Kohler MPAC 1000 automatic transfer switch controller Modbus register map
Updated 17 November 2026
The MPAC 1000 is a Kohler automatic transfer switch controller. Its Modbus RTU map reports source A and source B voltages and frequencies, contactor position and source availability, phase sequence, active time delay, I/O and accessory status, transfer statistics and write-only test and manual-action commands. This map covers the monitoring block, nominal ratings, status words, maintenance counters and the command register.
This page lists 43 Modbus registers for the Kohler MPAC 1000 automatic transfer switch controller — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.
- Manufacturer
- Kohler
- Model
- MPAC 1000 automatic transfer switch controller
- Equipment type
- Transfer switch
- Registers
- 43 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS
Integration notes: Kohler MPAC 1000 automatic transfer switch controller
Poll 40001-40015 in one FC 03 read for contactor position, source availability and both sources' voltages and frequencies. Use 41350 bit commands for remote tests, peak shave and exercise, and 41312-41319 for transfer statistics.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | System Overview | BITMAP16 | Contactor position and source availability | Read |
| HR 7 | Source A L1-L2 Voltage | UINT16 | Source A L1-L2 voltage | Read |
| HR 10 | Source B L1-L2 Voltage | UINT16 | Source B L1-L2 voltage | Read |
| HR 13 | Source A Frequency | UINT16 | Source A frequency | Read |
| HR 14 | Source B Frequency | UINT16 | Source B frequency | Read |
| HR 741 | Accessory Status | BITMAP16 | Accessory status (exercise, test, peak shave) | Read |
Enable Modbus control & writes
Set the Modbus address and baud rate (9600 or 19200) of the network interface port with the ATS Controller Setup Program on a PC; each device on the network needs a unique address.
Byte order & addressing
- Counters in 41300-41311 are high word first, unlike the LSW-first LONG type used by Kohler generator controllers.
- Phase sequence in 40022 is two bits per source with 01 = ABC and 00 = CBA.
Network setup
- Serial format is 8 data bits, no parity, 1 stop bit.
- Register 49999 returns 19 for the MPAC 1000.
Watch out for
- The general exception table caps reads at 50 registers and writes at 16.
- Bit 5 of 41350 forces the switch to OFF; use with care on a live load.
Kohler MPAC 1000 automatic transfer switch controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | System Overview | Contactor position, preferred source and source availability. | BITMAP16 | Read | bit 0 = Contactor position bit 0 (bits 0-1: 00 = off, 01 = normal, 10 = emergency, 11 = fault); bit 1 = Contactor position bit 1; bit 2 = Preferred source: 0 = source 1, 1 = source 2; bit 3 = Bits 3-12: top event on the warning stack; bit 13 = Preferred source available; bit 14 = Standby source available | |||
| HR | 1doc 40002 | Source A L1-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 2doc 40003 | Source A L2-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 3doc 40004 | Source A L3-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 4doc 40005 | Source B L1-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 5doc 40006 | Source B L2-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 6doc 40007 | Source B L3-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 7doc 40008 | Source A L1-L2 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 8doc 40009 | Source A L2-L3 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 9doc 40010 | Source A L3-L1 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 10doc 40011 | Source B L1-L2 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 11doc 40012 | Source B L2-L3 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 12doc 40013 | Source B L3-L1 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 13doc 40014 | Source A Frequency | x10. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 14doc 40015 | Source B Frequency | x10. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 21doc 40022 | Source Phase Sequence Actual | Two bits per source. | BITMAP16 | Read | bit 0 = Source A bit 0 (bits 0-1: 01 = ABC, 00 = CBA, 10 = N/A, 11 = error); bit 1 = Source A bit 1; bit 2 = Source B bit 0 (bits 2-3: same coding); bit 3 = Source B bit 1 | |||
| HR | 22doc 40023 | Source Phase Sequence Expected | UINT16 | Read/write | 0 = CBA; 1 = ABC | ||||
| HR | 23doc 40024 | Source A Nominal Voltage | x10. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 24doc 40025 | Source B Nominal Voltage | x10. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 25doc 40026 | Source A Nominal Frequency | x10. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 26doc 40027 | Source B Nominal Frequency | x10. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 27doc 40028 | Source A Number of Phases | 1 or 3. | UINT16 | Read/write | ||||
| HR | 28doc 40029 | Source B Number of Phases | 1 or 3. | UINT16 | Read/write | ||||
| HR | 29doc 40030 | Rated Amperage | 0-4000. | UINT16 | A | Read/write | |||
| HR | 600doc 40601 | MLB I/O Status | Main logic board I/O, one bit each. | BITMAP16 | Read | bit 0 = Programmable output; bit 1 = Programmable input 1; bit 2 = Programmable input 2; bit 3 = Fixed output LSDO; bit 4 = Fixed output source 2 engine start | |||
| HR | 649doc 40650 | Active Time Delay Number | UINT16 | Read | |||||
| HR | 650doc 40651 | Active Time Delay Remaining | UINT16 | s | Read | ||||
| HR | 651doc 40652 | Active Time Delay Preset | UINT16 | s | Read | ||||
| HR | 741doc 40742 | Accessory Status | BITMAP16 | Read | bit 0 = Exercise in progress; bit 1 = In-phase monitor active; bit 2 = Load shed in progress; bit 3 = Peak shaving in progress; bit 4 = Test occurring | ||||
| HR | 742doc 40743 | DIP Switch Position | BITMAP16 | Read | bit 0 = Transfer inhibited; bit 1 = Loaded/unloaded test; bit 2 = Exercise inhibited; bit 3 = Loaded exercise (push button only); bit 4 = Exercise interval 2 weeks (push button only) | ||||
| HR | 1009doc 41010 | Last Outage Time | Minutes since midnight. | UINT16 | min | Read | |||
| HR | 1199doc 41200 | ATS Controller Code Revision | High byte = major, low byte = minor version. | UINT16 | Read | ||||
| HR | 1299doc 41300-41301 | Minutes Not in Preferred Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1303doc 41304-41305 | Minutes in Standby Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1307doc 41308-41309 | Minutes of Operation Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1311doc 41312 | Switch Transfers Total | UINT16 | Read | |||||
| HR | 1313doc 41314 | Failures to Transfer Total | UINT16 | Read | |||||
| HR | 1315doc 41316 | Loss of Preferred Transfers Total | UINT16 | Read | |||||
| HR | 1317doc 41318 | Transfer Time N->E | UINT16 | ms | Read | ||||
| HR | 1318doc 41319 | Transfer Time E->N | UINT16 | ms | Read | ||||
| HR | 1349doc 41350 | Maintenance/Test and Manual Actions | Write-only command bits. | BITMAP16 | Write | bit 0 = Reset maintenance records; bit 1 = Start peak shave; bit 2 = End peak shave; bit 3 = Start remote test; bit 4 = End remote test; bit 5 = Force transfer to OFF; bit 6 = Resume programmed transition operation; bit 7 = End current time delay; bit 8 = Remote manual exercise start; bit 9 = Remote manual exercise end | |||
| HR | 1351doc 41352 | Disable Manual Exercise | UINT16 | Read/write | 0 = Enabled; 1 = Disabled | ||||
| HR | 9998doc 49999 | Device ID | MPAC 1000 = 19. | UINT16 | Read |
Notes on this map
- The MPAC 1000 map has no load-current registers; 40016-40021 are reserved.
- The 2-register maintenance counters (41300-41311) are stated as most significant word first, so they are ABCD. 41012-41013 (duration of last outage) has no stated word order and is left out.
- Left out: time delays and trip points (40032-40064), output/input event-code assignments, software-controlled RDOs, I/O module status words, accessory setup, exerciser, common alarms, customer strings, clock/DST registers, packed date fields and the event history.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Kohler MPAC 1000 automatic transfer switch controller
What Modbus registers does the Kohler MPAC 1000 automatic transfer switch controller have?
This map lists 43 registers: 43 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Kohler MPAC 1000 automatic transfer switch controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. This section prints 5-digit holding-register references starting at 40001, so 40001 is wire address 0 and 41350 is wire address 1349.
What byte order does the Kohler MPAC 1000 automatic transfer switch controller use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Kohler MPAC 1000 automatic transfer switch controller?
Start with HR 0 System Overview (Contactor position and source availability); HR 7 Source A L1-L2 Voltage (Source A L1-L2 voltage); HR 10 Source B L1-L2 Voltage (Source B L1-L2 voltage); HR 13 Source A Frequency (Source A frequency); HR 14 Source B Frequency (Source B frequency); HR 741 Accessory Status (Accessory status (exercise, test, peak shave)).
How do I enable Modbus control of the Kohler MPAC 1000 automatic transfer switch controller?
Set the Modbus address and baud rate (9600 or 19200) of the network interface port with the ATS Controller Setup Program on a PC; each device on the network needs a unique address.
Where is the official Kohler MPAC 1000 automatic transfer switch controller Modbus documentation?
The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.
More Kohler Modbus register maps
- Generator controller
Kohler Decision-Maker 3500 generator set controller
Kohler Decision-Maker 3500 generator set controllers (Modbus map version 2; some registers need firmware 1.4 or later), Modbus RTU on RS-485.
Also known as: Decision-Maker 3500, DEC3500, DEC 3500 - Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller - Generator controller
Kohler Decision-Maker 6000 generator set controller
Kohler Decision-Maker 6000 generator set controllers, Modbus RTU on the controller's RS-485/RS-232 port, per section 8 of TP-6113.
Also known as: Decision-Maker 6000, DEC 6000, Kohler 6000 controller - Transfer switch
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
Kohler Decision-Maker MPAC 750, 1200 and 1500 ATS controllers, Modbus RTU on the logic board RS-485 port or Modbus TCP, per section 14 of TP-6113.
Also known as: Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
Other generator controllers register maps
- Generator controller
Lovato Electric RGK750 genset controller
RGK750, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 750 - Generator controller
SmartGen HGM6100N / HGM6100CAN Series
HGM6100N and HGM6100CAN genset controllers (HGM6110 auto-start and HGM6120 AMF variants), protocol document v1.7.
Also known as: HGM6100CAN, HGM6110N, HGM6120N, HGM6110CAN, HGM6120CAN - Generator controller (utility-tie master synchronizer)
Woodward MSLC-2 Master Synchronizer and Load Control
MSLC-2, data protocol 5200, per manual 37444G.
Also known as: MSLC2, MSLC-2 master synchronizer - Generator controller
Cummins PowerCommand 2.2 / 2.3 / 3.3 genset control (Modbus RTU)
Cummins PowerCommand 2.x and 3.x generator set controls (PC 2.2, 2.3, 3.3), per section 2 of A029X159 Issue 7; registers marked PC 3.x only are absent on PC 2.x.
Also known as: PowerCommand 2.2, PowerCommand 2.3, PowerCommand 3.3, PC2.2, PC2.3, PC3.3 - Generator controller
DEIF AGC-4 Mk II Automatic Genset Controller
AGC-4 Mk II software 6.31.0 (Modbus tables revision N), genset (GEN) application only.
Also known as: AGC-4 Mk2, AGC-4 MkII - Generator controller
Lovato Electric RGK700SA stand-alone genset controller
RGK700SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700SA, RGK700 SA
All generator controllers Modbus register maps →
Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.