- Home
- Modbus register maps
- Kohler
Manufacturer
Kohler Modbus register maps
Updated 17 November 2026
6 Kohler models, 332 registers in all, each re-typed from Kohler’s own free documentation and checked against it.
- Generator controller
Kohler Decision-Maker 3500 generator set controller
Kohler Decision-Maker 3500 generator set controllers (Modbus map version 2; some registers need firmware 1.4 or later), Modbus RTU on RS-485.
Also known as: Decision-Maker 3500, DEC3500, DEC 3500 - Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller - Generator controller
Kohler Decision-Maker 6000 generator set controller
Kohler Decision-Maker 6000 generator set controllers, Modbus RTU on the controller's RS-485/RS-232 port, per section 8 of TP-6113.
Also known as: Decision-Maker 6000, DEC 6000, Kohler 6000 controller - Transfer switch
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
Kohler Decision-Maker MPAC 750, 1200 and 1500 ATS controllers, Modbus RTU on the logic board RS-485 port or Modbus TCP, per section 14 of TP-6113.
Also known as: Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC - Transfer switch
Kohler MPAC 1000 automatic transfer switch controller
Kohler MPAC 1000 ATS controllers, Modbus RTU on RS-485, per section 12 of TP-6113.
Also known as: MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
Kohler: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| Decision-Maker 3500 generator set controller | RTU | Not stated | 8N1 | CDAB | Modicon | 67 |
| Decision-Maker 550 generator set controller (application code 2.10+) | RTU | Not stated | 8N1 | CDAB | Modicon | 63 |
| Decision-Maker 6000 generator set controller | RTU | Not stated | 8N1 | CDAB | Modicon | 63 |
| Decision-Maker MPAC 750/1200/1500 ATS controller | RTU/TCP | Not stated | 19200 baud, 8N1 | ABCD | Modicon | 48 |
| MPAC 1000 automatic transfer switch controller | RTU | Not stated | 8N1 | ABCD | Modicon | 43 |
| MPAC 1500 automatic transfer switch controller | RTU/TCP | 1 | 8N1 | ABCD | Modicon | 48 |