Generator controller · Modbus register map
Kohler Decision-Maker 6000 generator set controller Modbus register map
Updated 17 November 2026
The Decision-Maker 6000 is a Kohler generator set controller whose Modbus map follows the same layout as the Decision-Maker 550. It answers Modbus RTU directly with a holding-register map of generator electrical output, engine status from the ECM or local senders, run-time and maintenance counters, system setpoints, remote timed-run commands and a 16-word system event stack. This map covers the electrical and engine blocks, master switch and mode status, run-time counters, key system settings and the remote functions.
This page lists 63 Modbus registers for the Kohler Decision-Maker 6000 generator set controller — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.
- Manufacturer
- Kohler
- Model
- Decision-Maker 6000 generator set controller
- Equipment type
- Generator controller
- Registers
- 63 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Decision-Maker 6000, DEC 6000, Kohler 6000 controller
Integration notes: Kohler Decision-Maker 6000 generator set controller
Read 400001-400028 for generator output and 400033-400047 for engine data in one or two FC 03 requests, check 400079/400080 for switch position and programming mode, and use 401306/401307 for remote timed starts once the controller is in remote programming mode.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | L1-L2 Voltage | UINT16 | L1-L2 voltage | Read |
| HR 6 | L1 Current | UINT16 | L1 current | Read |
| HR 9 | Frequency | UINT16 | Frequency | Read |
| HR 10 | Total kW | UINT16 | Total kW | Read |
| HR 34 | Engine Speed | UINT16 | Engine speed | Read |
| HR 35 | Local Battery Voltage | UINT16 | Battery voltage | Read |
| HR 78 | Master Switch Position | UINT16 | Master switch position | Read |
| HR 1499 | System Events word 1 (events 0-15) | BITMAP16 | System event stack word 1 | Read |
Enable Modbus control & writes
On the controller set the network address (unique per unit) and the baud rate (9600 or 19200) in the communications menu. Writes require the controller's programming mode to be Remote; otherwise writes are rejected with exception 01.
Byte order & addressing
- The exception table caps reads at 50 registers (section 1.3 says 100) and writes at 16; do not read past the end of a block or start a read at an undefined register.
- 32-bit LONG counters are low word first.
- Byte-packed fields (day|month, hr|min, min|sec) put the first item in the high byte.
Network setup
- Serial format is 8 data bits, no parity, 1 stop bit.
- Register 409999 returns device ID 41 for the 6000.
Watch out for
- Writes to system parameters are rejected unless the generator set is in OFF or AUTO.
- A timed-run start is refused while a timed run is already active.
Kohler Decision-Maker 6000 generator set controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 400001 | L1-L2 Voltage | UINT16 | V | Read | ||||
| HR | 1doc 400002 | L2-L3 Voltage | UINT16 | V | Read | ||||
| HR | 2doc 400003 | L3-L1 Voltage | UINT16 | V | Read | ||||
| HR | 3doc 400004 | L1-L0 Voltage | UINT16 | V | Read | ||||
| HR | 4doc 400005 | L2-L0 Voltage | UINT16 | V | Read | ||||
| HR | 5doc 400006 | L3-L0 Voltage | UINT16 | V | Read | ||||
| HR | 6doc 400007 | L1 Current | UINT16 | A | Read | ||||
| HR | 7doc 400008 | L2 Current | UINT16 | A | Read | ||||
| HR | 8doc 400009 | L3 Current | UINT16 | A | Read | ||||
| HR | 9doc 400010 | Frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 10doc 400011 | Total kW | UINT16 | kW | Read | ||||
| HR | 11doc 400012 | Percent of Rated kW | UINT16 | % | Read | ||||
| HR | 12doc 400013 | Total Power Factor | Signed, x100. | INT16 | × 0.01 | Read | |||
| HR | 13doc 400014 | L1 kW | UINT16 | kW | Read | ||||
| HR | 14doc 400015 | L1 Power Factor | Signed, x100. | INT16 | × 0.01 | Read | |||
| HR | 15doc 400016 | L2 kW | UINT16 | kW | Read | ||||
| HR | 16doc 400017 | L2 Power Factor | Signed, x100. | INT16 | × 0.01 | Read | |||
| HR | 17doc 400018 | L3 kW | UINT16 | kW | Read | ||||
| HR | 18doc 400019 | L3 Power Factor | Signed, x100. | INT16 | × 0.01 | Read | |||
| HR | 19doc 400020 | Total kVAR | Signed. | INT16 | kvar | Read | |||
| HR | 20doc 400021 | L1 kVAR | Signed. | INT16 | kvar | Read | |||
| HR | 21doc 400022 | L2 kVAR | Signed. | INT16 | kvar | Read | |||
| HR | 22doc 400023 | L3 kVAR | Signed. | INT16 | kvar | Read | |||
| HR | 23doc 400024 | Total kVA | UINT16 | kVA | Read | ||||
| HR | 24doc 400025 | L1 kVA | UINT16 | kVA | Read | ||||
| HR | 25doc 400026 | L2 kVA | UINT16 | kVA | Read | ||||
| HR | 26doc 400027 | L3 kVA | UINT16 | kVA | Read | ||||
| HR | 27doc 400028 | Current Lead/Lag | Two bits per item: 10 = leading, 01 = lagging. | BITMAP16 | Read | bit 0 = Total current lagging (bits 0-1 = 01); bit 1 = Total current leading (bits 0-1 = 10); bit 2 = L1 lagging (bits 2-3 = 01); bit 3 = L1 leading (bits 2-3 = 10); bit 4 = L2 lagging (bits 4-5 = 01); bit 5 = L2 leading (bits 4-5 = 10); bit 6 = L3 lagging (bits 6-7 = 01); bit 7 = L3 leading (bits 6-7 = 10) | |||
| HR | 32doc 400033 | Oil Pressure | kPa or psi per 400139. ECM: 0x7FD6 = unavailable, 0x7FFF = out of range. | UINT16 | kPa | Read | |||
| HR | 33doc 400034 | Coolant Temperature | °C or °F per 400139. ECM: 0x7FD6 = unavailable, 0x7FFF = out of range. | INT16 | °C | Read | |||
| HR | 34doc 400035 | Engine Speed | ECM data: 0x7FD6 = unavailable, 0x7FFF = out of range. | UINT16 | rpm | Read | |||
| HR | 35doc 400036 | Local Battery Voltage | x10. ECM data: 0x7FD6 = unavailable, 0x7FFF = out of range. | UINT16 | × 0.1 | V | Read | ||
| HR | 36doc 400037 | Fuel Pressure | DDEC/MDEC/ADEC engines only. kPa or psi. | UINT16 | kPa | Read | |||
| HR | 37doc 400038 | Fuel Temperature | DDEC/MDEC/ADEC engines only. | INT16 | °C | Read | |||
| HR | 42doc 400043 | Lube Oil Temperature | DDEC/MDEC/ADEC only. | INT16 | °C | Read | |||
| HR | 46doc 400047 | ECM Battery Voltage | x10. DDEC/MDEC/ADEC only. | UINT16 | × 0.1 | V | Read | ||
| HR | 47doc 400048 | ECM Status | UINT16 | Read | 0 = DDEC-equipped; 1 = Non-ECM; 2 = MDEC/ADEC-equipped | ||||
| HR | 50doc 400051 | MDEC/ADEC Fault Code | Numeric fault code, MDEC/ADEC only. | UINT16 | Read | ||||
| HR | 60doc 400061 | Analog Input 00 (Battery Voltage) | UINT16 | V | Read | ||||
| HR | 76doc 400077 | Digital Input Status word 1 | Inputs 0-15. | BITMAP16 | Read | bit 0 = Remote start contacts; bit 1 = Emergency stop; bit 2 = Low coolant level; bit 3 = Digital input 1; bit 4 = Digital input 2; bit 5 = Digital input 3; bit 6 = Digital input 4; bit 7 = Digital input 5; bit 8 = Digital input 6; bit 9 = Digital input 7; bit 10 = Digital input 8; bit 11 = Digital input 9; bit 12 = Digital input 10; bit 13 = Digital input 11; bit 14 = Digital input 12; bit 15 = Digital input 13 | |||
| HR | 77doc 400078 | Digital Input Status word 2 / option flags | BITMAP16 | Read | bit 0 = Digital input 14; bit 1 = Digital input 15; bit 2 = Digital input 16; bit 3 = Digital input 17; bit 4 = Digital input 18; bit 5 = Digital input 19; bit 6 = Digital input 20; bit 7 = Digital input 21; bit 8 = DDEC flag; bit 9 = MDEC/ADEC flag; bit 10 = Tier 1 flag; bit 11 = Waukesha flag | ||||
| HR | 78doc 400079 | Master Switch Position | UINT16 | Read | 0 = Error; 1 = Auto; 2 = Off; 3 = Run | ||||
| HR | 79doc 400080 | Programming Mode Status | UINT16 | Read | 1 = Off; 2 = Local; 3 = Remote | ||||
| HR | 83doc 400084 | Total Number of Starts | UINT16 | Read | |||||
| HR | 84doc 400085 | Total Run Time | x100, low word first. | UINT32 | CDAB | × 0.01 | h | Read | |
| HR | 86doc 400087 | Total Run Time Loaded | x100, low word first. | UINT32 | CDAB | × 0.01 | h | Read | |
| HR | 88doc 400089 | Total Run Time Unloaded | x100, low word first. | UINT32 | CDAB | × 0.01 | h | Read | |
| HR | 90doc 400091 | Total Run Time kW Hrs | Low word first. | UINT32 | CDAB | kWh | Read | ||
| HR | 92doc 400093 | RTSM Total Hrs | Run time since maintenance, x100, low word first. | UINT32 | CDAB | × 0.01 | h | Read | |
| HR | 98doc 400099 | RTSM kW Hrs | Since maintenance, low word first. | UINT32 | CDAB | kWh | Read | ||
| HR | 107doc 400108 | Last Run Length | x100. | UINT16 | × 0.01 | h | Read | ||
| HR | 111doc 400112 | Is Timed Run Active | UINT16 | Read | 0 = False; 1 = True | ||||
| HR | 125doc 400126 | System Voltage | Setpoint. | UINT16 | V | Read/write | |||
| HR | 126doc 400127 | System Frequency | Setpoint. | UINT16 | Hz | Read/write | |||
| HR | 127doc 400128 | System Phase | UINT16 | Read/write | 1 = 3 phase delta; 2 = 3 phase wye; 3 = Single phase | ||||
| HR | 128doc 400129 | kW Rating | UINT16 | kW | Read/write | ||||
| HR | 138doc 400139 | Metric Units | Sets metric or English units for engine values. | UINT16 | Read/write | 0 = False; 1 = True | |||
| HR | 140doc 400141 | Rated Current | UINT16 | A | Read | ||||
| HR | 1305doc 401306 | Start Timed Run | Write 1 to start a timed run. | UINT16 | Write | 0 = No start; 1 = Start | |||
| HR | 1306doc 401307 | Stop Timed Run | Write 1 to stop a timed run. | UINT16 | Write | 0 = No stop; 1 = Stop | |||
| HR | 1308doc 401309 | Remote Fault Reset | UINT16 | Write | 0 = No reset; 1 = Reset | ||||
| HR | 1499doc 401500 | System Events word 1 (events 0-15) | Read the whole 16-word stack 401500-401515 in one request. | BITMAP16 | Read | ||||
| HR | 9998doc 409999 | Device ID | 41 = Decision-Maker 6000. | UINT16 | Read |
Notes on this map
- Data types follow the manual's definitions: WORD = 16-bit unsigned, SWORD = 16-bit signed, LONG = 32-bit unsigned with the least significant word first, so LONG registers are listed CDAB.
- Oil, fuel and coolant pressures and temperatures follow 400139 Metric Units: kPa and °C when metric, psi and °F otherwise. The units shown assume metric.
- Left out: user-calibrated analog inputs 1-7, DDEC-only values, the 2-word date fields (byte-packed day|month), maintenance date/time fields, time-delay and protective setpoints, analog/digital input setup, relay driver definitions, event history, strings and the defined common faults.
- Only system event word 1 is listed; the stack runs 401500-401515 (events 0-255) and must be read as one 16-register block.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Kohler Decision-Maker 6000 generator set controller
What Modbus registers does the Kohler Decision-Maker 6000 generator set controller have?
This map lists 63 registers: 63 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Kohler Decision-Maker 6000 generator set controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints 6-digit holding-register references (400001 = first holding register, 409999 = register 49999 in 5-digit form), so 400001 is wire address 0 and 401306 is wire address 1305.
What byte order does the Kohler Decision-Maker 6000 generator set controller use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Kohler Decision-Maker 6000 generator set controller?
Start with HR 0 L1-L2 Voltage (L1-L2 voltage); HR 6 L1 Current (L1 current); HR 9 Frequency (Frequency); HR 10 Total kW (Total kW); HR 34 Engine Speed (Engine speed); HR 35 Local Battery Voltage (Battery voltage); HR 78 Master Switch Position (Master switch position); HR 1499 System Events word 1 (events 0-15) (System event stack word 1).
How do I enable Modbus control of the Kohler Decision-Maker 6000 generator set controller?
On the controller set the network address (unique per unit) and the baud rate (9600 or 19200) in the communications menu. Writes require the controller's programming mode to be Remote; otherwise writes are rejected with exception 01.
Where is the official Kohler Decision-Maker 6000 generator set controller Modbus documentation?
The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.
More Kohler Modbus register maps
- Generator controller
Kohler Decision-Maker 3500 generator set controller
Kohler Decision-Maker 3500 generator set controllers (Modbus map version 2; some registers need firmware 1.4 or later), Modbus RTU on RS-485.
Also known as: Decision-Maker 3500, DEC3500, DEC 3500 - Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller - Transfer switch
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
Kohler Decision-Maker MPAC 750, 1200 and 1500 ATS controllers, Modbus RTU on the logic board RS-485 port or Modbus TCP, per section 14 of TP-6113.
Also known as: Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC - Transfer switch
Kohler MPAC 1000 automatic transfer switch controller
Kohler MPAC 1000 ATS controllers, Modbus RTU on RS-485, per section 12 of TP-6113.
Also known as: MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
Other generator controllers register maps
- Generator controller
Lovato Electric RGK700 AMF genset controller
RGK700, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700, RGK700 AMF - Generator controller
Lovato Electric RGK900SA genset paralleling controller (stand-alone)
RGK900SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900SA, RGK900 SA - Generator controller
Woodward easYgen-2000 Series genset controller (easYgen-2200 / 2300 / 2500)
easYgen-2200/2300/2500, data protocol 5100 (basic visualization), per manual 37535D.
Also known as: easYgen-2200, easYgen-2300, easYgen-2500, easYgen-2000 Series - Generator controller (paralleling master control)
Cummins MCM3320 master control module (Modbus RTU)
Cummins MCM3320 master control modules on their RS-485 Modbus RTU port, per section 10 of A029X159 Issue 7.
Also known as: MCM3320, MCM 3320, PowerCommand MCM3320 - Generator controller
DEIF AGC 200 Advanced Genset Controller
AGC 200 series software 4.68.2.x, genset (DG) application only.
Also known as: AGC 222, AGC 242, AGC 243, AGC 244, AGC 245, AGC 246, AGC-200 - Generator controller
Lovato Electric RGK610 genset controller
RGK610, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 610
All generator controllers Modbus register maps →
Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.