Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus register map
Updated 17 November 2026
The Decision-Maker MPAC controllers are Kohler automatic transfer switch controllers sharing one Modbus map. It gives source A (1) and source B (2) voltages and frequencies, load current, contactor position and source availability, transition mode, time-delay status, accessory and I/O states, transfer statistics and write-only test and manual-operation commands. This map covers the monitoring block, nominal ratings, transition mode, I/O and accessory status, maintenance counters and the command registers.
This page lists 48 Modbus registers for the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Kohler’s own free documentation (linked below) and checked against it.
- Manufacturer
- Kohler
- Model
- Decision-Maker MPAC 750/1200/1500 ATS controller
- Equipment type
- Transfer switch
- Registers
- 48 (10 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Decision-Maker MPAC 750, Decision-Maker MPAC 1200, Decision-Maker MPAC 1500, DM MPAC
Integration notes: Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
Poll 400001-400019 in one FC 03 read for contactor position, source availability, both sources' voltages and frequencies and load current. Use 401350 bit commands for remote tests and peak shave, and 401312-401319 for transfer statistics.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | System Overview | BITMAP16 | Contactor position and source availability | Read |
| HR 7 | Source A L1-L2 Voltage | UINT16 | Source A L1-L2 voltage | Read |
| HR 10 | Source B L1-L2 Voltage | UINT16 | Source B L1-L2 voltage | Read |
| HR 13 | Source A Frequency | UINT16 | Source A frequency | Read |
| HR 14 | Source B Frequency | UINT16 | Source B frequency | Read |
| HR 15 | Current L1 | UINT16 | Load current L1 | Read |
| HR 741 | Accessory Status | BITMAP16 | Accessory status (tests, peak shave) | Read |
Enable Modbus control & writes
In SiteTech or on the controller enable Modbus (Modbus Server Port 0 / Modbus Server TCP), set the Modbus slave address (1-247) and baud rate (9600, 19200 or 57600), and for TCP the unit ID, IP address, subnet mask and gateway.
Byte order & addressing
- Counters in 401300-401311 are high word first, unlike the LSW-first LONG type used by Kohler generator controllers.
- 400045 packs source 1 rotation in bits 8-9 and source 2 rotation in bits 0-1.
Network setup
- Parity (none) and stop bits (1) are fixed.
- Register 409999 identifies the model: 23 = MPAC 1500, 27 = MPAC 1200, 26 = MPAC 750.
Watch out for
- The general exception table caps reads at 50 registers and writes at 16.
- Bit 7 of 401350 forces the switch to OFF; use with care on a live load.
Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 400001 | System Overview | Contactor position, preferred source and source availability. | BITMAP16 | Read | bit 0 = Contactor position bit 0 (bits 0-1: 0 = off, 1 = source 1, 2 = source 2, 3 = source 1 and source 2); bit 1 = Contactor position bit 1; bit 2 = Preferred source: 0 = source 1, 1 = source 2; bit 3 = Bits 3-12: active event code; bit 13 = Preferred source available; bit 14 = Standby source available | |||
| HR | 1doc 400002 | Source A L1-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 2doc 400003 | Source A L2-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 3doc 400004 | Source A L3-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 4doc 400005 | Source B L1-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 5doc 400006 | Source B L2-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 6doc 400007 | Source B L3-L0 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 7doc 400008 | Source A L1-L2 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 8doc 400009 | Source A L2-L3 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 9doc 400010 | Source A L3-L1 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 10doc 400011 | Source B L1-L2 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 11doc 400012 | Source B L2-L3 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 12doc 400013 | Source B L3-L1 Voltage | x10. | UINT16 | × 0.1 | V | Read | ||
| HR | 13doc 400014 | Source A Frequency | x10. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 14doc 400015 | Source B Frequency | x10. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 15doc 400016 | Current L1 | x10. | UINT16 | × 0.1 | A | Read | ||
| HR | 16doc 400017 | Current L2 | x10. | UINT16 | × 0.1 | A | Read | ||
| HR | 17doc 400018 | Current L3 | x10. | UINT16 | × 0.1 | A | Read | ||
| HR | 18doc 400019 | Closed Transition In-Phase Degree Delta | UINT16 | ° | Read | ||||
| HR | 44doc 400045 | Phase Rotation Actual | Bits 8-9 source 1, bits 0-1 source 2 (0 off, 1 ABC, 2 CBA). | UINT16 | Read | ||||
| HR | 46doc 400047 | Nominal Normal Voltage | x10. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 47doc 400048 | Nominal Emergency Voltage | x10. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 48doc 400049 | Nominal Normal Frequency | x10. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 49doc 400050 | Nominal Emergency Frequency | x10. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 50doc 400051 | Normal Number of Phases | 1 or 3. | UINT16 | Read/write | ||||
| HR | 51doc 400052 | Emergency Number of Phases | 1 or 3. | UINT16 | Read/write | ||||
| HR | 52doc 400053 | Rated Amperage | 0-4000. | UINT16 | A | Read/write | |||
| HR | 56doc 400057 | Transition/Operation Modes | Distributor-level password needed: send it in 400058 in the same write. | BITMAP16 | Read/write | bit 0 = Transition mode bit 0 (bits 0-1: 0 = open, 1 = programmed, 2 = closed); bit 1 = Transition mode bit 1; bit 2 = Operation mode bit 0 (bits 2-3: 0 = genset-genset, 1 = genset-utility, 2 = utility-genset-genset, 3 = utility-utility); bit 3 = Operation mode bit 1; bit 4 = Supervised transfer switch position: 0 = auto, 1 = manual | |||
| HR | 74doc 400075 | Active Time Delay Number | UINT16 | Read | |||||
| HR | 75doc 400076 | Active Time Delay Remaining | x10. | UINT16 | × 0.1 | s | Read | ||
| HR | 76doc 400077 | Active Time Delay Preset | x10. | UINT16 | × 0.1 | s | Read | ||
| HR | 193doc 400194 | MLB Output State | One bit per main logic board output. | BITMAP16 | Read | ||||
| HR | 194doc 400195 | MLB Input State | One bit per main logic board input. | BITMAP16 | Read | ||||
| HR | 741doc 400742 | Accessory Status | BITMAP16 | Read | bit 0 = Exercise in progress; bit 1 = In-phase monitor active; bit 2 = Load control in progress; bit 3 = Peak shaving in progress; bit 4 = Loaded test occurring; bit 5 = Unloaded test occurring; bit 6 = Auto-loaded test occurring; bit 7 = Synchronous check occurring; bit 8 = User forcing to OFF | ||||
| HR | 742doc 400743 | DIP Switch Position | BITMAP16 | Read | bit 0 = Maintenance mode; bit 1 = Password disabled; bit 2 = Spare 3 on; bit 3 = Spare 4 on | ||||
| HR | 1009doc 401010 | Last Outage Time | Minutes since midnight. | UINT16 | min | Read | |||
| HR | 1199doc 401200 | MPAC DM Code Version | High byte = major, low byte = minor version. | UINT16 | Read | ||||
| HR | 1299doc 401300-401301 | Minutes Not in Preferred Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1303doc 401304-401305 | Minutes in Standby Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1307doc 401308-401309 | Minutes of Operation Total | Most significant word first. | UINT32 | ABCD | min | Read | ||
| HR | 1311doc 401312 | Switch Transfers Total | UINT16 | Read | |||||
| HR | 1313doc 401314 | Failures to Transfer Total | UINT16 | Read | |||||
| HR | 1315doc 401316 | Loss of Preferred Transfers Total | UINT16 | Read | |||||
| HR | 1317doc 401318 | Transfer Time Source 1 to Source 2 | UINT16 | ms | Read | ||||
| HR | 1318doc 401319 | Transfer Time Source 2 to Source 1 | UINT16 | ms | Read | ||||
| HR | 1349doc 401350 | Maintenance/Test and Manual Operations | Write-only command bits. | BITMAP16 | Write | bit 0 = Reset maintenance records; bit 1 = Start peak shave; bit 2 = End peak shave; bit 3 = Start remote loaded test; bit 4 = Start remote unloaded test; bit 6 = End remote test; bit 7 = Force transfer to OFF; bit 8 = Resume operation (reset force to OFF); bit 9 = End current time delay; bit 10 = Start synchronous check; bit 11 = End synchronous check | |||
| HR | 1350doc 401351 | Auto-Loaded Test Run Time | Any non-zero value starts the test. | UINT16 | min | Write | |||
| HR | 9998doc 409999 | Device ID | MPAC 1500 = 23, MPAC 1200 = 27, MPAC 750 = 26. | UINT16 | Read |
Notes on this map
- Factory communication settings: 19200 baud, no parity, 1 stop bit (parity and stop bits are not adjustable), Modbus TCP unit ID 2; the serial slave address is listed with default 0, so set it before use.
- The 2-register history counters (401300-401311) are stated as most significant word first, so they are ABCD. 401012 (duration of last outage, 2 words) has no stated word order and is left out.
- The guide puts 400039-400058 (including the transition override at 400039 and transition/operation modes at 400057) in its distributor-password setup group and says to send the data register and the password (400040, 400058) in the same request. Factory settings and calibration are also password protected and not listed.
- Left out: synchronizing settings, time delays and trip points, I/O module events, expansion board states, accessory setup, load control, exerciser, common alarms, ATS strings, network/UART configuration, clock/DST, packed date fields, event history, current-based load control, prime power and min/max logging.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller
What Modbus registers does the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller have?
This map lists 48 registers: 48 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. This section prints 6-digit holding-register references starting at 400001, so 400001 is wire address 0 and 401350 is wire address 1349.
What byte order does the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller?
Start with HR 0 System Overview (Contactor position and source availability); HR 7 Source A L1-L2 Voltage (Source A L1-L2 voltage); HR 10 Source B L1-L2 Voltage (Source B L1-L2 voltage); HR 13 Source A Frequency (Source A frequency); HR 14 Source B Frequency (Source B frequency); HR 15 Current L1 (Load current L1); HR 741 Accessory Status (Accessory status (tests, peak shave)).
How do I enable Modbus control of the Kohler Decision-Maker MPAC 750/1200/1500 ATS controller?
In SiteTech or on the controller enable Modbus (Modbus Server Port 0 / Modbus Server TCP), set the Modbus slave address (1-247) and baud rate (9600, 19200 or 57600), and for TCP the unit ID, IP address, subnet mask and gateway.
Where is the official Kohler Decision-Maker MPAC 750/1200/1500 ATS controller Modbus documentation?
The source is Modbus Communications Protocol Operation (generator set, transfer switch and power monitor controllers) (TP-6113 12/21p), revision 2021-12, published free by Kohler at https://resources.kohler.com/power/kohler/industrial/pdf/tp6113.pdf.
More Kohler Modbus register maps
- Generator controller
Kohler Decision-Maker 3500 generator set controller
Kohler Decision-Maker 3500 generator set controllers (Modbus map version 2; some registers need firmware 1.4 or later), Modbus RTU on RS-485.
Also known as: Decision-Maker 3500, DEC3500, DEC 3500 - Generator controller
Kohler Decision-Maker 550 generator set controller (application code 2.10+)
Kohler Decision-Maker 550 generator set controllers with application code version 2.10 or higher, Modbus RTU on the controller's RS-485 port.
Also known as: Decision-Maker 550, DEC 550, Kohler 550 controller - Generator controller
Kohler Decision-Maker 6000 generator set controller
Kohler Decision-Maker 6000 generator set controllers, Modbus RTU on the controller's RS-485/RS-232 port, per section 8 of TP-6113.
Also known as: Decision-Maker 6000, DEC 6000, Kohler 6000 controller - Transfer switch
Kohler MPAC 1000 automatic transfer switch controller
Kohler MPAC 1000 ATS controllers, Modbus RTU on RS-485, per section 12 of TP-6113.
Also known as: MPAC 1000, MPAC1000, Kohler MPAC 1000 ATS - Transfer switch
Kohler MPAC 1500 automatic transfer switch controller
Kohler MPAC 1500 ATS controllers, Modbus RTU on main logic board RS-485 ports 1/2 or Modbus TCP on the Ethernet port, per section 13 of TP-6113.
Also known as: MPAC 1500, MPAC1500, Kohler MPAC 1500 ATS
Other generator controllers register maps
- Generator controller
Lovato Electric RGK700SA stand-alone genset controller
RGK700SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700SA, RGK700 SA - Generator controller
SmartGen HGM4010N / HGM4020N
HGM4010N (auto start) and HGM4020N (AMF) genset controllers, HGM4000N communication protocol v1.2.
Also known as: HGM4010N, HGM4000N - Generator controller
Woodward easYgen-3000XT Series
easYgen-3100XT-P1 / 3200XT-P1 / 3200XT-P1-LT, release 2.17-0, default Modbus data protocol 5010 (Basic Visualization).
Also known as: easYgen-3100XT-P1, easYgen-3200XT-P1, easYgen-3200XT-P1-LT, easYgen-3100XT, easYgen-3200XT - Generator controller
Cummins PCC 1301 / PowerCommand 1.1 / 1.2 genset control (Modbus RTU)
Cummins PCC 1301 and PowerCommand 1.1/1.2 generator set controls on their RS-485 Modbus RTU port, per section 1 of A029X159 Issue 7.
Also known as: PCC 1301, PCC1301, PowerCommand 1.1, PowerCommand 1.2, PC1.1, PC1.2 - Generator controller
DEIF AGC-4 Automatic Genset Controller
AGC-4 software 4.83.0 (Modbus tables revision I), genset (DG) application; mains and BTB variants share many addresses but are not covered.
Also known as: AGC-4 DG, AGC 4, Multi-line 2 AGC-4 - Generator controller
Lovato Electric RGK700 AMF genset controller
RGK700, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700, RGK700 AMF
All generator controllers Modbus register maps →