_1, relay_4 status; bit 4 = module_1, relay_5 status; bit 5 = module_1, relay_6 status; bit 6 = module_1, relay_7 status; bit 7 = module_1, relay_8 status; bit 8 = module_2, relay_1 status; bit 9 = module_2, relay_2 status; bit 10 = module_2, relay_3 status; bit 11 = module_2, relay_4 status; bit 12 = module_2, relay_5 status; bit 13 = module_2, relay_6 status; bit 14 = module_2, relay_7 status; bit 15 = module_2, relay_8 status
HR59doc 003BRelay function status 1BITMAP16Readbit 0 = choke; bit 1 = preheat; bit 2 = crank; bit 3 = alarm (timed); bit 4 = genset contactor; bit 5 = mains contactor; bit 6 = fuel; bit 7 = stop; bit 8 = load shedding; bit 9 = alarm (not timed); bit 10 = load contactor; bit 11 = auto ready; bit 12 = master relay; bit 13 = exerciser on; bit 14 = fuel pump
HR60doc 003CRelay function status 2BITMAP16Readbit 0 = external DC fail; bit 1 = idle speed operation; bit 2 = gas engine gas solenoid; bit 5 = flashing relay
HR61doc 003DOperating modeBITMAP16Readbit 4 = auto mode; bit 5 = off mode; bit 6 = test mode; bit 7 = load test mode
HR63doc 003FGenset operating statusUINT16Read0 = load on mains; 1 = waiting before fuel (preheat); 2 = waiting before/between cranks; 3 = cranking; 4 = engine heating; 5 = synchronization for load transfer to genset; 6 = genset contactor timer (synch mode); 7 = genset contactor timer (non synch mode); 8 = load on genset; 9 = synchronization for load transfer to mains; 10 = mains contactor timer (synch mode); 11 = mains conntactor timer (non synch mode); 12 = cooldown operation; 13 = stopping; 14 = soft transfer from gen to mains; 15 = soft transfer from mains to gen
HR64doc 0040Last pressed key / mode commandWrite a mode bit to change operating mode over Modbus.BITMAP16Read/writebit 4 = Auto mode; bit 5 = Off mode; bit 6 = Test mode; bit 7 = Load test mode
HR96doc 0060J1939 engine speedUINT16× 0.125rpmRead
HR98doc 0062J1939 oil pressureUINT16× 0.1barRead
HR99doc 0063-0064J1939 total engine hoursRaw value is hours x20.UINT32CDAB× 0.05hRead
HR103doc 0067J1939 fuel pressureUINT16× 0.1barRead
HR105doc 0069J1939 fuel rateUINT16× 0.1l/hRead
HR112doc 0070J1939 warning 1 FMIUINT16Read
HR113doc 0071J1939 warning 1 SPNUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Datakom DKG-705

What Modbus registers does the Datakom DKG-705 have?

This map lists 49 registers: 49 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Datakom DKG-705 Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register addresses are printed in hex and go straight into the request; the manual's example 01 03 00 20 00 10 reads 16 registers starting at 20h (32 decimal).

What byte order does the Datakom DKG-705 use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Datakom DKG-705?

Start with HR 3 Phase U voltage (Phase U voltage); HR 6 Phase U current (Phase U current); HR 19 Genset frequency (Genset frequency); HR 42 Engine speed (Engine speed); HR 50 Shutdown alarm bits 1 (Shutdown alarms); HR 63 Genset operating status (Genset operating status); HR 64 Last pressed key / mode command (Operating mode command).

How do I enable Modbus control of the Datakom DKG-705?

Set a controller address (1-250) in parameter P_650 to turn Modbus on; address 0 disables Modbus and returns the port to the Rainbow protocol.

Where is the official Datakom DKG-705 Modbus documentation?

The source is DKG-705 Modbus Application Manual (V-02-07), revision 2008-04-14, published free by Datakom at https://www.datakom.com.tr/upload/Files/705_MODBUS.pdf.

More Datakom Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: DKG-705 Modbus Application Manual · V-02-07 · rev. 2008-04-14. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.