Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus register map
Updated 19 November 2026
The ATL800 and ATL900 are Lovato's automatic transfer switch controllers for two (ATL800) or three (ATL900) sources. They talk Modbus RTU, ASCII and TCP through the optical port and EXP expansion modules. This map covers line voltages, frequencies, currents and powers, operating-time and operation counters, alarm and status words, and the mode, breaker and generator commands.
This page lists 114 Modbus registers for the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lovato Electric
- Model
- ATL800 / ATL900 automatic transfer switch controllers
- Equipment type
- Transfer switch
- Registers
- 114 (3 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- TCP port
- 1001
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ATL800, ATL900, ATL 800, ATL 900
Integration notes: Lovato Electric ATL800 / ATL900 automatic transfer switch controllers
Read 32-bit measures with function 04 at the table address minus one, high word first. 207Ch gives the mode and global alarm; write 2F00h (sent as 0x2EFF) to change mode, and 1C00h to open or close breakers.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 1 | Voltage of LINE1 L1-N | UINT32 ABCD | LINE1 L1-N voltage | Read |
| IR 13 | Voltage of LINE2 L1-N | UINT32 ABCD | LINE2 L1-N voltage | Read |
| IR 25 | Frequency of LINE1 | UINT32 ABCD | LINE1 frequency | Read |
| IR 8308 | LINE1 breaker status | BITMAP16 | LINE1 breaker status | Read |
| IR 8315 | Controller general status | BITMAP16 | Mode and global alarm | Read |
| IR 153 | Alarm bits A01-A32 | UINT32 ABCD | Alarm bits | Read |
| HR 12031 | Operating mode change | UINT16 | Mode change | Write |
Enable Modbus control & writes
Configure the port in setup menu M10 (node address P10.n.01, speed P10.n.02, data format P10.n.03, stop bits P10.n.04, protocol P10.n.05; IP settings for EXP1013).
Byte order & addressing
- Every address, read or write, is sent one lower than printed.
- Commands use function 06.
Network setup
- Up to three communication ports (n = 1-3) can be set in menu M10.
- Defaults: node 01, 9600 baud, 8 bits no parity, 1 stop bit, Modbus-RTU; Ethernet (EXP1013) default IP 192.168.1.1, IP port 1001.
Watch out for
- Line voltages are whole volts (no decimals).
- The default Modbus TCP port is 1001, not 502.
Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 1doc 02h | Voltage of LINE1 L1-N | UINT32 | ABCD | V | Read | |||
| IR | 3doc 04h | Voltage of LINE1 L2-N | UINT32 | ABCD | V | Read | |||
| IR | 5doc 06h | Voltage of LINE1 L3-N | UINT32 | ABCD | V | Read | |||
| IR | 7doc 08h | Voltage of LINE1 L1-L2 | UINT32 | ABCD | V | Read | |||
| IR | 9doc 0Ah | Voltage of LINE1 L2-L3 | UINT32 | ABCD | V | Read | |||
| IR | 11doc 0Ch | Voltage of LINE1 L3-L1 | UINT32 | ABCD | V | Read | |||
| IR | 13doc 0Eh | Voltage of LINE2 L1-N | UINT32 | ABCD | V | Read | |||
| IR | 15doc 10h | Voltage of LINE2 L2-N | UINT32 | ABCD | V | Read | |||
| IR | 17doc 12h | Voltage of LINE2 L3-N | UINT32 | ABCD | V | Read | |||
| IR | 19doc 14h | Voltage of LINE2 L1-L2 | UINT32 | ABCD | V | Read | |||
| IR | 21doc 16h | Voltage of LINE2 L2-L3 | UINT32 | ABCD | V | Read | |||
| IR | 23doc 18h | Voltage of LINE2 L3-L1 | UINT32 | ABCD | V | Read | |||
| IR | 25doc 1Ah | Frequency of LINE1 | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| IR | 27doc 1Ch | Frequency of LINE2 | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| IR | 29doc 1Eh | Battery voltage (DC power supply) | UINT32 | ABCD | × 0.1 | V | Read | ||
| IR | 31doc 20h | Total operation time | UINT32 | ABCD | s | Read | |||
| IR | 33doc 22h | LINE1 ok total time | UINT32 | ABCD | s | Read | |||
| IR | 35doc 24h | LINE2 ok total time | UINT32 | ABCD | s | Read | |||
| IR | 37doc 26h | LINE1 not ok total time | UINT32 | ABCD | s | Read | |||
| IR | 39doc 28h | LINE2 not ok total time | UINT32 | ABCD | s | Read | |||
| IR | 41doc 2Ah | LINE1 breaker closed total time | UINT32 | ABCD | s | Read | |||
| IR | 43doc 2Ch | LINE2 breaker closed total time | UINT32 | ABCD | s | Read | |||
| IR | 45doc 2Eh | Breaker opened total time | UINT32 | ABCD | s | Read | |||
| IR | 49doc 32h | Number of operations of LINE1 breaker in AUT | UINT32 | ABCD | Read | ||||
| IR | 51doc 34h | Number of operations of LINE2 breaker in AUT | UINT32 | ABCD | Read | ||||
| IR | 53doc 36h | Number of operations of LINE1 breaker in MAN | UINT32 | ABCD | Read | ||||
| IR | 55doc 38h | Number of operations of LINE2 breaker in MAN | UINT32 | ABCD | Read | ||||
| IR | 57doc 3Ah | Number of switching alarms of breaker 1 | UINT32 | ABCD | Read | ||||
| IR | 59doc 3Ch | Number of switching alarms of breaker 2 | UINT32 | ABCD | Read | ||||
| IR | 127doc 80h | Voltage of LINE3 L1-N | ATL900 only. | UINT32 | ABCD | V | Read | ||
| IR | 129doc 82h | Voltage of LINE3 L2-N | ATL900 only. | UINT32 | ABCD | V | Read | ||
| IR | 131doc 84h | Voltage of LINE3 L3-N | ATL900 only. | UINT32 | ABCD | V | Read | ||
| IR | 133doc 86h | Voltage of LINE3 L1-L2 | ATL900 only. | UINT32 | ABCD | V | Read | ||
| IR | 135doc 88h | Voltage of LINE3 L2-L3 | ATL900 only. | UINT32 | ABCD | V | Read | ||
| IR | 137doc 8Ah | Voltage of LINE3 L3-L1 | ATL900 only. | UINT32 | ABCD | V | Read | ||
| IR | 139doc 8Ch | Frequency of LINE3 | ATL900 only. | UINT32 | ABCD | × 0.1 | Hz | Read | |
| IR | 141doc 8Eh | LINE3 ok total time | Printed as h/3600, i.e. a count of seconds. ATL900 only. | UINT32 | ABCD | s | Read | ||
| IR | 143doc 90h | LINE3 not ok total time | Printed as h/3600, i.e. a count of seconds. ATL900 only. | UINT32 | ABCD | s | Read | ||
| IR | 145doc 92h | LINE3 breaker closed total time | Printed as h/3600, i.e. a count of seconds. ATL900 only. | UINT32 | ABCD | s | Read | ||
| IR | 147doc 94h | Number of operations of LINE3 breaker in AUT | ATL900 only. | UINT32 | ABCD | Read | |||
| IR | 149doc 96h | Number of operations of LINE3 breaker in MAN | ATL900 only. | UINT32 | ABCD | Read | |||
| IR | 151doc 98h | Number of switching alarms of breaker 3 | ATL900 only. | UINT32 | ABCD | Read | |||
| IR | 153doc 9Ah | Alarm bits A01-A32 | One alarm per bit; see notes. | UINT32 | ABCD | Read | |||
| IR | 155doc 9Ch | Alarm bits A33-A39, UA1-UA8 | One alarm per bit; see notes. | UINT32 | ABCD | Read | |||
| IR | 1079doc 438h | Current LINE1 - I1 | INT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 1081doc 43Ah | Current LINE1 - I2 | INT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 1083doc 43Ch | Current LINE1 - I3 | INT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 1085doc 43Eh | Current LINE2 - I1 | INT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 1087doc 440h | Current LINE2 - I2 | INT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 1089doc 442h | Current LINE2 - I3 | INT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 1091doc 444h | Current LINE3 - I1 | ATL900 only. | INT32 | ABCD | × 0.0001 | A | Read | |
| IR | 1093doc 446h | Current LINE3 - I2 | ATL900 only. | INT32 | ABCD | × 0.0001 | A | Read | |
| IR | 1095doc 448h | Current LINE3 - I3 | ATL900 only. | INT32 | ABCD | × 0.0001 | A | Read | |
| IR | 1097doc 44Ah | Active power LINE1 - L1 | INT32 | ABCD | × 0.0001 | kW | Read | ||
| IR | 1099doc 44Ch | Active power LINE1 - L2 | INT32 | ABCD | × 0.0001 | kW | Read | ||
| IR | 1101doc 44Eh | Active power LINE1 - L3 | INT32 | ABCD | × 0.0001 | kW | Read | ||
| IR | 1103doc 450h | Active power LINE2 - L1 | INT32 | ABCD | × 0.0001 | kW | Read | ||
| IR | 1105doc 452h | Active power LINE2 - L2 | INT32 | ABCD | × 0.0001 | kW | Read | ||
| IR | 1107doc 454h | Active power LINE2 - L3 | INT32 | ABCD | × 0.0001 | kW | Read | ||
| IR | 1109doc 456h | Active power LINE3 - L1 | ATL900 only. | INT32 | ABCD | × 0.0001 | kW | Read | |
| IR | 1111doc 458h | Active power LINE3 - L2 | ATL900 only. | INT32 | ABCD | × 0.0001 | kW | Read | |
| IR | 1113doc 45Ah | Active power LINE3 - L3 | ATL900 only. | INT32 | ABCD | × 0.0001 | kW | Read | |
| IR | 1115doc 45Ch | Reactive power LINE1 - L1 | INT32 | ABCD | × 0.0001 | kvar | Read | ||
| IR | 1117doc 45Eh | Reactive power LINE1 - L2 | INT32 | ABCD | × 0.0001 | kvar | Read | ||
| IR | 1119doc 460h | Reactive power LINE1 - L3 | INT32 | ABCD | × 0.0001 | kvar | Read | ||
| IR | 1121doc 462h | Reactive power LINE2 - L1 | INT32 | ABCD | × 0.0001 | kvar | Read | ||
| IR | 1123doc 464h | Reactive power LINE2 - L2 | INT32 | ABCD | × 0.0001 | kvar | Read | ||
| IR | 1125doc 466h | Reactive power LINE2 - L3 | INT32 | ABCD | × 0.0001 | kvar | Read | ||
| IR | 1127doc 468h | Reactive power LINE3 - L1 | ATL900 only. | INT32 | ABCD | × 0.0001 | kvar | Read | |
| IR | 1129doc 46Ah | Reactive power LINE3 - L2 | ATL900 only. | INT32 | ABCD | × 0.0001 | kvar | Read | |
| IR | 1131doc 46Ch | Reactive power LINE3 - L3 | ATL900 only. | INT32 | ABCD | × 0.0001 | kvar | Read | |
| IR | 1133doc 46Eh | Apparent power LINE1 - L1 | INT32 | ABCD | × 0.0001 | kVA | Read | ||
| IR | 1135doc 470h | Apparent power LINE1 - L2 | INT32 | ABCD | × 0.0001 | kVA | Read | ||
| IR | 1137doc 472h | Apparent power LINE1 - L3 | INT32 | ABCD | × 0.0001 | kVA | Read | ||
| IR | 1139doc 474h | Apparent power LINE2 - L1 | INT32 | ABCD | × 0.0001 | kVA | Read | ||
| IR | 1141doc 476h | Apparent power LINE2 - L2 | INT32 | ABCD | × 0.0001 | kVA | Read | ||
| IR | 1143doc 478h | Apparent power LINE2 - L3 | INT32 | ABCD | × 0.0001 | kVA | Read | ||
| IR | 1145doc 47Ah | Apparent power LINE3 - L1 | ATL900 only. | INT32 | ABCD | × 0.0001 | kVA | Read | |
| IR | 1147doc 47Ch | Apparent power LINE3 - L2 | ATL900 only. | INT32 | ABCD | × 0.0001 | kVA | Read | |
| IR | 1149doc 47Eh | Apparent power LINE3 - L3 | ATL900 only. | INT32 | ABCD | × 0.0001 | kVA | Read | |
| IR | 1151doc 480h | PF LINE1 - L1 | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 1153doc 482h | PF LINE1 - L2 | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 1155doc 484h | PF LINE1 - L3 | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 1157doc 486h | PF LINE2 - L1 | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 1159doc 488h | PF LINE2 - L2 | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 1161doc 48Ah | PF LINE2 - L3 | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 1163doc 48Ch | PF LINE3 - L1 | ATL900 only. | INT32 | ABCD | × 0.0001 | Read | ||
| IR | 1165doc 48Eh | PF LINE3 - L2 | ATL900 only. | INT32 | ABCD | × 0.0001 | Read | ||
| IR | 1167doc 490h | PF LINE3 - L3 | ATL900 only. | INT32 | ABCD | × 0.0001 | Read | ||
| IR | 1169doc 492h | PFT LINE1 | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 1171doc 494h | Current LINE1 - In | INT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 1175doc 498h | PFT LINE2 | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 1177doc 49Ah | Current LINE2 - In | INT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 1181doc 49Eh | PFT LINE3 | ATL900 only. | INT32 | ABCD | × 0.0001 | Read | ||
| IR | 1183doc 4A0h | Current LINE3 - In | ATL900 only. | INT32 | ABCD | × 0.0001 | A | Read | |
| IR | 1187doc 4A4h | Total active power LINE1 | INT32 | ABCD | × 0.0001 | kW | Read | ||
| IR | 1189doc 4A6h | Total reactive power LINE1 | INT32 | ABCD | × 0.0001 | kvar | Read | ||
| IR | 1191doc 4A8h | Total apparent power LINE1 | INT32 | ABCD | × 0.0001 | kVA | Read | ||
| IR | 1193doc 4Aah | Total active power LINE2 | INT32 | ABCD | × 0.0001 | kW | Read | ||
| IR | 1195doc 4ACh | Total reactive power LINE2 | INT32 | ABCD | × 0.0001 | kvar | Read | ||
| IR | 1197doc 4AEh | Total apparent power LINE2 | INT32 | ABCD | × 0.0001 | kVA | Read | ||
| IR | 1199doc 4B0h | Total active power LINE3 | ATL900 only. | INT32 | ABCD | × 0.0001 | kW | Read | |
| IR | 1201doc 4B2h | Total reactive power LINE3 | ATL900 only. | INT32 | ABCD | × 0.0001 | kvar | Read | |
| IR | 1203doc 4B4h | Total apparent power LINE3 | ATL900 only. | INT32 | ABCD | × 0.0001 | kVA | Read | |
| IR | 8307doc 2074h | LINE1 voltage status | BITMAP16 | Read | bit 0 = Line values within limits; bit 1 = Line values within limits (after delay); bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below minimum; bit 7 = Voltage above maximum; bit 8 = Voltage asymmetry; bit 9 = Phase loss; bit 10 = Frequency below minimum; bit 11 = Frequency above maximum; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK | ||||
| IR | 8308doc 2075h | LINE1 breaker status | BITMAP16 | Read | bit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded state (1 = close); bit 4 = Close command output; bit 5 = Open command output | ||||
| IR | 8315doc 207Ch | Controller general status | BITMAP16 | Read | bit 0 = OFF / reset mode; bit 1 = MAN mode; bit 2 = AUT mode; bit 3 = TEST mode; bit 4 = Error; bit 5 = AC supply present; bit 6 = DC supply present; bit 7 = Global alarm | ||||
| IR | 8322doc 2083h | LINE3 voltage status | ATL900 only. | BITMAP16 | Read | bit 0 = Line values within limits; bit 1 = Line values within limits (after delay); bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below minimum; bit 7 = Voltage above maximum; bit 8 = Voltage asymmetry; bit 9 = Phase loss; bit 10 = Frequency below minimum; bit 11 = Frequency above maximum; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK | |||
| IR | 8323doc 2084h | LINE3 breaker status | ATL900 only. | BITMAP16 | Read | bit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded state (1 = close); bit 4 = Close command output; bit 5 = Open command output | |||
| IR | 8565doc 2176h | LINE2 voltage status | Address exactly as printed in the table. | BITMAP16 | Read | bit 0 = Line values within limits; bit 1 = Line values within limits (after delay); bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below minimum; bit 7 = Voltage above maximum; bit 8 = Voltage asymmetry; bit 9 = Phase loss; bit 10 = Frequency below minimum; bit 11 = Frequency above maximum; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK | |||
| IR | 8566doc 2177h | LINE2 breaker status | Address exactly as printed in the table. | BITMAP16 | Read | bit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded state (1 = close); bit 4 = Close command output; bit 5 = Open command output | |||
| HR | 7167doc 1C00h | Breaker open/close command | BRK3 and TB2 values are ATL900 only. | UINT16 | Write | 1 = Open BRK1; 2 = Open BRK2; 4 = Open BRK3; 8 = Open TB1; 16 = Open TB2; 256 = Close BRK1; 512 = Close BRK2; 1024 = Close BRK3; 2048 = Close TB1; 4096 = Close TB2 | |||
| HR | 7169doc 1C02h | Generator start/stop command | UINT16 | Write | 1 = Stop generator 1; 2 = Stop generator 2; 4 = Stop generator 3; 256 = Start generator 1; 512 = Start generator 2; 1024 = Start generator 3 | ||||
| HR | 12031doc 2F00h | Operating mode change | Write a value to change mode. | UINT16 | Write | 0 = OFF; 1 = MAN; 2 = AUT |
Notes on this map
- Word order: the read example returns 00 00 00 0A for a count of 10, so the high word comes first (ABCD).
- Units as printed: line voltages are whole volts, frequency Hz/10, battery VDC/10, currents A/10000, powers kW, kvar and kVA /10000, power factor /10000.
- Alarm bits at 9Ah (32-bit): bit 0 A01 battery voltage low, 1 A02 battery high, 2 A03 BRK1 timeout, 3 A04 BRK2 timeout, 4 A05 BRK3 timeout, 5-7 A06-A08 phase sequence lines 1-3, 8 A09 load not powered timeout, 9 A10 local battery charger, 10-12 A11-A13 genset battery chargers, 13 A14 emergency, 14-16 A15-A17 breaker trips, 17-19 A18-A20 breakers withdrawn, 20-22 A21-A23 genset not available, 23-25 A24-A26 maintenance hours, 26-28 A27-A29 maintenance operations, 29 A30 auxiliary voltage breaker, 30 A31 non-priority load breaker timeout, 31 A32 TB1 timeout. At 9Ch: bits 0-6 A33-A39 (tie and non-priority breakers), bits 7-14 user alarms UA1-UA8.
- Left out: maintenance hours and operations-to-maintenance (units differ between lines), minimum/maximum battery voltage (unit printed as V while the live value is VDC/10), generic counters and analog I/O (user-defined units), digital I/O bit words, display-message and LED words, the 32-bit device global status at 2210h, remote variables, key simulation, and the setup parameters.
- LINE2 status words are printed at 2176h/2177h while LINE1 is at 2074h/2075h; they are listed exactly as printed.
- Input function status is left out: Table 3 lists it at 2078h, but the bit table for it says to read address 2178h, so the address is not settled.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers
What Modbus registers does the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers have?
This map lists 114 registers: 111 input registers, 3 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print hex addresses (for example 3Ah) and the document says to send one less. Its read example asks for 3Ah with start address 00 39, and its write example sends 2F03h as 2F02h. 'address' here is already reduced by one.
What byte order does the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers?
Start with IR 1 Voltage of LINE1 L1-N (LINE1 L1-N voltage); IR 13 Voltage of LINE2 L1-N (LINE2 L1-N voltage); IR 25 Frequency of LINE1 (LINE1 frequency); IR 8308 LINE1 breaker status (LINE1 breaker status); IR 8315 Controller general status (Mode and global alarm); IR 153 Alarm bits A01-A32 (Alarm bits); HR 12031 Operating mode change (Mode change).
How do I enable Modbus control of the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers?
Configure the port in setup menu M10 (node address P10.n.01, speed P10.n.02, data format P10.n.03, stop bits P10.n.04, protocol P10.n.05; IP settings for EXP1013).
Where is the official Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus documentation?
The source is ATL800 - ATL900 Automatic transfer switch controller - Communication protocol Modbus (I463 GB I 11 21), published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/31.%20COMMUTATORI%20DI%20RETE%20AUTOMATICI/I463IGB11_21.pdf.
More Lovato Electric Modbus register maps
- Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042 - Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Transfer switch
Lovato Electric ATL610 automatic transfer switch controller
ATL610 ATS controller via the optical port or an EXP1010/1011/1012/1013 communication module, per protocol document I428 GB I 09 22.
Also known as: ATL610, ATL 610, EXP1012, EXP1013 - Power meter (power factor controller)
Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers
DCRL3, DCRL5 and DCRL8 automatic power factor controllers with optical port or EXP10xx modules (Modbus TCP on DCRL8 only), per protocol document I427 GB 05 20.
Also known as: DCRL3, DCRL5, DCRL8, DCRL 3, DCRL 5, DCRL 8 - Power meter (power analyzer)
Lovato Electric DMG7000 / DMG7500 / DMG8000 / DMG9000 power analyzers
Lovato DMG7000, DMG7500, DMG8000 and DMG9000 panel power analyzers on any Modbus port (RTU, ASCII or TCP); DMG9000-only rows are marked.
Also known as: DMG7000, DMG7500, DMG8000, DMG9000, DMG 7000, DMG 8000, DMG 9000, Lovato DMG - Pump (diesel fire pump controller)
Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers
FFL700DP and FFL800DP diesel engine fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800DP), per protocol document I557 GB I 11 17.
Also known as: FFL700DP, FFL800DP, FFL 700 DP, FFL 800 DP - Pump (electric fire pump controller)
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
FFL700EP and FFL800EP electric fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800EP), per protocol document I589 GB I 08 22.
Also known as: FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP - Generator controller
Lovato Electric RGK610 genset controller
RGK610, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 610 - Generator controller
Lovato Electric RGK700 AMF genset controller
RGK700, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700, RGK700 AMF - Generator controller
Lovato Electric RGK700SA stand-alone genset controller
RGK700SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700SA, RGK700 SA - Generator controller
Lovato Electric RGK750 genset controller
RGK750, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 750 - Generator controller
Lovato Electric RGK800 AMF genset controller
RGK800, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800, RGK800 AMF - Generator controller
Lovato Electric RGK800SA stand-alone genset controller
RGK800SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800SA, RGK800 SA - Generator controller
Lovato Electric RGK900 genset paralleling controller
RGK900, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900 - Generator controller
Lovato Electric RGK900MC mains/master controller
RGK900MC, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900MC, RGK900 MC - Generator controller
Lovato Electric RGK900SA genset paralleling controller (stand-alone)
RGK900SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900SA, RGK900 SA - Variable frequency drive
Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)
Lovato VT1 series drives on the built-in RS-485 port, per communication manual I646 GB I 02 21 (Modbus part).
Also known as: VT1, Lovato VT1, VT1 series
Other generator controllers register maps
- Generator controller (synchronizer and load sharing control)
Woodward DSLC-2 Digital Synchronizer and Load Control
DSLC-2, data protocol 5200, per manual 37443J.
Also known as: DSLC2, DSLC-2 synchronizer - Transfer switch controller
BTicino M7000CBNCU03 automatic transfer switch controller (Modbus)
BTicino M7000CBNCU03 (Legrand cat. no. 4 226 82) automatic changeover controller, Modbus RTU/ASCII via the M7000CBNRS485 expansion module or the IR-USB / IR-WiFi front interfaces, per document LE09509AA-01/17-01.
Also known as: M7000CBNCU03, 4 226 82, 422682, Legrand 4 226 82 - Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2 - Generator controller
SmartGen HGM9510N / HGM9520N / HGM9530N
HGM9510N, HGM9520N and HGM9530N paralleling genset controllers, protocol document v1.5.
Also known as: HGM9520N, HGM9530N - Power meter (transfer switch metering)
ASCO Power Manager Xp power meter for transfer switches (Modbus RTU)
ASCO Power Manager Xp, firmware FS611842-006 (some registers AS629262-004); document 381339-221 revision I.
Also known as: ASCO Power Manager Xp, Power Manager Xp, 381339-221
All generator controllers Modbus register maps →
Source: ATL800 - ATL900 Automatic transfer switch controller - Communication protocol Modbus · I463 GB I 11 21. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.