Easy Modbus
  1. Home
  2. Modbus register maps
  3. Lovato Electric
  4. ATL610 automatic transfer switch controller

Transfer switch · Modbus register map

Lovato Electric ATL610 automatic transfer switch controller Modbus register map

Updated 19 November 2026

Short answer

The ATL610 is Lovato's two-line automatic transfer switch controller for mains/mains or mains/generator changeover. It speaks Modbus RTU, ASCII or TCP through its optical port or plug-in USB, RS-232, RS-485 and Ethernet modules. This map covers both lines' voltages and frequencies, battery voltage, run-time and operation counters, the 32-bit alarm word, line and breaker status words, controller status, and the mode, breaker, generator and reset commands.

This page lists 48 Modbus registers for the Lovato Electric ATL610 automatic transfer switch controller — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Lovato Electric
Model
ATL610 automatic transfer switch controller
Equipment type
Transfer switch
Registers
48 (9 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
9600 baud, 8N1
TCP port
1001
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
ATL610, ATL 610, EXP1012, EXP1013
Source document
ATL610 Automatic transfer switch controller - Communication protocol Modbus · I428 GB I 09 22 · rev. 2022-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lovato Electric ATL610 automatic transfer switch controller

Integration in brief

Read LINE 1/LINE 2 voltages (02h-18h), frequencies (1Ah/1Ch), the alarm word (40h) and the line, breaker and controller status words (2074h-207Ch) with function 04, subtracting one from each table address. Change mode by writing 0/1/2 to 2F00h.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 7LINE 1 voltage L1-L2UINT32 ABCDLINE 1 L1-L2 voltageRead
IR 19LINE 2 voltage L1-L2UINT32 ABCDLINE 2 L1-L2 voltageRead
IR 63AlarmsUINT32 ABCDAlarm bitsRead
IR 8307LINE 1 voltage statusBITMAP16LINE 1 voltage statusRead
IR 8308LINE 1 breaker statusBITMAP16LINE 1 breaker statusRead
IR 8315Controller general statusBITMAP16Controller mode and global alarmRead
HR 12031Operating mode changeUINT16Mode change OFF/MAN/AUTWrite

Enable Modbus control & writes

Fit an EXP1012 (RS-485) or EXP1013 (Ethernet) module, or use the optical port, then set menu M08 for that port: node address P08.n.01, speed .02, data format .03, stop bits .04, protocol .05 and, for Ethernet, IP address/mask/port .06-.08.

Byte order & addressing

Network setup

Watch out for

Lovato Electric ATL610 automatic transfer switch controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

48 of 48 shown
Lovato Electric ATL610 automatic transfer switch controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR1doc 02hLINE 1 voltage L1-NUINT32ABCDVRead
IR3doc 04hLINE 1 voltage L2-NUINT32ABCDVRead
IR5doc 06hLINE 1 voltage L3-NUINT32ABCDVRead
IR7doc 08hLINE 1 voltage L1-L2UINT32ABCDVRead
IR9doc 0AhLINE 1 voltage L2-L3UINT32ABCDVRead
IR11doc 0ChLINE 1 voltage L3-L1UINT32ABCDVRead
IR13doc 0EhLINE 2 voltage L1-NUINT32ABCDVRead
IR15doc 10hLINE 2 voltage L2-NUINT32ABCDVRead
IR17doc 12hLINE 2 voltage L3-NUINT32ABCDVRead
IR19doc 14hLINE 2 voltage L1-L2UINT32ABCDVRead
IR21doc 16hLINE 2 voltage L2-L3UINT32ABCDVRead
IR23doc 18hLINE 2 voltage L3-L1UINT32ABCDVRead
IR25doc 1AhLINE 1 frequencyUINT32ABCD× 0.1HzRead
IR27doc 1ChLINE 2 frequencyUINT32ABCD× 0.1HzRead
IR29doc 1EhBattery voltage (DC supply)UINT32ABCD× 0.1VRead
IR31doc 20hTotal operation timeUINT32ABCDsRead
IR33doc 22hLINE 1 OK total timeUINT32ABCDsRead
IR35doc 24hLINE 2 OK total timeUINT32ABCDsRead
IR37doc 26hLINE 1 not OK total timeUINT32ABCDsRead
IR39doc 28hLINE 2 not OK total timeUINT32ABCDsRead
IR41doc 2AhLINE 1 breaker closed total timeUINT32ABCDsRead
IR43doc 2ChLINE 2 breaker closed total timeUINT32ABCDsRead
IR45doc 2EhBreakers open total timeUINT32ABCDsRead
IR49doc 32hLINE 1 breaker operations in AUTUINT32ABCDRead
IR51doc 34hLINE 2 breaker operations in AUTUINT32ABCDRead
IR53doc 36hLINE 1 breaker operations in MANUINT32ABCDRead
IR55doc 38hLINE 2 breaker operations in MANUINT32ABCDRead
IR57doc 3AhBreaker 1 switching alarmsUINT32ABCDRead
IR59doc 3ChBreaker 2 switching alarmsUINT32ABCDRead
IR63doc 40hAlarmsUINT32ABCDReadbit 0 = A01 Battery voltage too low; bit 1 = A02 Battery voltage too high; bit 2 = A03 LINE 1 breaker timeout; bit 3 = A04 LINE 2 breaker timeout; bit 4 = A05 LINE 1 wrong phase sequence; bit 5 = A06 LINE 2 wrong phase sequence; bit 6 = A07 Load not powered timeout; bit 7 = A08 External battery charger failure; bit 8 = A09 Emergency; bit 9 = A10 LINE 1 breaker protection trip; bit 10 = A11 LINE 2 breaker protection trip; bit 11 = A12 LINE 1 generator not available; bit 12 = A13 LINE 2 generator not available; bit 13 = A14 LINE 1 maintenance hours elapsed; bit 14 = A15 LINE 2 maintenance hours elapsed; bit 15 = A16 LINE 1 maintenance operations; bit 16 = A17 LINE 2 maintenance operations; bit 17 = A18 Auxiliary voltage failure; bit 18 = UA1 User alarm; bit 19 = UA2 User alarm; bit 20 = UA3 User alarm; bit 21 = UA4 User alarm
IR8303doc 2070hFront panel keyboard statusBITMAP16Readbit 0 = UP; bit 1 = OFF/RESET; bit 2 = MAN; bit 3 = DOWN; bit 4 = AUT/ENTER
IR8307doc 2074hLINE 1 voltage statusBITMAP16Readbit 0 = Line values within limits; bit 1 = Line within limits (delayed); bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below min; bit 7 = Voltage above max; bit 8 = Voltage asymmetry; bit 9 = Voltage phase loss; bit 10 = Frequency below min; bit 11 = Frequency above max; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK
IR8308doc 2075hLINE 1 breaker statusBITMAP16Readbit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded closed; bit 4 = Close command output; bit 5 = Open command output
IR8313doc 207AhOutput functions statusBITMAP16Readbit 0 = LINE 1 breaker open; bit 1 = LINE 2 breaker open; bit 2 = LINE 1 breaker close; bit 3 = LINE 2 breaker close; bit 4 = Global alarm; bit 5 = Generator 1 start; bit 6 = Generator 2 start; bit 7 = ATS ready; bit 8 = Load shed; bit 11 = Open all; bit 12 = Undervoltage coil 1; bit 13 = Undervoltage coil 2; bit 14 = LINE 1 OK; bit 15 = LINE 2 OK
IR8314doc 207BhDisplay message statusBITMAP16Readbit 0 = Generator 1 start; bit 1 = Generator 2 start; bit 2 = Generator 1 cooling; bit 3 = Generator 2 cooling; bit 4 = Load transfer 2 to 1; bit 5 = Load transfer 1 to 2
IR8315doc 207ChController general statusBITMAP16Readbit 0 = Mode OFF / reset; bit 1 = Mode MAN; bit 2 = Mode AUT; bit 3 = Mode TEST; bit 4 = Error on; bit 5 = AC supply present; bit 6 = DC supply present; bit 7 = Global alarm on
IR8447doc 2100hDigital inputs statusBITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14
IR8565doc 2176hLINE 2 voltage statusBITMAP16Readbit 0 = Line values within limits; bit 1 = Line within limits (delayed); bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below min; bit 7 = Voltage above max; bit 8 = Voltage asymmetry; bit 9 = Voltage phase loss; bit 10 = Frequency below min; bit 11 = Frequency above max; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK
IR8566doc 2177hLINE 2 breaker statusBITMAP16Readbit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded closed; bit 4 = Close command output; bit 5 = Open command output
HR7167doc 1C00hBreaker open/closeUINT16Write1 = Open breaker 1; 2 = Open breaker 2; 256 = Close breaker 1 (0x100); 512 = Close breaker 2 (0x200)
HR7169doc 1C02hGenerator start/stopUINT16Write1 = Stop generator 1; 2 = Stop generator 2; 256 = Start generator 1 (0x100); 512 = Start generator 2 (0x200)
HR12031doc 2F00hOperating mode changeUINT16Write0 = OFF mode; 1 = MAN mode; 2 = AUT mode
HR12034doc 2F03hSave / rebootUINT16Write1 = Save to E2PROM; 4 = Reboot; 5 = Save and reboot
HR12038doc 2F07hDevice resetUINT16Write0 = Reset device; 1 = Reset device and save FRAM
HR12041doc 2F0AhFront panel key simulationUINT16Write2 = MAN mode (0x0002); 32 = OFF mode (0x0020); 64 = AUT mode (0x0040); 32769 = Key UP (0x8001); 32772 = Key RIGHT (0x8004); 33280 = Key DOWN (0x8200); 33792 = Key ENTER (0x8400); 34816 = Key LEFT (0x8800)
HR12271doc 2FF0hCommand menu executionUINT16Write0 = Reset maintenance 1; 1 = Reset maintenance 2; 2 = Reset maintenance operations 1; 3 = Reset maintenance operations 2; 4 = Reset generic counters CNTx; 5 = Reset LIMx limits; 6 = Reset hour counters LINE 1/LINE 2; 7 = Reset hour counters BREAKER 1/BREAKER 2; 8 = Reset breaker operations; 9 = Reset event list; 10 = Restore default parameters; 11 = Save parameters to backup; 12 = Reload parameters from backup; 14 = Reset A03-A04 alarms; 15 = Simulate line failure
HR20223doc 4F00hRemote variable REM1REM2-REM8 follow at 4F01h-4F07h.UINT16Write170 = Set to 1 (AAh); 187 = Set to 0 (BBh)
HR20224doc 4F01hRemote variable REM2UINT16Write170 = Set to 1 (AAh); 187 = Set to 0 (BBh)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lovato Electric ATL610 automatic transfer switch controller

What Modbus registers does the Lovato Electric ATL610 automatic transfer switch controller have?

This map lists 48 registers: 39 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lovato Electric ATL610 automatic transfer switch controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print hex addresses one higher than the address in the request; the document says the query address must be decreased by one, its RTU example reads breaker 1 switching alarms (table 3Ah) by sending 00 39, and the event-log examples show 5030h - 1 = 502Fh. Addresses here are already reduced by one.

What byte order does the Lovato Electric ATL610 automatic transfer switch controller use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lovato Electric ATL610 automatic transfer switch controller?

Start with IR 7 LINE 1 voltage L1-L2 (LINE 1 L1-L2 voltage); IR 19 LINE 2 voltage L1-L2 (LINE 2 L1-L2 voltage); IR 63 Alarms (Alarm bits); IR 8307 LINE 1 voltage status (LINE 1 voltage status); IR 8308 LINE 1 breaker status (LINE 1 breaker status); IR 8315 Controller general status (Controller mode and global alarm); HR 12031 Operating mode change (Mode change OFF/MAN/AUT).

How do I enable Modbus control of the Lovato Electric ATL610 automatic transfer switch controller?

Fit an EXP1012 (RS-485) or EXP1013 (Ethernet) module, or use the optical port, then set menu M08 for that port: node address P08.n.01, speed .02, data format .03, stop bits .04, protocol .05 and, for Ethernet, IP address/mask/port .06-.08.

Where is the official Lovato Electric ATL610 automatic transfer switch controller Modbus documentation?

The source is ATL610 Automatic transfer switch controller - Communication protocol Modbus (I428 GB I 09 22), revision 2022-09, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/31.%20COMMUTATORI%20DI%20RETE%20AUTOMATICI/I428IGB09_22.pdf.

More Lovato Electric Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: ATL610 Automatic transfer switch controller - Communication protocol Modbus · I428 GB I 09 22 · rev. 2022-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.