Generator controller · Modbus register map
DEIF AGC 200 Advanced Genset Controller Modbus register map
Updated 19 November 2026
The AGC 200 is DEIF's compact paralleling genset controller. Its Modbus RTU server is reached over RS-485 with option H2. This map lists the genset-variant AC measurements, energy and hour counters, DC supply, status flags and the control command words for remote start, stop, breaker and mode changes.
This page lists 159 Modbus registers for the DEIF AGC 200 Advanced Genset Controller — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DEIF’s own free documentation (linked below) and checked against it.
- Manufacturer
- DEIF
- Model
- AGC 200 Advanced Genset Controller
- Equipment type
- Generator controller
- Registers
- 159 (19 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 4.68.2.x
- Also known as
- AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200
- Source document
- AGC 200 Modbus tables · 4189341214
Integration notes: DEIF AGC 200 Advanced Genset Controller
Read generator values from input registers 501-538 with function 04 and the mode status flags with function 02. Write holding register 5 or 6 with bit 0 set plus the command bit to start, stop or change mode.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 501 | Generator voltage L1-L2 | INT16 | Generator voltage L1-L2 | Read |
| IR 507 | Generator f L1 | INT16 | Generator frequency | Read |
| IR 513 | Generator current L1 | INT16 | Generator current L1 | Read |
| IR 519 | Generator power | INT16 | Generator active power | Read |
| IR 554 | Absolute running hours | INT32 ABCD | Running hours | Read |
| DI 3 | Running | BIT | Engine running flag | Read |
| HR 5 | Control command word 5 | BITMAP16 | Remote start/stop and breaker commands | Write |
Enable Modbus control & writes
Fit option H2 for RS-485 Modbus RTU; its settings are parameters 7500-7520 (parameter list 4189340605).
Byte order & addressing
- A command word is ignored unless bit 0 is 1 in the same write.
- Function 04 addresses below 500 are a user-configurable copy area.
Network setup
- Option H2 RS-485: 9600 or 19200 bit/s, 8 data bits, no parity, 1 stop bit.
Watch out for
- AC voltages, currents and powers are whole units (scale 1); frequency and power factor use 0.01, and DC supply voltage uses 0.1.
DEIF AGC 200 Advanced Genset Controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 1 | MB position ON | BIT | Read | |||||
| DI | 3 | Running | BIT | Read | |||||
| DI | 4 | Generator voltage/frequency OK | BIT | Read | |||||
| DI | 5 | Mains failure | BIT | Read | |||||
| DI | 6 | Block mode | BIT | Read | |||||
| DI | 7 | Manual mode | BIT | Read | |||||
| DI | 8 | Semi-auto mode | BIT | Read | |||||
| DI | 9 | Auto mode | BIT | Read | |||||
| DI | 10 | Test mode | BIT | Read | |||||
| DI | 13 | Island | BIT | Read | |||||
| DI | 14 | Automatic mains failure (AMF) | BIT | Read | |||||
| DI | 15 | Peak shaving | BIT | Read | |||||
| DI | 16 | Fixed power | BIT | Read | |||||
| DI | 17 | Mains power export (MPE) | BIT | Read | |||||
| DI | 18 | Load takeover (LTO) | BIT | Read | |||||
| DI | 19 | Power management | BIT | Read | |||||
| DI | 20 | Any alarm on PMS ID1 | BIT | Read | |||||
| DI | 21 | Any alarm on PMS ID2 | BIT | Read | |||||
| DI | 22 | Any alarm on PMS ID3 | BIT | Read | |||||
| DI | 23 | Any alarm on PMS ID4 | BIT | Read | |||||
| DI | 24 | Any alarm on PMS ID5 | BIT | Read | |||||
| DI | 25 | Any alarm on PMS ID6 | BIT | Read | |||||
| DI | 26 | Any alarm on PMS ID7 | BIT | Read | |||||
| DI | 27 | Any alarm on PMS ID8 | BIT | Read | |||||
| DI | 28 | Any alarm mains (Mains Command Unit) | BIT | Read | |||||
| DI | 29 | Battery test | BIT | Read | |||||
| DI | 31 | Ready auto-start DG1 | BIT | Read | |||||
| DI | 32 | Ready auto-start DG2 | BIT | Read | |||||
| DI | 33 | Ready auto-start DG3 | BIT | Read | |||||
| DI | 34 | Ready auto-start DG4 | BIT | Read | |||||
| DI | 35 | Ready auto-start DG5 | BIT | Read | |||||
| DI | 36 | Ready auto-start DG6 | BIT | Read | |||||
| DI | 37 | Ready auto-start DG7 | BIT | Read | |||||
| DI | 38 | Ready auto-start DG8 | BIT | Read | |||||
| DI | 53 | Mains sync. inhibit | BIT | Read | |||||
| DI | 54 | Any mains sync. inhibit | BIT | Read | |||||
| DI | 518 | GB position ON | BIT | Read | |||||
| IR | 500 | Application version | INT16 | Read | |||||
| IR | 501 | Generator voltage L1-L2 | INT16 | V | Read | ||||
| IR | 502 | Generator voltage L2-L3 | INT16 | V | Read | ||||
| IR | 503 | Generator voltage L3-L1 | INT16 | V | Read | ||||
| IR | 504 | Generator voltage L1-N | INT16 | V | Read | ||||
| IR | 505 | Generator voltage L2-N | INT16 | V | Read | ||||
| IR | 506 | Generator voltage L3-N | INT16 | V | Read | ||||
| IR | 507 | Generator f L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 508 | Generator f L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 509 | Generator f L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 510 | Generator voltage phase angle L1-L2 | INT16 | × 0.1 | ° | Read | |||
| IR | 511 | Generator voltage phase angle L2-L3 | INT16 | × 0.1 | ° | Read | |||
| IR | 512 | Generator voltage phase angle L3-L1 | INT16 | × 0.1 | ° | Read | |||
| IR | 513 | Generator current L1 | INT16 | A | Read | ||||
| IR | 514 | Generator current L2 | INT16 | A | Read | ||||
| IR | 515 | Generator current L3 | INT16 | A | Read | ||||
| IR | 516 | Generator power L1 | INT16 | kW | Read | ||||
| IR | 517 | Generator power L2 | INT16 | kW | Read | ||||
| IR | 518 | Generator power L3 | INT16 | kW | Read | ||||
| IR | 519 | Generator power | INT16 | kW | Read | ||||
| IR | 520 | Generator reactive power L1 | INT16 | kvar | Read | ||||
| IR | 521 | Generator reactive power L2 | INT16 | kvar | Read | ||||
| IR | 522 | Generator reactive power L3 | INT16 | kvar | Read | ||||
| IR | 523 | Generator reactive power | INT16 | kvar | Read | ||||
| IR | 524 | Generator apparent power L1 | INT16 | kVA | Read | ||||
| IR | 525 | Generator apparent power L2 | INT16 | kVA | Read | ||||
| IR | 526 | Generator apparent power L3 | INT16 | kVA | Read | ||||
| IR | 527 | Generator apparent power | INT16 | kVA | Read | ||||
| IR | 528 | Generator Export, reactive energy counter | INT32 | ABCD | kvarh | Read | |||
| IR | 530 | Generator Export, active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 532 | Generator Export, active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 534 | Generator Export, active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 536 | Generator Export, active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 538 | Generator PF | INT16 | × 0.01 | Read | ||||
| IR | 539 | Bus B voltage L1-L2 | INT16 | V | Read | ||||
| IR | 540 | Bus B voltage L2-L3 | INT16 | V | Read | ||||
| IR | 541 | Bus B voltage L3-L1 | INT16 | V | Read | ||||
| IR | 542 | Bus B voltage L1-N | INT16 | V | Read | ||||
| IR | 543 | Bus B voltage L2-N | INT16 | V | Read | ||||
| IR | 544 | Bus B voltage L3-N | INT16 | V | Read | ||||
| IR | 545 | Bus B f L1 | INT16 | × 0.01 | Hz | Read | |||
| IR | 546 | Bus B f L2 | INT16 | × 0.01 | Hz | Read | |||
| IR | 547 | Bus B f L3 | INT16 | × 0.01 | Hz | Read | |||
| IR | 548 | Bus B voltage phase angle L1-L2 | INT16 | × 0.1 | ° | Read | |||
| IR | 549 | Bus B voltage phase angle L2-L3 | INT16 | × 0.1 | ° | Read | |||
| IR | 550 | Bus B voltage phase angle L3-L1 | INT16 | × 0.1 | ° | Read | |||
| IR | 551 | U BB L1 - U GEN L1 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 552 | U BB L2 - U GEN L2 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 553 | U BB L3 - U GEN L3 phase angle | INT16 | × 0.1 | ° | Read | |||
| IR | 554 | Absolute running hours | INT32 | ABCD | Read | ||||
| IR | 556 | Relative running hours | INT32 | ABCD | Read | ||||
| IR | 558 | No. of alarms | INT16 | Read | |||||
| IR | 559 | No. of unacknowledged alarms | INT16 | Read | |||||
| IR | 560 | No. of active acknowledged alarms | INT16 | Read | |||||
| IR | 561 | Running minute counter, shutdown override | INT16 | Read | |||||
| IR | 562 | Running hour counter, shutdown override | INT16 | Read | |||||
| IR | 563 | No. of GB operations | INT16 | Read | |||||
| IR | 564 | No. of MB operations | INT16 | Read | |||||
| IR | 566 | Start attempts | INT16 | Read | |||||
| IR | 567 | DC supply term. 1-2 | INT16 | × 0.1 | V | Read | |||
| IR | 569 | Service timer 1 running hours | INT16 | Read | |||||
| IR | 570 | Service timer 1 running days | INT16 | Read | |||||
| IR | 571 | Service timer 2 running hours | INT16 | Read | |||||
| IR | 572 | Service timer 2 running days | INT16 | Read | |||||
| IR | 573 | Cos-phi | INT16 | × 0.01 | Read | ||||
| IR | 574 | cos phi inductive/capacitive | INT16 | Read | 0 = Inductive; 1 = Capacitive | ||||
| IR | 576 | RPM | INT16 | Read | |||||
| IR | 577 | Running hours load profile | INT32 | ABCD | Read | ||||
| IR | 642 | Control register address 0 | INT16 | Read | |||||
| IR | 643 | Control register address 1 | INT16 | Read | |||||
| IR | 644 | Control register address 2 | INT16 | Read | |||||
| IR | 645 | Control register address 3 | INT16 | Read | |||||
| IR | 646 | Control register address 4 | INT16 | Read | |||||
| IR | 647 | Control register address 5 | INT16 | Read | |||||
| IR | 648 | Control register address 6 | INT16 | Read | |||||
| IR | 649 | Control register address 7 | INT16 | Read | |||||
| IR | 650 | Control register address 8 | INT16 | Read | |||||
| IR | 651 | Control register address 9 | INT16 | Read | |||||
| IR | 652 | Control register address 10 | INT16 | Read | |||||
| IR | 653 | Control register address 11 | INT16 | Read | |||||
| IR | 654 | Control register address 12 | INT16 | Read | |||||
| IR | 655 | Control register address 13 | INT16 | Read | |||||
| IR | 700 | Actual nominal power (Includes derate etc.) | INT16 | Read | |||||
| IR | 701 | Mains power transducer used | INT16 | Read | |||||
| IR | 790 | Generator Export reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 792 | Generator Export reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 794 | Generator Export reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 796 | Generator Import active energy counter, total | INT32 | ABCD | kWh | Read | |||
| IR | 798 | Generator Import active energy counter, month | INT32 | ABCD | kWh | Read | |||
| IR | 800 | Generator Import active energy counter, week | INT32 | ABCD | kWh | Read | |||
| IR | 802 | Generator Import active energy counter, day | INT32 | ABCD | kWh | Read | |||
| IR | 804 | Generator Import reactive energy counter, total | INT32 | ABCD | kvarh | Read | |||
| IR | 806 | Generator Import reactive energy counter, month | INT32 | ABCD | kvarh | Read | |||
| IR | 808 | Generator Import reactive energy counter, week | INT32 | ABCD | kvarh | Read | |||
| IR | 810 | Generator Import reactive energy counter, day | INT32 | ABCD | kvarh | Read | |||
| IR | 816 | Demand of peak current 1 | INT16 | Read | |||||
| IR | 817 | Demand of peak current 2 | INT16 | Read | |||||
| IR | 818 | Demand of peak current 3 | INT16 | Read | |||||
| IR | 819 | Demand of avg. peak current 1 | INT16 | Read | |||||
| IR | 820 | Demand of avg. peak current 2 | INT16 | Read | |||||
| IR | 821 | Demand of avg. peak current 3 | INT16 | Read | |||||
| IR | 822 | Start attempts standard | INT16 | Read | |||||
| IR | 823 | Start attempts double starter | INT16 | Read | |||||
| HR | 0 | Power regulator setpoint | 0 to 100 % of nominal power; activated in menu 7501. | INT16 | Read/write | ||||
| HR | 1 | cosPhi regulator setpoint | 60-100 means cos phi x 100 (100 = 1.00). Menu 7504. | INT16 | Read/write | ||||
| HR | 2 | Reactive power regulator setpoint | -100 to +100 % of nominal; negative = capacitive. Menu 7505. | INT16 | Read/write | ||||
| HR | 3 | Frequency regulator setpoint | -100 to +100 % = -10.0 to +10.0 % of nominal frequency. Menu 7502. | INT16 | Read/write | ||||
| HR | 4 | Voltage regulator setpoint | -100 to +100 % = -10.0 to +10.0 % of nominal voltage. Menu 7503. | INT16 | Read/write | ||||
| HR | 5 | Control command word 5 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Remote start; bit 2 = Remote GB ON; bit 3 = Remote GB OFF; bit 4 = Remote stop; bit 5 = Reset GOV/AVR regulation output to offset; bit 6 = Start+sync. (semi); bit 7 = Alarm inhibit 1; bit 8 = Alarm inhibit 2; bit 9 = Alarm inhibit 3; bit 10 = Alarm ack.; bit 11 = Nominal setting 1; bit 12 = Nominal setting 2; bit 13 = Nominal setting 3; bit 14 = Nominal setting 4; bit 15 = Deload/stop (semi) | |||
| HR | 6 | Control command word 6 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Island; bit 2 = Automatic mains failure (AMF); bit 3 = Peak shaving; bit 4 = Fixed power; bit 5 = Mains power export (MPE); bit 6 = Load takeover (LTO); bit 9 = MB ON (Single DG); bit 10 = MB OFF (Single DG); bit 11 = Auto start/stop; bit 12 = Manual mode; bit 13 = Auto mode; bit 14 = Semi-Auto mode; bit 15 = Test mode | |||
| HR | 7 | Control command word 7 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = External frequency control; bit 2 = External voltage control; bit 3 = External power control; bit 4 = External reactive power control; bit 5 = External power factor control; bit 6 = Capacitive PF; bit 7 = Base load; bit 8 = 1. priority; bit 9 = Application 1; bit 10 = Application 2; bit 11 = Application 3; bit 12 = Application 4; bit 13 = Battery test; bit 15 = Synchronise clock to 4:00 a.m. | |||
| HR | 8 | Control command word 8 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 1; bit 2 = Virtual event 2; bit 3 = Virtual event 3; bit 4 = Virtual event 4; bit 5 = Virtual event 5; bit 6 = Virtual event 6; bit 7 = Virtual event 7; bit 8 = Virtual event 8; bit 9 = Virtual event 9; bit 10 = Virtual event 10; bit 11 = Virtual event 11; bit 12 = Virtual event 12; bit 13 = Virtual event 13; bit 14 = Virtual event 14; bit 15 = Virtual event 15 | |||
| HR | 9 | Control command word 9 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 16; bit 2 = Virtual event 17; bit 3 = Virtual event 18; bit 4 = Virtual event 19; bit 5 = Virtual event 20; bit 6 = Virtual event 21; bit 7 = Virtual event 22; bit 8 = Virtual event 23; bit 9 = Virtual event 24; bit 10 = Virtual event 25; bit 11 = Virtual event 26; bit 12 = Virtual event 27; bit 13 = Virtual event 28; bit 14 = Virtual event 29; bit 15 = Virtual event 30 | |||
| HR | 10 | Control command word 10 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Virtual event 31; bit 2 = Virtual event 32; bit 4 = Clear log; bit 5 = Clear Parameter edits | |||
| HR | 13 | Control command word 13 | Write-only command bits; reads back 0. | BITMAP16 | Write | bit 0 = Bit 0 = write-enable (must be 1 or the word is ignored); bit 1 = Enable external frequency control; bit 2 = Disable external frequency control; bit 3 = Enable external voltage control; bit 4 = Disable external voltage control; bit 5 = Enable external power control; bit 6 = Disable external power control; bit 7 = Enable external VAr control; bit 8 = Disable external VAr control; bit 9 = Enable external CosPhi control; bit 10 = Disable external CosPhi control; bit 11 = Enable PM base load; bit 12 = Disable PM base load; bit 13 = Reset horn | |||
| HR | 58000 | Year (2003-2099) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58001 | Month (1-12) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58002 | Date (1-31) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58003 | Day (1-7, Monday - Sunday) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58004 | Hour (0-23) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58005 | Min (0-59) | Controller clock; write to set. | INT16 | Read/write | ||||
| HR | 58006 | Sec (0-59) | Controller clock; write to set. | INT16 | Read/write |
Notes on this map
- The source is an Excel workbook. Each row has a scaling exponent x; the value is raw x 10^-x, so x=2 means scale 0.01. Units are as printed.
- 32-bit values: the tables mark every 32-bit register with data format ABCD (high word at the lower address); DEIF's AGC 150 Modbus server manual (4189341435, section 3.4) uses the same notation with that meaning.
- Only rows marked for the DG (genset) application are listed.
- Left out: the configurable area, multi-input values, the engine-interface block marked 'See DRH manual' (593 upward), alarm bits, power-management data and the command-flag coils.
- Parameters are reached through address areas plus the parameter's USW address; see Option H2 Modbus communication AGC 200 (4189341208).
- The option H2 document covers Modbus RTU on RS-485 only; it does not describe Modbus TCP for the AGC 200, so TCP is not listed here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DEIF AGC 200 Advanced Genset Controller
What Modbus registers does the DEIF AGC 200 Advanced Genset Controller have?
This map lists 159 registers: 37 discrete inputs, 103 input registers, 19 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DEIF AGC 200 Advanced Genset Controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The 'Modbus address' column is what goes in the request. A 6-digit PLC address one higher is also printed (input 501 = PLC 300502).
What byte order does the DEIF AGC 200 Advanced Genset Controller use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the DEIF AGC 200 Advanced Genset Controller?
Start with IR 501 Generator voltage L1-L2 (Generator voltage L1-L2); IR 507 Generator f L1 (Generator frequency); IR 513 Generator current L1 (Generator current L1); IR 519 Generator power (Generator active power); IR 554 Absolute running hours (Running hours); DI 3 Running (Engine running flag); HR 5 Control command word 5 (Remote start/stop and breaker commands).
How do I enable Modbus control of the DEIF AGC 200 Advanced Genset Controller?
Fit option H2 for RS-485 Modbus RTU; its settings are parameters 7500-7520 (parameter list 4189340605).
Where is the official DEIF AGC 200 Advanced Genset Controller Modbus documentation?
The source is AGC 200 Modbus tables (4189341214), published free by DEIF at https://deif-cdn-umbraco.azureedge.net/media/d5bbyqkm/agc_200_modbus_tables_4189341214_uk.xlsx.
More DEIF Modbus register maps
- Generator controller
DEIF AGC 150 Generator controller
AGC 150 software 1.39.0 (Modbus server tables revision Z), GEN (genset) controller type. The iE 150 Land tables 4189341430 rev. H for the same software match these tables apart from the product name.
Also known as: AGC 150 GEN, AGC 150 Generator, iE 150 Land, iE 150 GEN - Generator controller
DEIF AGC 150 Generator Marine controller
AGC 150 Marine software 1.39.0 (marine Modbus server tables revision E), GEN-M (marine genset) controller type. The iE 150 Marine tables 4189341431 rev. H match these tables.
Also known as: AGC 150 GEN-M, AGC 150 Generator Marine, iE 150 Marine - Generator controller
DEIF AGC-4 Automatic Genset Controller
AGC-4 software 4.83.0 (Modbus tables revision I), genset (DG) application; mains and BTB variants share many addresses but are not covered.
Also known as: AGC-4 DG, AGC 4, Multi-line 2 AGC-4 - Generator controller
DEIF AGC-4 Mk II Automatic Genset Controller
AGC-4 Mk II software 6.31.0 (Modbus tables revision N), genset (GEN) application only.
Also known as: AGC-4 Mk2, AGC-4 MkII - Generator controller
DEIF SGC 120 / SGC 121 Single Genset Controller
SGC 120 and SGC 121 (first generation, not Mk II); the SGC 120 user manual 4189341340B covers application software 9.04.
Also known as: SGC 120, SGC 121, SGC120, SGC121 - Generator controller
DEIF SGC 120 Mk II Single Genset Controller
SGC 120 Mk II software R18.0 (Modbus tables revision C).
Also known as: SGC 120 MkII, SGC 120 Mk2 - Generator controller
DEIF SGC 420 Mk II Single Genset Controller
SGC 420 Mk II software R19.0 (Modbus tables revision C).
Also known as: SGC 420 MkII, SGC 420 Mk2
Other generator controllers register maps
- Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller - Generator controller
Lovato Electric RGK610 genset controller
RGK610, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 610 - Generator controller
Lovato Electric RGK900MC mains/master controller
RGK900MC, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900MC, RGK900 MC - Generator controller
Woodward easYgen-1000 Series genset controller (Modbus RTU)
easYgen-1000 series software version 2.1xxx, transmission telegram protocol 4003, per interface manual 37393B.
Also known as: easYgen-1000, easYgen1000, easYgen-1000 Series - Generator controller
ComAp InteliGen4 200
InteliGen4 200 with firmware 2.2.0: the fixed (reserved) registers only; measurement registers depend on the configuration.
Also known as: InteliGen 4 200, IG4 200 - Generator controller
Kohler Decision-Maker 3500 generator set controller
Kohler Decision-Maker 3500 generator set controllers (Modbus map version 2; some registers need firmware 1.4 or later), Modbus RTU on RS-485.
Also known as: Decision-Maker 3500, DEC3500, DEC 3500
All generator controllers Modbus register maps →
Source: AGC 200 Modbus tables · 4189341214. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.