- Power Manager Xp power meter for transfer switches (Modbus RTU)
Power meter (transfer switch metering) · Modbus register map
ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus register map
Updated 17 November 2026
The Power Manager Xp is ASCO's metering module for 7000 Series transfer switches. Over Modbus RTU it reports per-phase voltage, current, kW, kvar, kVA and power factor, frequency, demand, separate energy totals for the normal and emergency sources, digital I/O and switch position, all as holding registers.
This page lists 62 Modbus registers for the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ASCO’s own free documentation (linked below) and checked against it.
- Manufacturer
- ASCO
- Model
- Power Manager Xp power meter for transfer switches (Modbus RTU)
- Equipment type
- Power meter (transfer switch metering)
- Registers
- 62 (7 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- FS611842-006; AS629262-004 for the nominal-rating and later registers
- Also known as
- ASCO Power Manager Xp, Power Manager Xp, 381339-221
Integration notes: ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)
Read 40011-40026 for voltage and current, 40031-40046 for power and power factor, and the LO/HO energy pairs from 40051 (normal source) and 40071 (emergency source).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 17 | VL AVE - average L-L voltage | UINT16 | VL AVE average L-L voltage | Read |
| HR 23 | I AVE - average current | UINT16 | Average current | Read |
| HR 33 | kW T - total active power | INT16 | Total kW | Read |
| HR 41 | Pf T - total power factor | INT16 | Total power factor | Read |
| HR 50 | Normal kWh import | INT32 CDAB | Normal kWh import | Read |
| HR 92 | Frequency (phase A) | UINT16 | Frequency | Read |
Enable Modbus control & writes
The 485 port (J1) protocol, baud rate and address are configuration registers 40208-40210 (writable with FC06).
Byte order & addressing
- RTU only, 8 data bits, no parity, 1 stop bit; maximum 64 bytes per packet.
- Energy pairs are low word first.
Network setup
- Device address 1-247; 0 is broadcast.
Watch out for
- Only the listed address ranges are supported; keep block reads inside them (e.g. skip undefined 40027-40030).
ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 10doc 40011 | V AN - voltage A-N | UINT16 | V | Read | ||||
| HR | 11doc 40012 | V BN - voltage B-N | UINT16 | V | Read | ||||
| HR | 12doc 40013 | V CN - voltage C-N | UINT16 | V | Read | ||||
| HR | 13doc 40014 | V AVE - average L-N voltage | UINT16 | V | Read | ||||
| HR | 14doc 40015 | V AB - voltage A-B | UINT16 | V | Read | ||||
| HR | 15doc 40016 | V BC - voltage B-C | UINT16 | V | Read | ||||
| HR | 16doc 40017 | V CA - voltage C-A | UINT16 | V | Read | ||||
| HR | 17doc 40018 | VL AVE - average L-L voltage | UINT16 | V | Read | ||||
| HR | 18doc 40019 | VL UNBAL - L-L voltage unbalance | UINT16 | % | Read | ||||
| HR | 19doc 40020 | V UNBAL - L-N voltage unbalance | UINT16 | % | Read | ||||
| HR | 20doc 40021 | I A - current A | UINT16 | A | Read | ||||
| HR | 21doc 40022 | I B - current B | UINT16 | A | Read | ||||
| HR | 22doc 40023 | I C - current C | UINT16 | A | Read | ||||
| HR | 23doc 40024 | I AVE - average current | UINT16 | A | Read | ||||
| HR | 24doc 40025 | I UNBAL - current unbalance | UINT16 | % | Read | ||||
| HR | 25doc 40026 | I N - CT4 / neutral current | UINT16 | A | Read | ||||
| HR | 30doc 40031 | kW A | INT16 | kW | Read | ||||
| HR | 31doc 40032 | kW B | INT16 | kW | Read | ||||
| HR | 32doc 40033 | kW C | INT16 | kW | Read | ||||
| HR | 33doc 40034 | kW T - total active power | INT16 | kW | Read | ||||
| HR | 34doc 40035 | kVAR A | INT16 | kVAR | Read | ||||
| HR | 35doc 40036 | kVAR B | INT16 | kVAR | Read | ||||
| HR | 36doc 40037 | kVAR C | INT16 | kVAR | Read | ||||
| HR | 37doc 40038 | kVAR T - total reactive power | INT16 | kVAR | Read | ||||
| HR | 38doc 40039 | Pf A | Power factor x 100 (-0.99 to +1.00). | INT16 | × 0.01 | Read | |||
| HR | 39doc 40040 | Pf B | Power factor x 100 (-0.99 to +1.00). | INT16 | × 0.01 | Read | |||
| HR | 40doc 40041 | Pf C | Power factor x 100 (-0.99 to +1.00). | INT16 | × 0.01 | Read | |||
| HR | 41doc 40042 | Pf T - total power factor | Power factor x 100 (-0.99 to +1.00). | INT16 | × 0.01 | Read | |||
| HR | 42doc 40043 | kVA A | UINT16 | kVA | Read | ||||
| HR | 43doc 40044 | kVA B | UINT16 | kVA | Read | ||||
| HR | 44doc 40045 | kVA C | UINT16 | kVA | Read | ||||
| HR | 45doc 40046 | kVA T - total apparent power | UINT16 | kVA | Read | ||||
| HR | 50doc 40051 | Normal kWh import | LO word first, then HO word. | INT32 | CDAB | kWh | Read | ||
| HR | 52doc 40053 | Normal kWh export | LO word first, then HO word. | INT32 | CDAB | kWh | Read | ||
| HR | 54doc 40055 | Normal kWh net | LO word first, then HO word. | INT32 | CDAB | kWh | Read | ||
| HR | 56doc 40057 | Normal kvarh import | LO word first, then HO word. | INT32 | CDAB | kvarh | Read | ||
| HR | 58doc 40059 | Normal kvarh export | LO word first, then HO word. | INT32 | CDAB | kvarh | Read | ||
| HR | 60doc 40061 | Normal kvarh net | LO word first, then HO word. | INT32 | CDAB | kvarh | Read | ||
| HR | 62doc 40063 | Normal kVAh net | LO word first, then HO word. | INT32 | CDAB | kVAh | Read | ||
| HR | 64doc 40065 | Nom_Volt - nominal voltage | 115-59999. Firmware AS629262-004. | UINT16 | V | Read/write | |||
| HR | 65doc 40066 | Nom_Amps - nominal current | 0-29999. Firmware AS629262-004. | UINT16 | A | Read/write | |||
| HR | 66doc 40067 | kW_Capacity - nominal kW capacity | 0-24999. Firmware AS629262-004. | UINT16 | kW | Read/write | |||
| HR | 67doc 40068 | Nom_Freq - nominal frequency | UINT16 | Read/write | 0 = 60 Hz; 1 = 50 Hz | ||||
| HR | 70doc 40071 | Emergency kWh import | LO word first, then HO word. | INT32 | CDAB | kWh | Read | ||
| HR | 72doc 40073 | Emergency kWh export | LO word first, then HO word. | INT32 | CDAB | kWh | Read | ||
| HR | 74doc 40075 | Emergency kWh net | LO word first, then HO word. | INT32 | CDAB | kWh | Read | ||
| HR | 76doc 40077 | Emergency kvarh import | LO word first, then HO word. | INT32 | CDAB | kvarh | Read | ||
| HR | 78doc 40079 | Emergency kvarh export | LO word first, then HO word. | INT32 | CDAB | kvarh | Read | ||
| HR | 80doc 40081 | Emergency kvarh net | LO word first, then HO word. | INT32 | CDAB | kvarh | Read | ||
| HR | 82doc 40083 | Emergency kVAh net | LO word first, then HO word. | INT32 | CDAB | kVAh | Read | ||
| HR | 87doc 40088 | kWDemand T - instantaneous demand | INT16 | kW | Read | ||||
| HR | 88doc 40089 | MaxkWDemand - maximum demand | INT16 | kW | Read | ||||
| HR | 92doc 40093 | Frequency (phase A) | Hz x 100, 40.00-80.00. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 93doc 40094 | StatusInputs - digital inputs S1-S8 | BITMAP16 | Read | bit 0 = Input S1; bit 1 = Input S2; bit 2 = Input S3; bit 3 = Input S4; bit 4 = Input S5; bit 5 = Input S6; bit 6 = Input S7; bit 7 = Input S8 | ||||
| HR | 94doc 40095 | RelayOutputs - outputs DO1-DO4 | BITMAP16 | Read/write | bit 0 = Output DO1; bit 1 = Output DO2; bit 2 = Output DO3; bit 3 = Output DO4 | ||||
| HR | 95doc 40096 | SwitchPosition - main / auxiliary switch position | 0 = normal, 1 = emergency (per the map). | UINT16 | Read | ||||
| HR | 101doc 40102 | V_String - software version | 12 ASCII characters. | STRING[12] | Read | ||||
| HR | 113doc 40114 | SerialNumber | 12 ASCII characters. | STRING[12] | Read | ||||
| HR | 119doc 40120 | ModelNumber | 12 ASCII characters. | STRING[12] | Read | ||||
| HR | 126doc 40127 | H_STATUS - health status word | UINT16 | Read | |||||
| HR | 213doc 40214 | Reset_Demand - reset demand registers | UINT16 | Write | |||||
| HR | 214doc 40215 | Clear_Energy - clear energy registers | UINT16 | Write |
Notes on this map
- Host: copy hosted by Contemporary Controls. Schneider Electric lists a newer revision (381339-221Q) on se.com behind a bot check; it was not opened.
- Energy registers are 32-bit pairs printed as 'LO word' then 'HO word' with a signed range (-1,999,999,999 to +1,999,999,999), so they are INT32, low word first (CDAB).
- Power factor is published as (value) x 100; frequency as Hz x 100.
- Readable addresses (wire, decimal): 11-26, 31-48, 51-64, 71-84, 87-94, 96-125, 127-128, 130-137, 149-159.
- Duplicate copies of total kW/kvar/kVA/PF/frequency at 40087-40101 and 40130-40132 and the configuration block 40200-40215 (system type, PT/CT ratios, port settings) are mostly not listed; their coding is described on pp. 6-8 of the document.
- Switch position register 40096 is printed as '0:norm & 1:emer.' for main and auxiliary; the bit layout is not stated.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)
What Modbus registers does the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) have?
This map lists 62 registers: 62 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. ASCO says the address sent is the map address minus 40001. The read example asks for IA-IAVE at 40021 with start address 0x0014 (20).
What byte order does the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)?
Start with HR 17 VL AVE - average L-L voltage (VL AVE average L-L voltage); HR 23 I AVE - average current (Average current); HR 33 kW T - total active power (Total kW); HR 41 Pf T - total power factor (Total power factor); HR 50 Normal kWh import (Normal kWh import); HR 92 Frequency (phase A) (Frequency).
How do I enable Modbus control of the ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)?
The 485 port (J1) protocol, baud rate and address are configuration registers 40208-40210 (writable with FC06).
Where is the official ASCO Power Manager Xp power meter for transfer switches (Modbus RTU) Modbus documentation?
The source is Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus (381339-221 I). ASCO doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Asco%207000%20Group%205.pdf. It may be an older revision, so check it against the live unit.
More ASCO Modbus register maps
Other generator controllers register maps
- Generator controller
Datakom DKG-705
Datakom DKG-705 AMF, parallel-to-mains and dual genset synchronization unit with J1939, Modbus application manual V-02-07 (14.04.2008).
Also known as: DKG 705, DKG705 - Generator controller
DEIF SGC 120 Mk II Single Genset Controller
SGC 120 Mk II software R18.0 (Modbus tables revision C).
Also known as: SGC 120 MkII, SGC 120 Mk2 - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS - Generator controller
Lovato Electric RGK800 AMF genset controller
RGK800, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800, RGK800 AMF - Generator controller
SmartGen HGM7100N Series
HGM7110N (auto start) and HGM7120N (AMF) genset controllers, protocol document v1.3.
Also known as: HGM7110N, HGM7120N - Generator controller
Datakom D-300 / D-500 / D-700 genset controllers
Datakom D-300, D-500 and D-700 controllers, Modbus application manual V5.6 (firmware 5.6 era).
Also known as: D-300, D-500, D-700, D300, D500, D700
All generator controllers Modbus register maps →
Source: Connectivity to the ASCO Power Manager Xp & 7000 Series Group 5 Controller via Modbus · 381339-221 I · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.