ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Power Manager Xp is ASCO's metering module for 7000 Series transfer switches. Over Modbus RTU it reports per-phase voltage, current, kW, kvar, kVA and power factor, frequency, demand, separate energy totals for the normal and emergency sources, digital I/O and switch position, all as holding registers.

This page lists 62 Modbus registers for the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ASCO’s own free documentation (linked below) and checked against it.

Manufacturer
ASCO
Model
Power Manager Xp power meter for transfer switches (Modbus RTU)
Equipment type
Power meter (transfer switch metering)
Registers
62 (7 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
FS611842-006; AS629262-004 for the nominal-rating and later registers
Also known as
ASCO Power Manager Xp, Power Manager Xp, 381339-221
Source document
Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus · 381339-221 I · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)

Integration in brief

Read 40011-40026 for voltage and current, 40031-40046 for power and power factor, and the LO/HO energy pairs from 40051 (normal source) and 40071 (emergency source).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 17VL AVE - average L-L voltageUINT16VL AVE average L-L voltageRead
HR 23I AVE - average currentUINT16Average currentRead
HR 33kW T - total active powerINT16Total kWRead
HR 41Pf T - total power factorINT16Total power factorRead
HR 50Normal kWh importINT32 CDABNormal kWh importRead
HR 92Frequency (phase A)UINT16FrequencyRead

Enable Modbus control & writes

The 485 port (J1) protocol, baud rate and address are configuration registers 40208-40210 (writable with FC06).

Byte order & addressing

Network setup

Watch out for

ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

62 of 62 shown
ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR10doc 40011V AN - voltage A-NUINT16VRead
HR11doc 40012V BN - voltage B-NUINT16VRead
HR12doc 40013V CN - voltage C-NUINT16VRead
HR13doc 40014V AVE - average L-N voltageUINT16VRead
HR14doc 40015V AB - voltage A-BUINT16VRead
HR15doc 40016V BC - voltage B-CUINT16VRead
HR16doc 40017V CA - voltage C-AUINT16VRead
HR17doc 40018VL AVE - average L-L voltageUINT16VRead
HR18doc 40019VL UNBAL - L-L voltage unbalanceUINT16%Read
HR19doc 40020V UNBAL - L-N voltage unbalanceUINT16%Read
HR20doc 40021I A - current AUINT16ARead
HR21doc 40022I B - current BUINT16ARead
HR22doc 40023I C - current CUINT16ARead
HR23doc 40024I AVE - average currentUINT16ARead
HR24doc 40025I UNBAL - current unbalanceUINT16%Read
HR25doc 40026I N - CT4 / neutral currentUINT16ARead
HR30doc 40031kW AINT16kWRead
HR31doc 40032kW BINT16kWRead
HR32doc 40033kW CINT16kWRead
HR33doc 40034kW T - total active powerINT16kWRead
HR34doc 40035kVAR AINT16kVARRead
HR35doc 40036kVAR BINT16kVARRead
HR36doc 40037kVAR CINT16kVARRead
HR37doc 40038kVAR T - total reactive powerINT16kVARRead
HR38doc 40039Pf APower factor x 100 (-0.99 to +1.00).INT16× 0.01Read
HR39doc 40040Pf BPower factor x 100 (-0.99 to +1.00).INT16× 0.01Read
HR40doc 40041Pf CPower factor x 100 (-0.99 to +1.00).INT16× 0.01Read
HR41doc 40042Pf T - total power factorPower factor x 100 (-0.99 to +1.00).INT16× 0.01Read
HR42doc 40043kVA AUINT16kVARead
HR43doc 40044kVA BUINT16kVARead
HR44doc 40045kVA CUINT16kVARead
HR45doc 40046kVA T - total apparent powerUINT16kVARead
HR50doc 40051Normal kWh importLO word first, then HO word.INT32CDABkWhRead
HR52doc 40053Normal kWh exportLO word first, then HO word.INT32CDABkWhRead
HR54doc 40055Normal kWh netLO word first, then HO word.INT32CDABkWhRead
HR56doc 40057Normal kvarh importLO word first, then HO word.INT32CDABkvarhRead
HR58doc 40059Normal kvarh exportLO word first, then HO word.INT32CDABkvarhRead
HR60doc 40061Normal kvarh netLO word first, then HO word.INT32CDABkvarhRead
HR62doc 40063Normal kVAh netLO word first, then HO word.INT32CDABkVAhRead
HR64doc 40065Nom_Volt - nominal voltage115-59999. Firmware AS629262-004.UINT16VRead/write
HR65doc 40066Nom_Amps - nominal current0-29999. Firmware AS629262-004.UINT16ARead/write
HR66doc 40067kW_Capacity - nominal kW capacity0-24999. Firmware AS629262-004.UINT16kWRead/write
HR67doc 40068Nom_Freq - nominal frequencyUINT16Read/write0 = 60 Hz; 1 = 50 Hz
HR70doc 40071Emergency kWh importLO word first, then HO word.INT32CDABkWhRead
HR72doc 40073Emergency kWh exportLO word first, then HO word.INT32CDABkWhRead
HR74doc 40075Emergency kWh netLO word first, then HO word.INT32CDABkWhRead
HR76doc 40077Emergency kvarh importLO word first, then HO word.INT32CDABkvarhRead
HR78doc 40079Emergency kvarh exportLO word first, then HO word.INT32CDABkvarhRead
HR80doc 40081Emergency kvarh netLO word first, then HO word.INT32CDABkvarhRead
HR82doc 40083Emergency kVAh netLO word first, then HO word.INT32CDABkVAhRead
HR87doc 40088kWDemand T - instantaneous demandINT16kWRead
HR88doc 40089MaxkWDemand - maximum demandINT16kWRead
HR92doc 40093Frequency (phase A)Hz x 100, 40.00-80.00.UINT16× 0.01HzRead
HR93doc 40094StatusInputs - digital inputs S1-S8BITMAP16Readbit 0 = Input S1; bit 1 = Input S2; bit 2 = Input S3; bit 3 = Input S4; bit 4 = Input S5; bit 5 = Input S6; bit 6 = Input S7; bit 7 = Input S8
HR94doc 40095RelayOutputs - outputs DO1-DO4BITMAP16Read/writebit 0 = Output DO1; bit 1 = Output DO2; bit 2 = Output DO3; bit 3 = Output DO4
HR95doc 40096SwitchPosition - main / auxiliary switch position0 = normal, 1 = emergency (per the map).UINT16Read
HR101doc 40102V_String - software version12 ASCII characters.STRING[12]Read
HR113doc 40114SerialNumber12 ASCII characters.STRING[12]Read
HR119doc 40120ModelNumber12 ASCII characters.STRING[12]Read
HR126doc 40127H_STATUS - health status wordUINT16Read
HR213doc 40214Reset_Demand - reset demand registersUINT16Write
HR214doc 40215Clear_Energy - clear energy registersUINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)

What Modbus registers does the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) have?

This map lists 62 registers: 62 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. ASCO says the address sent is the map address minus 40001. The read example asks for IA-IAVE at 40021 with start address 0x0014 (20).

What byte order does the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)?

Start with HR 17 VL AVE - average L-L voltage (VL AVE average L-L voltage); HR 23 I AVE - average current (Average current); HR 33 kW T - total active power (Total kW); HR 41 Pf T - total power factor (Total power factor); HR 50 Normal kWh import (Normal kWh import); HR 92 Frequency (phase A) (Frequency).

How do I enable Modbus control of the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)?

The 485 port (J1) protocol, baud rate and address are configuration registers 40208-40210 (writable with FC06).

Where is the official ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus documentation?

The source is Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus (381339-221 I). ASCO doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Asco%207000%20Group%205.pdf. It may be an older revision, so check it against the live unit.

More ASCO Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus · 381339-221 I · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.