Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus register map

Updated 17 November 2026

Short answer

The Decision-Maker MPAC controllers are Kohler automatic transfer switch controllers sharing one Modbus map. It gives source A (1) and source B (2) voltages and frequencies, load current, contactor position and source availability, transition mode, time-delay status, accessory and I/O states, transfer statistics and write-only test and manual-operation commands. This map covers the monitoring block, nominal ratings, transition mode, I/O and accessory status, maintenance counters and the command registers.

This page lists 48 Modbus registers for the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.

Manufacturer
Kohler
Model
Decision-Maker MPAC 750/1200/1500 ATS controller
Equipment type
Transfer switch
Registers
48 (10 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
19200 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC
Source document
Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Kohler Decision-Maker MPAC 750/1200/1500 ATS controller

Integration in brief

Poll 400001-400019 in one FC 03 read for contactor position, source availability, both sources' voltages and frequencies and load current. Use 401350 bit commands for remote tests and peak shave, and 401312-401319 for transfer statistics.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0System OverviewBITMAP16Contactor position and source availabilityRead
HR 7Source A L1-L2 VoltageUINT16Source A L1-L2 voltageRead
HR 10Source B L1-L2 VoltageUINT16Source B L1-L2 voltageRead
HR 13Source A FrequencyUINT16Source A frequencyRead
HR 14Source B FrequencyUINT16Source B frequencyRead
HR 15Current L1UINT16Load current L1Read
HR 741Accessory StatusBITMAP16Accessory status (tests, peak shave)Read

Enable Modbus control & writes

In SiteTech or on the controller enable Modbus (Modbus Server Port 0 / Modbus Server TCP), set the Modbus slave address (1-247) and baud rate (9600, 19200 or 57600), and for TCP the unit ID, IP address, subnet mask and gateway.

Byte order & addressing

Network setup

Watch out for

Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

48 of 48 shown
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 400001System OverviewContactor position, preferred source and source availability.BITMAP16Readbit 0 = Contactor position bit 0 (bits 0-1: 0 = off, 1 = source 1, 2 = source 2, 3 = source 1 and source 2); bit 1 = Contactor position bit 1; bit 2 = Preferred source: 0 = source 1, 1 = source 2; bit 3 = Bits 3-12: active event code; bit 13 = Preferred source available; bit 14 = Standby source available
HR1doc 400002Source A L1-L0 Voltagex10.UINT16× 0.1VRead
HR2doc 400003Source A L2-L0 Voltagex10.UINT16× 0.1VRead
HR3doc 400004Source A L3-L0 Voltagex10.UINT16× 0.1VRead
HR4doc 400005Source B L1-L0 Voltagex10.UINT16× 0.1VRead
HR5doc 400006Source B L2-L0 Voltagex10.UINT16× 0.1VRead
HR6doc 400007Source B L3-L0 Voltagex10.UINT16× 0.1VRead
HR7doc 400008Source A L1-L2 Voltagex10.UINT16× 0.1VRead
HR8doc 400009Source A L2-L3 Voltagex10.UINT16× 0.1VRead
HR9doc 400010Source A L3-L1 Voltagex10.UINT16× 0.1VRead
HR10doc 400011Source B L1-L2 Voltagex10.UINT16× 0.1VRead
HR11doc 400012Source B L2-L3 Voltagex10.UINT16× 0.1VRead
HR12doc 400013Source B L3-L1 Voltagex10.UINT16× 0.1VRead
HR13doc 400014Source A Frequencyx10.UINT16× 0.1HzRead
HR14doc 400015Source B Frequencyx10.UINT16× 0.1HzRead
HR15doc 400016Current L1x10.UINT16× 0.1ARead
HR16doc 400017Current L2x10.UINT16× 0.1ARead
HR17doc 400018Current L3x10.UINT16× 0.1ARead
HR18doc 400019Closed Transition In-Phase Degree DeltaUINT16°Read
HR44doc 400045Phase Rotation ActualBits 8-9 source 1, bits 0-1 source 2 (0 off, 1 ABC, 2 CBA).UINT16Read
HR46doc 400047Nominal Normal Voltagex10.UINT16× 0.1VRead/write
HR47doc 400048Nominal Emergency Voltagex10.UINT16× 0.1VRead/write
HR48doc 400049Nominal Normal Frequencyx10.UINT16× 0.1HzRead/write
HR49doc 400050Nominal Emergency Frequencyx10.UINT16× 0.1HzRead/write
HR50doc 400051Normal Number of Phases1 or 3.UINT16Read/write
HR51doc 400052Emergency Number of Phases1 or 3.UINT16Read/write
HR52doc 400053Rated Amperage0-4000.UINT16ARead/write
HR56doc 400057Transition/Operation ModesDistributor-level password needed: send it in 400058 in the same write.BITMAP16Read/writebit 0 = Transition mode bit 0 (bits 0-1: 0 = open, 1 = programmed, 2 = closed); bit 1 = Transition mode bit 1; bit 2 = Operation mode bit 0 (bits 2-3: 0 = genset-genset, 1 = genset-utility, 2 = utility-genset-genset, 3 = utility-utility); bit 3 = Operation mode bit 1; bit 4 = Supervised transfer switch position: 0 = auto, 1 = manual
HR74doc 400075Active Time Delay NumberUINT16Read
HR75doc 400076Active Time Delay Remainingx10.UINT16× 0.1sRead
HR76doc 400077Active Time Delay Presetx10.UINT16× 0.1sRead
HR193doc 400194MLB Output StateOne bit per main logic board output.BITMAP16Read
HR194doc 400195MLB Input StateOne bit per main logic board input.BITMAP16Read
HR741doc 400742Accessory StatusBITMAP16Readbit 0 = Exercise in progress; bit 1 = In-phase monitor active; bit 2 = Load control in progress; bit 3 = Peak shaving in progress; bit 4 = Loaded test occurring; bit 5 = Unloaded test occurring; bit 6 = Auto-loaded test occurring; bit 7 = Synchronous check occurring; bit 8 = User forcing to OFF
HR742doc 400743DIP Switch PositionBITMAP16Readbit 0 = Maintenance mode; bit 1 = Password disabled; bit 2 = Spare 3 on; bit 3 = Spare 4 on
HR1009doc 401010Last Outage TimeMinutes since midnight.UINT16minRead
HR1199doc 401200MPAC DM Code VersionHigh byte = major, low byte = minor version.UINT16Read
HR1299doc 401300-401301Minutes Not in Preferred TotalMost significant word first.UINT32ABCDminRead
HR1303doc 401304-401305Minutes in Standby TotalMost significant word first.UINT32ABCDminRead
HR1307doc 401308-401309Minutes of Operation TotalMost significant word first.UINT32ABCDminRead
HR1311doc 401312Switch Transfers TotalUINT16Read
HR1313doc 401314Failures to Transfer TotalUINT16Read
HR1315doc 401316Loss of Preferred Transfers TotalUINT16Read
HR1317doc 401318Transfer Time Source 1 to Source 2UINT16msRead
HR1318doc 401319Transfer Time Source 2 to Source 1UINT16msRead
HR1349doc 401350Maintenance/Test and Manual OperationsWrite-only command bits.BITMAP16Writebit 0 = Reset maintenance records; bit 1 = Start peak shave; bit 2 = End peak shave; bit 3 = Start remote loaded test; bit 4 = Start remote unloaded test; bit 6 = End remote test; bit 7 = Force transfer to OFF; bit 8 = Resume operation (reset force to OFF); bit 9 = End current time delay; bit 10 = Start synchronous check; bit 11 = End synchronous check
HR1350doc 401351Auto-Loaded Test Run TimeAny non-zero value starts the test.UINT16minWrite
HR9998doc 409999Device IDMPAC 1500 = 23, MPAC 1200 = 27, MPAC 750 = 26.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller

What Modbus registers does the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller have?

This map lists 48 registers: 48 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. This section prints 6-digit holding-register references starting at 400001, so 400001 is wire address 0 and 401350 is wire address 1349.

What byte order does the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller?

Start with HR 0 System Overview (Contactor position and source availability); HR 7 Source A L1-L2 Voltage (Source A L1-L2 voltage); HR 10 Source B L1-L2 Voltage (Source B L1-L2 voltage); HR 13 Source A Frequency (Source A frequency); HR 14 Source B Frequency (Source B frequency); HR 15 Current L1 (Load current L1); HR 741 Accessory Status (Accessory status (tests, peak shave)).

How do I enable Modbus control of the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller?

In SiteTech or on the controller enable Modbus (Modbus Server Port 0 / Modbus Server TCP), set the Modbus slave address (1-247) and baud rate (9600, 19200 or 57600), and for TCP the unit ID, IP address, subnet mask and gateway.

Where is the official Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus documentation?

The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.

More Kohler Modbus register maps

Other generator controllers register maps

All generator controllers Modbus register maps →

Source: Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) · TP-6113 12/21p · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.