Transfer switch · Modbus register map

Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus register map

Updated 19 November 2026

Short answer

The ATL800 and ATL900 are Lovato's automatic transfer switch controllers for two (ATL800) or three (ATL900) sources. They talk Modbus RTU, ASCII and TCP through the optical port and EXP expansion modules. This map covers line voltages, frequencies, currents and powers, operating-time and operation counters, alarm and status words, and the mode, breaker and generator commands.

This page lists 114 Modbus registers for the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Lovato Electric
Model
ATL800 / ATL900 automatic transfer switch controllers
Equipment type
Transfer switch
Registers
114 (3 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
9600 baud, 8N1
TCP port
1001
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
ATL800, ATL900, ATL 800, ATL 900
Source document
ATL800 - ATL900 Automatic transfer switch controller - Communication protocol Modbus · I463 GB I 11 21
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lovato Electric ATL800 / ATL900 automatic transfer switch controllers

Integration in brief

Read 32-bit measures with function 04 at the table address minus one, high word first. 207Ch gives the mode and global alarm; write 2F00h (sent as 0x2EFF) to change mode, and 1C00h to open or close breakers.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 1Voltage of LINE1 L1-NUINT32 ABCDLINE1 L1-N voltageRead
IR 13Voltage of LINE2 L1-NUINT32 ABCDLINE2 L1-N voltageRead
IR 25Frequency of LINE1UINT32 ABCDLINE1 frequencyRead
IR 8308LINE1 breaker statusBITMAP16LINE1 breaker statusRead
IR 8315Controller general statusBITMAP16Mode and global alarmRead
IR 153Alarm bits A01-A32UINT32 ABCDAlarm bitsRead
HR 12031Operating mode changeUINT16Mode changeWrite

Enable Modbus control & writes

Configure the port in setup menu M10 (node address P10.n.01, speed P10.n.02, data format P10.n.03, stop bits P10.n.04, protocol P10.n.05; IP settings for EXP1013).

Byte order & addressing

Network setup

Watch out for

Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

114 of 114 shown
Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR1doc 02hVoltage of LINE1 L1-NUINT32ABCDVRead
IR3doc 04hVoltage of LINE1 L2-NUINT32ABCDVRead
IR5doc 06hVoltage of LINE1 L3-NUINT32ABCDVRead
IR7doc 08hVoltage of LINE1 L1-L2UINT32ABCDVRead
IR9doc 0AhVoltage of LINE1 L2-L3UINT32ABCDVRead
IR11doc 0ChVoltage of LINE1 L3-L1UINT32ABCDVRead
IR13doc 0EhVoltage of LINE2 L1-NUINT32ABCDVRead
IR15doc 10hVoltage of LINE2 L2-NUINT32ABCDVRead
IR17doc 12hVoltage of LINE2 L3-NUINT32ABCDVRead
IR19doc 14hVoltage of LINE2 L1-L2UINT32ABCDVRead
IR21doc 16hVoltage of LINE2 L2-L3UINT32ABCDVRead
IR23doc 18hVoltage of LINE2 L3-L1UINT32ABCDVRead
IR25doc 1AhFrequency of LINE1UINT32ABCD× 0.1HzRead
IR27doc 1ChFrequency of LINE2UINT32ABCD× 0.1HzRead
IR29doc 1EhBattery voltage (DC power supply)UINT32ABCD× 0.1VRead
IR31doc 20hTotal operation timeUINT32ABCDsRead
IR33doc 22hLINE1 ok total timeUINT32ABCDsRead
IR35doc 24hLINE2 ok total timeUINT32ABCDsRead
IR37doc 26hLINE1 not ok total timeUINT32ABCDsRead
IR39doc 28hLINE2 not ok total timeUINT32ABCDsRead
IR41doc 2AhLINE1 breaker closed total timeUINT32ABCDsRead
IR43doc 2ChLINE2 breaker closed total timeUINT32ABCDsRead
IR45doc 2EhBreaker opened total timeUINT32ABCDsRead
IR49doc 32hNumber of operations of LINE1 breaker in AUTUINT32ABCDRead
IR51doc 34hNumber of operations of LINE2 breaker in AUTUINT32ABCDRead
IR53doc 36hNumber of operations of LINE1 breaker in MANUINT32ABCDRead
IR55doc 38hNumber of operations of LINE2 breaker in MANUINT32ABCDRead
IR57doc 3AhNumber of switching alarms of breaker 1UINT32ABCDRead
IR59doc 3ChNumber of switching alarms of breaker 2UINT32ABCDRead
IR127doc 80hVoltage of LINE3 L1-NATL900 only.UINT32ABCDVRead
IR129doc 82hVoltage of LINE3 L2-NATL900 only.UINT32ABCDVRead
IR131doc 84hVoltage of LINE3 L3-NATL900 only.UINT32ABCDVRead
IR133doc 86hVoltage of LINE3 L1-L2ATL900 only.UINT32ABCDVRead
IR135doc 88hVoltage of LINE3 L2-L3ATL900 only.UINT32ABCDVRead
IR137doc 8AhVoltage of LINE3 L3-L1ATL900 only.UINT32ABCDVRead
IR139doc 8ChFrequency of LINE3ATL900 only.UINT32ABCD× 0.1HzRead
IR141doc 8EhLINE3 ok total timePrinted as h/3600, i.e. a count of seconds. ATL900 only.UINT32ABCDsRead
IR143doc 90hLINE3 not ok total timePrinted as h/3600, i.e. a count of seconds. ATL900 only.UINT32ABCDsRead
IR145doc 92hLINE3 breaker closed total timePrinted as h/3600, i.e. a count of seconds. ATL900 only.UINT32ABCDsRead
IR147doc 94hNumber of operations of LINE3 breaker in AUTATL900 only.UINT32ABCDRead
IR149doc 96hNumber of operations of LINE3 breaker in MANATL900 only.UINT32ABCDRead
IR151doc 98hNumber of switching alarms of breaker 3ATL900 only.UINT32ABCDRead
IR153doc 9AhAlarm bits A01-A32One alarm per bit; see notes.UINT32ABCDRead
IR155doc 9ChAlarm bits A33-A39, UA1-UA8One alarm per bit; see notes.UINT32ABCDRead
IR1079doc 438hCurrent LINE1 - I1INT32ABCD× 0.0001ARead
IR1081doc 43AhCurrent LINE1 - I2INT32ABCD× 0.0001ARead
IR1083doc 43ChCurrent LINE1 - I3INT32ABCD× 0.0001ARead
IR1085doc 43EhCurrent LINE2 - I1INT32ABCD× 0.0001ARead
IR1087doc 440hCurrent LINE2 - I2INT32ABCD× 0.0001ARead
IR1089doc 442hCurrent LINE2 - I3INT32ABCD× 0.0001ARead
IR1091doc 444hCurrent LINE3 - I1ATL900 only.INT32ABCD× 0.0001ARead
IR1093doc 446hCurrent LINE3 - I2ATL900 only.INT32ABCD× 0.0001ARead
IR1095doc 448hCurrent LINE3 - I3ATL900 only.INT32ABCD× 0.0001ARead
IR1097doc 44AhActive power LINE1 - L1INT32ABCD× 0.0001kWRead
IR1099doc 44ChActive power LINE1 - L2INT32ABCD× 0.0001kWRead
IR1101doc 44EhActive power LINE1 - L3INT32ABCD× 0.0001kWRead
IR1103doc 450hActive power LINE2 - L1INT32ABCD× 0.0001kWRead
IR1105doc 452hActive power LINE2 - L2INT32ABCD× 0.0001kWRead
IR1107doc 454hActive power LINE2 - L3INT32ABCD× 0.0001kWRead
IR1109doc 456hActive power LINE3 - L1ATL900 only.INT32ABCD× 0.0001kWRead
IR1111doc 458hActive power LINE3 - L2ATL900 only.INT32ABCD× 0.0001kWRead
IR1113doc 45AhActive power LINE3 - L3ATL900 only.INT32ABCD× 0.0001kWRead
IR1115doc 45ChReactive power LINE1 - L1INT32ABCD× 0.0001kvarRead
IR1117doc 45EhReactive power LINE1 - L2INT32ABCD× 0.0001kvarRead
IR1119doc 460hReactive power LINE1 - L3INT32ABCD× 0.0001kvarRead
IR1121doc 462hReactive power LINE2 - L1INT32ABCD× 0.0001kvarRead
IR1123doc 464hReactive power LINE2 - L2INT32ABCD× 0.0001kvarRead
IR1125doc 466hReactive power LINE2 - L3INT32ABCD× 0.0001kvarRead
IR1127doc 468hReactive power LINE3 - L1ATL900 only.INT32ABCD× 0.0001kvarRead
IR1129doc 46AhReactive power LINE3 - L2ATL900 only.INT32ABCD× 0.0001kvarRead
IR1131doc 46ChReactive power LINE3 - L3ATL900 only.INT32ABCD× 0.0001kvarRead
IR1133doc 46EhApparent power LINE1 - L1INT32ABCD× 0.0001kVARead
IR1135doc 470hApparent power LINE1 - L2INT32ABCD× 0.0001kVARead
IR1137doc 472hApparent power LINE1 - L3INT32ABCD× 0.0001kVARead
IR1139doc 474hApparent power LINE2 - L1INT32ABCD× 0.0001kVARead
IR1141doc 476hApparent power LINE2 - L2INT32ABCD× 0.0001kVARead
IR1143doc 478hApparent power LINE2 - L3INT32ABCD× 0.0001kVARead
IR1145doc 47AhApparent power LINE3 - L1ATL900 only.INT32ABCD× 0.0001kVARead
IR1147doc 47ChApparent power LINE3 - L2ATL900 only.INT32ABCD× 0.0001kVARead
IR1149doc 47EhApparent power LINE3 - L3ATL900 only.INT32ABCD× 0.0001kVARead
IR1151doc 480hPF LINE1 - L1INT32ABCD× 0.0001Read
IR1153doc 482hPF LINE1 - L2INT32ABCD× 0.0001Read
IR1155doc 484hPF LINE1 - L3INT32ABCD× 0.0001Read
IR1157doc 486hPF LINE2 - L1INT32ABCD× 0.0001Read
IR1159doc 488hPF LINE2 - L2INT32ABCD× 0.0001Read
IR1161doc 48AhPF LINE2 - L3INT32ABCD× 0.0001Read
IR1163doc 48ChPF LINE3 - L1ATL900 only.INT32ABCD× 0.0001Read
IR1165doc 48EhPF LINE3 - L2ATL900 only.INT32ABCD× 0.0001Read
IR1167doc 490hPF LINE3 - L3ATL900 only.INT32ABCD× 0.0001Read
IR1169doc 492hPFT LINE1INT32ABCD× 0.0001Read
IR1171doc 494hCurrent LINE1 - InINT32ABCD× 0.0001ARead
IR1175doc 498hPFT LINE2INT32ABCD× 0.0001Read
IR1177doc 49AhCurrent LINE2 - InINT32ABCD× 0.0001ARead
IR1181doc 49EhPFT LINE3ATL900 only.INT32ABCD× 0.0001Read
IR1183doc 4A0hCurrent LINE3 - InATL900 only.INT32ABCD× 0.0001ARead
IR1187doc 4A4hTotal active power LINE1INT32ABCD× 0.0001kWRead
IR1189doc 4A6hTotal reactive power LINE1INT32ABCD× 0.0001kvarRead
IR1191doc 4A8hTotal apparent power LINE1INT32ABCD× 0.0001kVARead
IR1193doc 4AahTotal active power LINE2INT32ABCD× 0.0001kWRead
IR1195doc 4AChTotal reactive power LINE2INT32ABCD× 0.0001kvarRead
IR1197doc 4AEhTotal apparent power LINE2INT32ABCD× 0.0001kVARead
IR1199doc 4B0hTotal active power LINE3ATL900 only.INT32ABCD× 0.0001kWRead
IR1201doc 4B2hTotal reactive power LINE3ATL900 only.INT32ABCD× 0.0001kvarRead
IR1203doc 4B4hTotal apparent power LINE3ATL900 only.INT32ABCD× 0.0001kVARead
IR8307doc 2074hLINE1 voltage statusBITMAP16Readbit 0 = Line values within limits; bit 1 = Line values within limits (after delay); bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below minimum; bit 7 = Voltage above maximum; bit 8 = Voltage asymmetry; bit 9 = Phase loss; bit 10 = Frequency below minimum; bit 11 = Frequency above maximum; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK
IR8308doc 2075hLINE1 breaker statusBITMAP16Readbit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded state (1 = close); bit 4 = Close command output; bit 5 = Open command output
IR8315doc 207ChController general statusBITMAP16Readbit 0 = OFF / reset mode; bit 1 = MAN mode; bit 2 = AUT mode; bit 3 = TEST mode; bit 4 = Error; bit 5 = AC supply present; bit 6 = DC supply present; bit 7 = Global alarm
IR8322doc 2083hLINE3 voltage statusATL900 only.BITMAP16Readbit 0 = Line values within limits; bit 1 = Line values within limits (after delay); bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below minimum; bit 7 = Voltage above maximum; bit 8 = Voltage asymmetry; bit 9 = Phase loss; bit 10 = Frequency below minimum; bit 11 = Frequency above maximum; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK
IR8323doc 2084hLINE3 breaker statusATL900 only.BITMAP16Readbit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded state (1 = close); bit 4 = Close command output; bit 5 = Open command output
IR8565doc 2176hLINE2 voltage statusAddress exactly as printed in the table.BITMAP16Readbit 0 = Line values within limits; bit 1 = Line values within limits (after delay); bit 2 = Voltage within limits; bit 3 = Voltage OK; bit 4 = Frequency within limits; bit 5 = Frequency OK; bit 6 = Voltage below minimum; bit 7 = Voltage above maximum; bit 8 = Voltage asymmetry; bit 9 = Phase loss; bit 10 = Frequency below minimum; bit 11 = Frequency above maximum; bit 12 = Wrong phase sequence; bit 13 = All line parameters OK
IR8566doc 2177hLINE2 breaker statusAddress exactly as printed in the table.BITMAP16Readbit 0 = Breaker closed; bit 1 = Trip alarm; bit 3 = Commanded state (1 = close); bit 4 = Close command output; bit 5 = Open command output
HR7167doc 1C00hBreaker open/close commandBRK3 and TB2 values are ATL900 only.UINT16Write1 = Open BRK1; 2 = Open BRK2; 4 = Open BRK3; 8 = Open TB1; 16 = Open TB2; 256 = Close BRK1; 512 = Close BRK2; 1024 = Close BRK3; 2048 = Close TB1; 4096 = Close TB2
HR7169doc 1C02hGenerator start/stop commandUINT16Write1 = Stop generator 1; 2 = Stop generator 2; 4 = Stop generator 3; 256 = Start generator 1; 512 = Start generator 2; 1024 = Start generator 3
HR12031doc 2F00hOperating mode changeWrite a value to change mode.UINT16Write0 = OFF; 1 = MAN; 2 = AUT

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers

What Modbus registers does the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers have?

This map lists 114 registers: 111 input registers, 3 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print hex addresses (for example 3Ah) and the document says to send one less. Its read example asks for 3Ah with start address 00 39, and its write example sends 2F03h as 2F02h. 'address' here is already reduced by one.

What byte order does the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers?

Start with IR 1 Voltage of LINE1 L1-N (LINE1 L1-N voltage); IR 13 Voltage of LINE2 L1-N (LINE2 L1-N voltage); IR 25 Frequency of LINE1 (LINE1 frequency); IR 8308 LINE1 breaker status (LINE1 breaker status); IR 8315 Controller general status (Mode and global alarm); IR 153 Alarm bits A01-A32 (Alarm bits); HR 12031 Operating mode change (Mode change).

How do I enable Modbus control of the Lovato Electric ATL800 / ATL900 automatic transfer switch controllers?

Configure the port in setup menu M10 (node address P10.n.01, speed P10.n.02, data format P10.n.03, stop bits P10.n.04, protocol P10.n.05; IP settings for EXP1013).

Where is the official Lovato Electric ATL800 / ATL900 automatic transfer switch controllers Modbus documentation?

The source is ATL800 - ATL900 Automatic transfer switch controller - Communication protocol Modbus (I463 GB I 11 21), published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/31.%20COMMUTATORI%20DI%20RETE%20AUTOMATICI/I463IGB11_21.pdf.

More Lovato Electric Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: ATL800 - ATL900 Automatic transfer switch controller - Communication protocol Modbus · I463 GB I 11 21. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.