Transfer switch · Modbus register map

Kohler MPAC 1000 automatic transfer switch controller Modbus register map

Updated 17 November 2026

Short answer

The MPAC 1000 is a Kohler automatic transfer switch controller. Its Modbus RTU map reports source A and source B voltages and frequencies, contactor position and source availability, phase sequence, active time delay, I/O and accessory status, transfer statistics and write-only test and manual-action commands. This map covers the monitoring block, nominal ratings, status words, maintenance counters and the command register.

This page lists 43 Modbus registers for the Kohler MPAC 1000 automatic transfer switch controller — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.

Manufacturer
Kohler
Model
MPAC 1000 automatic transfer switch controller
Equipment type
Transfer switch
Registers
43 (10 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS
Source document
Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Kohler MPAC 1000 automatic transfer switch controller

Integration in brief

Poll 40001-40015 in one FC 03 read for contactor position, source availability and both sources' voltages and frequencies. Use 41350 bit commands for remote tests, peak shave and exercise, and 41312-41319 for transfer statistics.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0System OverviewBITMAP16Contactor position and source availabilityRead
HR 7Source A L1-L2 VoltageUINT16Source A L1-L2 voltageRead
HR 10Source B L1-L2 VoltageUINT16Source B L1-L2 voltageRead
HR 13Source A FrequencyUINT16Source A frequencyRead
HR 14Source B FrequencyUINT16Source B frequencyRead
HR 741Accessory StatusBITMAP16Accessory status (exercise, test, peak shave)Read

Enable Modbus control & writes

Set the Modbus address and baud rate (9600 or 19200) of the network interface port with the ATS Controller Setup Program on a PC; each device on the network needs a unique address.

Byte order & addressing

Network setup

Watch out for

Kohler MPAC 1000 automatic transfer switch controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

43 of 43 shown
Kohler MPAC 1000 automatic transfer switch controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001System OverviewContactor position, preferred source and source availability.BITMAP16Readbit 0 = Contactor position bit 0 (bits 0-1: 00 = off, 01 = normal, 10 = emergency, 11 = fault); bit 1 = Contactor position bit 1; bit 2 = Preferred source: 0 = source 1, 1 = source 2; bit 3 = Bits 3-12: top event on the warning stack; bit 13 = Preferred source available; bit 14 = Standby source available
HR1doc 40002Source A L1-L0 Voltagex10.UINT16× 0.1VRead
HR2doc 40003Source A L2-L0 Voltagex10.UINT16× 0.1VRead
HR3doc 40004Source A L3-L0 Voltagex10.UINT16× 0.1VRead
HR4doc 40005Source B L1-L0 Voltagex10.UINT16× 0.1VRead
HR5doc 40006Source B L2-L0 Voltagex10.UINT16× 0.1VRead
HR6doc 40007Source B L3-L0 Voltagex10.UINT16× 0.1VRead
HR7doc 40008Source A L1-L2 Voltagex10.UINT16× 0.1VRead
HR8doc 40009Source A L2-L3 Voltagex10.UINT16× 0.1VRead
HR9doc 40010Source A L3-L1 Voltagex10.UINT16× 0.1VRead
HR10doc 40011Source B L1-L2 Voltagex10.UINT16× 0.1VRead
HR11doc 40012Source B L2-L3 Voltagex10.UINT16× 0.1VRead
HR12doc 40013Source B L3-L1 Voltagex10.UINT16× 0.1VRead
HR13doc 40014Source A Frequencyx10.UINT16× 0.1HzRead
HR14doc 40015Source B Frequencyx10.UINT16× 0.1HzRead
HR21doc 40022Source Phase Sequence ActualTwo bits per source.BITMAP16Readbit 0 = Source A bit 0 (bits 0-1: 01 = ABC, 00 = CBA, 10 = N/A, 11 = error); bit 1 = Source A bit 1; bit 2 = Source B bit 0 (bits 2-3: same coding); bit 3 = Source B bit 1
HR22doc 40023Source Phase Sequence ExpectedUINT16Read/write0 = CBA; 1 = ABC
HR23doc 40024Source A Nominal Voltagex10.UINT16× 0.1VRead/write
HR24doc 40025Source B Nominal Voltagex10.UINT16× 0.1VRead/write
HR25doc 40026Source A Nominal Frequencyx10.UINT16× 0.1HzRead/write
HR26doc 40027Source B Nominal Frequencyx10.UINT16× 0.1HzRead/write
HR27doc 40028Source A Number of Phases1 or 3.UINT16Read/write
HR28doc 40029Source B Number of Phases1 or 3.UINT16Read/write
HR29doc 40030Rated Amperage0-4000.UINT16ARead/write
HR600doc 40601MLB I/O StatusMain logic board I/O, one bit each.BITMAP16Readbit 0 = Programmable output; bit 1 = Programmable input 1; bit 2 = Programmable input 2; bit 3 = Fixed output LSDO; bit 4 = Fixed output source 2 engine start
HR649doc 40650Active Time Delay NumberUINT16Read
HR650doc 40651Active Time Delay RemainingUINT16sRead
HR651doc 40652Active Time Delay PresetUINT16sRead
HR741doc 40742Accessory StatusBITMAP16Readbit 0 = Exercise in progress; bit 1 = In-phase monitor active; bit 2 = Load shed in progress; bit 3 = Peak shaving in progress; bit 4 = Test occurring
HR742doc 40743DIP Switch PositionBITMAP16Readbit 0 = Transfer inhibited; bit 1 = Loaded/unloaded test; bit 2 = Exercise inhibited; bit 3 = Loaded exercise (push button only); bit 4 = Exercise interval 2 weeks (push button only)
HR1009doc 41010Last Outage TimeMinutes since midnight.UINT16minRead
HR1199doc 41200ATS Controller Code RevisionHigh byte = major, low byte = minor version.UINT16Read
HR1299doc 41300-41301Minutes Not in Preferred TotalMost significant word first.UINT32ABCDminRead
HR1303doc 41304-41305Minutes in Standby TotalMost significant word first.UINT32ABCDminRead
HR1307doc 41308-41309Minutes of Operation TotalMost significant word first.UINT32ABCDminRead
HR1311doc 41312Switch Transfers TotalUINT16Read
HR1313doc 41314Failures to Transfer TotalUINT16Read
HR1315doc 41316Loss of Preferred Transfers TotalUINT16Read
HR1317doc 41318Transfer Time N->EUINT16msRead
HR1318doc 41319Transfer Time E->NUINT16msRead
HR1349doc 41350Maintenance/Test and Manual ActionsWrite-only command bits.BITMAP16Writebit 0 = Reset maintenance records; bit 1 = Start peak shave; bit 2 = End peak shave; bit 3 = Start remote test; bit 4 = End remote test; bit 5 = Force transfer to OFF; bit 6 = Resume programmed transition operation; bit 7 = End current time delay; bit 8 = Remote manual exercise start; bit 9 = Remote manual exercise end
HR1351doc 41352Disable Manual ExerciseUINT16Read/write0 = Enabled; 1 = Disabled
HR9998doc 49999Device IDMPAC 1000 = 19.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Kohler MPAC 1000 automatic transfer switch controller

What Modbus registers does the Kohler MPAC 1000 automatic transfer switch controller have?

This map lists 43 registers: 43 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Kohler MPAC 1000 automatic transfer switch controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. This section prints 5-digit holding-register references starting at 40001, so 40001 is wire address 0 and 41350 is wire address 1349.

What byte order does the Kohler MPAC 1000 automatic transfer switch controller use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Kohler MPAC 1000 automatic transfer switch controller?

Start with HR 0 System Overview (Contactor position and source availability); HR 7 Source A L1-L2 Voltage (Source A L1-L2 voltage); HR 10 Source B L1-L2 Voltage (Source B L1-L2 voltage); HR 13 Source A Frequency (Source A frequency); HR 14 Source B Frequency (Source B frequency); HR 741 Accessory Status (Accessory status (exercise, test, peak shave)).

How do I enable Modbus control of the Kohler MPAC 1000 automatic transfer switch controller?

Set the Modbus address and baud rate (9600 or 19200) of the network interface port with the ATS Controller Setup Program on a PC; each device on the network needs a unique address.

Where is the official Kohler MPAC 1000 automatic transfer switch controller Modbus documentation?

The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.

More Kohler Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.